Description The Is0 setting is the vertical asymptote of the curve, and T is the operation time
The earth fault function comprises 4 independant delay for 10 Is0.
elements divided into two groups of 2 settings called The tripping time for I0/Is0 values of less than 1.2 depends on the type of curve
Group A and Group B respectively. chosen.
The use of the two elements may be chosen by
parameter setting: Name of curve Type
b operation with Group A or Group B exclusively, with Standard inverse time (SIT) 1.2
switching from one group to the other dependent on the Very inverse time (VIT or LTI) 1.2
state of logic input I13 exclusively, or by remote control Extremely inverse time (EIT) 1.2
(TC3, TC4), Ultra inverse time (UIT) 1.2
I13 = 0 group A RI curve 1
I13 = 1 group B IEC standard inverse time SIT / A 1
b operation with Group A and Group B active for 4-set IEC very inverse time VIT or LTI / B 1
point operation IEC extremely inverse time EIT / C 1
b enabling/disabling of each group of 2 elements IEEE moderately inverse (IEC / D) 1
(A, B). IEEE very inverse (IEC / E) 1
3 Operation
Earth fault protection is single-phase.
IEEE extremely inverse (IEC / F)
IAC inverse
IAC very inverse
1
1
1
It picks up if the earth fault current reaches the
IAC extremely inverse 1
operation set point.
It includes a time delay, which is either definite The curve equations are given in the chapter entitled "IDMT protection functions".
(constant, DT) or IDMT depending on the curves on the
facing page. The function takes into account current variations during the time delay interval.
The protection function includes a harmonic 2 restraint For currents with a very large amplitude, the protection function has a definite time
set point which can be used to bypass the incorrect characteristic:
residual current on the sum of the 3 phase CTs when b if I0 > 20 Is0, tripping time is the time that corresponds to 20 Is0
the transformers are energized. The restraint can be b if I0 > 15 In0, tripping time is the time that corresponds to 15 In0.
selected by parameter setting.
The principle of this harmonic 2 restraint allows this Block diagram
protection to trip on intermittent earth faults.
The protection function can be inhibited by input I23 for " "
DE80520
(for S24)
IDMT protection
IDMT protection operates in accordance with the
IEC 60255-3, BS 142 and IEEE C-37112 standards.
DE50246
60 CRED301005EN
Protection functions Earth fault
ANSI code 50N/51N or 50G/51G
2 A rating 0.2 A to 30 A
20 A rating 2 A to 300 A
CT 0.1 In0 y Is0 y 15 In0 (min. 0.1 A)
Core balance CT
with ACE990 0.1 In0 < Is0 < 15 In0
IDMT time setting 0.1 In0 y Is0 y In0 (1) expressed in Amps
Sum of CTs (1) (5) 0.1 In0 y Is0 y In0
With CSH sensor
2 A rating
20 A rating
0.2 A to 2 A
2 A to 20 A
3
CT 0.1 In0 y Is0 y In0 (min. 0.1 A)
Core balance CT
with ACE990 0.1 In0 y Is0 y In0
Resolution 0.1 A or 1 digit
Accuracy (2) ±5 % or ±0.01 In0
Drop out/pick-up ratio 93.5 % ±5 % (with CSH sensor, CT or core
balance CT + ACE990)
b IDMT for IEC, IEEE and IAC curves 93.5 % ±5 % or > (1 - 0.015 In0/Is0) x 100 %
(sum of CTs)
I > Is time-delayed output Harmonic 2 restraint
Fixed threshold 17 % ±5 %
DE50248
PCRED301005EN 61