ECP EVAPORATIVE CONDENSERS

Technical Bulletin: 0306_216


Evaporative Condensers
Provide Refrigeration Solutions
Designed with New Innovative Coil Technology
To Provide Improved Thermal Transfer and Operating Performance
on Large Refrigeration Systems

ECP Evaporative Condenser is the preferred ■ Five cabinet sizes 10x18, 12x12, 12x18,
heat of rejection method for large refrigeration 12x24 and 12x36.
systems by combining superior water delivery
and coil technology.
■ 60 total models ranging from 331 to 1922
nominal tons.
■ Unique water delivery through patented 3/4”
diameter spray nozzle providing clog-free
operation that minimizes mineral build up.
■ Advanced design drift eliminators.
■ Heavy wall steel tube coil for longer coil life.
The coil assembly is hot dipped galvanized
after fabrication for added protection.

How It Works
ECP Series Principle of Operation –
Forced Draft, Axial Fan, and Counter Flow Design

1
1 PVC Moisture eliminators 3 Highly-Efficient Air Delivery
minimize moisture loss while 2 System allows maximum airflow
maximizing airflow. and is driven by high efficiency
totally enclosed motors.
2 Water Recirculation Systems
combines PVC and stainless 4 The Water Delivery and Catch
steel for superior corrosion System provides efficient
protection while incorporating operation through a close-
spray nozzles that deliver 360˚ coupled pump
spray pattern for maximum coil driven by a high efficient totally
coverage. enclosed pump motor.

3 4

2 ECP EVAPORATIVE CONDENSERS


Evaporative Condenser Nomenclature

ECP 1106 – 03 M D

Evaporator Tons Coil Code

Nominal unit capacity in tons of B E


R-22 at standard conditions of
C F
105˚F condensing, 40˚F suction
and 78˚F air wet bulb. D G

Box Size Designator

01 = 12' wide x 12' long

02 = 12' wide x 18' long

03 = 12' wide x 24' long


(connections one end)
Total Fan Horsepower Code
04 = 12' wide x 24' long
(connections both ends) A= 5 I = 40

05 = 12' wide x 36' long B = 7.5 J = 45


(connections both ends) C = 10 K = 50
06 = 10' wide x 18' long D = 15 L = 60

E = 20 M = 80

F = 22.5 N = 90

G = 25 O = 120

H = 30

ECP EVAPORATIVE CONDENSERS 3


Model Selection

Selection Procedure 1 – Based on Heat of Rejection Method


Heat of Rejection Method is typically Example
applied with centrifugal, hermetic reciprocating, Given:
Type of Compressor Hermetic Compressor
or rotary screw type compressors for selecting
Entering Wet Bulb Temperature 74 ºF
an evaporative condenser. This method can also Compressor KW 55.0 KW
be used with an open compressor along with the Compressor Evaporator Capacity 850 tons
Evaporator Ton Method. Condensing Temperature 100 ºF
Refrigerant Type R22
Heat of Rejection by the compressor loads can be
calculated by using the following two formulas: Selection
1) Determine Total Heat Rejection
Open Compressors Evaporator - 850 tons x 12,000 = 10,200,000 BTU/hr
Heat Rejection = Compressor - 55.0 KW x 3413 = 187,715 BTU/hr
Evaporator Load (BTU/hr) + Compressor BHP x 2545
Total Heat of Rejection = 10,387,715 BTU/hr
Hermetic Compressors
Heat Rejection = 2) Correction for Design Conditions
Evaporator Load (BTU/hr) + Compressor KW x 3413 Capacity Factor for 74 ºF WB and 100 ºF condensing
temperature = 10,387,825 BTU/hr x 1.09 = 11,322,729
Selection Procedure
BTU/hr or 11,323 MBH. The select model ECP-786-02-
Use the capacity factor from Tables 1 or 2 (depending
JD has a heat of rejection of 11,546 MBH, which is
on refrigerant). Next multiply total heat of rejection
greater than or equal to the required total heat of
times the capacity factor. Select model from Table 3.
rejection. This can change based on required layout
Models are grouped by housing size. The selected unit
and horsepower.
heat of rejection should be greater or equal to what
has been calculated.

TABLE 1 - R717 - AMMONIA - HEAT REJECTION CAPACITY FACTORS


Cond. Pressure - Cond.
psig Wet Bulb Temperature - °F
Temperature
R717 °F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82
151.7 85 0.98 1.02 1.06 1.11 1.18 1.24 1.34 1.43 1.56 1.70 1.89 2.13 2.47 2.96 - - -

165.9 90 0.83 0.86 0.89 0.93 0.97 1.01 1.08 1.14 1.22 1.28 1.39 1.51 1.66 1.87 2.12 2.51 3.08

171.9 92 0.78 0.81 0.84 0.87 0.91 0.95 1.00 1.03 1.09 1.16 1.24 1.34 1.47 1.62 1.81 2.07 2.44

178.0 94 0.73 0.76 0.79 0.82 0.85 0.88 0.93 0.98 1.00 1.07 1.13 1.20 1.31 1.42 1.57 1.77 2.03

181.1 95 0.71 0.74 0.76 0.79 0.82 0.84 0.89 0.94 0.98 1.03 1.08 1.17 1.25 1.34 1.48 1.64 1.87

185.0 96.3 0.69 0.71 0.73 0.76 0.78 0.81 0.84 0.88 0.92 0.97 1.02 1.09 1.16 1.25 1.36 1.50 1.68

190.6 98 0.66 0.68 0.70 0.73 0.75 0.78 0.81 0.84 0.88 0.91 0.97 1.02 1.08 1.15 1.23 1.35 1.49

197.2 100 0.63 0.65 0.67 0.69 0.71 0.73 0.75 0.78 0.80 0.83 0.89 0.92 0.97 1.03 1.12 1.21 1.32

214.2 105 0.56 0.57 0.58 0.59 0.61 0.62 0.64 0.66 0.68 0.70 0.74 0.76 0.81 0.85 0.89 0.93 1.01

