Вы находитесь на странице: 1из 86

Exarnvle Svstern Design Contents -Page ex -i

EXAMPLE SYSTEM DESIGN

Solar Design Manual


EXAMPLE SYSTEM DESIGN

l2sEmxE
Page

INTRODUCTION .......................... ..................................................................... EX-1


SECTION t .CONCEPTUAL ANALYSIS ...............................................................EX-1

Owner/Architect/Engineer Conference ................................................................


EX-1

Conceptual Site Survey ........................................................................................... EX-1


Preliminary Load Estimate ...................................................................................... EX-1

Conceptual PerforrnancetCost Study ..................................................................EX-2


Conceptual Array Sizing Method .............................................................................EX-2
Preliminary System Cost Estimate .......................................................................EX-3
Evaluation of Cost Effectiveness.............................................................................EX-3

SECTION 2 .FEASIBILIN STUDY ........................................................................EX-9

Application Review ............................................................................................ EX-9


Data Gathering and Conservation Measures ....................................................... EX-9
Thermal Load Requirements................................................................................... EX-9

Sizing/Performance Analysis ...................................................................................EX-9


Computer System Simulation .................................................................................. EX-9
Construction Costs ..................................................................................................EX-12
Economic Evaluation ...............................................................................................EX-13

SECTION 3 .DETAILED DESIGN ........................................................................ EX-30

Overall System Schematic ......................................................................................


EX-30

Collector Subsystem Design ................................................................................... EX-30


Array Design............................................................................................................
EX-30
Piping Design ..........................................................................................................
EX-31
Collector Subsystem Component Requirements ....................................................EX-32

Storage Subsystem Design ...................................................................... ...............EX-50


Storage Tank Design ............................................................................................... EX-50
Piping Design .........................................................................................................
EX-50
Storage Subsystem Component Requirements .................................................... EX-51
Example System Design Contents -Page ex iii -

EXAMPLE SYSTEM DESIGN

CONTENTS (continued)
Page

3.5 Instrumentation and Controls Subsystem Design ...................................................EX-52


3.5.1 Solar Energy System Operational Controls.............................................................EX-52
3.5.2 Solar Energy System-to-Load Interface Controls .................................................... EX-52
3.5.3 Operational instrumentation .................................................................................... EX-52
3.5.4 System Performance Monitoring Instrumentation ................................................. EX-52
3.5.5 Instrumentation and Control Component Requirements .........................................EX-52

3.9 Perforrnance/CostVerification................................................................................. EX-74


3.9.1 Verification of Thermal Performance ..................................................................... EX-74
3.9.2 Cost Estimate ..........................................................................................................
EX-76
3.9.3 Economic Evaluation ............................................................................................. EX-76

TABLES

First Economic Evaluation of Solar Energy System ................................................EX-14


Results of F-CHART Runs for Variety of Array Sizes .............................................EX-15
Results of TLCC Calculations for Various Solar fnergy System Sizes .................. EX-15
Second Economic Evaluation of Solar Energy System ...........................................EX-16
Design Cost Estimate Detail ...................................................................................
EX-77

Solar Energy System Goals ....................................................................................EX-5


Service Hot Water Data ...........................................................................................EX-6
Building Information.................................................................................................
EX-7
Collector and Storage Locations .............................................................................EX-8

Building Information..................................... .. ......................................................... EX-17


Site and Environmental Considerations ................................................................ EX-21
Energy Conservation Measures ..............................................................................EX-23
Service Hot Water Data ...........................................................................................EX-27
Construction Cost Estimate Summary .................................................................. EX-29

*Only those checklists applicable to this specific system design were used. Other designs may require use of
all checklists .

Solar Design Manual


EXAMPLE SYSTEM DESIGN

FlGURES
Page

Building Sketches ........................................................................................ EX-4


Example System P & ID................................................................................EX-33
Typical 8-Collector Bank ............................................................................... EX-34
Location of Collector Banks on Roof ..............................................................EX-34
Collector Pipe Sizes and Flow Rates ..............................................................EX-34
Typical Collector Bank Piping ........................................................................ EX-34
CollectorlPipe Support ...................................................................................EX-35
Storage Tank ..................................................................................................EX-35
Storage Tank Details ......................................................................................EX-35
Collector Sensor Locations................................................................. EX-53
Storage Tank Sensor Locations................................................................... EX-53

PEClFlCATlON WORKSHEETS

Flat Plate liquid Collectors ....................................................................................EX-36


Heat Transfer Fluids ................................................................................................ EX-39
Pumps .................................................................................................................... EX-40
Expansion Tanks .................................................................................................. EX-42
Air Separator Valve .......................................................................................... EX-43
Flex Couplings ....................................................................................................... EX-44
Insulation ................................................................................................................ .
EX-45-
.,. ,. ...=., ..T...=..,. ....--..T ...I. ....: ..................................................EX-46
- . . .
. . . . .

Aidlent ,
- .

Check Valves .......................................................................................................... EX-47


Pressure Relief Valves ..........................................................................................EX-48
Piping .................................................................................................................... EX-49
Thermal Storage Tanks ...........................................................................................EX-54
Heat Exchangers .................................................................................................. EX-55
Pumps .....................................................................................................................EX-57
Tempering Valve ....................................................................................................EX-59
Pressure Temperature Relief Valves .................................................................... EX-60
Insulation ................................................................................................................. EX-61
Air Vent ................................................................................................................. EX-62
Check Valves ......................................................................................................... EX-63
Pressure Relief Valves ......................................................................................... EX-64
Piping ................................................................................................................ EX-65
Differential Temperature Controller ....................................................................... EX-66
Temperature Switches ......................................................... . . .............................EX-67
Temperature Sensor ............................................................................................ EX-68
Btu Meters ............................................................................................................... EX-69
Pressure/Temperature Ports .................................................................................EX-71
Pressure Gauges .................................................................................................... EX-72
Thermometers .................... .... ............................................................................. EX-73

Solar Design Manual


Example System Design Conceptual Analysis- Page EX-I

EXAMPLE SYSTEM DESIGN

INTRODUCTION

An example solar energy system design was prepared following the guidelines of the design manual. The
example is intended to show how the equations, tables, figures, checklists, worksheets, and evaluations are
used in the solar energy system design process.

The system selected for the example application is a closed-loop antifreeze system that can be used to
supplement heating of service water for a dormitory. The example system uses flat plate collectors that are
mounted on the roof of the dormitory.

Numbers used to identify sections, headings, tables, figures, checklists, and worksheets for the example are
directly relatedto those used in the main text of the design manual.

The example solar energy system design was performed using the inch-pound (I-P) units and symbols.

SECTION 1

CONCEPTUAL ANALYSIS

1.2 Owner/Archltect/EnglneerConference

The "owner" is a college in Tucson, Arizona, that is considering a solar energy system to supplement the
service hot water load in a men's dormitory. Checklist 1-1 summarizes the owner's goals.

1.3 Conceptual Site Survey


1.3.2 Preliminary Load Estimate

Ideally, either historical records of service hot water usage or real-time data collection would be used to
estimate the service hot water load. In this example, these methods were not available for use. The load is
estimated based on the ASHRAE 1980 Systems Handbook guidelines for hot water demand (Table 6 of the
Service Water Heating section).

The dormitory contains 100 rooms, 25 per floor, and there are three students per room. The school is on the
trimester system with about h2lf the capacity during the summer trimester (Mayto August). The hot water
load, by month, is determined below using the equation from Worksheet 1-1. The average hot water demand
is 13.1 gavstudent per day.

Solar Design Manual


Example System Design Conceptual Analysis- Page EX-2

Cold Water Hot Water


Month Gallons Temperature ( O F ) Temperature (OF) Load(Btu/month)

January 122,000 48 140 93.16 x loa


February 110,000 48 140 84.0 x 10e

March 122,000 50 140 91.13 x 10e

April 118,000 52 140 86.19 x 10"

May 61,000 57 140 42.02 x 10"

June 59,000 59 140 39.66 x 106

July 61,000 63 140 38.98 x 1Og

August 61,000 75 140 32.91 x 108

September 118,000 79 140 59.74 x 108

October 122,000 69 140 71.90 x 10B

November 118,000 59 140 79.33 x 10s

December 122,000 54 140 87.08 x 108

Total 806.00 x 1Os

Load {Btu/month) = (gaVmonth)(8.3 Ib/gal)(l Bt~/lb.~F)(f,- TJ°F

1.3.3 Physical Constraints

A sketch of the dormitory building is illustrated by Figure A. Checklists 1-4 and 1-5 outline the results of the
building site survey.

1.4 Conceptual System Selection

Due to the relatively large static head, approximately 50 ft, and the freeze potential at the site, the conceptual
system selected for this site is a closed-loop antifreeze system, as illustrated by Figure 1-3 of the manual. 4

1.5 Conceptual PerforrnanceICost Study

1.5.1 Conceptual Array Sizing Method

The expected performance of the system, for both an average flat plate and an average evacuated tube
collector, can be found in Table 1-3 of the manual.

Flat plate performance - 269,000 Btu/ft&yr


Evacuated tube performance = 287,000 BtuMGyr
I

Solar Design Manual


Exam~leSvstem Design Conceptual Analysis- Page EX-3

The estimated required array, storage, and mechanical room sizes are calculated per Section 1.5.1 as
follows.

a. Array area = (806 x 1 0 % ~ x 0.80) + (269,000 Btu/ft2eyr)@ 2400 ft2 (flat plate)

b. Array area = 2250 ft2 (evacuated tube)

c. Storage size = 2250 to 2400 gallons

d. Mechanical room size = 100 to 150 ft2

15 . 2 Preliminary System Cost Estimate

The cost estimate will be based on the assumption that flat plate collectors will be used. The sytem cost
range is estimated as follows.

a. Minimum cost = $40/ft2x 2400 ft2 = $96,000

b. Maximum cost = $801ft2x 2400 ft2 = $192,000

A representative 40-ft2flat plate collector can currently be purchased for $520. This represents less than 30%
of the system cost and is acceptable.

13 . 3 Evaluation of Cost-Effectiveness

The simple payback period can be calculated following the steps in Section 1.5.3.

a. Output = 269,000 Btu/ft2*yrx 2400 ft2 = 646 x 1O6 Btu/yr

b. The cost of electricity in Tucson, Arizona, is $19,92/MMBtu

C. Therefore, the value of the annual energy saved is

646 x 1O6 Btulyr x $19.92 x 10" Btu = $12,870Jyr

d. The simple payback periods for both the minimum and maximum cost estimate are

Minimum = $96,000 + $12,870Jyr = 7.5 yr

The payback periods are within the owner's goal of 15 years. The allowable first cost can be calculated
following the steps in Section 1.5.3.

e. Value of energy saved = $12,87O/yr

f. From Table 5, using an interest rate of 12% (estimated over the life of the system, an
economic life of 20 years and a fuel price change of +2.50/dyr, the economic factor is 8.956.

