Академический Документы
Профессиональный Документы
Культура Документы
ASTM F2280 (A490TC) tension control bolts. Bolts were flange plates and beam flanges. For additional instrumentation
initially brought to the snug-tight condition with connected information see Sato et al. (2008). The data reduction proce-
plies in firm contact followed by systematic tensioning of the dure was a modified version of one formulated by Uang and
bolts. For the beam web to shear tab connection the middle Bondad (1996). The procedure (see Appendix II) was used
bolt was tensioned first and then bolts were tensioned out- to compute the components of beam tip displacement, δtotal,
ward from the middle progressing in an alternating up and that are contributed by deformation of the beam, column,
down pattern. Flange plate to beam flange bolts were ten- panel zone and slip-bearing between the flange plates and
sioned, starting with the most rigid portion of the connection beam flanges.
near the face of the column and then working progressively
outward. EXPERIMENTAL RESULTS
Material Properties Several observations were made during testing that were
similar for all three specimens. Bolt slip, which produced
ASTM A992 steel was specified for all beam and column
very loud noises, occurred during early cycles (at 0.375%
members. ASTM A572 Gr. 50 steel was specified for all
or 0.5% drift) and on all subsequent cycles. Yielding in the
plate material. Material properties determined from tension
connection region, as evidenced by flaking of the whitewash,
coupon testing are shown in Table 2 and additional informa-
was observed to initiate at 2% drift. Beam flange and web
tion may be found in Sato, Newell and Wang (2008).
local buckling initiated at 4% drift, and lateral-torsional
buckling (LTB) of the beam together with twisting of the
Loading Protocol and Instrumentation
column was observed at 5% drift.
The loading sequence for beam-to-column moment connec- Testing of Specimen BFP-2 was stopped after one com-
tions as defined in the 2005 AISC Seismic Provisions was plete cycle at 6% drift due to safety concerns resulting from
used for testing (see Figure 3). Displacement was applied the observed column twisting [see Figure 5(a)]. For Speci-
at the beam tip and was controlled by the interstory drift men BFP-3 significant beam LTB and column twisting, as
angle. Specimens were instrumented with a combination of shown in Figure 5(b), were observed at 6% drift. For this
displacement transducers, strain gage rosettes, and uniaxial specimen, which did not require continuity plates, the unusu-
strain gages to measure global and local responses. Figure 4 al yielding pattern of the column, shown in Figure 6, might
shows the location of displacement transducers. Displace- have been caused by column flange local bending, web local
ment transducer δtotal measured the overall vertical displace- yielding, and column twisting (i.e., warping stress).
ment of the beam tip. δ1 and δ2 measured column movement. Specimen BFP-1 experienced net section fracture of the
δ3 and δ4 measured the average shear deformation of the beam bottom flange at the outermost bolt row on the second
column panel zone. δ5 and δ6 measured the slippage between excursion to 6% drift. Specimen BFP-3 failed in the same
Fig. 5. Beam lateral-torsional buckling and column twisting at 6% drift. Fig. 6. Specimen BFP-3: yielding in column.
Fig. 7. Specimen BFP-3: beam flange net section fracture. Fig. 8. Moment versus beam tip displacement relationships.
Fig. 9. Components of beam tip displacement. Fig. 10. Beam cyclic overstrength ratio.
(b) Comparison of strain gauges S26 and S27 (a) Strain profile (S17, S18, S19)
Fig. 11. Specimen BFP-2: column flange strains. Fig. 12. Specimen BFP-3: strain profiles across beam bottom flange.
Mpr = C pr Ry Fy Z x (A-1)
17. Check the column panel zone according to Section 9.3 NOTATION
or 10.3 of the AISC Seismic Provisions, as appropriate.
Ab Nominal unthreaded body area of bolt
The required shear strength of the panel zone shall be
determined from the summation of the moments at the Cpr Factor to account for peak connection strength, in-
column faces as determined by projecting moments cluding strain hardening, local restraint, additional
equal to Ry Fy Zx at the plastic hinge points to the column reinforcement, and other connection conditions
faces. Add twice the thickness of the flange plate to the
D Nominal dead load
beam depth for determining the value of d.