Multiple installation options

MagnaClean® DualXP's in-line design and 360° rotational connectors provide


multiple installation options for both vertical and horizontal pipework. This ensures
greater flexibility within tight working environments.
Dual
Installation and servicing
instructions

MagnaClean DualXP
MagnaClean DualXP delivers exceptional protection against the damaging effects
of black iron oxide sludge and non-magnetic debris. The unique design makes it
a leader in its class giving professional installers a dedicated filter bridging the gap
between ADEY’s extensive domestic filter range, which is installed in more than
three million UK homes, and the company’s heavy duty commercial filters.

IMPORTANT Follow the Standard Electrical Best Practice guidelines when installing
a MagnaClean filter. A copy of these guidelines can be found at:
www.hse.gov.uk/electricity
Maximum working pressure: 6 bar The inlet and outlet on MagnaClean DualXP are reversible and there is no flow
restriction. Following installation, don’t forget to complete the warranty card.
Maximum working temperature: 95°C
Alternatively, complete the registration online at adey.com/warranty
Flow rate: Recommended rate for optimum capture up to 100 litres per minute

Volume: 2.43 litres (when telescopic connectors are retracted)

LF2-01-02132
FOR BEST RESULTS
Install and service with MC1+ Protector, the advanced system
inhibitor from ADEY, Europe’s largest water treatment

M03633
manufacturer for central heating systems. Telephone: +44 (0)1242 546717 Email: info@adey.com
adey.com

Produced from recycled material


A carbon neutral company
Installation
Open vented system Combi/Sealed system

Exceptional protection for 1½” or 1¼” light commercial heating systems The following instructions are designed to In both diagrams, position A is best
support engineers in the safe and effective practice, while B is suitable.
MagnaClean DualXP has been developed by the industry leading and multi-award
®
installation and servicing of MagnaClean
winning company that pioneered magnetic filtration within this sector. ADEY’s filters are DualXP and should be followed at all times. A

already protecting more than three million heating systems in the UK. N.B. We firmly recommend
Any queries should be directed to your
MagnaClean DualXP can be installed anywhere on the main circuit. However, to achieve MagnaClean DualXP is installed
supervisor or ADEY direct on 01242 546717.
the best level of protection for the boiler, it is recommended to install the filter after the FITTING DUAL XP TO 1-1/2" PIPEWORK
and serviced by a qualified
last radiator on the system and before the boiler. It is important to install valves either MagnaClean DualXP is suitable for both A
heating engineer.
side of the MagnaClean DualXP. Isolation valves and fittings for copper pipework domestic heating systems shown here as well Knurled nuts should be
as larger light commercial heating systems. hand-tightened only.
A

not included.

3. FIT TOP ELBOW, DO NOT LOCK - MOVE


FITTING DUAL XP TO 1-1/2" PIPEWORK
CONNECTION AND PUSH FILTER ON TO SPIGOTS -

PIPE CUT LENGTH


DO NOT LOCK FILTER TO CONNECTORS.

4. LOCK CONNECTOR - BLACK NUT AGAINST RED

375
FITTING DUAL XP TO 1-1/2" PIPEWORK NUT ONLY.

1 1¼“ 1 1½“ 2 3 4 5 6
5. LOCK CONNECTORS TO FILTER.
7 2

FIXED PORT CENTRES


118
2
2 25mm 2 1
25mm
3
1½’’
ü û
1¼’’
BSPT
BSPT
û 1
1
C
1 2. BOTTOM ELBOW TO BE IN FULLY RETRACTED
POSITION, AFTER LOCKING BLACK NUT AGAINST RED 3. FIT TOP ELBOW, DO NOT LOCK - MOVE

üHold
BUSH. TURN RED BUSH CLOCKWISE UNTIL COMPLETE CONNECTION AND PUSH FILTER ON TO SPIGOTS -

PIPE CUT LENGTH


ASSEMBLY HAS BECOME RIGID (CONNECTION TO FILTER, DO NOT LOCK FILTER TO CONNECTORS.
1
ü
CANNOT BE TURNED).
3. FIT TOP ELBOW, DO NOT LOCK - MOVE
4. LOCK CONNECTOR - BLACK NUT AGAINST RED
400mm

375
CONNECTION AND PUSH FILTER ON TO SPIGOTS -
NUT ONLY.

PIPE CUT LENGTH


1. AFTER CUTTING PIPE AND CUTTING DO NOT LOCK FILTER TO CONNECTORS.

ORR
THREAD. FIT BOTTOM ELBOW ASSEMBLY.

2
5. LOCK CONNECTORS TO FILTER.
375mm

4. LOCK CONNECTOR - BLACK NUT AGAINST RED

375
NUT ONLY.
1 1

FIXED PORT CENTRES


5. LOCK CONNECTORS TO FILTER.

118
FIXED PORT CENTRES
ü

118
1 A

Hold 1
2 1 107mm
25mm
1¼’’
25mm
1½’’
2 1
û 2. BOTTOM ELBOW TO BE IN FULLY RETRACTED
POSITION, AFTER LOCKING BLACK NUT AGAINST RED
BUSH. TURN RED BUSH CLOCKWISE UNTIL COMPLETE

ü
2. BOTTOM ELBOW TO BE IN FULLY RETRACTED
BSPT POSITION, AFTER LOCKING BLACK NUT AGAINST RED
ASSEMBLY HAS BECOME RIGID (CONNECTION TO FILTER,
CANNOT BE TURNED).

BSPT BUSH. TURN RED BUSH CLOCKWISE UNTIL COMPLETE


ASSEMBLY HAS BECOME RIGID (CONNECTION TO FILTER,
CANNOT BE TURNED).
2
1. AFTER CUTTING PIPE AND CUTTING
THREAD. FIT BOTTOM ELBOW ASSEMBLY.

1. AFTER CUTTING PIPE AND CUTTING


THREAD. FIT BOTTOM ELBOW ASSEMBLY.

Servicing
A

A SECTION A-A
SCALE 1 : 2

1 1 2 3 4 Remove 1 5 6 7 1
sleeve
D D
2

Your system is protected by Close Close Close


3
3 3
D
D

2
2 Open 2 2 Open
Open Clean SECTION A-A
SCALE 1 : 2

Dual
SECTION A-A

3 SCALE 1 : 2

Clean

DETAIL D
SCALE 1 : 2
Annual service required D

DETAIL D
SCALE 1 : 2

adey.com 4
1

1 Clean
DETAIL D 1 DETAIL D 1
SCALE 1 : 2 SCALE 1 : 2

DETAIL D
SCALE 1 : 2