232.3 110 0.50 0.51 0.52 0.53 0.54 0.55 0.57 0.58 0.60 0.62 0.63 0.67 0.69 0.72 0.75 0.78 0.83

4 ECP EVAPORATIVE CONDENSERS


Model Selection

Selection Procedure 1 continued


TABLE 2 - R134A AND R22 - HEAT REJECTION CAPACITY FACTORS
Cond. Pressure - Cond.
psig Wet Bulb Temperature - °F
Temperature
R134A R22 °F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82
95.2 155.7 85 1.10 1.15 1.20 1.25 1.32 1.39 1.50 1.61 1.76 1.91 2.13 2.40 2.78 3.33 - - -

104.3 168.4 90 0.93 0.97 1.00 1.04 1.09 1.14 1.21 1.28 1.37 1.44 1.56 1.70 1.87 2.10 2.38 2.82 3.46

108.1 173.7 92 0.88 0.91 0.94 0.98 1.02 1.06 1.13 1.16 1.23 1.31 1.40 1.51 1.65 1.82 2.04 2.33 2.74

112.0 179.1 94 0.83 0.86 0.89 0.92 0.95 0.99 1.04 1.10 1.13 1.20 1.27 1.35 1.47 1.60 1.76 1.99 2.28

113.9 181.9 95 0.80 0.83 0.86 0.89 0.92 0.95 1.00 1.05 1.11 1.16 1.22 1.32 1.41 1.50 1.66 1.84 2.10

115.9 184.6 96 0.78 0.81 0.83 0.86 0.89 0.92 0.97 1.02 1.07 1.11 1.18 1.24 1.34 1.43 1.56 1.72 1.93

120.0 190.2 98 0.75 0.77 0.79 0.82 0.84 0.87 0.91 0.95 0.98 1.02 1.09 1.15 1.22 1.30 1.38 1.51 1.68

124.1 195.9 100 0.71 0.73 0.75 0.77 0.80 0.82 0.85 0.88 0.90 0.93 1.00 1.03 1.09 1.16 1.26 1.36 1.49

134.9 210.8 105 0.63 0.64 0.65 0.67 0.68 0.70 0.72 0.75 0.77 0.790 0.83 0.86 0.91 0.95 1.00 1.05 1.14

146.4 226.4 110 0.56 0.57 0.58 0.60 0.61 0.62 0.64 0.65 0.67 0.70 0.71 0.75 0.78 0.81 0.84 0.88 0.93

TABLE 3 - HEAT OF REJECTION MBH FOR ECP MODELS

Model Number Heat Rej. MBH Model Number Heat Rej. MBH Model Number Heat Rej. MBH
ECP-331-01-BB 4,862 ECP-867-03-HC 12,736 ECP-1572-05-ND 23,093
ECP-344-01-CB 5,053 ECP-935-03-IC 13,735 ECP-1648-05-NF 24,209
ECP-362-01-DB 5,318 ECP-1000-03-KC 14,690 ECP-1754-05-OF 25,766
ECP-416-01-DC 6,111 ECP-1070-03-LD 15,718 ECP-1798-05-NG 26,413
ECP-437-01-EC 6,420 ECP-1123-03-LF 16,497 ECP-1922-05-NG 28,234
ECP-470-01-ED 6,904 ECP-1200-03-MF 17,628 ECP-475-06-DB 6,978
ECP-498-01-GD 7,316 ECP-688-04-EB 10,107 ECP-514-06-FB 7,551
ECP-519-01-HD 7,624 ECP-723-04-HB 10,621 ECP-572-06-FC 8,403
ECP-540-01-HF 7,933 ECP-832-04-HC 12,222 ECP-608-06-HC 8,932
ECP-574-01-IF 8,432 ECP-875-04-IC 12,854 ECP-640-06-IC 9,402
ECP-588-01-HG 8,638 ECP-940-04-ID 13,809 ECP-684-06-ID 10,048
ECP-629-01-IG 9,240 ECP-996-04-KD 14,631 ECP-700-06-JD 10,283
ECP-524-02-CB 7,698 ECP-1038-04-LD 15,248
ECP-581-02-DB 8,535 ECP-1080-04-LF 15,865
ECP-620-02-HB 9,108 ECP-1148-04-MF 16,864
ECP-646-02-FC 9,490 ECP-1175-04-HG 17,261
ECP-686-02-HC 10,077 ECP-1257-04-IG 18,465
ECP-730-02-HD 10,724 ECP-1048-05-HB 15,395
ECP-767-02-ID 11,267 ECP-1162-05-JB 17,070
ECP-786-02-JD 11,546 ECP-1240-05-LB 18,216
ECP-824-02-JF 12,105 ECP-1292-05-FC 18,979
ECP-877-02-LF 12,883 ECP-1372-05-LC 20,155
ECP-899-02-JG 13,206 ECP-1460-05-LD 21,447
ECP-961-02-LG 14,117 ECP-1534-05-MD 22,534

ECP EVAPORATIVE CONDENSERS 5


Model Selection

Selection Procedure 2 – Based on Evaporator Ton Method

This method is only used when using an Example


open type reciprocating compressor application. Given:
Evaporator Head Load 500 tons
The condenser model numbers are equal to Entering Wet Bulb Temperature 74 ºF
the capacity of the evaporator condenser at Condensing Temperature 100 °F
Suction Temperature 10 °F
standard conditions of 105 °F condensing,
Refrigerant Type R134A
40 °F suction, and 78 °F wet bulb temperatures Unit Size -01
for R22 or R134 refrigerants. Selections using
non-standard conditions can be accomplished Selection
by using Tables 4 and 5 to select an adjustment Evaporative Capacity Factor = 1.08
Suction Pressure Capacity Factor = 1.09
factor. The adjustment factor would be
500 tons x 1.08 x 1.09 = 589 adjusted tons
multiplied by the system heat load in tons.
Then select the model that has an evaporator The following selection in the -01 size meets
ton load equal or greater to the calculated result. the capacity requirements.

