Вы находитесь на странице: 1из 1

TESTCOM SERVICES SDN BHD (755984-D)

NO. 17 & 19, JALAN ASTAKA U8/83, BUKIT JELUTONG BUSINESS AND TECHNOLOGY CENTRE,
40150 SHAH ALAM, SELANGOR DARUL EHSAN
TEL NO: +603-7848 1888, FAX NO: +603-7848 1881, Website: www.spm.com.my

Circuit Installation: SJ SULTAN AZLAN SHAH MANJUNG Bay No


BUS.SECTION SWITCH Switchboard: 3.3KV UNIT SWITCHBOARD (09BBC)
WITH METERING (RISER Client: TNB JANAMANJUNG SDN BHD 09BBC08
PANEL) Contract No: TNBJ/KON 34/2016

TEST REPORT FOR: UNDERVOLTAGE RELAY TEST

No Test Equipments Serial Number Calibration Due Date


1 DRTS6 2012/19266 1/12/17

Relay Details
Make ALSTOM Function UNDER VOLTAGE
Type MVTU11 Rated Current N.A
Frequency 50 Hz Rated Voltage, Vn 100-120 VAC
Serial No. 648449M DC Aux Voltage, Vx 110VAC

Setting Value
tsec 3
Vs=(62+) 15

1. Voltage Setting Check


Operating Voltage (V)
Phase Pick-up
Setting (V)
Expected Measured %Error
62+15=
P-P 77 75.971 -1.34%
77

2. Timer Setting Check


Operating Time (s)
Setting (s)
Pickup Errors%
3 3.1202 4.01%

Comments by Service Engineer:

PASS / FAIL
Client Verified By:
Tested By:
……………………………. Name: MUZAFAR
Date/Time: 20-Dec-17
Witness By
Page:
TCS TEST REPORT REF: TCS-WI-750-01-2B03