Dagachhu Hydro Power Project Annexure-2

Design of Upstream Wing Wall on Left Bank

Calculation of Bond Length Calculations of Rock Bolt

Calculation of Bond Length of grouted Rock Bolt

a) Bond between Bolt and grout


Grade of steel = Fe 500
Dia of bar used = 25.00 mm
Maximum service load on 1 anchor,P = 190.00 kN

As per clause 6.4.2 of IS 14448 : 1997


Assuming characteristic strength of the grout,fck = 25.00 N/mm2
Allowable bond stress, (fck/10) = 25.00/10 = 2.50 N/mm2
Max. Permissible allowable bond stress of deformed bars = 2.50 N/mm2
Considered allowable bond stress,ta (min of the above) = 2.50 N/mm2
As per clause 6.4.2.3 of IS 14448 : 1997
Anchorage length shall be obtained from following experssion

L = P.F
pdta
where,
L= Effective/fixed anchor length
P= Pull out force per anchor
F= FOS taken as 3
d= dia. of bar

L = 190.00*1000*FOS taken as = 2903 mm


3/(3.14*25.00*2.50)

b) Bond between Rock Bolt and Grout


As per Table 2 of IS 14448 : 1997
Safe bond stregth between grout and soil nail
Considering safe bond strength of 0.35 N/mm2 (t/FOS)
Dia. of hole for anchor bar = 45.00 mm
Anchorage length shall be = 190.00*1000/(3.14*45.00*0.35) = 3840 mm

As per clause 6.4.2.2 of IS 14448 : 1997


Fixed anchor length should not be less than 60*25.00 i.e 1500 mm

169122-41ER-0041-PB Page 1 of 1