Qw The allowable first cost is then $1 2,870 x 8.956 = $115,300

This is in between the minimum and maximum cost estimates of the system. The system will be cost-effec-
tive if it can be installed for this amount or less.
Basement
Entrance

Roof Plan

Floor Plan

Ground Level

Furnace
, ~ . ~ C r . ~ . c c , r r r . r r Storage
1
*r &
: Sohr ; Workspace
Existing j Equipment
Water R o o m :
i
Heater d
1 #I

Mechanical Room Plan Scale: 1 in. = 50 ft

Figure A. Building Sketches

S o b Design Manual
Example System Design Conceptual Analysis- Page EX-5

CHECKLIST 1-1

SOLAR ENERGY SYSTEM GOALS

Building ownerluser A college in Arizona


(name)
Address Tucson, Arizona

Desired solar application:

Hot water only -X-Space heating Space heating and hot water

Reasons for interest (rank in order):

-2-Promotion of renewable energyfwnservation of fossil fuel


-1-Save money
-3-Own a solar system
Expected solar f radon:

Hot water heating (%) -80-


Space heating (%) -NIA-

Overall expected cost benefits

Maximum initial investment allowed ($)-200,000-

Maximum years allowed to pay back investment (yr) 15

Minimum yearly fuel cost saving ($/yr)--

Solar Design Manual


CHECKLIST 1-2

SERVICE HOT WATER DATA

A. Building Hot Water Requirements

1. Daily Load 22 gal/day (maximum per student), -13.1 @/day


(average per student)

How determined? ASHRAE 1980 Systems Guidelines

2. Daily use pattern Mostly daytime, 7 days/week

3. Temperature 12OP0F

4. Load profile (list monthly hot water load estimates) (gallons): (000 omitted)

Jan -122- Feb 1 1 0 - Mar -122- Apr -1 18- May - 6 1 Jun -59-

J u l - 6 1 A u g 6 1 S e p ~ 1 1 8 O c t ~ 1 2 2 ~ N o v Dec-122-
~118~

5. Total annual load 1 ,I 96,000gallons

B. Main Heating System

1. Energy source: Gas Electric X O i l Steam

2. Hot water heaterhtorage capacity 1 0 7 0 _ _ g a l l o n s

3. Hot water circulation: Yes No x -


4. Cold water temperature 7 9 - O F (max) 4 5 - O F (min)

Solar Design Manual


Example System Design Conceptual Analysis- Page EX-7

CHECKLIST 1-4

BUIL1)ING 1NFORMATlON

Date July 1987

Building A college in Tucson

1. Primary building use: Dormitory

2. Number of floors: 4 Total floor area -77,350-ft2

3. Utilities available:

Natural gas Propane gas Fuel oil


Electric: -1 20/208- volt, -1/3- phase, -214- kW

4. Water quality: pH -8.5 Dissolved solids c 1 0 - pprn

Solar D e s i ~ nManual
CHECKLIST 1-5

COLLECTOR AND STORAGE LOCATIONS

1. Potential collector location: Roof -X- Ground Wail

Ifroof, type: Fiat -X- Pitched

If pitched, pitch line direction and slope

Roofing material B u i l t up with cap sheet

Area available for collectors -59.5- ft (N/S) x -325- ft (UW)


Potential shading problems e l e v a t o r equipment room

Provide sketch showing shape, overall dimensions, and location and type of any
obstructions or potential shading sources.

2; Potential storage location: Indoor -X- Outdoor

If indoor, available area 5 0 - ft x 3 0 - ft; Ceiling height -1 5-ft

Access to storage location: 2 0 x 8- door sues other

3. Potential mechanical equipment location: indoor X Outdoor

If indoor, available area 5 ft x 7 . 5 ft

4. Approximate distance collector to HX or storage 5 0 - ft (elev),2 5 - ft (horiz)

5. Approximate distance HX to storage 0 ft (elev), -1 0-ft (horiz)

Solar Design Manual


Example System Design Feasibility Study- Page EX-9

SECTION 2

FEASIBILITY STUDY

2.2 Appllcatfon Revlew

2.2.1 Data Gathering and Conservation Measures

Checklists 2-1 through 2-4 are filled out as attached. The only conservation measure is to lower the tank set
temperature to 120°F.

2.2.3 Thermal Load Requirements

The ASHRAE data for hot water usage calculated in Section 1 still applies.

2,3 Sizing/Perforrnance Analysis

2.3.1 Computer System Simulation

The example system simulation program chosen for this example feasibility study is F-CHART version 5.5.
The initial input required to run F-CHART 5.5 is determined using Appendix 2B and the F-CHART user's
manual.

Collector Parameter Set


1. Number of collector panels

As a first cut, 54 collectors are estimated. This is an area, 10% less than that calculated in
Section 1.

2. Collector pane[ area = 40 ft2

3. FRUL= 0.792; this is the value for an average flat plate collector as shown in Section 1.5.

4. F,m = 0.61 6; this is the value for an average flat plate collector as shown in Section 1.5.
5. Collector slope = 32". For this first run, this is set to the site latitude.

6. Collector azimuth = default value (0).

7. Incidence angle modifier = 8, for the program to calculate the modifier values.

8. Number of glazings = 1.

9. incidence angle modifier constant = (no input required).

10, Incidence angle modifier values = (no input required).

ai. Collector flow rate/area = 17.5 Ib/h*ft2,as recommended in Appendix 28.

Solar Design Manual


Collector fluid specific heat = 0.875 Btu/lbe°F, the value for 50/50pmpyleoe gly

Modify test values = 2, for no modification.

Test collector flow ratehrea = (no input required).

Test fluid specific heat = (no input required).

City call number = 215 for Tucson, Arizona

Water storage volume = 2140 gallons, 1 gaWt2 of array area

Building UA = 0 for DHW only

Fuel = 1 for electricity

Efficiency of fuel usage = 100%

Domestic hot water = 1

Daily hot water usage; the monthly values are input by typing "7 V"

Jan 3936 May 1968 Sept 3933


Feb 3929 June t 967 Oct 3936
Mar 3936 July 1968 Nov 3933
AP~ 3933 Aug 1968 Dec 3936

Water set temperature = 120°F

City water temperature; the monthly values are input by typing '9 Vw

Jan 60 May 65 Sept 70


Feb 60 June 75 Oct 70
Mar 65 July 75 Nov 65
AP~ 65 Aug 75 Dec 60
DHW storage tank size = 2140 gallons

UA of auxiliary storage tank = 23.8 Btu/hm°F; the auxiliary tank is 1070 gallons. 4.5
diameter, and 9 ft high. The installed insulation is 2.5 inches thick with a k = 0.031

Pipe heat loss = 2

Inlet pipe UA = (no input required)

Outlet pipe UA = (no input required)

the default value


Relative load heat exchanger size = I,

Collector storage heat exchanger = 1 ,

Solar Design Manlral


Example System Design Feasibility Study- Page E X 4
-
C

17. Tank side flow rate = 18.375 Ib/hr*ft2;calculated as 5% greater than collector side flow rate

(1.05)(17.5 Ib/hr.ft2) = 18.375 Ib/hraft2

18. Heat exchanger effectiveness = 0.60, as recommended in Appendix 28

Results are listed below.

Tucson, AZ

Design Handbook Sample Run 1

Water Storage System


Flat Plate Collector

Solar Heat DHW Aux


MMBtu* MMBtu* MMBtu* MMBtu*

Jan
Feb
Mar
AP~
May
Jun
Jul
Aug
S ~ P
Oct
Nov
Dec
Yr i J

Note: MMBtu = Btu x 106

The results show that with 54 collectors, the solar fraction will be 0.79, meeting 100% of the load during the
months of May through August.

Assuming that the example simulation program overestimates the output by 20%, the installed performance
can be estimated by:

Installed Solar Contribution -


= (DHW Aux) + 1.20

= 348.1 MMBtu

Installed Solar Fraction

Solar Design Manual


2.3.2 Construction Costs

Following the guidelines of Appendix 2C (Casts are expressed in 1985 U.S. dollars and must be adju
the year of proposed construction):

The National Average "Bare Costs" are:

1. Collector + Thermal Storage Tanks

BC = 9.13(2,160 ft2) + 21,308 = $411029


2. Mechanical Material

-
BC 7.05 (2,160 ft2) + 5,337 =-$

3. Electrical Material
BC = 0.134 (2,160 ft2) + 2,432 = $9.771

4. Mechanical Labor

BC = 2.93(2,160 ft2) + 18,662 = $24.991

5. Electrical Labor
BC = 0.026 (2,160 ft2) + 1,550 = $1.608
6. Other

BC = 0.018 (2,160f12)+743 = $782


7. -
Freight Costs $1000 assume for this example

Bare Cost at Tucson, Arizona

B C ~ ~ ~ n= 41,029 + (.989)(20,565) + (1.022)(2,721)


+ (.961)(24,991) + (.953)(1,61)6) + (.961)(782)
= su&z
Subtotal Cost at Tucson, Arizona

Subtotal Cost = 90,447 + .07(41,029 + 20,565 + 2,721)


+ (.0529 + .0715 + .01)(24,991 + 1,606)
=$98.524

Total Cost

Total Cost ~($98,524+ 1,000)(1.296) = $128.983

where: $1,000 = freight cost

Cost/ft2 ~$59.71
/ft2

Solw Design Manual


Exam~leSystem Design Feasibility Study- Page EX-13

2.3.3 Economic Evaluation

The system is evaluated economically by looking at the total life cycle costs (TLCC) of the existing system
and of the solar retrofit system. The two TLCCs are assumed to be:

where: PMT = design and installation costs


PV,,,,= present value of the annual auxiliary
fuel expenses
Pv~,~ = present value of the annual solar energy
system O&M casts

No tax credits or salvage value is included in this example, and the design cost is exduded. Also, the existing
system is assumed to last as long as the solar energy system.

To convert the annual auxiliary fuel and O&M costs to a present value, the modified uniform present worth
(MUPW) formula is utilized as follows:
(Note: Table 5 of Section 1 can be used, also.)

+ e)/(d- e)] [I
MUPW = A. [(i - ((1 + e)/(i + d)IN]
where: A, = annual cost at beginning of study period ($/yr)
e = annual energy escalation rate (decimal)
d -- annual discount rate (decimal)
N = study period, yr

For this example, the following values are assumed:

Therefore, MUPW = 8.9564 A,

The annual auxiliary fuel cost is determined from the F-CHART run.

Aux fuel cost = Aux MMBtu x $19.92/MMBtu

The annual operating costs are assumed to be 5% of the solar energy collected, or:

The annual maintenance cost is assumed to be 20h of the installed costs.

The first cut of the economic evaluation is as shown in Table I.

Solar Design Manual


-
Table 1 First Economlc Evaluation of Solar Energy System

Aux. Oper- Mainte-


Design and Aux. Energy Energy ating nance
InstallatIon Requlrernent Costs Costs Costs
System Costs ($) (MMBtutyr) ($/Yr) ($/Y J') ( $ 1 r)
~ TLCC ($1
- - - - - - -

No solar 0 531-7 10,591 0 0 94,861

With solar 128,983 183.6 3,658 347 2,580 187,961

As can be seen from Table 1, the TLCC with the solar energy system is much greater than the TLCC without
a system. Therefore, some optimization is required.

The first step in optimization is to maximize the output of the system. The second step is to reduce the array
area and, therefore, the system cost until the TLCC, with solar, is less than the TLCC without solar.

Since the maximum load exists during the winter months, the system output can be increased by increasing
the collector slope. This results in an optimum slope of 42", with the corresponding F-CHART run shown
below.

Tucson, AZ
- - - -

Water Storage System


Flat Plate Cotlector

Solar Heat DHW Aux


MMBtu MMBtu MMBtu MMBtu

Jan
Feb
Mar
Ap r
May
Jun
Jul
Aw
S~P
Oct
Nov
Dec
Yr

Table 2 summarizes the F-CHART runs for a variety of array sizes. I.

Solar Design Manual


Examde System Design Feasibilitv Studv- Puae EX-15

-
Table 2 Results of F-CHART Runs for Varlety of Array Sizes

20% Reduction
In F-CHART Output
Number
of Panels Solar MMBtu Aux MMBtu F Aux MMBtu F

The first cut at the economic evaluation assumes that the installation cost remains $59.711ft2. Table 3
summarizes the results of the TLCCs for the various system sizes.

-
Table 3 Results of TLCC Calculations for Various Solar Energy System Sizes

Aux. Oper- MaInte-


system Design and Aux. Energy Energy sting . nance
(No. of lnstallatlon Requlrement Costs Costs Costs
panels) Costs ($) (MMBtulyr) ( $ 1 r)~ ( $ 1 r)
~ ( $ 1 r)
~ T u x ($)

As can be seen, none of the systems have a lower TLCC than the existing nonsolar water heater.
To complete this example, Table 4 summarizes a second economic evaluation with an assumed
electrical energy cost of $39.84/MMBtu.

Solar Design Manual


-
Table 4 Second Economic Evaluation of Solar Energy System

Aux. Oper- Malnte-


System Design and Aux. Energy Energy atlng nance
(No. of Installation Requirement Costs Costs Costs
panels) costs ($) (MMBtulyr) ( $ 1r)~ ($/Yr) ( $ 1r)~

'These values are based on the cost estimating procedures of Section 2 instead of the assumed cost
of $59.71 /ft2.

Using the assumed installation cost of $59.71/ft2,the installation is economical from approximately 35 panels
down to at least 20 panels. Using the installation cost estimating procedure outlined in Section 2, the TLCC
bottoms out at 40 panels and at that level is approximately $30,000 more than the TLCC without a solar
energy system. This example solar system will be designed using 40 panels.

