Capacitance Level Control —

the end of an Era? Technology> Eclipse Guided RF Admittance/


Conditions Wave Radar Capacitance
>400F Yes Yes
Is it time to replace your troublesome >700 psi Yes Yes
e r <2 * Yes Yes
RF Capacitance/Admittance Changing r * e Yes No
Changing SG Yes Yes
Liquid Level Transmitters? Vapors Yes Yes
Foam Most No
by Boyce Carsella, Product Manager Turbulence Yes Yes
Magnetrol International certainly experienced this Buildup Most er)
No (high
first hand. To date we have Obstructions Yes Yes
Grounding to
RF Capacitance/Admittance is one of addressed the issue with No Yes
fluid required
training and support so users
Yes (high er)
the most flexible level measurement tech- Insulated coating
No
nologies ever developed. RF devices can can understand the correct required on probe
application and implementa- Leak Sources
be used in almost any type of media, and (pollution)
1 1

the probes are actually mechanical tion of this technology. Accuracy:


Training however does not <0.25% 1-2%
devices that serve an electronic function +/- % of Span

in the system. The probes can be made address usability issues, such Installation $ Low Low
High (must vary
of almost any material and, therefore, as the need to calibrate the Calibration $ Low
& verify level)
they are very flexible devices. They can devices in the vessel by mov- Hardware $ Low Low
handle very high temperatures and pres- ing and verifying the level * er = electrical dielectric of the process fluid.

sures and corrosive media. manually. In many cases this


is difficult, if not, impossible. The labor be confused with expensive, less efficient
Why then do some people refer to involved in completing the task can cost through air radar, this technology uses a
capacitance level, as “the level technology more than the instrument itself. probe very similar to RF capacitance.
some people love to hate”?
But rather than measuring a capaci-
What if there was a way to make tance change that can drift with some
It seems that with this flexibility comes all these problems disappear? process conditions, Eclipse Guided Wave
extreme application sensitivity as well. It's
Recent advances in microwave technol- Radar measures the transit time of thou-
not difficult to find people who have had
ogy have resulted in a level transmitter sands of microwave pulses transmitted
a capacitance application that did not
that has the look and functionality of RF down the probe and reflected by the
work properly. As a leading manufactur-
capacitance, but works on a very different process level.
er of capacitance devices, Magnetrol has
principal — Guided Wave Radar. Not to

Eclipse Guided Wave Radar RF Admittance/Capacitance

24 Vdc, 4-20 mA
Loop Powered
24 Vdc, 4-20 mA
Loop Powered

Buildup of Significant
media has error due to
little effect buildup of
No media
level change media (high
needed for Media level dielectric)
calibration; must be
can be varied for
configured on Not affected proper Foam can cause
workbench by most foam calibration error (high dielectric)

No ground reference Stable ground reference


to tank wall is critical (tank wall)
is necessary

Variation in media Dielectric stability of


dielectric has no media is critical;
significant effect significant error if
on performance dielectric varies

Liquid level surface is detected measuring transit time Liquid level measured by change in capacitance
of pulses of microwave energy. between probe and tank wall.

Figure 1
A more complete explanation is Q: Is it suitable for use in hazardous dielectric media (e.g. hydrocarbon) devel-
included below, but first let's ask a few areas? op a weaker reflection. The surface of
questions comparing the two approaches: low dielectric media allows some of the
A: Yes, it is CSA approved for both energy to continue down the probe until
Questions & Answers intrinsically safe and explosion-proof it dissipates or is reflected by a higher
environments. dielectric media.
Q: Capacitance calibration can be
expensive, difficult, and time consuming, The essential differences between This opens the possibility of interface
as you must move and verify the level in Eclipse GWR and RF capacitance are measurement — but that is a topic for
the vessel. How do I calibrate Eclipse summarized in the table on page 1. another day.
GWR? Figure 1 compares these two technologies
graphically. Is it proven?
A: Eclipse GWR requires no level
movement to calibrate. You simply con- Eclipse Guided Wave radar has been in
figure it right on the bench, in a few min- Magnetrol’s development and testing for about 3
utes. Eclipse years. It has been extensively tested, and
Guided Wave evaluated by major companies around the
In many applications, startup is sim- Radar Level world, and was finally released to the
ply connecting the loop and walking Transmitter market this summer. It is finding rapid
away. A simple menu-driven display lets acceptance in the market place, due to its
you change settings at anytime. problem solving nature, and cost effec-
tiveness.
Q: A low and changing electrical dielec-
tric of the fluid causes a capacitance Conclusion —
transmitter to drift; how is Eclipse GWR
Is Capacitance now dead?
affected?
Capacitance level controls have been
A: It is not. Capacitance measures total around since the 1950’s and will probably
dielectric effect over the length of the be around for some time to come; partic-
probe, and any dielectric change adverse- ularly as switches.
ly affects performance.
How does this new Guided Wave Transmitters, however, will experience
Radar technology work? a steady decline in use as the market
GWR on the other hand just meas-
ures the distance to level; a change in The recently introduced Guided Wave becomes aware of the significant advan-
impedance created by the dielectric of the Radar works in much the same way as tages of Guided Wave Radar.
process medium on the probe. It does conventional through-air radar only more
not matter what the change is, only the efficiently. The basis for GWR is TDR, The choice is clear; install an Eclipse
distance to it. or Time Domain Reflectometry. Guided Wave Radar transmitter and
achieve superior performance over con-
As a result it is not affected by media TDR has been used for many years to ventional level measurement technologies
changes, including specific gravity, and find cable breaks in underground and in- like RF capacitance and admittance
electrical dielectric. wall cables. More than 200K pulses of transmitters in a variety of difficult and
energy are developed by a TDR generator everyday applications.
Q: A proper ground reference is some- and sent down the wave-guide (probe).
times difficult to accomplish, but critical Guided Wave Radar is calibration-free,
for reliable RF capacitance operation. Is When the pulses meet a discontinuity, is not affected by process complications
this a concern for GWR? a change in impedance due to a dielectric such as: low and varying dielectric, vary-
change, a reflection is developed. An ing specific gravity, vapors/foam/ turbu-
A: No, the microwave pulses are com- engineered impedance change is devel- lence; and offers excellent performance at
pletely contained within the probe. oped in the top of the probe to generate a a competitive price.
Further, neither plastic nor lined vessels fiducial pulse, or baseline reflection.
Reprinted with permission from
are a problem. IPP&T magazine.
When the primary level reflection is Copyright © 1999 IPP&T.
Q: Is Guided Wave Radar available as a detected, it is compared to the fiducial
compact, two wire, loop powered device and the level of the media is then calcu- Magnetrol International, Inc.
5300 Belmont Road
like RF capacitance? lated.
Downers Grove, IL 60515
Phone: 630-969-4000
A: Yes, smart HART capability is avail- High dielectric liquids (e.g. water) Fax: 630-969-9489
able as well. develop a strong reflection while low E-mail: info@magnetrol.com
www.magnetrol.com.
BULLETIN: 57-202.0