Model Heat Rej. MBH


ECP-629-01-IG 629

TABLE 4 - R717 - AMMONIA - EVAPORATOR CAPACITY FACTORS

Cond. Pressure - Cond.


psig Wet Bulb Temperature - °F
Temperature
R717 °F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82
151.7 85 0.99 1.03 1.07 1.12 1.19 1.25 1.34 1.44 1.56 1.71 1.90 2.15 2.49 - - - -

165.9 90 0.85 0.88 0.91 0.95 1.00 1.04 1.08 1.15 1.22 1.31 1.41 1.54 1.69 1.90 2.19 2.54 -

171.9 92 0.80 0.83 0.86 0.89 0.94 0.98 1.01 1.06 1.12 1.20 1.28 1.38 1.51 1.66 1.86 2.13 -

178.0 94 0.76 0.78 0.81 0.84 0.88 0.91 0.95 1.00 1.05 1.11 1.18 1.25 1.35 1.47 1.64 1.83 -

181.1 95 0.73 0.76 0.79 0.81 0.85 0.88 0.92 0.96 1.00 1.05 1.11 1.20 1.27 1.39 1.52 1.69 1.93

185.0 96.3 0.72 0.74 0.76 0.79 0.81 0.84 0.88 0.91 0.96 1.01 1.06 1.13 1.21 1.30 1.41 1.56 1.74

190.6 98 0.69 0.71 0.73 0.76 0.78 0.81 0.84 0.87 0.91 0.95 0.99 1.06 1.12 1.20 1.29 1.40 1.55

197.2 100 0.66 0.68 0.70 0.72 0.74 0.76 0.79 0.81 0.84 0.88 0.91 0.97 1.02 1.08 1.15 1.24 1.39

214.2 105 0.59 0.60 0.62 0.63 0.64 0.66 0.68 0.70 0.72 0.74 0.78 0.81 0.85 0.90 0.94 0.99 1.07

232.3 110 0.54 0.55 0.56 0.57 0.58 0.59 0.61 0.62 0.64 0.66 0.68 0.71 0.74 0.77 0.80 0.84 0.89

Suction Pressure - psig 3.6 9.0 15.7 23.8 33.5 45.0 58.6 74.5

Suction Temperature °F -20 -10 0 +10 +20 +30 +40 +50

Capacity Factor 1.14 1.11 1.07 1.04 1.00 0.98 0.95 0.93

6 ECP EVAPORATIVE CONDENSERS


Model Selection

Selection Procedure 2 continued

TABLE 5 - R134A AND R22 - EVAPORATOR CAPACITY FACTORS

Cond. Pressure - Cond.


psig Wet Bulb Temperature - °F
Temperature
R134A R22 °F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82
95.2 155.7 85 1.05 1.09 1.14 1.19 1.26 1.33 1.42 1.53 1.66 1.82 2.02 2.29 2.65 - - - -
104.3 168.4 90 0.90 0.93 0.96 1.01 1.06 1.11 1.15 1.22 1.30 1.39 1.50 1.64 1.80 2.02 2.33 2.70 -
108.1 173.7 92 0.85 0.88 0.91 0.95 0.99 1.04 1.07 1.13 1.19 1.27 1.36 1.47 1.60 1.76 1.98 2.26 -
112.0 179.1 94 0.80 0.83 0.86 0.89 0.93 0.97 1.01 1.06 1.12 1.18 1.25 1.33 1.43 1.56 1.74 1.94 -
113.9 181.9 95 0.78 0.81 0.84 0.87 0.90 0.93 0.97 1.02 1.07 1.12 1.18 1.28 1.35 1.48 1.62 1.80 2.05
115.9 184.6 96 0.76 0.79 0.82 0.85 0.88 0.91 0.95 0.99 1.03 1.08 1.14 1.23 1.30 1.39 1.52 1.66 1.89
120.0 190.2 98 0.73 0.76 0.78 0.80 0.83 0.86 0.89 0.93 0.96 1.01 1.05 1.13 1.19 1.27 1.37 1.49 1.65
124.1 195.9 100 0.70 0.72 0.74 0.76 0.79 0.81 0.84 0.87 0.90 0.93 0.97 1.03 1.08 1.15 1.22 1.32 1.47
134.9 210.8 105 0.63 0.64 0.65 0.67 0.68 0.70 0.72 0.75 0.77 0.79 0.83 0.86 0.91 0.95 1.00 1.05 1.14
146.4 226.4 110 0.57 0.58 0.59 0.61 0.62 0.63 0.65 0.66 0.68 0.70 0.72 0.75 0.78 0.82 0.85 0.89 0.94

Suction Pressure - R134A -1.8 1.9 6.5 11.9 18.4 26.1 35.0 45.4
psig
R22 10.2 16.5 24.0 32.8 43.0 54.9 68.5 84.0
Suction Temp. °F -20 -10 0 +10 +20 +30 +40 +50
Capacity Factor 1.20 1.16 1.13 1.09 1.06 1.03 1.00 0.98