Solar D e s i ~ nManual
Example System Design Feasibility Study- Page EX-1 7

CHECKLIST 2-2

BUILDING INFORMATION

(Sheet 1 of 4)
Date July 1987

Building A college in Arizona

BUILDING CONSTRUCTION CHARACTERISTICS

Primary building use: D o r m i t o r y

Provide sketchtplan with overall dimensions and orientation.

Number of floors: 4

Volume of occupied space: -61 8,800-ft3


Gross floor area: -7?,350- ft2

Window glazing: - X s i n g l e - X double

Window shading coefficient:

Windows, number and area: north windows ea. -ft2 = ft2

west -ft2 r ft2

east ft2 = ft2

south -ft2= ft2

TOTAL ft2
Door types and number:
north single vestibule revolving - -doors
west -single vestibule revolving = -doors
east -single vestibule revolving = -doors
south -single vestibule revolving = -doors
Gross wall area: north

Gross wall area: west

Gross wall area: east

Gross wall area: south it2


TOTAL ft2

*Items8 through 19 are not applicable.

Solar Design Manual


CHECKLIST 2-2

BUILDING INFORMATION

"U"Value

20.' Net wall area: north ft2 (Net E gross less window
and door area)
21. Net wall area: west ft2

22. Net wall area: east ft2

23. Net wall area: south ft2

TOTAL ft2

24. Roof construction: Support structure

Surface material

Slope Area ft2

"U"Value
25. Floor:

Over unheated space ft2

"U"Value

BUILDING USE CHARACTERISTICS

26. a. Number of occupied hours per week: -1 68- hours

b. Number of occupants: -300- occupants (for offices, employees and visitors; for stores,
employees and customers; for religious buildings, schools only count occupants)

27. Number of custodial hours per week: after dark, summer -N/A- hours

after dark, winter -N/A- hours

Saturdays -N/A- hours

Sundays -N/A- hours

*Items 20 through 25 are not applicable.

Solar ueszgn Manual


Example System Design Feasibility Study- Page EX-I 9

CHECKLIST 2-2

BUILDING INFORMATION

(Sheet 3 of 4)

28.' Temperature and relative humidity inside canditions:

Season Temperature Humidity

-
a. heated winter Occupied hours O F % RH

Unoccupied hours OF % RH

-
b. air-conditioned summer Occupied hours O F % RH

Unoccupied hours O F % RH

29. Ventilation, outside air:

a. during occupied hours -onloff: amount in total d m = ft3/min

b. cfm per person (line 29a +- line 26b) = dmfperson

c. during unoccupied hours -on/off; amaunt in total cfrn = ft3/min

30. Type and location of space heating equipment: Single unit Multiple units

Boosters

-OutsrdeJocati~
- - - - -
- - - - - - - - - - - - -

- - - - - - -

-Inside, location
Type and location of water heating equipment: X Single unit Multiple units

-Outside, location
-X- Inside, locatian -Basement
31. Utilities available

Natural gas Propane gas Fuel oil

Electric: -1 2O/208-volt, -1 13- phase

32. Water quality: pH 8 . 5 - Dissolved solids < 0I


- ppm Solids -None-

Dormitory has installed water treatment system.

*Items 28 through first part of 30 are not applicable.

Solar Design Manual


CHECKLIST 2-2

BUILDING INFORMATION

33. Collector and thermal storage locations

a. Collector location -- Roof - X Ground Wall

If roof, type - Flat X Pitched

If pitched, pitch line direction -and slope


Area available for collectors -59.5- ft (N/S)
x 3 2 5 - ft (EM)

Provide sketch showing shape and overall dimensions of collector location with
location and type of any obstructions or potential shading sources.

b. Thermal storage location - Indoor -X- Outdoor

Provide sketch/plan showing all dimensions and access.

c. Mechanicalequipmentlocation-IndoorXOutdoor

Provide sketcNplan showing all dimensions and access.

d. Approximate distance collector to HX or storage -50-ft (elev), - 2 5 ft (horiz)

e. Approximate distance HX to storage -Q-fi (elev).-1 0-ft (horiz)

Solar Design Manual


Example System Design FeasibiZiO Study- Page EX-21

CHECKLIST 2-3

SITE AND ENVIRONMENTAL CONSIDERATIONS

(Sheet 1 of 2)
Building location T u c s o n - (City), -Arizona-(State)

3 2 (Latitude), 1 1OW (Longitude)

Local population

If small city or noncity, distance city of 50,000 or more miles

Local zoning ordinances affecting solar Yes NoX-


If yes, describe

Local code requirements affecting solar system Yes NoX-


If yes, describe:
Building:
Plumbing:
Electrical:
Fire:
Other:

5. Requirement for double separation between antifreeze


solutions and water Yes No X

6. Long-term climatic condition (as available: use NWS data or SERl Atlas')

Maximum daily temperature 81.5-OF


- - - - - - - - -
Minimum daily temperature -54.1-OF
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - -

Maximum monthly average temperature -86.3-OF (Aug.) '

Minimum monthly average temperature -50.9-OF (Jan.)

Heating degree days -1,751-

Maximum global insolation - Daily Btu/ft2 - Monthfy -2,730-Btu/ft2 (June)


Minimum global insolation - Daily Btulft2 - MonthJy -995-Btu/ft2 (Dec.)

Clear days per year -K, = ,679- Clearest month -May-

Cloudiest month Dee.- Daily cloud pattern: a.m. p.m.

Maximum (mean) snowfall -6- inches

Maximum wind velocity -8-mph

Direction of maximum wind N W - Direction of prevailing w i n d N W -

* "Climatic Atlas of the United States," U.S. Department of Commerce, 1977.


SERI/SP-642-1037, "Solar Radiation Energy Resource Atlas of the United States," October
1981.
SERVSP-755-789, "Insolation Data Manual," October 1980.

Solar Design Manual


CHECKLIST 2-3

SITE AND ENVIRONMENTAL CONSlDERATlONS


(Sheet 2 of 2)

Solar Design Manual


Example System Design Feasibility Study- Page EX-23
-6

CHECKLIST 2-4

ENERGY CONSERVATION MEASURES


(Sheet 1 of 4)
A. NO COSTJLOW COST
HVAC
To be
Implemented
_Yes&

Install locking thermostats


Adjust supply or heat transfer medium temperature
Install nighttime thermostat setback
Restrict heat and air conditioning in unoccupied areas
Clean radiators, air registers, filters, condenser coils
Check operation of automatic controls
Reduce heat in garages, dock, and platform areas
Balance heating system
Evaluate humidification system
Check operation of all electric heating units
Establish a regular program to inspect, clean, and tubricate
equipment
Lower (winter} or raise (summer) indoor thermostat settings
Replace filters.
VENTILATION

Shut down system in unoccupied areas


Improve operation controls (tirneclocks)
Reduce ventilation rates to code allowables
Reduce outside air intake
TnspectoutdKor air &ampem - - - -
- - - -

Balance air intake-to-occupant load


Balance intake and exhaust air rate
Improve mechanical operation (fans, motors, dampers)
lmprove filter maintenance
Maintain positive interior pressure
Inspect all central systems and unitary controls.

INFILTRATION

Repair door and window caulking


Repair door and window weatherproofing
Replace broken glass
Adjust door closer
Refit doors and windows
Install temporary storm windows.

UTlhlTY PLANT DISTRIBUTION SYSTEMS

Adjust barometric damper


Monitor boiler makeup water
Operate minimum number of boilers
Isolate off -line boilers
Check condensate return system
Repair boiler, tank, and pipe insulation

Solar Design Manual


Example System Design

--;-
CHECKLIST 2 4
- -
As

ENERGY CONSERVATION MEASURES


(Sheet 2 of 4)

To be
Implemented
Yes&
UTILITY PLANT DISTRIBUIIONSYSTEMS (Continued)

Check boiler efficiency and monitor combustion


Eliminatdturn off gas pilot
Reduce steam pressure
Repair faulty radiator shutoff valves
Check operation of steam traps
Repair all leaks
Clean plant and distribution system equipment
Adjust airfluel ratios.

SERVICE WATER SYSTEMS

Repair leaks (piping, pump glands, steam traps)


-
Reduce the quantity of water used add restrictors
Lower hot water temperature setting
Check efficiency of oil- or gas-fired equipment
Raise cold water temperature settings on water fountains
Repair insulation on pipes and storage tanks
Install timeclock on recirculation pump.

Reduce illuminationk v e k where appropriate


Maximize use of daylight
Use higher efficiency lamps
Reduce or eliminate evening cleaning
Ciean lamps and fixtures
Improve reflectance of surfaces
Utilize task lighting
Use lower wattage lamps
Turn off when not in use.

8. MODERATE COST/HIGH COST


HVAC

1. Shut off air handling units whenever possible -3-


2. Reduce outside air intake when air must be heated or cooled
before use; repair or replace outside air dampers if necessary -2-
3. Reduce volume of air circulated through air handling units -2-
4. Shut off or reduce speed of room fan coils -3-
5. Shut off or reduce stairwell heating -2-
6. Shut off unneeded circulating pumps -2-
7. Reduce humidificationto minimum requirements -3-
8. Cycle fans and pumps where appropriate -x -
9. Reduce pumping flow --x-
10.
11.
Use damper controts to shut off air to unoccupied areas
Raise chilled water temperature
-2-
-3-
12. Shed loads during peak electrical use periods -3-
Solar Design Manual
~ x ~ l fSystem
l e Design Fearibil* Study- Page EX-25

CHECKLIST 2-4

ENERGYCONSERVATIONMEASURES
(Sheet 3 of 4)

To be
Implemented
YssNa
HVAC (Continued)

Use outside air for free cooling whenever possible


Reduce reheating of cooled air
Recover heating or cooling with energy recovery units
Reduce chilled water circulated during light cooling Loads
install minimum sized motor to meet loads
Replace hand valves with automatic controls
lnstall variable air volume controls
Install common manifolding of chillers
Insulate ducts and piping
Eliminate simuhaneous heating and cooling
lnstall night setback controls
Install water treatment to prevent tube fouling
lnstall multispeed/variablespeed cooling tower fans.

UTlLlN PLANT DlSTRlBUTlON SYSTEMS

Reduce steam distribution pressure


Shut off steam to laundry when not in use
increase boiler efficiency
Insulate boiler and boiler piping
-

InstalFeG6noflzer - - - - - - - -

lnstall air preheater


Install blowdown controls
Modernize boiler and chiller controls
Convert gas pilot to electronic ignition.

Convert to energy efficient systems


lnstall reflector systems.

BUILDING ENVELOPE

Reduce infiltration by caulking and weatherstripping


Install storm windows or double-pane windows
Install roof insulation
Install loading dock seals
lnstall vestibules on entrances
lnstall solar shading, screening, curtains, and blinds
install insulation in walls.
PLUMBING

lnstall faucets that automatically shut off water flow


Decentralize hot water heating or install tankless heaters
Add piping insulation
Electrically trace hot water supply piping to eliminate return piping
and pumps.

Solar Design Manual


-
Example System Design

ENERGY CONSERVATION MEASURES


(Sheet 4 of 4)

Implemented
Yes&
LAUNDRY

lnstall heat reclamation system for laundry wash water


Install heat reclamation system on dryers
Shut off equipment and appliances whenever possible
Install makeup air supply for exhaust.

KITCHEN

Shut off range hood exhaust whenever possible and install


dampers
lnstall high-efficiency steam control valves
Shut off equipment and appliances whenever possible
lnstall makeup air supply for exhaust
Install heat reclamation system for exhaust heat
Turn off lights in coolers
lnstall nighttime automatic steam cutoff.

SERVICE WATER

lnstall local boost heater(s) for 140 to 180°F water in lieu of raising
heater set temperature.

MISCELLANEOUS

lnstall incinerator heat recovery system


lnstall computerized energy monitoring and control system
Install motion sensors
lnstall thermal storagekogenerationsystem
Replace electric hot water heater with heat pump system.

