Software HOW TO MONITOR AND ARCHIVE DATA FROM SIEMENS SIMATIC S7 INTO MS EXCEL USING ACCON
of Life phase
Industrial Monitors S7 EASYLOG
Industrial Switches FOXON academy tour 2018
This document will show you how to configure ACCON S7 EasyLog correctly for successful monitoring and archiving of
Training data from PLC Siemens SIMATIC S7 into MS Excel.
Remote Management Please, don’t hesitate to contact us in case of any questions. Case Study: “Manually measuring
Thank you in advance. temperatures in halls is obsolete
Wireless Communications
and inefficient.” Třinecké
Software / hardware used for this test:
železárny, a.s. – Moravia Steel
ADS
PLC SIMATIC S7 CPU 315-2DP (real data source)
Hardware adapter ACCON Netlink PRO Compact – firmware 2.52 KEPServerEX® Version 6.4 Now
ACCON S7 EasyLog – version 3.5.0.3 Available
Microsoft Office Excel 2010 SP2
  The newest version 3.5.0 of PLC
analyser AutoSPY is now available
Solution example

ACCON S7 EasyLog serves for simple data recording from PLC Siemens SIMATIC S7 into a CSV file (Comma-
PF 2018 - May the force 4.0 be
separated values) readable by MS Excel.
with you!
If you want to communicate with multiple PLC’s at the same moment, you must install an adequate number of
EasyLog applications – each in a different folder (even in this case you need only one licence per a computer).
 
https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 1/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

GALLERY Reportáž: SPC/IPC Norimberk


ACCON S7 EASYLOG CONFIGURATION 2017 očima FOXONu

1. Install ACCON S7 EasyLog.


Nová aplikace eCatcher Mobile!
The trial version (SetupS7EasyLog.exe file) is available for free on the www.foxon.cz website - on the ACCON S7
Spravujte modemy eWON přes
EasyLog page or in the Downloads menu.
telefon
2. EasyLog configuration can be launched from StartProgramyDELTALOGICACCON-S7-EasyLog menu via ACCON-S7-
EasyLog item.
Jak probíhala letošní FOXON
Academy Tour?
(http://www.foxon.cz/en/gallery-
4/examples-of-broken-or-
repaired- Třetí část velké eWON Flexy
servomotors.html) recenze: Vzdálený přístup na
Sample of broken or LOGO!
repaired servomotor in
FOXON company, type: ADS
1FK7042-2AF71-1BG0
(http://www.foxon.cz/en/gallery-
SEND INQUIRY
4/examples-of-broken-or-
repaired-
servomotors.html)

(http://www.foxon.cz/en/gallery-
4/examples-of-broken-or- 3. Press the Config button to create a new configuration.
repaired- 4. Set the following parameters in Basis configuration tab:
servomotors.html)
Sample of broken or Device number = a number in the list of devices in Devices tab
repaired servomotor in PLC number = device address in MPI network (or in some other network used)
FOXON company, type: Rack number and Slot number = identification numbers for S7 devices (e.g. the default values for S7-300 are 0 and
1FK7042-5AF71-1AA0 2)
(http://www.foxon.cz/en/gallery-
https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 2/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

4/examples-of-broken-or-
repaired- Then set parameters defining the way of data archiving – parts called Protocol configuration and Archiving
servomotors.html) configuration.

All images (http://www.foxon.cz/en/gallery-1/home.html)

ZPRAVODAJ
Přihlašte se pro zasílání FOXON
zpravodaje obsahujícího novinky,
doporučení, recenze, update
software atd.

e-mail adresa
5. Press AGLink40_Config button to open a dialog where you can configure connection to a device and set corresponding
parameters according to the selected type of connection.
6. We use ACCON NetLink PRO in this example, and therefore select S7-NetLink-PRO. Přihlásit
The following parameters should be set in the dialog (on Devices tab):

NetLink IP-Address = IP address of ACCON NetLink PRO Adapter


Automatic reconnaissance of the net-related parameters = automatic reconnaissance of the network parameters
for connection
https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 3/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

PG-Address = profibus card address (a number range from 0 to “Highest node address”)
Timeout = time limit for the connection with a device (the value can be increased if any communication problems
arise, e.g. in case of a longer response time)
Transmission rate = transmission speed used in the network
Highest node address = the highest address which can be used in the network (the same value must be set for all
participants)
Profile = setting of communication using MPI protocol
Connection type = type of used connection

7. The Test button on Test tab enables testing of connection to the device.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 4/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

8. Press OK to finish configuration of connection to the device.


9. Define the name and the location of the .CSV file on File configuration tab in EasyLog configuration.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 5/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

10. Define variables (with addresses according to S7 symbolism) in Variable configuration tab. In our case we added the
following variables into the table: DB1.DBW0 and DB1.DBW2.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 6/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

11. You can receive information about the device when press Read PLC info button on the PLC-Information tab.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 7/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

12. Press OK button to set variables into the basic dialog.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 8/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

13. Press Start button to start data archiving.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 9/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

14. History tab allows you to monitor the list of variable values.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 10/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

15. The list of variable values is saved in .CSV file which you can view in MS Excel.

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 11/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

Related products

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 12/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

Ethernet adapter ACCON NetLink PRO Compact for Simatic S7-200/-300/-400

USB adaptér ACCON NetLink USB Compact pro Simatic S7-200/-300/-400

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 13/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

Wifi adaptér ACCON NetLink WLAN pro Simatic S7-200/-300/-400

FOXON s.r.o.
Česká 615/25
463 12 Liberec 25, Czech Republic
+420 484 845 555
foxon@foxon.cz

https://www.foxon.cz/en/blogs/70-simatic-s7-300-400-data-archivation-into-ms-excel.html 14/15
18/2/2018 How to monitor and archive data from Siemens SIMATIC S7 into MS Excel using ACCON S7 EasyLog, opravy a prodej průmyslové automatizace

Trainings
Školení diagnostiky
SIEMENS repairs / PROFIBUS
Informations spare parts Školení základů
programování SIMATIC
New products SIMATIC S5
S7
TOP-selling products SIMATIC S7
Školení základů SIMATIC
Industry 4.0 SINUMERIK
S7-1200/HMI a TIA portal
About us SIMODRIVE 611
Školení komunikace
Our team Mitsubishi Electric OPC, sběr dat MES/ERP
Bazaar HMI panels Rezervace termínů