Background

Testing solutions For protection engineers, the


increasing complexity of modern

of a special kind
protection devices represents a
major challenge when preparing
automated tests. Defining special
Integrated expert knowledge in distance and differential protec-
tion characteristics can turn out to
the Protection Testing Library
be particularly complex and time
consuming. OMICRON recognized
this trend many years ago and

PTL
PROTECTION
since then has been offering op-
timized solutions in its Protection
TESTING
LIBRARY Testing Library (PTL).

  Magazine | Volume 4 Issue1 2013


Background  5

T60 testing template in the PTL: easy testing despite complex


characteristic.

Today, the PTL includes predefined and all important protection functions and 1 T60 – Cubic Spline Interpolated
editable test templates for more than 270 suitable XRIO converters. The experts Transformer Differential Tripping
types of protection devices and covers a constantly face challenging tasks when Characteristic
comprehensive range of topics. Aside from developing new templates. At a glance, Differential protection characteristics can
overcurrent protection, distance protection the logical structure of the user-friendly represent a major challenge to testers. For
and differential protection applications, it input masks used in the templates may example, The GE Multilin T60 transformer
also includes machine protection (gene- appear to be based on simple background differential protection employs an operat-
rator and motor). Furthermore, it offers algorithms. However, this would only be an ing characteristic whose progression is de-
solutions for testing grid disconnection assumption because they actually function termined by using a cubic spline interpola-
protection devices for interconnection at a high level of complexity. Being able to tion. In the PTL template, these calculations
(including Q-U protection) or the recloser facilitate test solutions which can be ad- are performed in the corresponding XRIO
and sectionalizer controls used by many justed to specific testing tasks and the test converter. Here, they are defined in such a
countries in distribution grids. equipment at hand is precisely what makes way that the characteristic is displayed for
the innovative functions of this library so all potential setting values in the differen-
At OMICRON, a team of protection experts useful. The following section uses three tial protection test modules, making it easy
is responsible for maintaining the library examples from the world of differential to perform tests on a protection device
and ensures that it is kept up-to-date. The protection to help you learn more about such as this.
testing templates include test plans for these special functionalities.

  Magazine | Volume 4 Issue 1 2013


6  Background

Ifault
Idiff

IN
triggering

approximation

current transformer
fault

n1/n Icurrent transformer


Istab
IN

7SD610 trigger characteristic: testing complexity not Current transformer faults: taking into account
immediately apparent. approximation with adaptive characteristics.

2 7SD610 (7SD523) — With its graphic support, the ’Advanced Differential’ test-
Adaptive Tripping Operating Characteristic ing module group of the Test Universe software facilitates
Aside from complex mathematical algorithms, efficient testing of differential protection relays. Due to
protection devices sometimes employ dynamic and its unique nature, the stabilization characteristic for the
adaptive methods with corresponding complex- 7SD610 is defined here in the PTL’s XRIO converter and
ity for considering current conditions. For example, shown with existing stabilization quantities.
in Siemens’ 7SD610 line differential protection the
actual trigger characteristic is represented as a simple
straight line.

However, an exceptional type of stabilization is


defined for calculating IStab. Since the coefficients of
the stabilization formula also depend on the actual
measured values here, this makes determining the
test quantities significantly more difficult. Beside the
measured line-end currents, the stabilization formula
also includes quantities which describe the trans-
mission behavior of the current transformer. These
properties and, in particular, the characteristic data of
the current transformers (f1 , f2), strongly depend on
the current level.

Testing 7SD610: display of the transformed characteristic in the ’differential


operating characteristic’ testing module.
  Magazine | Volume 4 Issue1 2013
Background  7

P7
P8

External Faults
and Load Current
Restraint Area
� P5
P6
P2 P1 P3 P4

1�180°
P10
P9

P12
P11

The alpha plane: an alternative display form. Testing the alpha plane: graphic support provided by the PTL template.

3 SEL 311L — A wealth of knowledge packaged into


Alpha Plane Current Differential Algorithm user-friendly solutions
Algorithms of phase comparison protection relays in par- With the PTL, OMICRON offers integrated ex-
ticular are often very individual. Therefore, the solutions pert knowledge in the form of pioneering and
offered by protection device manufacturers vary accord- practical solutions for automated protective
ingly. For example, the SEL 311L protection relay does equipment testing. PTL users not only benefit
not determine a differential current in a typical fashion from the extensive range of expertise, but also
with a protection trip being triggered when a threshold is from the flexibility of the testing templates,
exceeded. Instead, it continuously calculates the ratio of which allow predefined approaches to be
the complex currents at the two ends of the line. A plane, freely adjusted and extended to cater to in-
the so-called alpha plane, is then stretched over the real dividual requirements. In addition to this, the
and imaginary part of this ratio. integrated XRIO converters can also be used
independently in test plans. Since the import
The PTL provides optimum support for efficient testing. masks used in the templates are based on the
The template specially developed for the SEL 311L calcu- parameter setting software of the respective
lates test points automatically, whereby the automation protective relay, this makes them especially
approach employed is represented in a clear and compre- easy to use.
hensible way.

Michael Albert
Product manager

  Magazine | Volume 4 Issue 1 2013