TABLE 6 - CONDENSER MODEL NUMBERS

Model Number Evaporator Tons Model Number Evaporator Tons Model Number Evaporator Tons
ECP-331-01-BB 331 ECP-899-02-JG 899 ECP-1292-05-FC 1,292
ECP-344-01-CB 344 ECP-961-02-LG 961 ECP-1372-05-LC 1,372
ECP-362-01-DB 362 ECP-867-03-HC 867 ECP-1460-05-LD 1,460
ECP-416-01-DC 416 ECP-935-03-IC 935 ECP-1534-05-MD 1,534
ECP-437-01-EC 437 ECP-1000-03-KC 1,000 ECP-1572-05-ND 1,572
ECP-470-01-ED 470 ECP-1070-03-LD 1,070 ECP-1648-05-NF 1,648
ECP-498-01-GD 498 ECP-1123-03-LF 1,123 ECP-1754-05-OF 1,754
ECP-519-01-HD 519 ECP-1200-03-MF 1,200 ECP-1798-05-NG 1,798
ECP-540-01-HF 540 ECP-688-04-EB 688 ECP-1922-05-NG 1,922
ECP-574-01-IF 574 ECP-723-04-HB 723 ECP-475-06-DB 475
ECP-588-01-HG 588 ECP-832-04-HC 832 ECP-514-06-FB 514
ECP-629-01-IG 629 ECP-875-04-IC 875 ECP-572-06-FC 572
ECP-524-02-CB 524 ECP-940-04-ID 940 ECP-608-06-HC 608
ECP-581-02-DB 581 ECP-996-04-KD 996 ECP-640-06-IC 640
ECP-620-02-HB 620 ECP-1038-04-LD 1,038 ECP-684-06-ID 684
ECP-646-02-FC 646 ECP-1080-04-LF 1,080 ECP-700-06-JD 700
ECP-686-02-HC 686 ECP-1148-04-MF 1,148
ECP-730-02-HD 730 ECP-1175-04-HG 1,175
ECP-767-02-ID 767 ECP-1257-04-IG 1,257
ECP-786-02-JD 786 ECP-1048-05-HB 1,048
ECP-824-02-JF 824 ECP-1162-05-JB 1,162
ECP-877-02-LF 877 ECP-1240-05-LB 1,240

ECP EVAPORATIVE CONDENSERS 7


Engineering Data

AIR FLOW

OPTIONAL PUMP
PIPING LOCATION

11' 9"
2' 3-15/16"
5' 7-7/8" 3' 9/16"

BFW REFRIG IN

AIR INLET SCREENING


NOT SHOWN FOR B
CLARITY BFW REFRIG OUT
2' 2-1/2" 11' 7-1/4" 1' 10"

5-3/4"
2" DIA. MAKEUP

A 9' 0" ACCESS


3" DIA. OVERFLOW

2" DIA. DRAIN


11' 7-3/4"

OPTIONAL PUMP
PIPING LOCATION

TABLE 7 - ENGINEERING DATA


Fans Pump Refrigerant Coil Weight - lbs Remote Sump Dimensions - in
R717 Motor R717 Charge Volume Heaviest Gallons Outlet Height - Coil -
Model Number Tons HP CFM HP GPM - lbs - ft3 Shipping Operating Section Reg. Size A B
ECP-331-01-BB 227 7.5 55,000 5 551 446 47 15,020 21,920 9,730 500 8 in 173.75 32
ECP-344-01-CB 243 10 59,750 5 551 446 47 15,020 21,920 9,730 500 8 in 173.75 32
ECP-362-01-DB 271 15 68,970 5 551 446 47 15,160 22,060 9,730 500 8 in 173.75 32
ECP-416-01-DC 297 15 70,322 5 551 549 58 17,320 24,220 11,890 500 8 in 182.75 41
ECP-437-01-EC 311 20 73,040 5 551 549 58 17,360 24,260 11,890 500 8 in 182.75 41
ECP-470-01-ED 328 20 71,990 5 551 652 69 19,380 26,280 13,910 500 8 in 191.75 50
ECP-498-01-GD 349 25 77,200 5 551 652 69 19,450 26,350 13,910 500 8 in 191.75 50
ECP-519-01-HD 365 30 82,400 5 551 652 69 19,470 26,370 13,910 500 8 in 191.75 50
ECP-540-01-HF 382 30 80,900 5 551 698 74 20,470 27,420 14,910 500 8 in 191.75 50
ECP-574-01-IF 406 40 88,200 5 551 698 74 20,680 27,630 14,910 500 8 in 191.75 50
ECP-588-01-HG 417 30 77,800 5 551 808 86 22,680 29,640 17,120 500 8 in 200.75 59
ECP-629-01-IG 446 40 85,600 5 551 808 86 22,890 29,850 17,120 500 8 in 200.75 59

Notes: 4. Left hand arrangement, which is available upon request is shown as


1. Air Inlet screens, which are included with condenser units, are not hidden lines. Model only has single pump unless pumps are shown
shown on drawing to allow for clarity of unit. as solid lines.
2. The model number represents the nominal tons using R-22 at 5. The remote sump gallons required are based on water volume in unit
105 ºF cond., 40 ºF suction, and 78 ºF wet bulb temperatures. spray system plus unit basin operating level. Allow for additional
Example: ECP-437-01-EC has a nominal ton rating of 437. water in remote sump to cover pump suction and piping.
3. R717 nominal tons are based on 96.3 ºF cond., 20 ºF suction and 6. Refrigerant charge is based on R717. To determine charge of R134A
78 ºF wet bulb temperatures. multiply by 1.98. To determine charge of R22 multiply by 1.93.

8 ECP EVAPORATIVE CONDENSERS


Engineering Data

AIR FLOW

OPTIONAL PUMP
PIPING LOCATION

11' 9"
2' 3-15/16"
5' 7-7/8" 3' 9/16"

AIR INLET BFW REFRIG IN


SCREENING NOT
SHOWN FOR
CLARITY B
BFW REFRIG OUT
2' 2-1/2" 17' 7-1/4" 1' 10"

5-3/4" 2" DIA. MAKEUP

A 9' 0" ACCESS


3" DIA. OVERFLOW

2" DIA. DRAIN


11' 7-3/4"

