PANEL : PP-A1 TO PP-A7, PP-B1 & PP-B2, PP-B5 & PP-B6 SYSTEM : 1∅ PANEL : PP-B3 & PP-B4 SYSTEM : 1∅
MAIN CIRCUIT BREAKER : 50 AT MOUNTING : RECESSED TYPE MAIN CIRCUIT BREAKER : 70 AT MOUNTING : RECESSED TYPE
FEEDER CABLE : 2 - 8.0 mm² + 1 - 3.5 mm² THHN/THWN WIRE ENCLOSURE : HOME PANELBOARD FEEDER CABLE :2 - 14.0 mm² + 1 - 5.5 mm² THHN/THWN WIRE ENCLOSURE : HOME PANELBOARD
RACEWAY : 20mmØ PVC LOCATION : UNIT RACEWAY : 25mmØ PVC LOCATION : UNIT
CKT. CB RATING WIRES CONDUIT (PVC) CKT. CB RATING WIRES CONDUIT (PVC)
NO. CO LO HP DESCRIPTION VA VOLTS AMPERE AT PHASE THHN/THWN mmØ NO. CO LO HP DESCRIPTION VA VOLTS AMPERE AT PHASE THHN/THWN mmØ
1 2 ACU SPLIT TYPE 6240 230 27.13 40 1 2 - 5.5 mm² + 1 - 3.5 mm² 20 mmØ 1 2 ACU SPLIT TYPE 6240 230 27.13 40 1 2 - 5.5 mm² + 1 - 3.5 mm² 20 mmØ
2 8 CONVENIENCE OUTLET 1440 230 6.26 20 1 2 - 3.5 mm² + 1 - 3.5 mm² 20 mmØ 2 2 ACU SPLIT TYPE 6240 230 27.13 40 1 2 - 5.5 mm² + 1 - 3.5 mm² 20 mmØ
3 20 LIGHTING 800 230 3.48 20 1 2 - 3.5 mm² + 1 - 3.5 mm² 20 mmØ 3 8 CONVENIENCE OUTLET 1440 230 6.26 20 1 2 - 3.5 mm² + 1 - 3.5 mm² 20 mmØ
4 SPARE 1000 230 4.35 20 1 4 20 LIGHTING 800 230 3.48 20 1 2 - 3.5 mm² + 1 - 3.5 mm² 20 mmØ
5 SPARE 1000 230 4.35 20 1 5 SPARE 1000 230 4.35 20 1
TOTAL 10480 45.57 TOTAL 15720 68.35
COMPUTATION: COMPUTATION:
Icb = (AMPERE x 80% x 1.15) = 41.92 A Icb = (AMPERE x 80% x 1.15) = 62.88 A
PROJECT TITLE: PROJECT OWNER: SHEET CONTENTS: DESIGNED BY: W.P.B SHEET NO.
EARCON Builders
Wilfred P. Balagot SCHEDULE OF LOADS
Commercial Building w/ Basement & Roof Deck
P.T.R. NO.:
PROFESSIONAL ELECTRICAL ENGINEER
E.O.RAMIREZ
E-2
NOTE :
ACAD BY:
LOCATION : 31 Commonwealth Ave. Ext., Brgy. Sta. Monica, Nova., Q.C. PAGE NO. OF TOTAL NO.
DATE ISSUED: 01-09-18 T.I.N.: 125-478-641 THIS DRAWING AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF THE E.C.G.R. OF PAGES
TELEFAX : 9379493 l 9379495 ARCHITECT AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN WHOLE OR IN PART
CHECKED BY: