OVERVIEW USER INTERFACE • Six states can be visually SYSTEM SETUP OPERATIONS
represented for each
• Operates on Microsoft • Customizable interface • Graphic Editing mode • Macros provide
input device: Normal,
Windows 10 (64 bit, provides flexibility to allows on-site or off-site customizable
Fault, Fire Alarm,
Enterprise) display information as system setup. programming to simplify
Pre-Alarm (detectors),
desired. repetitive tasks.
• Monitor options: 24" Disabled and Security. • Import building floor
(disable/enable,
Touch screen • Supports dual monitors plan CAD drawings (as a
• Automatic screen de-activate/activate)
.dxf, .wmf, .bmp, .jpg, or .
• Supports up to 200 • Dynamically generated navigation
gif). • Individual device control
intelligent gateways, floor plan overview (configurable) to the
and system information
with 200 nodes per provides point of device in alarm, based • Customizable device
through icon right-click
gateway reference when using on event priority. icon and colors to
function
the zoom function. visually represent each
• Maximum Remote • Multimedia (text, audio,
event type. • History Manager:
Users: 50 • Global Zoom Level for video and bitmaps) can
Filterable history
devices (0 – 100%), be linked to any device, • User defined icons can
• Point Capacity: 250,000 reporting serves as a
definable by the providing instructions to be globally defined
• History File Capacity: valuable maintenance
administrator. operators for event (.PNG, .BMP, .WMF, .
2.5 Million Records and diagnostic tool to
response. JPG, and .GIF formats).
• Device information, identify patterns.
• Supports the following including point address • Operator log with SECURE ACCESS
additional languages: SYSTEM MAINTENANCE
and description, can be response tracking. • System Administrator-
Spanish, French, quickly accessed • Backup capability for
• ONYX-NOTIFY feature definable user profiles
Korean, Portuguese, through icon left-click screen, member, and
provides e-mail and text provide strict levels of
Hebrew, and Chinese function. history databases.
notification for access.
(Traditional and
• Navigational tree, icons off-normal events. • Obtain software version
Simplified) • Monitoring and Control
and configurable areas numbers for network
• NOTIFY-IP feature profiles delineate
• Compatible with provide easy access to panels (ONYX® Series
supports Voice-Over-IP defined operator
standard, high-speed system floor plans. fire panels.)
paging for mass accounts.
NOTI•FIRE•NET™, and
EVENT NOTIFICATION notification. • Upload/Download
Ethernet-based • Operator Login/
AND RESPONSE databases to NOTIFIER
networks. • Real-time message Logout/Change
ONYX series panels and
• Graphic and text display override capability to Password feature allows
• NOTI•FIRE•NET™ perform panel upgrades
of all off-normal events. LED-Signs on only authorized
gateway redundancy for (ONYX Series only) over
NOTI•FIRE•NET™. personnel to access the
network survivability. the network using
system.
VeriFire Tools.
• Logs in history of any
operator changes in the
workstation.
NOTI•FIRE•NET™ Monitoring
An ONYXWorks system is an ideal component of a Fire Command Center for real-time fire system status
and system control options. ONYXWorks interfaces directly to a NOTI•FIRE•NET™ fire system using an NFN
Gateway. The NFN Gateway is an intelligent interface used by an ONYXWorks system that facilitates monitoring
and control of a NOTI•FIRE•NET (version 5.0) network and NOTIFIER fire panels. The NFN Gateway is available
in two versions: PC-based gateway and embedded gateway (see NFN Gateway data sheet DN-7060). The
embedded NFN Gateway enables users to monitor multiple sites (local or remote) over an IP network.
Minimum ONYXWorks equipment options/requirements are available on the NFN Gateway data sheet.
ONYXWorks
Workstation
Software
History
Manager
ORDERING
WARRANTY
The PC and monitors are warranted from date of purchase for a period of 12 months. Please
refer to the NOTIFIER Limited Warranty Policy for additional information.
Workstation
with ONYXWorks GUI software and computer hardware. One monitor required
per workstation; dual-monitor capable (monitors sold separately).
Components
MONITOR 24" widescreen HD LED color touchscreen monitor. Other options on demand.
NFN-GW-PC-F NFN Gateway PC card with fiber.
NFN-GW-PC-W NFN Gateway PC card with wire.
NFN-GW-AU-EM-3 NFN Gateway, embedded.
NFN-GW-PC-HNSF High-speed NFN Gateway PC card for single-mode fiber.
NFN-GW-PC-HNMF High-speed NFN Gateway PC card for multi-mode fiber.
NFN-GW-PC-HNW High-speed NFN Gateway PC card for wire.
NOTIFY-IP Mass notification voice paging; can page up to 50 NFN gateways simultaneously.
ONYX-NOTIFY Adds e-mail and text option to ONYXWorks.
ONYX-MM Adds Floatable/Dockable Windows option to support dual monitors.
LEDSIGN-GW Emergency sign integration. Can operate with or without ONYXWorks Workstation.
OAX2-24V Two-line sign for use with LEDSIGN-GW. TCP/IP, 24V or POE (Power over Ethernet).
NOTE: If adding to an existing system, please provide customer service with the 5-digit software key number of your workstation.
An upgrade authorization will be provided to you.
For more information