Solar Design Manual


Example System Design Feasibility Study- Page EX-27

CHECKLIST 2-5

SERVICE HOT WATER DATA


(Sheet 1 of 2)

Building Load Requirements

Daily Load: 22galiday-student (maximum), 13.lgaVday


-
(average before conservation)-

How determined? ASHRAE 1980 Systems Guidelines

Daily load after conservation -Same BtuJday (maximum)


Same- Btulday (minimum)

Load temperature -1 20-OF

Load profile (list hot water load estimates) (Btu/month): (x 1Os)

Jan 9 3 Feb 8 4 - Mar -91- Apr 8 6 - May 4 2 - Jun 4 1 -

Jut 3 9 - Aug 3 3 - Sep 6 0 - Oct 7 2 Nov 7 9 - Dec 8 7 -

Annual load -007 x 106 Btu

Weekly use -7 days X w e e k d a y only


Daily use- Mostly days - X Mostly night Day and night

Use Patlern - Mostly steady Intermittent -X-

-
Use Rate Mostly constant
Variable (--I
(-
-
O ~ p tom - 2 O a p m )
gpm),

Typical daily load profile:

-See ASHRAE Systems p. 37.15 for sample profile

10. Usage - Lavatories , Showers - X , Food Preparation ,


Process ,Other (indicate usage by percent)

11. Distance from heater to point of use 20-ft (nearest),


- 200- ft (farthest)

Solar Design Manual


CHECKLIST 2-5

SERVICE HOT WATER DATA


(Sheet 2 of 2)

B. Main Heating System

1. Energy source: Gas Electric -X-Oil Steam


If steam, energy source for steam

2. Hot water heaterlstorage capacity 1,07O__gallons

3. Hot water heater type - Storage tankhurner - X Tankless


In-storage HX

4. Hot water set point 120-OF

5. Hot water draw rate -1 9 a p m (maximum), nominal

6. Hot water circulation Yes No -X-

7. Number of circulation loops Total piping length ft

8. Total circulation flow rate gpm

9. HW circulation operation -Day only Night onty


Constant

10. Cold water temperature 7 9 O F (max) 48 O F (min)

11. Cold water pressure 8 0 pig

12. Hot water pressure 80 psig

13. Hot water pressure relief valve setting: -1 2S__psi

14. Hot water high-temperature relief valve setting 2 10-OF

Solar Design Manual


CHECKLIST 2-7

CONSTRUCTION COST ESTIMATE SUMMARY


(See Appendix 2C for Calculations)

System Application: -Service hot water

Collector Type (i.e., fiat plate or evacuated tube): Flat plate

Collector Area (ft2): 1 , 6 0 0 -

Collector and Storage Tank Material Costs ($): -35,916


Mechanical Material Costs ($): -16,617
Electrical Material Costs ($): -2,646
Mechanical Labor Costs ($):

Electrical Labor Costs ($):

Other Costs ($1:

Bare Cost ($):

Subtotal Cost ($): ( Including freight)

Miscellaneous Costs (includes contingency,


overhead, profit, bonds and permits,
and liability) ($):

Total Construction Costs ($1:

Solar Design Manual


Exarnde Svstem Design Detailed Design- P a ~ EX-30
e

SECTION 3

DETAILED DESIGN

3.2 Overall System Schematic

From Table 3-1, Figures 3-2 and 3-6are selected as the coltector subsystem and interface subsystem
schematics, respectively. From Table 3-10, Figure 3-31 is used to determine the controls components.
Figures 3-38, 3-39,and 3-40are used to determine the performance instrumentation components.
Figure B illustrates the Example System P&ID.

3.3 Coltector Subsystem Design


3.3.1 Array Design

Array design is determined as follows:

a. The collector type is a flat plate, single-glazed coliector with internal manifolds

b. The collector size is 40 ft2 and the estimated number of collectors required is 40 panels

c. The collector tilt and orientation are to be 42" and 0° of true south, respectively. The 42" tilt was
determined by the example simulation program, and the 0' of true south is used because the
b

building orientation is true south.

d. The collector field layout is determined as follows:

1. The collectors should be mounted to one side of the elevator equipment structure on the roof.
The available width is approximately 150 ft. Using the suggestion in the manual for using 8
collectors to a bank, the required space per bank would be as illustrated by Figure C .

At 38 ftlbank, five banks will not fit to one side of the elevator equipment structure. Therefore,
to make two symmetrical rows of collectors, the design will be modified to contain 6 banks of
7 collectors each, for a total of 42 collectors.

2. Shading Calculation

Using the shading calculation methodology in Section 3.3.1.4, the minimum spacing distance
between rows is calculated as follows:

D = (L)(cos S) + (L)(sin S)(cos f) + (tan q)


where: L = loft
S = 42"
f = azimuth = 33.2' at 10 a.m., December 21 for a 32"N latitude
q = altitude = 30.8' at 10 a.m., December 21 for a 32"N latitude
D = 16.8ft~17ft

The layout of the collectors on the roof is illustrated by Figure D.

Solar Design Manual


Exarnvle Svstem Design Detailed Design- Page E X 3 1

e. Structural analysis and design is left for a structural engineer to do. The collectors will be roof
mounted, attached to a rack recommended by the collector manufacturer. The rack will be
supported on columns, penetrating the roof membrane, attached to I-beams in the roof structure.
The rack should be a minimum of 2 ft above the finished roof membrane. The collector weight is
120 Ib/collector. The fluid weight is estimated as:

(8.4 lb/gal)(2 gaWcollector)(42 collectors) + 200 ft pipe)(nlrl)(3/12)*(ft2)(63lb/ft3)= 1,324 lb fluid

Weight of 2-in. average copper pipe is: 21 lbl20 ft x 200 ft = 210 lb of copper pipe

Therefore, the dead weight on the roof, excluding the supporl structure, is estimated to be:

(120 Iblcollector x 42) + 1,324 lb fluid + 210 Ib of pipe = 6,574 Ib

The support structure must be designed to withstand 100-mph winds and support the collectors at
a 42' slope angle.

3.3.2 Piping Design

The piping design is determined as follows:

Piping material will be copper Type L

The pipe size for the collector loop is determined based on the recommended maximum velocity
of 4 to 6 ftlsec. Using the flow data from Table 3-5, Figure E illustrates the estimated volumetric
flow rates throughout the collector loop and the pipe sizes. The collector manufacturer recorn-
mends a flow rate of 2.5 gpm per collector.

The typical collector bank piping arrangement is illustrated by Figure F. The entire array is
plumbed in reverse return as shown in Figure E.

Pipe support shall be provided by the collector rack as shown in Figure G. Pipjng inside the
building should be supported in the same manner that the existing piping is supported.

Calculation of piping head loss. The head losses for the various components are listed below.
Table 3-5 was used to find the pressure drop of 150°F 50/50 propylene glycol.
Commnent Quantitv Pressure Drao (mil

3" Type L, Cu 4.55


2" Type L, Cu 2.50
1 114" Type L, Cu 4.06
1 1/4" ball valve 0.1 3
3" ball valve 0.1 0
3" check valve 0.02
Air separator 0.04
Heat exchanger 5.00
2" tee 0.1 3
3" standard elbow 0.91
3" coupling 0.27
2" coupling 0.15
1
1 1/4" coupling 0.10
Collector w
Subtotal pressure drop 18.0 psi
Allowance for error u
Total pressure drop 21.6 psi

Solar Design Manual


Example System Design -
Detailed Design Page EX-32

To convert to feet of glycol: 21.6 psi x 2.3 Wpsi = 49.7 ft

f. The initial loop pressurization requirement is calculated as follows:

Total static head = 50 + 12 + 10 = 72 ft

Initial pressurization = 72 + 4 = 76 ft (at pump level in basement)

76 ft / (2.3 Wpsi) = 33 psi (at pump level in basement)

3.3.3 Collector Subsystem Component Requirements

The component specification sheets are attached. The calculations for the pump and expansion tank are
outlined below.

a. Pump NPSH available: Using the procedure from Section 3.3.3.4.;

1. Suction pressure = 33 psig + 14.7 psi = 47.7 psia

2. Vapor pressure for 50150 glycol at 150°F = 3 psi

3. . NPSH allowable = 47.7 - 3 - 2 = 42.7 psia = 98.21 ft (Note: The fluid velocity head is
considered negligible)

b. Pump speed specification: Using the procedure of Section 3.3.3.4.;

2. Nl sr,so mm = (1750) (105 gpm)la / (49.7 ft)" = 958 rprn

3. N, ssm rpn = (3500) (105 gpm)lR1(49.7 ft)" = 1916 rpm

Based on the requirements discussed in Section 3.3.3.4, the 3500 tpm pump speed provides the
allowable specific speed (N,) closest to 2500 rprn.

c. Expansion Tank Sizing

Using the procedure of Section 3.3.3.6,the fluid volume estimate is:

collectors: 1.75 gallon/collector x 42 collectors = 74.0 gallons


3 inch pipe: (6.81I144) ft2x 250 ft x7.48 gallon/ft3= 88.4
2 inch pipe: (3.091144) ft2 x 85 ft x 7.48 gallon/ft3= 13.6
1 114 inch pipe: (1.261144) fF x 80 ft x 7.48 gallonlft3= 52
Subtotal fluid volume: 107.2 gallons
1Ooh contingency 10.7
Total: -1 18.0 galions

Solar Design Manual


-- C1 Collector Temperalure Sensor
Collector Array Data: Freeze Temperature Switch (NC)
42 collector panels
a,
'3,
FS1, FS2 Flow switch (NO)
40 ft2 /panel (3.7 rr?tWel) FM1, FM2, FM3 8tu Meter Flobwneter
42" slope TH1, TC1 Btu Meter 1 Temperature Sensor
M 2 ,TC2 Btu Meter 2 Temperature Sensor
M3, TC3 Bhr Meter 3 Temperature Sensor
Si, s2 Storage Temperature Sensor
53 Overtemperature Switch (NC)
From
4 I Other
NOTE: Use of Bhr meters is optional

COLD WATER

--
PI Air
/
Separator H4
Fill & Drain
P2

tines

Figure 0. Example System P&ID.


Example System Design Detailed Design- Page EX-34

Note: Minimum space required is 38 feet @I bank

Figure C. Typical 8 - Collector Bank

t
North Roof Plan (Not to Scale)

Figure D. Location of Collector Banks on Roof

2"/'
52.5 gpm

) gpmq
(7.5 ~ P ~ ( T Y P ) 35 ~ P ~ C T Y P 105 I
Array
Flgure E. Collector Pipe Sizes and Flow Rates supply

Solar Design Manual


Exam~leSvstem Design Detailed Design- fage EX-35

Flexible
Coupling q
-4- Bank Supply (TYP)
Figure F. Typical Collector Bank Piping

Figure G. CollectorIPipe Support

Location of
314" Female NPT Ports
Top & Bottom (Typ)

e
+ 6b+ Male N m 6q

9'

e
b

Figure H. Storage Tank


T-
Figure I. Storage Tank Details
Examvle Svstern Desi'an Detailed Desian- P a ~ EX-36
e

SPECIFICATION WORKSHEET
Flat Plate Liquid Collectors
Designer Owner Date

Project Page 1 of 3

Item Requirement

General Data

Application: (i.e., DHW heating, space heating, etc. -DHW heating


Fluid Type: 50150 propylene glycol and water-

System Type: (i.e., draindown, recirculation, etc.) -Closed loop anti-freeze


Quantity:

Nominal Size: i-e., 4 x 8 ft, 4 x 10 ft (1219 x 2438 rnm,


1219 x 3048 mm)
Gross Area: -40 ft2
Net Area: -37.5 ft2
Filled Weight: (Max., based on structural estimates) 140 Ibs

Wind Loading Capability: 100 rnph

Design Life:

Warranty:

Absorber Plate

Material: -Copper
Flow Pattern: ( i a , series, parallel) -Parallel
Manifold: (i.e., internal or external size) -Internal
Maximum Operating Pressure: 150 psig

Coating Type: Black chrome

Absorptivity: (Min.) 0.97

Emissivity: (Max.) -0.12


Expansion Capability: (fixed or floating within frame) -Floating absorber plate
Degradation: None

Solar Design Manuat


Examvle System Design Detailed Design- Page EX37

i SPEC1FlCATlON WORKSHEET
Flat Plate Liquid Collectors
'i
/ Designer Owner Date

Project Page 2 of 3

I
Requirement

Cover Glazing

Glazing Material: Low iron tempered glass

Glazing Fasteners: (easy field replacements) -Anodized aluminum strips


Number of Covers:

Impact Resistance:

