Вы находитесь на странице: 1из 1

Phase Test Current (A) Expected (A) Relay Measurement (A) %Error

Ia 750 0.00
Ib 750 751 -0.13
1.00
Ic 749 0.13
Ig 60 59.83 0.28
Phase Test Voltage Expected (kV) Relay Measurement (kV) %Error
Vab 32.9 0.30
Vbc 110.0 33.0 32.3 2.12
Vac 33.1 -0.30

Expected Measured %Error


Phase Setting Remarks
P/U D/O P/U D/O P/U D/O
Pickup at
R 0.80 0.88 0.836 0.85 0.81 3.41 3.11 1.1xIs ±5%
1.1xIes ±5%
Y 0.80 0.88 0.836 0.85 0.81 3.41 3.11
Reset at
0.95x(1.1XIs)
B 0.80 0.88 0.836 0.85 0.81 3.41 3.11
±5%

E/F 0.42 0.462 0.439 0.45 0.41 2.60 6.61 0.95x(1.1XIes)


±5%

Setting Expected Pick-up Errors Setting Measured Expected


Phase
(A) (A) (A) (%) Time (s) Time (s) Time
R 8.1 -1.25 0.142
I>> Y 8.00 8.00±5% 8.1 -1.25 0.1 0.142 0.05
B 8.1 -1.25 0.142 ±55ms
Ie>> N N/A N/A N/A N/A N/A N/A

Operating Voltage (V)


Phase Pick-up Drop-of Remarks
Setting (V)
Expected Measured %Error Measured
R-N 73.0 71.5 – 74.5 73.2 -0.27 70.8 OK

Y-N 73.0 71.5 – 74.5 73.2 -0.27 70.8 OK

B-N 73.0 71.5 – 74.5 73.2 -0.27 70.8 OK