OPTIONAL PUMP
PIPING LOCATION

TABLE 8 - ENGINEERING DATA


Fans Pump Refrigerant Coil Weight - lbs Remote Sump Dimensions - in
R717 Motor R717 Charge Volume Heaviest Gallons Outlet Height - Coil -
Model Number Tons HP CFM HP GPM - lbs - ft3 Shipping Operating Section Reg. Size A B
ECP-524-02-CB 375 10 & 5 90,000 5 837 655 69 21,710 32,170 14,230 720 10 in 173.75 32
ECP-581-02-DB 416 15 & 7.5 103,200 5 837 655 69 21,900 32,360 14,230 720 10 in 173.75 32
ECP-620-02-HB 447 20 & 10 115,696 5 837 655 69 21,970 32,430 14,230 720 10 in 173.75 32
ECP-646-02-FC 458 15 & 7.5 100,200 5 837 810 86 24,890 35,350 17,220 720 10 in 182.75 41
ECP-686-02-HC 484 20 & 10 110,034 5 837 810 86 24,960 35,420 17,220 720 10 in 182.75 41
ECP-730-02-HD 505 20 & 10 108,492 5 837 965 102 27,960 38,420 20,220 720 10 in 191.75 50
ECP-767-02-ID 538 25 & 15 116,400 5 837 965 102 28,170 38,630 20,220 720 10 in 191.75 50
ECP-786-02-JD 551 30 & 15 124,320 5 837 965 102 28,190 38,650 20,220 720 10 in 191.75 50
ECP-824-02-JF 583 30 & 15 121,350 5 837 1035 110 29,700 40,250 21,740 720 10 in 191.75 50
ECP-877-02-LF 620 40 & 20 132,300 5 837 1035 110 29,960 40,500 21,740 720 10 in 191.75 50
ECP-899-02-JG 638 30 & 15 116,700 7.5 900 1202 127 32,670 43,470 24,950 720 10 in 200.75 59
ECP-961-02-LG 682 40 & 20 128,400 7.5 900 1202 127 32,920 43,720 24,950 720 10 in 200.75 59

Notes: 4. Left hand arrangement, which is available upon request is shown as


1. Air Inlet screens, which are included with condenser units, are not hidden lines. Model only has single pump unless pumps are shown
shown on drawing to allow for clarity of unit. as solid lines.
2. The model number represents the nominal tons using R-22 at 5. The remote sump gallons required are based on water volume in unit
105 ºF cond., 40 ºF suction, and 78 ºF wet bulb temperatures. spray system plus unit basin operating level. Allow for additional
Example: ECP-437-01-EC has a nominal ton rating of 437. water in remote sump to cover pump suction and piping.
3. R717 nominal tons are based on 96.3 ºF cond., 20 ºF suction and 6. Refrigerant charge is based on R717. To determine charge of R134A
78 ºF wet bulb temperatures. multiply by 1.98. To determine charge of R22 multiply by 1.93.

ECP EVAPORATIVE CONDENSERS 9


Engineering Data

AIR FLOW

11' 9"
2' 3-15/16"
5' 7-7/8" 3' 9/16"

AIR INLET BFW REFRIG IN


SCREENING
NOT SHOWN
FOR CLARITY B
BFW REFRIG OUT
2' 2-1/2" 23' 8" 1' 10"

9-1/8" 2" DIA. MAKEUP

A 9' 0" ACCESS


3" DIA.
OVERFLOW
2" DIA. DRAIN
11' 7-3/4"

TABLE 9 - ENGINEERING DATA


Fans Pump Refrigerant Coil Weight - lbs Remote Sump Dimensions - in
R717 Motor R717 Charge Volume Heaviest Gallons Outlet Height - Coil -
Model Number Tons HP CFM HP GPM - lbs - ft3 Shipping Operating Section Reg. Size A B
ECP-867-03-HC 614 (2) 15 133,600 (2) 5 1,122 1,071 114 32,720 46,790 23,510 1,060 10 in 185.75 41
ECP-935-03-IC 661 (2) 20 147,120 (2) 5 1,122 1,071 114 32,800 46,870 23,510 1,060 10 in 185.75 41
ECP-1000-03-KC 708 (2) 25 160,800 (2) 5 1,122 1,071 114 32,940 47,010 23,510 1,060 10 in 185.75 41
ECP-1070-03-LD 759 (2) 30 164,800 (2) 5 1,122 1,279 136 36,950 51,020 27,480 1,060 10 in 194.75 50
ECP-1123-03-LF 795 (2) 30 160,400 (2) 5 1,122 1,373 145 38,980 53,150 29,510 1,060 10 in 194.75 50
ECP-1200-03-MF 850 (2) 40 175,600 (2) 5 1,122 1,373 145 39,400 53,530 29,510 1,060 10 in 194.75 50
ECP-688-04-EB 485 (2) 10 119,500 (2) 5 1,122 892 95 28,400 42,470 9,730 1,060 10 in 173.75 32
ECP-723-04-HB 543 (2) 15 137,940 (2) 5 1,122 892 95 28,670 42,740 9,730 1,060 10 in 173.75 32
ECP-832-04-HC 595 (2) 15 140,644 (2) 5 1,122 1,098 116 32,990 47,060 11,890 1,060 10 in 182.75 41
ECP-875-04-IC 621 (2) 20 146,080 (2) 5 1,122 1,098 116 33,070 47,140 11,890 1,060 10 in 182.75 41
ECP-940-04-ID 656 (2) 20 143,980 (2) 5 1,122 1,303 138 37,110 51,180 13,910 1,060 10 in 191.75 50
ECP-996-04-KD 697 (2) 25 154,400 (2) 5 1,122 1,303 138 37,250 51,320 13,910 1,060 10 in 191.75 50
ECP-1038-04-LD 729 (2) 30 164,800 (2) 5 1,122 1,303 138 37,250 51,320 13,910 1,060 10 in 191.75 50
ECP-1080-04-LF 764 (2) 30 161,800 (2) 5 1,122 1,395 148 39,290 53,460 15,910 1,060 10 in 191.75 50
ECP-1148-04-MF 812 (2) 40 176,400 (2) 5 1,122 1,395 148 39,710 55,880 15,910 1,060 10 in 191.75 50
ECP-1175-04-HG 834 (2) 30 155,600 (2) 5 1,122 1,617 171 43,710 57,900 18,290 1,060 10 in 200.75 59
ECP-1257-04-IG 892 (2) 40 171,200 (2) 5 1,122 1,617 171 44,130 58,320 18,290 1,060 10 in 200.75 59

Notes:
See 1 through 6 under Table 8 on page 11. Model with -03 box size (ECP-xxxx-03) have refrigerant connections on one end and pump piping on
both ends. Models with -04 box size (ECP-xxxx-04) have refrigerant connections on both ends and pump piping on both ends.

