Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Middel PI 5 KV >1T >1T >1T Left PI 5 KV >1T >1T >1T Right PI 5 KV >1T >1T >1T
2) Test of 66 KV Incoming Line Bus Iso:
Make GR Power SR. NO. 2532/5670 MFG Year 2016
Insulation Resistance Test of Iso:
Test Connection Test R Y B
Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Middel PI 5 KV >1T >1T >1T Left PI 5 KV >1T >1T >1T Right PI 5 KV >1T >1T >1T 1 Page
Name of Substation: 66 KV 25 MW ASTRA
SOLTRAN Date of Testing: 13/04/2017 Tested By: Jayesh Patel Approved By: Naresh Soni 3) Test of 66 KV Transformer-1 Bus Iso: Make GR Power SR. NO. 2532/5664 MFG Year 2016
Insulation Resistance Test of Iso:
Test Connection Test R Y B
Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Middel PI 5 KV >1T >1T >1T Left PI 5 KV >1T >1T >1T Right PI 5 KV >1T >1T >1T
4) Test of 66 KV BUS PT Iso:
Make GR Power SR. NO. 2532/5669 MFG Year 2016
Insulation Resistance Test of Iso:
Test Connection Test R Y B
Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Middel PI 5 KV >1T >1T >1T Left PI 5 KV >1T >1T >1T Right PI 5 KV >1T >1T >1T 2 Page
Name of Substation: 66 KV 25 MW ASTRA
SOLTRAN Date of Testing: 13/04/2017 Tested By: Jayesh Patel Approved By: Naresh Soni 1) Test of 66 KV Incoming Line CB: Make ABB SR. NO. 700 19 505 MFG Year 2016
Insulation Resistance Test of CB:
Test Connection Test R Y B
Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Top To Earth 5 KV >1T >1T >1T Bottom To Earth 5 KV >1T >1T >1T Top To Bottom 5 KV >1T >1T >1T
2) Test of 66 KV Transformer-1 CB:
Make ABB SR. NO. 700 19 504 MFG Year 2016
Insulation Resistance Test of CB:
Test Connection Test R Y B
Voltege. Phase (GΩ) Phase (GΩ) Phase(GΩ) Top To Earth 5 KV >1T >1T >1T Bottom To Earth 5 KV >1T >1T >1T Top To Bottom 5 KV >1T >1T >1T 3 Page
Name of Substation: 66 KV 25 MW ASTRA
SOLTRAN Date of Testing: 13/04/2017 Tested By: Jayesh Patel Approved By: Naresh Soni