Collector Casing

Casing Fastener: Screws

Frame Material: -Aluminum


Weep Hole Locations: -2-bottom
Finish: -Anodized brown
InleUOutlet Connection Locations: Sides

Mounting Method: (integral flange, etc.) -integral flange


Cover Gaskets and Outlet Grommets

Temperature Limits: (operation)

Temperature Limits: (installation)

insulation

Material and Type: -Polyisocyanurate


Back Thickness: -2 inch (1 inch fibergjass)
Side Thickness: -112 inch
R-Value for Back: -R-14

Solar Design Manual


Example System Design Detailed Design- Page EX-38
/ \

f SPECIFICATION WORKSHEET
\
Flat Plate Liquid Collectors
Designer Owner Date

Project Page 3 of 3

Item Requirement

Fluids and Flows

Fluid Type: -50/50 propylene glycol and water-


Operating Temperature Range: 0 -212 O F

Flow Rate Range: 2.5 gprn / collector

Allowable Pressure Drop at Design Flow Rate: 0.03 psi

ASHRAE Performance Test Data

F@): (Min.) 0.778

F,U,: Max.) -0.855 8tu/h*ft2*OF


Test Fluid: Water

Test Flow Rate: 2.5 gpm

Incident Angle Modifiers: -Kat =l.O -0.143 ( l / c o & - 1)

Certifications: -SRRC
SRCC Approvals: Yes

Mounting Requirements

Installation Orientation: (vertical or horizontal) -Vertical


Drainability Requirement: Yes

Maximum Collector-to-CollectorLateral Space: 4 inch

Manufacturer'sTypelModeI (or equivalent)


Example System Design Detailed Design- Page E X 3 9

SPECIFICATION WORKSHEET
Heat Transfer Fluids
) Designer Owner Date

I Project Page 1 of 1

Item Requirement

Application: -DHW heating


Type: (i.e.,glycol, water, etc.) -Propylene glycol and water
Operating Temperature Range: Maximum 2 5 0 ° F -Viscosity -0.64 cps-

Minimum - 3 0 ° F -Viscosity -1 87 cps-

Mixture Ratio: -50150


Toxicity Rating: -20.3 LD, 50
Vapor Pressure: (at rnax. temperature) -19.9psia
Maintenance Requirements: -2 yr change
Available Container Sizes: -55 gallon drum
Material Compatibility: -Copper and bronze compatibility
- -
- - - - - - - - - - - - - - - - -
- - - - - - - - -

Special Additives: - - - - - -

GuaranteeNarranty:

Manufacturer's Type/Model: (or equivalent)


,Item Requirement

Application: -DHW heating


Pump Type: -Single-stage, single suction, centrifugal-
Pumped Fluid: -50/50 propylene glycol and water
Pumping Temperature Range: ,

Fluid Specific Gravity @ Temperature: -I.024 @ 100°F


Fluid Viscosity @ Temperature: -3 cps @ 100°F
Design Flow: -105 gpm
Developed Head:

Shutoff:

Loop Max. Operating Pressure:

Available NPSH: -42.7 psig


Pump Speed: -3500
Pump Seals Compatibility with Fluid: -50/50 propylene glycol
Motor Impeller Connection: -Direct couple
System Connection Sizes and Types: -3 inch flanged
Mounting Orientation: -Horizontal
Pump Support Requirements: -Concrete pad
Available Electrical Service (V, I, 0, Hz) -120 v, 30 amp & 208 v, 60 amp, 3 phase-
Pump Code Requirements:

Pump Material: -Cast iron


Pump Operating Environment: -Indoor

Solar Design Manual


Exarnvle System Design Detailed Design- Page E X 4

SPECIFICATION WORKSHEET
Pumps
Designer Owner Date

I Project Page 2 of 2 I

Item Requirement

Ambient Temperature:

Motor Code Requirements: -Explosion proof


Space Requirements: -None
Drainback Operation Capability: (if applicable)
(Note: For some drainback systems,fluid must be
able b flow backward through pump.)

Manufacturer's TypelModel: (or equivaient)

Solar Design Manual


Example System Design Detailed Design- Page EX-42

SPECIFICATION WORKSHEET
Expansion Tanks

Designer Owner Date


Project Page 1 of 1

Item Requirement

Application: DHW Heating

Type: (bladder or free surface) -Bladder


Bladder replaceableinonreplaceable: -Replaceable
Total Volume: 1 18 gallons (in collector loop)

Type of Fluid: -50/50 propylene glycal and water


Operating Temperature Range: 30 to 250 O F

Maximum Operating Pressure: -75 psig


Fluid Expansion: (over temperature range) -10 gallons
Material Compatibility: -EPDM-50/50propyiene glycol compatibility-
Overall Envelope Limits: -None
Connection Type and Size: 112 inch NPT male

Warranty: 1 Yr

Manufacturer's TypeIModel: (or equivalent)


Example System Design Detailed Design- Page E X 4 3

SPEClFlCATlON WORKSHEET
Air Separator Valve
Designer Owner Date

Project Page 1 of 1

Item Requirement

Application: DHW heating

Size and Type of End Connections: 3 inch NPT, female, bronze

Material Compatibility: -50/50propylene glycol compatibility-


Minimum/Maximum Working Temperature: -30 to 250 O F

Maximum Working Pressure: -75 psig


Vent Connection Size and Type: -112 inch NPT, female
Warranty: 1 Yr

Manufacturer's TypdModel: (or equivalent)


Example System Design Detailed Design -Page EX-44
SPECIFICATION WORKSHEET
Flex Couplings

Designer Owner Date

Project Page1 of 1 I

Application: (torsion, lateral) -Lateral


Material: -Copper
Compatibility: -50/50 propylene glycol compatibility-
Connection Size and Type: -1 1/4 inch sweat
Geometry: -Bellows
Nominal Length: -1 ft
Maximum Expansion: -118 inch
Maximum Contraction: -118 inch
Maximum Operating Pressure: -25 psig
Minirnum/Maximum Temperature:

Insulation Requirements: Must be insulated

Cycles to Failure:

Warranty:

Manufacturer's Typehlodel (or equivalent)

Solar Design Man uaE


Exarn~leSvstem Design Detailed Design- Page EX-45

SPECIFICATION WORKSHEET
Insulation
Designer Owner Date

Project Page 1 of 1

Requirement

Application: -DHW heating


Type: -Rigid, closed cell
Material: Polyisocyanurate

Thermal Conductivity: -0.25 Btu inch/h ft2 O F

Operating Temperature Range: 0 to 350 O F

Ozone Resistance: -Yes


U.V. Resistance: -Yes
Odor/Outgassing: None

Flame and Smoke Characteristics: Stable to 350 O F

Code Requirements:

WeatherproofingNacketing: PVC jacket

Water Absorption: -None


Mildew Resistance: -Yes
Wall Thickness: (La., overall R-value requirement) R-8 minimum

Warranty: 1 Yr

Manufacturer's TypefModel: (or equivalent)

Solar Design Manual


Air Vent

Requirement

Application: DHW heating

Type: (i.e.,automatic, float, and manual, etc.) Automatic

Minimum/Maximum Operating Pressure: 0 to 25 psig

Minimum/Maxirnum Temperature Range: -0 to 350 O F


Size and Type of End Connection: 1/2 inch NPT, male

Fluid Compatibility: -50f50 propylene glocal compatibility-


Environmental Conditions: (i.e., freezing, dirt, rain, etc.) Outdoor, freezing, rain, dirt, etc,.

Warranty:

Manufacturer's Type/Model (or equivalent)


Example System Design Detailed Design- Page E X 4 7
\
/-
SPECIFICATION WORKSHEET
Check Valves

Designer Owner Date

I Project I
Requirement

Application: -DHW heating


Type: (La,
spring-loaded or swing check) -Swing check
End Connections: (type and size) -3 inch sweat
Material: -Copperlbronze
Pressure Rating: -150 psig
Code Requirements: ASME

Minimum/Maxirnurn Temperature: 30 to 250 O F

Minimum/Maxirnum Pressure: -0 to 75 psig


Minimum/Maximurn Pressure Differential
(i.e., across f IapperJplug): -0 to 40 psig
Fluid Compatibility: 50/50propylene glycol

Mounting Orientation: -Horizontal


Required Opening Pressure: -0.02 psig
Warranty: -1 Yr

Manufacturer's TypdModel: (or equivalent)

Solar Design Manual


cample System Design Detailed Design - Page EX-48

SPECiFICATION WORKSHEET
Pressure Relief Valves

Designer Owner Date

Project Page 1 of 1 I
\
Requirement

Application: -DHW heating


End Connections: -314 inch NPT, male
Material: Bronze

Set Pressure Limit: (setting) As noted below

Working Pressure: As noted below

Code Requirements:

Fluid Compatibility: 50150 propylene glycol compatiblity-

Steam Rating or Relief Capacity: -650,000 Btulh ASME steam rating


MinimumIMaximurn Working Temperature: 0 to 350 O F

Lifting Lever: Yes

Set Pressure Adjustability:

Warranty:

Manufacturer's Type/Model: (or equivalent)

-
PRVs at collectors 6 each at 25 psig setting, 20 psig working pressure

-
PRVs at heat exchanger 1 each at 75 psig setting, 50 psig working pressure

Polar Design Manual


Example System Design Detailed Design- Page EX-49
7 - -

SPEC1FlCATlQN WORKSHEET
Piping
>
Designer Owner Date

Project Page 1 of 1 ,

item Requirement

Application: DHW heating

Maximum Operating Pressure: -75 psig


Minimum/Maximum Temperature Range: -0 to 350 OF

Fluid Compatibility: 50/50 prapylene glycol compatibility-

Fluid Velocity: (Maximum) -6 ft/s


Material: Copper

Size and Type or Schedule: See below

ASTM Specification Requirements:

Dissimilar Material Connections: -None


Manufacturer's TypelModel: (or equivalent)

-
3 inch 250 ft Type L-
-
2 inch - 85 ft Type L

-
1 1/4 inch 80 ft Type L -

Solar Design Manuc


,ample System Design Detailed Design- Page EX-50
Storage Subsystem Design

..I Storage Tank Design

e storage volume for this design, using the 1 gallon/ft2requirement, is:

42 collectors x 40 ft2/collectorx 1 gallon/ft2= 1680 gallons

lettical tank will be designed. Typically vertical tanks have a length-to-diameter ratio of 3. The dimensions
the tank can be determined as follows:

1680 gallons x 0.1 337 ft3/gallon= 225 ft3

3/4~tD3= 225 ft3


D = 4.56 ft and L = 13.7 ft

\isis taller than the space available, but a diameter of 6 ft will provide a height of 9 it, which is acceptable.
eref fore, the storage tank will be 6 ft D x 9 ft H and will have four nozzles located as illustrated by Figure H.

4.2 Piping Design

a. Piping material will be copper Type t

b. The pipe size from the heat exchanger to the tank is determined based on the recommended
maximum velocity of 4 - 6 Ws. The required volumetric flowrate from Section 3.4.2 is calculated
as follows:

),g
n
p
(,r (62.1b/ft3)(1 Btu/lb*OF)> (1.05) (105 gpm) (64.27 lblft3)(0.866 Btu/Ib*OF)

gprn = 98.97 z 100 gprn

From Table 3-2A, the pipe diameter should be 3 inches. The pipe size from the solar storage
tank to the existing storage tank is based on existing line sizes which are 2 inch copper Type L.

c. Calculation of piping head loss

The head losses for the various components in the collector/storage subsystem interface are:

Component Quantity Pressure Drop-psi

Heat exchanger 1 5.0


3 in. Type L Cu 50 ft 1.O
3 in. ball valve 4=4ft 0.07
3 in. check valve I =lft 0.02
3 in. coupling 5 = 7.5 ft 0.14
3 in. standard els 10=50ft ful
Subtotal 7.14
Calculation error - 20 5% 1.43
Total 8.57 G 9.0 psi

To convert to feet of glycol: 9 psi x 2.3 ft/psi = 21 ft

'olarDesign Manual
Example System Design Detailed Design- Page EX-5j

3.4.3 Storage Subsystem Component Requirements

The component specification sheets are attached. Additional information regarding the components is
discussed as follows:

a. Storage Tank

In addition to the specification sheets, Figure I is required to complete the tank specification.

b. ,Heat Exchanger

A plate heat exchanger will be utilized. Using the procedure outlined in Section 3.4.3.2:

1. Effectiveness = 0.7

2. Fluid properties @ 110 O F are:

Glycol

C1= 2.84 cps


Water
P= 62.0 lb/ft3
C, = 1.0 E3tu/b°F
P= 0.68 cps

5. C, = 8.021 (105 gpm) (63.96 lblft3)(0.871 Btu/lba°F) = 46,918 Btulh-F

6. Cc = 8.021 (100 gpm) (62 Ib/ft3)(1.O B t ~ l l b ~=~ 49,730


F) Btu/he°F

7. T,,, = [(201,600 Btu/h)l{(O.7)(46,918 Btu/hm°F)}] + 100 OF = 106.1 OF

, = [{(0.7) (106.1-100°F) (46,918 Btuh))/(49,730 Bt~lha'F)] + 100 O F = 104.1 O


8. T

, = 106.1°F - [0.7(106.1 -100 OF)] = 101.8 OF


T

9. Estimated fouling factor = 0.00020

The specification sheet contains the balance of the requited information.

