96 Control terminal strip and serial interface

1.2 Terminal connection

Connecting Term. Function, notes


example
-X100
1 Transmit- and receive line -RS485, differential input / -output, positive
(RS485R/T+)
2 Transmit- and receive line -RS485, differential input / -output, negative
(RS485R/T−)
3 Transmit output RS485 Standard, differential output, positive (RS485T+)
4 Transmit output RS485 Standard, differential output, negative (RS485T−)
5 Reference potential, RS485 interface
In addition to the GSST_2 interface on -X100, a GSST_1 interface -X300
NOTE is available on the parameterization unit; ☞ Chapter 4 „Start-up“.

NOTE Binary output 1 is connected at -X9:4,5 main contactor control

6 Binary output 2 (changeover contact) reference contact


7 Binary output 2 (changeover contact) NO contact
8 Binary output 2 (changeover contact) NC contact
9 Binary output 3 (NO contact) reference contact
10 Binary output 3 (NO contact) NO contact
11 Binary output 4 (NO contact) reference contact
12 Binary output 4 (NO contact) NO contact

NOTE Load capability of the binary outputs: 60 V AC, 60 VA, cosϕ = 1


60 V AC, 16 VA, cosϕ = 0.4
60 V DC, 24 W
Inductive loads, e.g. contactors, relays, for DC voltage loads, must be damped
using a diode or varistor, and for AC loads, with a varistor or RC element.
-X101
13 +24 V, 75 mA for binary inputs and outputs (150 mA if term. 23 unassigned)
14 Ref. potential for 24 V (ground)
15 Ref. potential for binary inputs 1 to 7 for ext. signal voltage
16 Binary input 1
17 Binary input 2
18 Binary input 3
19 Binary input 4
20 Binary input 5
21 Binary input 6
22 Binary input 7
Signal sensitivity H = 24 V (13 V to 33 V) Imax = 15.7 mA
NOTE of the binary inputs: L = 0 V (−0.6 V to 3 V)
23 +24 V, 75 mA for binary inputs and outputs (150 mA if term. 13 unassigned)
24 Ref. potential for 24 V

Table 1.2 Connecting example for control terminal strips -X100 and -X101

Siemens AG 6SE7087-6XX20 1-3


SIMOVERT MASTER DRIVES Operating Instructions
Control terminal strip and serial interface 08.96

Connecting Term. Function, notes


example
-X102
25 +10 V / 5 mA, ±2 %, for setpoint pot., non-floating
26 −10 V / 5 mA, ± 2%, for setpoint pot., non-floating
271) Analog input 1 (0 V to ±10 V)
28 Ref. potential, analog input 1
291) Analog input 1 (0 mA to 20 mA or. 4 mA to 20 mA) int. load resistor 250 Ω
302) Analog input 2 (0 V to ±10 V)
31 Ref. potential, analog input 2
322) Analog input 2 (0 mA to 20 mA or 4 mA to 20 mA) int. load resistor 250 Ω
33 Ref. potential, analog output 1
e.g. measuring
meter 34 Analog output 1 (0 V to 10 V) permissible load ≤ 5 mA =
^ > 2 kΩ
Terminals 33 and 34: To increase the noise immunity of the signals, an
NOTE isolating amplifier should be connected between the analog output and
measuring unit for cables > 4 m.
Table 1.3 Connecting-up example for the control terminal strip -X102

Connecting Term. Function, notes


example
-X103

35 Ref. potential for digital tacho
K1
36 Track A, digital tacho
K2
37 Track B, digital tacho
K0
38 Zero track, digital tacho
39 Check input, digital tacho
+
40 +15 V, 190 mA, digital tacho power supply
As standard, an HTL encoder without differential outputs can be connected.
NOTE Option DTI is required for other applications (digital tacho interface).

ϑ 41 Ref. potential for the motor temperature sensor


42 Motor temperature input (KTY84)
Protective separation must be externally guaranteed.
NOTE
43 Ref. potential, analog output 2
44 Analog output 2 (0 V bis 10 V) permissible load ≤ 5 mA =
^ > 2 kΩ
NOTE Terminals 43 and 44: Isolating amplifiers should be connected between the
analog output and measuring unit to increase the signal noise immunity for
cable lengths > 4 m.

Table 1.4 Connecting-up example for control terminal strip -X103

1) Only one of the two terminals, 27 or 29, may be assigned


2) Only one of the two terminals, 30 or 32, may be assigned

1-4 Siemens AG 6SE7087-6XX20


SIMOVERT MASTER DRIVES Operating Instructions