10 ECP EVAPORATIVE CONDENSERS


Engineering Data

AIR FLOW

AIR INLET
SCREENING
NOT
SHOWN 11' 9"
FOR 2' 3-15/16"
CLARITY 5' 7-7/8" 3' 9/16"

BFW REFRIG IN
2' 2-1/2"
35' 7-7/8" 1' 10" B
BFW REFRIG
OUT
2" DIA.
5-3/4" MAKEUP
ACCESS
A 9' 0"
3" DIA.
OVERFLOW
2" DIA.
DRAIN
11' 7-3/4"

TABLE 10 - ENGINEERING DATA


Fans Pump Refrigerant Coil Weight - lbs Remote Sump Dimensions - in
R717 Motor R717 Charge Volume Heaviest Gallons Outlet Height - Coil -
Model Number Tons HP CFM HP GPM - lbs - ft3 Shipping Operating Section Reg. Size A B
ECP-1048-05-HB 750 (2) 10 & (2) 5 180,000 (2) 5 1,693 1,310 139 43,310 64,500 14,230 1,460 12 in 173.75 32
ECP-1162-05-JB 832 (2) 15 & (2) 7.5 206,400 (2) 5 1,693 1,310 139 43,700 64,890 14,230 1,460 12 in 173.75 32
ECP-1240-05-LB 894 (2) 20 & (2) 10 231,392 (2) 5 1,693 1,310 139 43,840 65,030 14,230 1,460 12 in 173.75 32
ECP-1292-05-FC 915 (2) 15 & (2) 7.5 200,400 (2) 5 1,693 1,620 172 49,680 70,870 17,220 1,460 12 in 182.75 41
ECP-1372-05-LC 968 (2) 20 & (2) 10 220,068 (2) 5 1,693 1,620 172 49,820 71,010 17,220 1,460 12 in 182.75 41
ECP-1460-05-LD 1010 (2) 20 & (2) 10 216,984 (2) 5 1,693 1,931 205 55,820 77,010 20,220 1,460 12 in 191.75 50
ECP-1534-05-MD 1075 (2) 25 & (2) 15 232,800 (2) 5 1,693 1,931 205 56,230 77,420 20,220 1,460 12 in 191.75 50
ECP-1572-05-ND 1102 (2) 30 & (2) 15 248,640 (2) 5 1,693 1,931 205 56,280 77,470 20,220 1,460 12 in 191.75 50
ECP-1648-05-NF 1166 (2) 30 & (2) 15 242,700 (2) 5 1,693 2,070 219 59,300 73,770 21,740 1,460 12 in 191.75 50
ECP-1754-05-OF 1240 (2) 40 & (2) 20 264,600 (2) 5 1,693 2,070 219 59,820 81,880 21,740 1,460 12 in 191.75 50
ECP-1798-05-NG 1276 (2) 30 & (2) 15 233,400 (2) 7.5 1,800 2,405 255 65,240 87,780 24,950 1,460 12 in 200.75 59
ECP-1922-05-NG 1364 (2) 40 & (2) 20 256,800 (2) 7.5 1,800 2,405 255 65,740 88,280 24,950 1,460 12 in 200.75 59

Notes: 3. R717 nominal tons are based on 96.3 ºF cond., 20 ºF suction and 78
1. Air Inlet screens, which are included with condenser units, are not ºF wet bulb temperatures.
shown on drawing to allow for clarity of unit. 4. The remote sump gallons required are based on water volume in unit
2. The model number represents the nominal tons using R-22 at spray system plus unit basin operating level. Allow for additional
105 ºF cond., 40 ºF suction, and 78 ºF wet bulb temperatures. water in remote sump to cover pump suction and piping.
Example: ECP-437-01-EC has a nominal ton rating of 437. 5. Refrigerant charge is based on R717. To determine charge of R134A
multiply by 1.98. To determine charge of R22 multiply by 1.93.

ECP EVAPORATIVE CONDENSERS 11


Engineering Data

AIR FLOW

OPTIONAL PUMP
PIPING LOCATION

9' 9"
2' 3-15/16"
5' 7-7/8" 2' 9/16"

AIR INLET BFW REFRIG IN


SCREENING NOT
SHOWN FOR
CLARITY B
BFW REFRIG OUT
2' 2-1/2" 17' 7-1/4" 1' 10"

5-3/4" 2" DIA. MAKEUP

A 9' 0" ACCESS


3" DIA. OVERFLOW

2" DIA. DRAIN


9' 7-3/4"

OPTIONAL PUMP
PIPING LOCATION

TABLE 11 - ENGINEERING DATA


Fans Pump Refrigerant Coil Weight - lbs Remote Sump Dimensions - in
R717 Motor R717 Charge Volume Heaviest Gallons Outlet Height - Coil -
Model Number Tons HP CFM HP GPM - lbs - ft3 Shipping Operating Section Reg. Size A B
ECP-475-06-DB 345 10 & 5 85,221 5 694 529 56 19,240 28,000 12,220 670 10 in 173.75 32
ECP-514-06-FB 380 15 & 7.5 96,399 5 694 529 56 19,430 28,190 12,220 670 10 in 173.75 32
ECP-572-06-FC 407 15 & 7.5 93,970 5 694 654 69 21,980 30,740 14,770 670 10 in 182.75 41
ECP-608-06-HC 438 20 & 10 102,663 5 694 654 69 22,050 30,810 14,770 670 10 in 182.75 41
ECP-640-06-IC 467 25 & 15 111,066 5 694 654 69 22,260 31,020 14,770 670 10 in 182.75 41
ECP-684-06-ID 482 25 & 15 106,950 5 694 780 83 24,800 33,560 17,310 670 10 in 191.75 50
ECP-700-06-JD 499 30 & 15 110,576 5 694 780 83 24,820 33,580 17,310 670 10 in 191.75 50

Notes: 4. Left hand arrangement, which is available upon request is shown as


1. Air Inlet screens, which are included with condenser units, are not hidden lines. Model only has single pump unless pumps are shown
shown on drawing to allow for clarity of unit. as solid lines.
2. The model number represents the nominal tons using R-22 at 5. The remote sump gallons required are based on water volume in unit
105 ºF cond., 40 ºF suction, and 78 ºF wet bulb temperatures. spray system plus unit basin operating level. Allow for additional
Example: ECP-437-01-EC has a nominal ton rating of 437. water in remote sump to cover pump suction and piping.
3. R717 nominal tons are based on 96.3 ºF cond., 20 ºF suction and 6. Refrigerant charge is based on R717. To determine charge of R134A
78 ºF wet bulb temperatures. multiply by 1.98. To determine charge of R22 multiply by 1.93.