Solar Design Manuc


xarnvle Svstem Design Detailed Design- Page EX-52

c. Pump NPSH-Available and Speed

10 ft = estimated static head (4.35 psig)


184 ft = city pressure (80 psig)
3.72 psia = vapor pressure of water at 150 O F

= 248 ft of water

2. Pumpspeed

,N = [(4000) (248 ft)34]/(100)1R


= 25,998 rpm

N,, 750) (1OO)1Y(21)Y4


= [(I = 1784 rpm

Based on the requirements discussed in Section 3.3.3.4, the1750 rpm pump


provides the allowable specific speed (Ns) closest to 2500 rpm.

3.5 Instrumentation and Controls Subsystem Design

3.5.1 Solar Energy System Operational Controls

The recommended operational controls schematic is illustrated by Figure 3-31 as determined from
Table 3-10. The collector sensor and thermal switches will be located as illustrated by Figure J.

3.5.2 Solar Energy System-to-Load Interface Controls

System-to-load interface controls are not required.

3.5.3 Operational Instrumentation

The operational monitoring instrumentationconsists of temperature gauges, pressure gauges, and pressure/
temperature ports. These are located as illustrated by the PBID, Figure B. The pressureltemperatureports
will be installed within a few feet of each temperature gauge.

3.5.4 System Performance Monitoring lnstrumentation

Performance monitoring instrumentation consists of three Btu meters located as illustrated by


Figures 3-38(top), 3-39, and 3-40(top).

3.5.5 lnstrumentation and Control Component Requirements


The component specification sheets are attached. The locations of the sensors and switches on the storage
tank are illustrated by Figure K.

Solar Design Manual


Exarnvle Svstem Desian Detailed Design- Page EX-53

I A I
South T

Array
Return

Figure J. Collector Sensor Locations

f Valve

'Array \Spare
Outlet Return Well
Left Side! Front Riaht Side
w w w

>
Spare Cold Water Drain
Well T - Gage Array
S1 Valve
WP~Y
0
' 0 \0 d o '
.
Figure K. Storage Tank Sensor Locations

Solar Design Manui


Example System Design Detailed Design- Page E X 4 4
/
-
'
SPECIFICATION WORKSHEET
Thermal Storage Tanks
Designer Owner Date

Project Page 1 of 2 *

Item

Applicatiion: DHW heating

Volume: 1680 gallons

Dimensions: (refer to tank drawing) See sketch

Material: Steel

Code Requirements:

Maximum Allowable Pressure: 250 psig

Maximum Allowable Temperature: 225 O F

Mounting Orientation: Vertical

Mounting Supports: Flat bottom on concrete pad

Connection Types and Sizes: 3 inch NPT, male & 3/4 inch NPT, female

Connection Locations: See sketch

Manhole: No

Baffles: No

Lining: -Epoxy coating


Corrosion Protection: Epoxy coating

Level Gauge Requirements: Not required

Insulation Requirements: (if factory installed) N/A

Warranty:

Auxiliary Heating Type:

Manufacturer'sTypeIModel: (or equivalent)

*Second page not applicable to this system design.

Solar Design Manual


Exarnvle Svstem Design Detailed Design- Page EX-55

SPECIFICATION WORKSHEET
Heat Exchangers
Designer Owner Date
1
Project Page 1 of 2

Requirement

,pplication: (i.e., liquid-to-liquid, liquid-to-air,etc.) Liquid to liquid

ype: (i-e., shell and tube, multiplate, etc.) -Multiplate


lumber of Units:

IveraH Envelope: 4 wide x 4 long x 4 high

.imitations: -None
>odeRequirements: ASME

>onnectionSizes and Types: i.e., 2-in. (51 mm) flanged -3 inch flanged
system Interface Materiat: (i.e., copper tubing, etc.) -Copper Type L
service Life: (casing materials) -20 yr
Mounting Requirements: (i.e., floor, wall, etc.) Floor

:leaning Requirements: -Must be accessible


Number of Walls: (i.e., single wall, double wall, etc.) -Single
Venting: (for double-wail designs)

Operating Effectiveness: (nominal conditions)

Hot Side Cold Side

Fluid Type: -50/50 propylene glycol -Water


Fluid pH: -8.0 -8.0-
Dissolved Salts:

Nominal Inlet Temperature: -106.1 O F -100 O F


Nominal Outlet Temperature: -101.8 O F -104.1OF

Minimum Operating Temperature: -35 O F -35 O F

Nominal Flow Rate: -105 gpm - -1DO O F

Energy Transfer Rate: -201,600 Btulh- -201,600 Btulh-

Solar Design Manua


Example System Design Detailed Desi~n-Page EX-56

SPECIFICATION WORKSHEET
Heat Exchangers
Designer Owner Date

I Project Page 2 of2 I

Requirement

Hot Side Cold Side

Face Velocity: (for liquid-to-air systems only) -N/A -NIA


Specific Heat: -0.871 -1.O
Specific Gravity of Fluid: -1.025 -0.994
Thermal Condudivity of Fluid: -4.36 Btu*in/h*ft2*OF -2.63 Bt~*in/h*ft**~F
Viscosity of Fluid at Min. Temperature: N/A -NIA
Viscosity of Fluid at Operating Temperature: -2.84 cps @ I 1 0 OF -0.68 cps @ 110 O F
Maximum Allowable Pressure: -150 psig -250 psig
Operating Pressure: -75 psig -125 psig
Maximum Allowable Pressure Drops at Nominal Flow Rate: -5 psi -5 psi
Fouling Factor: -0.0002
Warranty: -5 Y r

Manufacturer's TypelModel: (or equivalent)

Solar Design Manual


SPECIFICATION WORKSHEET
Pumps
Designer Owner Date

Project Page 1 of 2

Requirement

Application: DHW heating

Pump Type: Single stage, single suction, centrifugal-

Pumped Fluid: -Water


Pumping Temperature Range:

fluid Specific Gravity @ Temperature:

Fluid Viscosity @ Temperature: -0.68cps @ 100 O F


Design Flow: -100 gpm
Devetoped Head: 21 ft at design flow

Shutoff: -25 ft
Loop Max. Operating Pressure: -125 psig
Availabfe NPSH: 108 psia

Pump Speed: -1750 rpm


Pump Seals Compatibility with Fluid: -N/A
Motor Impeller Connection: -Direct couple
System Connection Sizes and Types: -3 inch flanged
Mounting Orientation: Horizontaf

Pump Support Requirements: -Concrete pad


Available Electrical Service (V, I,0, Hz) 120 v. 30 amp & 208 v, 3 phase, 60 amp

Pump Code Requirements:

Pump Material: All bronze

Pump Operating Environment: -Indoor

Solar Design Manua


Examnle Svstem Design Detailed Design- Page E X 4 8

SPECIFICATION WORKSHEET
Pumps
Designer Owner Date

Project Page 2 of 2

Requirement

Ambient Temperature: -80 OF

Motor Code Requirements: Explosion proof

Space Requirements: NIA

Drainback Operation Capability: (if applicable)


(Note: For some drainback systems, fluid must be
able to flow backward through pump.)

Warranty:

Manufacturer'sType/Model: (or equivalent)

Solar Design Manual


Example System Design Detailed Design- Page E X 5
-
SPECIFICATION WORKSHEET
Tempering Valve

/ Designer Owner Date

Project Page 1 of 1

Item Requirement

Application: DHW heating

End Connections: 3 inch sweat

Operating Pressure: 125 p i g

Operating Temperature Range: 35 to 212 OF

Output Temperature Adjustment Range: 90 to 140 O F

Code Requirements:

Output Temperature Indicator: -Yes


Response Time: <1os

Warranty:

Manufacturer's Type/Model: (or equivalent)

Solar Design Manuc


Exam vle Svstem Deskn Detailed Design- Pane E X 4 0
SPECIFICATIQNWORKSHEET
Pressure Temperature Relief Valves

t Designer Owner Date

Page 1 of 1
Project

Requirement

Application : -DHW heating


End Connections: -314 inch NPT, male
Material: -Bronze
Set Pressure: -125 psig
Working Pressure: -125 psig
Set Temperature: -210 OF
MinimumIMaximum Working Temperature: -210 O F

Code Requirements: -ASME


Fluid: -Water
Steam Rating or Relief Capacity: -650,000 Btulh, ASME pressure steam rating
Minimum Temperature Element Length: -6 inch
Lift Lever: -Yes
Test Capability: -Yes
Set Temperature and Pressure Adjustability:

Warranty:

Solar Design Mallual


E x a m ~ l eSvstem Design Detailed Design - Page EX-61
\
SPECIFICATION WORKSHEET

Insulation
Designer Owner Date

Project Page 1 of 1

Item Requirement

Application: -DHW heating


Type: Rigid dosed cell

Material: Polyisacyanurate

Thermal Conductivity: -0.25 Btu*in/h*ft2*OF


Operating Temperature Range:

Ozone Resistance: Yes

U.V. Resistance: -Yes


Odor/Outgassing : None E

Flame and Smoke Characteristics: -Stable to 350 O F

Code Requirements:

Weatherproofing/Jacketing: None

Water Absorption: None

Mildew Resistance: -Yes


Wall Thickness: (i.e., overall R-value requirement) Tank & Hx, R-j 6 min.; Piping, R-8 min.

Warranty: 1 Yr

Manufacturer's Type/Model: (or equivalent)

Solar Design Manu4


Example System Design Detailed Design - Page EX-62
SPECIFICATION WORKSHEET
Air Vent

Designer Owner Date

I Project Page 1 of 1 I

Application: DHW heating

Type: (i.e.,automatic, float, and manual, etc.) Automatic

Minimum/Maximum Operating Pressure: -0to 125 psig


Minimum/Maximum Temperature Range: 35 to 210 O F

Size and Type of End Connection: -112 inch NPT, male


Fluid Compatibility: -Water
Environmental Conditions: (i.e.,freezing, dirt, rain, etc.) -NIA
Warranty: 1 Yr

Manufacturer's Type/Model (or equivalent)

Mar Design Manual


Example System Design Detailed Design- Page EX-63

SPECIFICATION WORKSHEET
Check Valves
Designer Owner Date

Project Page 1 of 1

ltem Requirement
Application: DHW heating

Type: (i.e., spring-loaded or swing check) Swing check

End Connections: (type and size) -3 inch sweat


Material:

Pressure Rating: 125 psig

Code Requirements:

MinimumIMaxirnum Temperature:

Minimurn/Maximum Pressure: -O to 125 psig


Minimum/Maxirnum Pressure Differential
(i.e., across ffapperlplug): -0 to 40 psig
Fluid Compatibility: Water

Mounting Orientation: -Horizontal


Required Opening Pressure: -0.02 psi
Warranty:

Manufacturer'sTypeIModel: (or equivalent)

Solar Design Manu


Example System Design Detailed Design - Page EX-64
/ \

f SPECIFICATION WORKSHEET
'i
Pressure Relief Valves
I Designer Owner Date

Project Page 1 of 1

Requirement

Application: -DHW heating


End Connections: -314 inch NPT, male
Material: -Bronze
Set Pressure Limit: (setting) -125 psig
Working Pressure: 80 psig

Code Requirements: -ASME


Fluid Compatibility: -Water
Steam Rating or Relief Capacity: 650,000Btulh ASME pressure rating-

