Expanded Volume (Vₑ) (in litres) = Total System Volume (in litres) X Coeffecient at Maximum Flow Temperature
Acceptance Factor (a) = Maximum System Working Pressure (Absolute) - Cold Fill Pressure (Absolute)
NOTE: Cold fill pressure is calculated from the static height, plus 0.3 bar to expel air.
NOTE: Cold fill pressure (including 0.3 bar to expel air) must not be less than 0.7 bar i.e. 1.7 bar (absolute).
Acceptance Factor (a) = (Maximum Working Pressure + 1.0 bar) - (Static Height + 0.3 bar + 1 bar)