12 ECP EVAPORATIVE CONDENSERS


ECP Specifications

Base Drive assembly and fan shall be located at


Furnish a factory assembled evaporative lower section of unit to provide easy access
condenser with galvanized steel structure and from exterior of unit.
pan. Shall consist of ______ unit(s), as shown
on plans. The limiting overall dimensions of the Fan Motor(s) shall be ______ hp maximum,
unit shall be ______ wide, ______ long, and Totally Enclosed, Fan-Cooled, 1.15 service factor,
______ high. Total operating horsepower of suitable for outdoor condenser applications.
all fans shall not exceed ______ hp. Condenser Electrical characteristics shall be _____ volts,
shall be similar and equal in all respects to _____ phase, _____ hertz. Motor shall be
model ECP-__________. located near base of unit to provide easy access.
Motor shall be mounted on an easy to adjust
Performance motor base.
Evaporative condenser(s) shall have a condensing
capacity of _______ MBH total heat rejection The water recirculation pump shall be a close-
______ refrigerant at ______ ºF condensing coupled, centrifugal pump with a mechanical
temperature and ______ ºF design entering air seal. The pump shall be bronze fitted and cast
wet-bulb temperature. iron. Pump shall be located so that drainage
may occur freely when required when unit is
Construction drained. Pump motor shall be ______ hp
All components of the evaporator condenser maximum, Totally Enclosed, Fan-Cooled, 1.15
shall be fabricated of heavy-gauge steel, service factor, suitable for outdoor condenser
protected against corrosion by G-235 applications. Electrical characteristics shall be
galvanizing, unless otherwise specified. _____ volts, _____ phase, _____ hertz. Motor
All hardware shall be fabricated of heavy shall be located near base of unit to provide
gauge galvanized steel. Unit shall be capable easy access.
of withstanding water having pH of 6.5 to 8.0;
a chloride content (NaCl) up to 500 ppm; a Drift Eliminators
sulfate content (SO4) up to 250 ppm; a calcium Drift eliminators shall be PVC, triple pass, and
content (CaCO3) up to 500 ppm; and silica shall limit drift losses to no more than 0.001%
(SiO2) up to 150 ppm. of the circulating water rate.

Mechanical Equipment Water Distribution


Propeller type axial fans shall be used. Fan Shall be designed to provide full and even
material to be cast aluminum or equivalent for coverage over coil. Spray nozzles shall be PVC
industrial duty outdoor use. Fan housing to have large orifice, non-clogging design, attached to
inlet ventury for optimum efficiency. Fan shall PVC header system using clamps to provide easy
be driven through an industrial grade system of and quick maintenance. Nozzle spray pattern
a single banded multi-groove neoprene V-belt shall be a full 360 degrees for maximum
designed for 150% of motor nameplate hp and distribution. Nozzles should be operated at a
tapered roller bearings. Bearings shall be rated minimum flow rate of 4 gpm/sq.ft. to provide
at a minimum L10 bearing life of 50,000 hours. required wetness over coils. All piping and
Bearing lubrication shall be extended to exterior fittings shall be constructed of schedule
of unit to provide ease of maintenance. Fan 40 PVC to provide corrosion resistance.
shall be located outside of wet air stream.

ECP EVAPORATIVE CONDENSERS 13


ECP Specifications

Access Heat Transfer Coil


An access door shall be provided for entry The heat transfer coil(s) shall be all prime
into pan area of evaporator condenser. surface steel and hot dipped galvanized after
fabrication. The design pressure of the coil
Pan shall be 400 psig, and the coil shall be leak
Pan Assembly shall be constructed of heavy tested at 400 psig air pressure by submerging
gauge G-235 galvanized steel. Shall include in water. The coil should be designed with
the fan assembly, drive system, stainless steel sloping tubes for drainage.
strainer, make-up valve, overflow connection,
pump assembly, drain connection, motors, and
access door. A factory installed make-up shall
be two inch diameter. The overflow connection
shall be 3” diameter. The drain connection
shall be 2” diameter.

Options

Basin Heaters Dedicated Motor-Fan System


Provide a system of electric immersion heaters Unit shall have motor and drive system dedicated
for each unit of the evaporative condenser to to each fan assembly to allow for control and
prevent freezing of water in the collection basin ability to operate each fan system individually.
during periods of shutdown. The system shall
consist of one or more stainless steel electric Platform
immersion heaters installed in threaded couplings There shall be a platform to allow access to
provided in the side of the pan. A control probe spray system and eliminators. The platform
shall be located in the pan basin to monitor shall be galvanized steel bar grating, supported
water level and temperature. The system shall be by galvanized steel framework attached to the
capable of maintaining 40 ºF water temperature evaporative condenser. The platform shall be
at an ambient air temperature of _____ ºF. surrounded by a handrail, knee-rail, and toe-
board. A permanently attached ladder with
Remote Sump non-slip rungs shall be supplied. Ladder and
For applications using a remote sump arrange- platform shall conform to OSHA regulations.
ment, the evaporative condenser shall be
supplied with a ____ inch diameter bottom
outlet connection for gravity flow to remote
sump. When using the bottom outlet connection
the pump system, strainer, and make-up will be
removed from unit.

