type FK-K90 with approval No. Z-41.3-321
type FK-K90 with approval No. Z-41.3-318 and
type E01-K90 with approval No. Z-41.3-323
Design changes reserved · All rights reserved © Gebrüder Trox GmbH (7/2003) · Leaflet No. E016KM6
casing II. with additional release mechanism via
Spare parts in accordance with Spare Parts Price List solenoid or electro magnet Page 4
EP/4/2/D/... Information for electrical wiring Page 5
Lubricating points: Lubricate only if not moving III. Pneumatic actuator 1,2 and 6 bar Page 6
smoothly. Information for electrical wiring and
Use only oils and fats free of resin and acid as functional diagram Page 8
lubricants.
IV. Electrical actuator (power off to close) Page 9
If the fire damper is actuated the drive rods follow Information for electrical wiring and function Page 10
the movement sequence indicated by the arrow.
Do not touch the marked areas if the fire Maintenance records (available on request) Annex
damper is in operation because of injury danger.
1
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
1. External inspection
2
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
3
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
4. Internal inspection
Carry out inspection, as described at 2
4
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
L(+) AC 230 V / 50 Hz or DC 24 V
1 4
5 7
N(-)
PE
5
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
7. External inspection
8. Internal inspection
11
8.1 Internal casing inspection:
- Remove electric plug item of the solenoid valve
item after releasing the securing screw
- Dismantle triggering device item
- Through the open inspection aperture, with a light
source, check directly visible parts
- Clean as necessary; in the process the perimeter
Fig. 8 Fig. 9 seal item
must not be damaged
unlocked
26 25 27 1 4
locked
17
6
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
7
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
Group control
AC 230 V / 50 Hz or DC 24 V
L(+)
9 9
Electrical push-button, supplied by others
1
(close fire damper)
FD2
4 8 8 Sensor or detector, supplied by others (close fire
FD1 damper); for release mechanism using power off to
10 close principle, e. g. Trox smoke detector type RM-O/2
7 10 or RM-O-VS
11 7 11 7 7
Consumer electrics, supplied by others
N(-)
PE
(e. g. pilot lamp for position indication)
Electrical limit switch with double change-over contact
Damper blade shown in OPEN position (open and close circuit)
Electrical push-botton or switch with timing relay,
Functional diagram supplied by others (open fire damper)
1
Electric limit switch – Break circuit to the solenoid valve
PE item
in case of pressure loss (fire damper closes)
3/2 way solenoid valve (if no current, supply of
L(+) compressed air isolated)
S
10 N(-)
D Adjustable throttle valves (the valves marked * are
Control 9
Damper centre ommited in case of 1.2 bar pneumatic actuator)
blade
R P
A R
Compressed air connection
P Pneumatic actuator (operating pressure 1.2 or 6 bar)
A
A R
P R1/8” formale thread for
1.2 or 6 bar (overpressure)
S Fusible link, release temperature 72°C
P
D *
execute 0.5 m flexibly
V Quick-exhaust valve (only for pneumatic actuator
P V W 11 D D *
1.2 bar)
L(+) = AC 230 V / 50 Hz or DC 24 V
W 3/2 way pneumatic valve (pneumatic cylinder venting in
Damper blade shown in OPEN position the case of fusible link release)
8
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
29 11
9
Operating and Maintenance Instructions
for Fire Dampers of the
Types FK-K90 · FKN-K90 · E01-K90
W-4/2/EN/7
Type BLF230-T TR and BF230-T TR: To isolate from the Optionally BUS-Systems can be used to achieve the
main power supply, the system must incorporate a device required function, e. g. control-equipment of TroxNetCom
which disconnects the phase conductors (with at least a (pre wired for connection).
3 mm contact gap).
10
Gebrüder Trox GmbH Maintenance Protocol
Heinrich-Trox-Platz for fire damper
D-47504 Neukirchen-Vluyn
Telephone +49 / 28 45 / 2 02- 0 1
serial No. ____________
Telefax +49 / 28 45 / 2 02- 2 65
www.troxtechnik.com
e-mail trox@trox.de
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
The following maintenance steps were
in: ____________
in: ____________
in: ____________
in: ____________
February 04
Commissioning
carried out according to general buildings
August 03
next service
next service
next service
next service
supervision authorisations and Trox
Operating and Maintenance Instructions
prior to
W-4/2/EN/7,
___________
E016KM6
Article No. __________,
____________________________________________________________________________________
le
External inspection:
50
System: ___________
5.1
Item: ______________
p
____________________________________________________________________________________
am
Internal inspection:
50
System: ___________
Design changes reserved · All rights reserved © Gebrüder Trox GmbH (7/2003) · Leaflet No. E016ER0 · Edition 1
6
Item: ______________
____________________________________________________________________________________
5.3
Item: ______________
____________________________________________________________________________________
04.08.03
without deficits
Date /inspector
____________________________________________________________________________________
03.02.03
with deficits (see reverse)
Date /inspector
____________________________________________________________________________________
04.02.03
Deficits repaired
Date/inspector
1
Gebrüder Trox GmbH Maintenance Protocol
Heinrich-Trox-Platz for fire damper
D-47504 Neukirchen-Vluyn
Telephone +49 / 28 45 / 2 02- 0 1
serial No. ____________
Telefax +49 / 28 45 / 2 02- 2 65
www.troxtechnik.com
e-mail trox@trox.de
03.02.03
Deficits identified during inspection on: ___________
____________________________________________________________________________________
Deficits identified during inspection on: ___________
le
p
____________________________________________________________________________________
am
____________________________________________________________________________________
Deficits identified during inspection on: ___________