Minimum/Maximum Working Temperature: 35 to 210 O F

Lifting Lever: Yes

Set Pressure Adjustability:

Warranty:

Manufacturer's TypeiModel: (or equivalent)

Solar Design Manual


Example System Design Detailed Design- Page EX-65

SPECIFICATION WORKSHEET
Piping

Designer Owner Date

Project Page 1 of I

Item Requirement

Appiication: DWH heating

Maximum Operating Pressure: 125 psig

Minimum/Maximum Temperature Range: -Oto210 O F


Fluid Compatibility: Water

Fluid Velocity: (Maximum) 6 ft/s

Material: -Copper
Size and Type or Schedule: 3 inch Type 1

ASTM Specification Requirements:

Dissimilar Material Connections: -Dielectric unions required at tank-


Manufacturer's Type/Model: (or equivalent)

Solar D e s i ~ nManual
Exam~leSvstem Design Detailed Design- Page EX-66

SPEClFlCATlON WORKSHEET
Differential Temperature Controller
Designer Owner Date

Project Page 1 of 1

Requirement

Application: -DHW heating


Number of Outputs:

On/Off ThresholdsIRange: -20A°F


Storage High Temperature Shutoff: -160 to 210 O F

Freeze Protection: Not required

Operating Environment: -Indoor


Input Power: -110 v, 20 amp
Output Relay Capacity: (Volt, amp) -1lOv,20amp
Power Backup: -Not required
Set Point Adjustability: -No
Control Accuracy: -* 2%
Display Capability: -Temperature readings
ManualfAuto Capability: Yes

Mounting Dimensions: Wall mounting

UL Requirements: -UL listed


Warranty:

Manufacturer's Type/Model (or equivalent)

Solar Design Manual


Example System Design Detailed Design- Page EX47

SPECIFICATION WORKSHEET
Temperature Switches
Designer Owner Date
Project Page 1 of 1

Requirement

Application: Freeze & overheat protection

Type: (NC, NO, DP, ST, DT) -As shown on electrical schematic-
Temperature Set Point Range: -As shown on electrical schematic-
Switch Contact Rating:

Number of Contacts: 1

Construction: -Copper
Warranty: 5 Yr

Manufacturer's TypeIModel: (or equivalent)

Solar Design Manuc


Example System Design Detailed Design- Page EX-68
.-- \
SPECIFICATION WORKSHEET \
Temperature Sensor

1 Designer Owner Date


I
Project Page 1 of 1 1

Requirement

Application: Differential temperature controller-

Type: (thermister, RTD, IC) RTD

Resistance/TemperatureCharacteristics: As required for contro!ler

Operating Temperature Range:

Accuracy: *2 O F

Leads: -As required for controller


Casing Material: Copper

Interchangeability: -Not required


Matching: Yes

Attachment: -Strap or bolt on


Response Time: As required for controller

Warranty: -5 Yr

Manufacturer's Type/Model: (or equivalent)

Solar Design Manual


Example System Design Detailed Design- Page EX-69

SPECIFICATION WORKSHEET
Btu Meters

Designer Owner Date

Project Page 1 of 2 I
Item Requlrernent
Application: DHW heating

Type: Electronic

#1 #2 #3

Average Continuous Flaw:

Peak Flow:

Minimum Flow:

Operating Temperature Range:

Maximum Operating Pressure:

Temperature Sensor Type: -RTD


Temperature Sensor Matching: -Yes
Temperature Sensor Attachment: -Thermowell
Flowmeter Type: -Nutating disk
Flowmeter Connection Sizes and Types: -3 inch sweat
Maximum Allowable Pressure Drop Across Flowmeter: -1 psi
Integrator Readout Requirements: -Btu, DT, Volume, & flowrate
Fluid: prop-glycol w a t e r water

Fluid Specific Gravity: (@ 11O°F) 1.025 0.993 0.993

Fluid Specific Heat: (Btu/lba°F @ 1 10°F) -0.871 1 1

Sensor (Temp and Flow) Mounting Requirements: Horizontal

Input Power Requirement: -110 volts, ac


Warranty:

Solar Design Manual


Example System Design Detailed Design -Page EX-70
/ --,
f SPECIFICATION WORKSHEET \I
Btu Meters 1
Designer Owner Date

Project Page 2 of 2

Item Requirement 1

Site Adjustment Capability: -Yes


Tamper Resistance: -Yes
Power Backup: -Yes - batteries
Environmental Conditions of Integration:

Manufacturer's TypeIModet: (or equivalent)


SYstem Design
Exam~h? Detailed Design- Page EX-71

SPECIFICATION WORKSHEET
PressureRemperature Ports
Designer Owner Date

Project Page 1 of 1

Item Requirement

Application: -Performance monitoring of solar system-


Material: (body and gasket) -Brass, Nordel
Connection Size and Type: -112 inch NPT, male
Maximum Operating Pressure: -250 psig
Minirnum/Maximum Operating Temperature: -0 to 350 O F

Test Probe Diameter Requirements: -1/8 inch diameter probe


Manufacturer's TypeIModel: (or equivalent)

Solar Design Manual


Exam ole Svstern Desian Detailed Design- Page EX-72
- - - - - - - - - - - -- -

SPECIFICATION WORKSHEET
Pressure Gauges

I Designer Owner Date


I
I Project Page 1 of 1

Item Requirement
Application: -DHW heating
Pressure Range: (max.) -250 psig
Operating Pressure Range: 0 to 250 psig

Operating Temperature Range: -0 to 212QF


Connection Type and Size: -1/2 inch NPT,male
Dial Size: -4 inch
Pressure Indication Range: -collector loop-0-100; storage loop-0-150-
Accuracy:

Indication Increment: -1 psi


Fluid Compatibility: -Collector-50f50 pro-glycol; storage-water-
Warranty:

Manufacturer's Type/Model: (or equivalent)

- -

Solar Design Manual


Example System Design Detailed Design- Page EX-73
/ \
SPECIFICATION WORKSHEET
Thermometers
Designer Owner Date

Project Page 1 of 1

Requirement
Application: 7
DHW heating

Type: -Mercury bulb


Maximum Operating Pressure: -250 psig
Operating Temperature Range: 0 to 212 O F

Temperature Indication Range: -0 to 225 O F

Connection Type and Size: -1 2 inch NPT, male-


Dry Well or Immersion: -Dry well
Size of Readout: 7
8 inch

Accuracy: -f 5%
Stern Length: -As required
Fluid Compatibility: -N/A
Warranty: 5 Yr

Manufacturer's Type/Model: (or equivalent)

Solar Design Manual


Example System Design Detailed Design - Page EX-74

3.9 PerformancelCostVerification

3.9.1 Verification of Thermal Performance

Ideally, a sophisticated simulation computer program would be used to determine the performance of the de-
signed system. For this example, the example simulation program used in Section 2.3.1 will be used. The
inputs for the program are fisted as foilows.

Collector Parameter Set

1 NUMBER OF COLLECTOR PANELS


2 COLLECTOR PANEL AREA
3 FRWL (TEST SLOPE)
4 FR*TAU*ALPHA (TEST INTERCEPT)
5 COLLECTOR SLOPE DEG
6 COLLECTOR AZIMUTH (SOUTH = 0) DEG
7 INCIDENCE ANGLE MOD TYPE (8-10)
8 NUMBER OF GLAZINGS
9 INC ANGLE MODIFIER CONSTANT
10 INC ANGLE MODIFIER VALUE(S)
11 COLLECTOR FLOW RATVAREA
12 COLLECTOR FLUID SPEClFtC HEAT
13 MODIFY TEST VALUES (1=Y,2=N)
14 TEST COLLECTOR FLOW RATOAREA LB/HR- IT2
15 TEST FLUID SPECIFIC HEAT BTUILB-F

Storage Parameter Set

1 CITY CALL NUMBER


2 WATER STORAGEVOLUME - - - - GALLONS
3 BUILD~NG
- - - - - - - - -

UA (0FOR DHW ONLY) BTU/HR-F


4 FUEL (I=EL, 2=NG, 3=01L, 4=OTHER)
5 EFFICIENCY OF FUEL USAGE
6 DOMESTIC HOT WATER (1=Y, 2=N)
7 DAILY HOT WATER USAGE GALLONS
8 WATER SET TEMPERATURE F
9 ENVIRONMENT TEMPERATURE F
10 DHW STORAGE TANK SlZE GALLONS
II UA OF AUX STORAGE TANK BTUtHR-F
12 PlPE HEAT LOSS (l-Y, 2-N)
13 INLET PlPE UA
14 OUTLET PlPE UA
f 5 RELATIVE LOAD HX SlZE
16 COLLECTOR-STORAGE H (1=Y, 2 4
17 TANK SIDE FLOW RATEIAREA
18 HEAT EXCHANGER EFFECTIVENESS

Solar Design Manual


Example System Design Detailed Design- Page EX-75

Note:
*Daily hot water usage; the monthly values are input by typing "7V"

Jan 3936 May 1968 Sept 3933


Feb 3929 June 1967 Oct 3936
Mar 3936 July 1968 Nov 3933
AP~ 3933 AW 1968 Dec 3936

**Environment temperature; the monthly values are input by typing'9 V"

Jan 60 May 65 Sept 70


Feb 60 June 75 Oct 70
Mar 65 Juty 75 Nov 65
AP~ 65 Aug 75 Dec 60

"*Value indicated is based on the following:

where: L= pipe length (ft)


AT = temperature difference (OF)
r, = outside radius of insulation (ft)
ri = inside radius of insulation
k= insulation thermal conductivity (Btu/h8fte°F)
h= convective coefficient (Btu/h*ft2*OF)

0.03 1 0.214 0.13 36.9


0.03 1 0.172 0.088 9.5
0.03 1 0.141 0.057 13.5
Total 59.9 z 60.0

The results are listed as follows:

Design Handbook Sample Run 2

Water Storage System


Ftat Plate Collector

Solar Heat DHW Aux


MMBtu MMBtu MMBtu MMBtu F

Jan
Feb
Mar
AP~
May
Jun
Jut
Aug
S ~ P
Oct
Nov
Dec
Yr

Solar Design Manual


Example System Design Detailed Design- Page EX-76

3.9.2 Cost Estimate

The attached tables show the estimated cost for the example, expressed in 1985 U.S. dollars. The
costs must be adjusted to the year of proposed construction. The system cost is:

Material = $44,452.00
Labor = 14,861.00
Freight = 1,290.00
Work Comp (5.29%) = 776.00
Soc. Sec. (7.05%) = 1,034.00
Unempl. Tax (1%) = 147.00
Sales Tax (7%) = 3.lf2.00
Subtotal $65 ,472.00

Contingency (5%) =
G & A (I Oa/o) =
Profit (10%) =
Bonds & Permits (1%) =
Liability t nsurance (1%) =
Subtotal

Total iiu&&!u
The design cost estimate detail is listed in Table 5.

3.9.3 Economic Evaluation

The installed performance for the Detail Design run is estimated to be:

Solar contribution = (531.7 - 101.5)/1.20 = 358.5 MMBtu

Solar fraction = 358.5/531.7 = 0.67

Assuming the electrical energy cost of $39.84/MMBtu, the TLCC with solar is:

Design and Installation Costs $84,855.00


Auxiliary energy requirement (MMBtuIyr) 173.2
Auxiliary energy costs ($/yr) 6,900.00
Operating cost ($/yr) 714.00
Maintenance costs ($/yr) 1,697.00

Total Life Cycle Cost $168,248.00

When this cost is compared with the TLCC without solar of $189,723, the design is seen to be cost-
effective.