14 ECP EVAPORATIVE CONDENSERS


Performance Improvement Options

Dedicated Motor – Fan System Electronic Liquid Level Controls


Provides a dedicated single motor per fan with Solid-state liquid level controls provide state
compartmentalized fan sections, which offers the of the art system to control and monitor the
ability to cycle off a single fan while maintaining water level in condenser. Relays operating in
other fans in operation. This option replaces the conjunction with suspended stainless steel
standard single motor dedicated to a multiple electrode probes monitor basin water levels,
fan system. providing simple solenoid valve water make-up
or discrete on/off signals to more sophisticated
Motor Options automation controls. Optional configurations
Multiple motor configurations are available might include makeup along with high and low
including selections of premium efficiency, severe water level alarm and cutoff, or pump cutoff.
duty, two speed, and various voltages and hertz The electrode probes are 316 stainless steel
options. rods suspended from non-corrosive PVC box.
Control Panel Multi-relay control panels are pre-wired to
Control system in NEMA 3R rain tight enclosure terminals and mounted in NEMA 4X non-
is available for units. The control system operates metallic enclosure.
the fan motor and contains the following Vibration Limit Switch
elements: A vibration limit switch interrupts power to
■ Fused disconnect switch with an external the motor in the event of excessive vibration.
operating handle that is lockable in the off Unless specified otherwise, a Metrix switch will
position. be provided. It is adjustable for sensitivity and
requires manual reset to assure that the unit will
■ Fused control-circuit transformer to provide be serviced to determine the cause of excessive
120 volt control power. vibration. A double-pole, double-throw model
is also available.
■ Across the line magnetic contractor for each
primary motor speed. Platform with Ladder and Handrail
Periodic inspection and maintenance of a
■ Enclosure mounted “Hand Off Auto”
selector switch. condenser distribution system is fundamental.
Therefore, safe and easy access to these
Other control panel options include a two- components is a significant value to the operator.
speed control panel with a High-Low selector For maximum safety and convenience an access
switch and multiport terminal block for the platform with guardrails make this task as safe
connection of alarms and auxiliary equipment. and user-friendly as possible. The platform and
Panel has a UL508A label for the control ladder is located on the side of the condenser
enclosure. Please contact a sales representative and does not add height to the overall unit.
for more information about the NEMA 4X
enclosure.

ECP EVAPORATIVE CONDENSERS 15


Condenser Steel Support

E
B C

Notes: 3. Unit may be placed on a flat concrete slab.


1. Recommended ECP condenser support is two I-beams, which would 4. Shipping weights do not include optional equipment.
run the length of model. 5. Unit must not exceed 1/2” deflection at anchor bolts and should be
2. The supporting steel is to be designed, constructed, and furnished 1/360 of span. This will ensure proper performance of condenser.
by the customer. It shall include customer supplied anchor bolts 6. Unit should not be directly supported on vibration isolators.
with washers. Unit will be predrilled at anchor bolt locations with If necessary the beam should be installed between base of unit
7/8” diameter holes to anchor to support steel. and isolators. Contact sales representative for any questions.

Steel Support Dimensions


TABLE 12 - STEEL SUPPORT
Model Number A (in) B (in) C (in) D (in) E (in)
ECP-xxxx-01 139.25 - - 128 -
ECP-xxxx-02 139.25 94.375 94.375 200 11.25
ECP-xxxx-03 139.25 128 128 272.75 16.75
ECP-xxxx-04 139.25 128 128 272.75 16.75
ECP-xxxx-05 139.25 200 200 416.75 16.75
ECP-xxxx-06 115.25 94.375 94.375 200 11.25

16 ECP EVAPORATIVE CONDENSERS


Freeze Prevention

When the ambient air temperature falls below 32 ºF, the water in unit can freeze.

During shutdown, water collects in the pan and may freeze solid. Freeze protection is achieved
by adding heat to the remaining water in the unit or by draining the unit and all exposed piping
at shutdown.

Electric Pan Heaters

There are automatic basin water heater systems ■ Stainless steel electric immersion heater(s).
available consisting of the components at right. - Threaded couplings are in the side
of the collection basin.
■ Control probe in the collection basin to
Note:
Any exposed piping that is still filled with water at
monitor water temperature level.
shutdown – including the makeup water line – should be
Heater components are normally shipped
electrically traced and insulated (by others).
separately for installation by others.

TABLE 13 - HEATERS
Total KW Requirements at Ambient Air
Model Number 0 °F -20 °F
ECP-xxxx-01 15.1 29.6
ECP-xxxx-02 22.7 44.6
ECP-xxxx-03 30.2 59.3
ECP-xxxx-04 30.2 59.3
ECP-xxxx-05 45.4 89.3
ECP-xxxx-06 18.0 26.5

Note:
1. The basin heater will maintain a water temperature
above 40 °F at the ambient temperatures shown.
2. Heater selection may require two elements.
3. Call factory for lower ambient temperature requirements.

ECP EVAPORATIVE CONDENSERS 17


Bottom Outlet Details

Y
ALTERNATE PUMP SIDE

STANDARD PUMP SIDE


L R
FAN SIDE

Dimensions
TABLE 14 - BOTTOM OUTLET
Model Number X (in) Y (in) Pipe Flange Outlet
ECP-xxxx-01 42.00 43.875 8
ECP-xxxx-02 87.75 43.875 10
ECP-xxxx-03 114.25 43.875 10
ECP-xxxx-04 114.25 43.875 10
ECP-xxxx-05 20.5 or 196.125 43.875 12
ECP-xxxx-06 87.75 32.875 10

Note:
Full gasket and flange/piping by others.

18 ECP EVAPORATIVE CONDENSERS


ECP EVAPORATIVE CONDENSERS
Providing equipment and services to manage controlled-temperature environments
for food and other perishables, our Climate Control Technologies sector encompasses
both transport and stationary refrigeration solutions. Our product brands include
Thermo King®, , world leader in transport temperature control systems, and
Hussmann®, a manufacturer of refrigeration and food merchandising equipment.

www.thermoking.com www.hussmann.com www.ingersollrand.com

Krack Corporation
401 S. Rohlwing Rd., Addison, IL 60101
Ph: 630.629.7500 Fax: 630.629.0168 Printed in U.S.A. 0306-216-CEN-1.5M
www.krack.com ©2006 Ingersoll-Rand Company Limited

Вам также может понравиться