MEGAPOWER GENERATOR SETS

(80 KW TO 140 KW)

Gen-Set Specifications
GENSET MODEL: 80 GF 100 GF 120 GF 140 GF
Standby output(KW/KVA): 88KW/ 110 KVA 110 KW/ 137.5 KVA 132 KW/ 165 KVA 154 KW/ 192.5 KVA
Prime output(KW/KVA): 80 KW/ 100 KVA 100 KW/ 125 KVA 120 KW/ 150 KVA 140 KW/ 174 KVA
Voltage: 220 V (Other Voltage Accept such as 440V, 480V)
Phase: 3 Phase / (1-Phase as optional)
Rated power factor: 0.8 or (1.0)
Frequency: 60 Hz
Maximum output current(A)
262 A 328 A 393 A 459 A
@ 3 Ø, 220V:
Genset type: SUPERSILENT
Dimension(L*W*H) (mm): 2750*1050*1400 2750*1050*1400 2900*1050*1400 2900*1050*1400
Weight(kg): 1600 kgs 1700 kgs 1850 kgs 1900 kgs

Engine Specifications
ENGINE BRAND: MEGAPOWER
Rated / Max output (KW): 100 KW/ 110 KW 132 KW/ 145 KW 132 KW/ 145 KW 158 KW/ 173 KW
Rated speed: 1800 RPM
No. of cylinders: 6
Engine Type: Water-cooled, in-line, 4-cycle, direct injection
TURBO/ TURBO/ TURBO/
Air intake method TURBO
AFTERCOOLER AFTERCOOLER AFTERCOOLER
Bore(mm)×Stroke (mm): 105 mm x 125 mm 105 mm x 130 mm 105 mm x 130 mm 105 mm x 135 mm
Compression ratio: 16.4 : 1
Fuel consumption @ 100% load: 20 L/ hr 25.8 L/ hr 31 L/ hr 36.20 L/ hr
Displacement (Liters): 6.49 L 6.75 L 6.75 L 7L
Distilled Water/ Coolant capacity
28 L 28 L 28 L 28 L
(Liters):
Exhaust highest temperature ≤ 600
Lube-oil pan capacity (Liters): 13 L 13 L 13 L 18 L
Voltage for start (V): 24 V
Governor Method: Mechanical

Page 1
MEGAPOWER GENERATOR SETS
(80 KW TO 140 KW)

ALTERNATOR BRAND: MEGA


Excitation: Brushless
Insulation class: H
Protection class: IP22
Connection type: Re-connectable
Voltage Regulation: ≤1.5%
Waveform Distortion: No load<1.5% and non-distorting balanced linear load<5%
THF/TIF: <2%/50%

Control Module Specifications


The GU3311 is an Auto Mains Failure Control Module
● Back-lit LCD display
● 3 Phase generator and 3 Phase Mains monitoring
● Monitoring speed, frequency, voltage, current, oil
pressure, coolant temperature and fuel level
● Display warning, shutdown and engine status
information
● Hours counter provides accurate information
for monitoring and maintenance

Remarks
Prime Rating: These ratings are applicable for supplying continuous electrical power(at variable load) in lieu
of commercially purchased power. There is no limitation to the annual hours of operation and this model can
supply 10% overload power power for 1 hour in 12 hours.
Standby Rating: These ratings are applicable for supplying continuous electrical power (at variable load) in the
event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak
continuous tested (as defined in ISO 8528 - 3).

Standard Reference Conditions


Note: Standard reference conditions of 25 °C (77°F) Air Inlet Temp, at 100 m (328 ft) A.S.L. With 30% relative
humidity. The fuel consumption data are at full load with diesel fuel with specific gravity of 0.85 and in
compliance with to BS2869: 1998, Class A2.

Noted: As continous product developing, we reserve right to change the above specifications without notice.