--

Solar Design Manual


Example System Design Detailed Design- Page EX-77

-
Table 5 Design Cost Estimate Detail
Description Quantity Unit Materials Labor Total

Coltectors 42 each
Collector supports $2140
Crane 4 hours 90
Tank ( I 680 gallon) 1 each 31 6
Crane 2 hours 90
Piping
3 in., Cu L 300 feet 10.65
2 in., Cu L 115 feet 7.70
1 1/4 in., Cu L 80 feet 5.75
Ets
3 in., Cu L 20 each 29.00
2 in. ,CuI. 10 each 16.15
I 114 Cu., L 12 each 12.38
Tees
3 in., Cu L 4 each 46.00
2 in., Cu L 10 each 25.00
1 114 in., Cu L 6 each t 9.88
Couplings
3 in., Cu I. 15 each 25.00
2 in., Cu L 10 each 13.65
1 1/4 in., Cu L 10 each 10.85
Air separator 3 in I each 80 .
Check valves 3 in. 2 each 25
Ball valves 3 in. 9 each 25
Bal valves 1 114 in 12 each 11.SO
Pump P1 1 each 80
Pump P2 1 each 80
Valve V1 1 each 125
Expansion tank 1 each 75
Automatic air vent 8 each 5.55
Insulationfoam
pipe 3 in. 300 feet 1.99
pipe 2 in. 115' feet 1.87
pipe 1 If4 in. 80 feet 1.72
el 3 in. 20 each 3.99
el 2 in. 10 each 3.72
el 1 1/4 in. 12 each 3.43
tee 3 in. 4 each 5.90
tee 2 in. 10 each 5.60
tee 1 114 in. 6 each 5.17
valve 3 in. 9 each 5.90
valve 1 1/4 in 12 each 5.17
tank urethane 230 SF 0.78
Controls/instruments Est. 1750
Electrical Est. 9M,
Subtotal $14,661

Freight

Totals $14,661

Solar Design Manual


Desian Manual Index Index- Paze I N 4

ACTIVE SOLAR HEATING SYSTEMS


DESIGN MANUAL

Air collector system, 1-10, 3-110 Component specifications


Air cooled collectors, 3-110, 3-114 sample worksheets, 4-4,4-5, 4-6
Air filters, 3-13, 3-113, 3-129 Conceptual analysis, 1-1
Air handler unit, 3-116 summary, 1-29
Air separator, 3-12,3-54 Conference
Air vent owner-NE, 1-2
manual, 3-54 Conservation methods, 2-3
automatic, 3-12,3-54 Construction
Antifreeze system, 1-8, 5-4 cost, 2-8,2-27,2C-1
Array(see collector array) package, 4-2
ASHRAE specifications, 4-3, 4B-1
handbooks, 1-3,3-51 Control mode matrix, 3-77, 3-108, 3-132,3-142
standards, 2-7,3-40 Control schematic drawing, 3-77, 3-108,3-132,
3-142
Backflow preventer, 3-13,3-70 Controllers, 3-105, 5-15
Btu meter, 3-99,3-106,546 Coolant(see heat transfer fluids)
Building information, 1-33, 2-2, 2-15 Corrosion, 3-42,3-62, 5-7
Costs, 1-13
Checkout procedures, 3-98 construction, 2-8
Codes and standards, 3-28, 3-39, 3-113 estimate for installed system, 3-144
Collectors preliminary estimate, 1-28
certification, 2-6, 3-40 Cost-effectiveness, 1-28, 2-9
evacuated tube, 3-17, 3-40,3B-1 allowable first cost, I-28
flat plate life-cycle cost, 2-9
air cooled, 3-110, 3-114 simple payback, 1-28
liquid cooled, 3-17,3-39
lessons learned, 5-9 Damper
mounting location, 3-25, 3-26, 3-27 backdraft, 3-116
orientation, 2-7, 2A-2,3-19,3-110 flow balancing, 3-113
performance range, 1-13 lessons learned, 5-18
size, 3-18, 3-110 manually operated, 3-116
slope, 2-7, 2A-2,3-19,3-110 remotely operated, 3-115
Collector array Design
arrangement, 3-19,3-22,3-56, 3-111 drawings, 3-56, 3-72, 3-108, 3-117, 3-130,
design, 3-17 3-142,4-2
manifold package, 4-2
external, 3-19, 3-21 review, 3-14,3-59, 3-73, 3-109, 3-119, 3-131,
internal, 3-19, 3-20 3-143,3-145
shading, 3-19, 3-23 Detailed system design, 3-1
sizing calculations ,I-13J-27, 2-6, 2-10, 5-2, 5-3 Dielectric insulator, 3-29
spacing, 3-19,3-24, 3-111 Differential temperature controller(DTC),3-74,
support structure, 3-24,3-28,3-111 3-1O5,3-l4l
thermal expansion, 3-1 9 Drainback system, 1-6, 5-4
Collector subsystem design Ducting
air collector, 1-10, 3-110 constnrction requirements, 3-118
liquid collector, 1-5, 3-17 design, 3-112
drawings, 3-117

Solar Design Manual


Design Manual Index Index- Page IN-2

ACTIVE SOLAR HEATING SYSTEMS


DESIGN MANUAL

W E X (Continued)
Ducting(c0ntinued) Heat exchangers(c0ntinued)
flow balancing, 3-113 shell-and-tube, 3-63
flow rate, 3-112 waterlair, 3-129
insulation, 3-113 Heat transfer fluids, 3-41
leaks, 3-1 13 corrosion control, 3-42
lessons learned, 5-18 density, 3-43
pressure drop, 3-112 double separation, 2-2,2-16,3-42
reverse return, 3-112 glycol, 3-42,5-4
routing, 3-113 heat capacity, 3-43
sealing, 3-113 potable water, 3-42
thermal conductivity, 3-44
Economics(see cost) viscosity, 3-44
Electrical drawings, 4-3 Hot water recirculation loop, 2-5, 2-6, 2-24
Energy conservation methods, 2-3,2-18
Environmental constraints, 2-2, 2-16 Insolation, 2A- 1
Evacuated collectors, 3-17, 3-40, 38-1 lnstallation checkout procedure, 3-98
Expansion compensation device, 3-34 sample, 4A-1
Installation drawings, 4-2
Fans, 3-114,s-17 Instrumentationand controls
F-CHART,2-6 air collector system, 3-132
adjustment, 2-7 liquid collector system, 3-74
guidelines for use, 2B-1 operational, 3-14, 3-74, 3-98, 3-132, 3-140, 5-15
Feasibility study, 2-1 performance monitoring, 3-99, 3-140
Filters fnsulation, 3-54, 3-71, 5-14
air, 3-13, 3-113,3-129 ducting, 3-113
Fiat plate collector materials, 3-54
air cooled, 3-110,3-114 piping, 3-55
liquid cooled, 3-17, 3-39 Interface controls
Flexible coupling, 3-56 solar/conventional, 3-89
Flow indicator, 3-98 IOM manual, 4-6
Flow switch, 3-75
Freeze protection methods, 1 4 5 - 4 Lessons learned, 5-1
Freezestat, 3-75 Btu meters, 5-16
collectors, 5-9
Glycok, 3-42, 5-4 controllers, 5-15
Goals, 1-2, 1-30, 2-2, 2-1 1 corrosion, 5-7
dampers, 5-18
Heat exchangers, 3-63 drainback system, 5-4
design requirements, 3-64 drainback tank, 5-17
double-walled, 1-9, 3-42 ducting, 5-18
drawing, 3-72 fans, 5-17
effectiveness, 3-64, 3-65, 5-12 freeze protection, 5-4
fouling factor, 3-67, 3-68,3-69 glycol system, 5-4
in-tank, 3-2, 3-63, 3A-1 heat exchanger, 5-12
insulation, 3-71 insulation, 5-14
muftiplate, 3-63 lightning, 5-8
overpressure, 5-7
Design Manual Index Index- Page IN-3

ACTIVE SOLAR HEATING SYSTEMS


DESIGN MANUAL

JlDF&(Continued)

Lessons learned(continued) Piping(continued)


oversizing system, 5-2 drainback systems, 3-30,5-13
overtemperature, 5-6 drawing, 3-57
pebble bed, 5-19 flow balancing, 3-53
piping, 5-13 head loss, 3-36
pumps, 5-12 insulation, 3-55
recirculation system, 5-5 materials, 3-29
storage tank, 5-11 oversize return, 3-30
undersizing system, 5-3 pressure drop, 3-36
valves, 5-14 reverse return, 3-20,3-21, 3-29
Lightning protection, 3-26,3-27,5-8 size, 3-29,5-13
Liquid collector systems, 1-5,347 soldered joints, 3-35
Load, 2-4 support, 3-34
preliminary estimate, 1-3 vent, 3-32
profiles, 2-4 Piping and instrumentation diagram(P&ID), 3-2,
service water heating, 1-3, 2-5, 2-22 3-1 4, 3-15,3-16
space heating, 1-3, 2-5,2-25 Pressure drop, system, 3-36,3-123
Location, 1-3 Pressure gauge, 3-98 a,

collectors, 3-25 Pressure regulator, 3-13,3-70


storage, 3-61, 3-121 Pressure temperature port, 3-56, 3-99
Pressurization, initial, 3-36
Manning equation, 3-30 Problems(see lessons learned)
Pumps, 3-45,3-70,s-12
National Weather Service, 2-2, 2A-1 capacity, 3-45
drive motor, 3-49
Owner dual pump installation, 3-50
A/E conference, 1-2 headlflow curve, 3-46
goals, 1-2, 1-30, 2-2, 2-11 materials, 3-49
NPSH minimum, 3-47
Pebble bed, 1-11,3-121,5-19 port size, 3-49
air velocity, 3-123 selection, 3-45
configurations, 3-122,3-124, 3-126, 3-127 speed, 3-48
container design, 3-124
filling procedure, 3-128 Recirculation system, 1-9,5-5
insulation, 3-124 Reverse return, 3-20, 3-21, 3-29
pebbles, 3-125 Roof penetrations, 3-26, 3-57, 3-58
plenums, 3-123, 3-124
pressure drop, 3-123 Service water heating
sizing, 3-122 toad, 1-3, 1-31, 2-5,2-22
Performance schematics, 3-3
collectors, 2-6 with air collector system, 1-11,3-129,3-130
systems, 1-13, 2-6, 3-144 with antifreeze system, 1-8
Pete's plug, 3-56, 3-99 with drainback system, 1-6
Physical constraints, 1-3, 1-27 with recirculation system, 1-10
Piping, 3-28, 3-61 Sight gauge, 3-51,3-62
branch connections, 3-32,3-33
design, 3-28, 3-61, 5-13
Design Manual Index Index- Page IN-Q

ACTIVE SOLAR HEATING SYSTEMS


DESIGN MANUAL

JNQFX(Continued)

Site survey, 1-2, 2-2,2-16 Thernometers, 3-98


environment, 2-2 Thermsiphoning, 1-8
physical constraints, 1-3 TRNSYS, 2-8
Solar in Federal Buildings Program, 1-3 N A
Solar radiation, 2A-1 energy design guidelines, 1-3
Solder, 3-35
Space heating Valves, 3-52,s-14
load, 1-3,2-5, 2-25 check, 3-53
schematics, 3-3 control, 3-13
with air collector system, 1-10 drain(manual), 3-54
with antifreeze system, 1-8 fill/flush, 3-13, 3-54
with drainback system, 1-6 flow setting(circuit setter), 3-12,3-30,3-53
with hydronic radiant heat system, 1-12, 3-2 flushtfreeze protection, 3-12, 3-54
with recirculation system, 1-10 isolation, 3-12,3-30,3-53
Specification pressure relief, 3-12, 3-53,3-70, 5-7
components, sample worksheet, 4-4, 4-5, 4-6 pressure/temperature relief, 3-12,3-70
construction, example, 4-3, 48-1 tempering, 3-13,3-71
Standards, ASHRAE, 2-7 vent, 3-12
Standards, HVAC, 3-112 Vent pipe, 3-32
Storage size estimation, 1-27,3-60, 3-122
Storage subsystem design Wire routing drawing, 3-108,3-142
air collector system, 3-121 Wiring diagram, 3-1O8,3-142
liquid collector system, 3-60
Structural analysis, 3-24,3-28
Supply water temperature, 1-3,1-4
System configurations, 1-5,3-2
System design description, 2-10, 2D-1
System schematic drawing, 3-2

Tanks
drainback, 3-50, 5-17
drawings, 3-51! 3-58, 3-72
expansion, 3-13, 3-51
lining, 3-5 1, 3-62
material, 3-50
preheat, 3-61
size estimating, 3-60
storage, 3-60,3-62,5-11
Temperature sensors, 3-107
limit switch, 3-75
location, 3-75,3-78
RTDs, 3-105, 3-107
thermistors, 3-105,3-107
thermometers, 3-98
Thermal expansion, 3-32
Thermal load(see load)
Thermal storage(see storage)

1
Solar Design Manual

Вам также может понравиться