Академический Документы
Профессиональный Документы
Культура Документы
Coveral is a custom built internal floating deck, designed for installation in existing or new fixed roof
storage tanks. Coveral decks are sandwiched between sheets of high purity aluminium.
Coveral deck prevent losses of valuable volatile petroleum fractions by evaporation and during the
filling and emptying cycles of the storage tanks.
Additionally, Coveral decks prevent contamination of stored products by water vapour and dust.
Oxidation of product is also reduced be elimination of the liquid vapour interface.
The shallow structure of Coveral, which floats in full contact with the liquid surface causes virtually no
reduction of the storage capacity of the storage tank.
GENERAL
Normally Coveral panels can be introduced into an
existing tank through clean-out doors or manholes. If
these are not suitable, a slot can be cut in the roof
and subsequently repaired. Cutting the storage tank
shell is not recommended.
Coveral decks are modular in construction the panels are 2500mw long x 500mw wide, 4Omm thick.
The panels are joined by extruded aluminium H section and built in an interlocking herringbone pattern.
When decks are being fitted to existing tankage, the panels are normally introduced through manholes
or cleanout doors.
On-site construction is simple and does not require specialist labour. The decks are normally built on
acrow-prop supported falsework which is moved as the root becomes self supporting on its built
support legs. The deck is rigid, both during construction and when completed and will adequately
support maintenance or inspection personnel both when floating and in the on-support condition.
Safety
The aluminium surface of Coveral decks is electrically conductive and ensures sale removal of any build-
up or static electricity. The deck and tanks form a Faraday cage which gives protection during electrical
storms. Vapour build-up between Coveral and the tank roof is negligible under normal operation
conditions it is recommended that air vents around the root edge are provided in conversion of existing
storage tanks, in accordance with the recommendations of BS2654 Appendix E. Coveral decks float in
full contact with the liquid surface and are not liable to corrosion damage . The deck cannot be
submerged by accidental overflows though fining of an inlet extension to the filling line is suggested to
minimise turbulence in the seal area.
SPECIFICATIONS
Rim seals : Polyurethane coated nylon fabric envelope, flexible Polyether loam filling, of
rectangular or pentagonal section.
Rectangular seals : 80mm rim gap for tanks up to and including 35 metre diameter.
Pentagonal seals : 110mm rim gap for tanks over 36 metres diameter
Standard : Anti-rotation cable (not necessary in column supported roof tanks)
NOTE If 1800mm level used the deck should not be walked on without additional support.