Академический Документы
Профессиональный Документы
Культура Документы
Abstract. Some work activities in electrical electric shock and/or the effects of short circuits and
installations are sensitive to unexpected sources, arcing. Dead working is obviously the preferred basic
especially when working on conductors to be broken procedure. Making certain that a circuit is 'dead' can
or joined or on overhead lines. Generally there is involve more than simply opening a switch. In dead
uncertainty about existence, gravity level, risk or working, de-energizing is only one part of creating an
seriousness of exposure to the unexpected sources. electrically safe work condition.
The possibility of unexpected electrical energy, the What, exactly, is the meaning of 'de-energized'?
need for additional protective measures and its The term 'de-energized' can be found in several IEC
resolution frequently are decisions made under and IEEE Standards and documents where it is
pressure in the field, entrusted to the person defined as "free from any electrical connection to a
performing the work. source of potential difference and from electric
The authors submit that methods to detect charge; not having a potential different from that of
unexpected energy sources, together with guidelines the earth." [3]. Determining whether or not there may
for addressing such situations, can and should be be an additional energy sources and if so, the nature
developed for incorporation into safety procedures. of the source and the best approach to removing it,
The authors also indicate approaches to system can be a difficult and uncertain process involving
design that can reduce exposure to unexpected power extensive analysis of the system.
sources. A practical approach is to find out the presence
and magnitude of currents on the working circuits,
Index terms - Safety procedures, Employee such as grounding conductors and overhead lines, by
Workplaces, Maintenance & Operation, Risk detection tests or measurements in the field that
assessment, Overhead Lines Safety verify the effectiveness of the protective measures. In
case the measures should prove to be insufficient, the
tests will identify:
INTRODUCTION - the need to disconnect all additional interfering
sources of energy to comply fully with the basic first
Circuits may be energized from many sources in requirement of dead work
addition to the obvious one of a metallic connection - or alternatively, the need to adopt live working
through a switch or breaker. Examples of less procedures such as working with insulating glove or
obvious energy sources include capacitors, transfer with bare hands, as suggested by EN 50110-1 and the
switches, UPS, batteries, mechanical sources equivalent by NFPA 70E.
(rotating motors), electrostatic coupling, magnetic For the sake of brevity, this paper focuses on
coupling, and others. Creating an electrically safe situations where the source of unexpected energy is
condition at the work location is mandatory for the an adjacent power line. The reader will have little
duration of the work itself, including safety from difficulty in applying the same line of reasoning to
unexpected power sources. other sources of unexpected energy.
European Standard EN 50110-1, Operation on
electrical installations [1], divides the work into three ACTIVITIES SENSITIVE To UNEXPECTED SOURCES
different procedures: 1- dead working (the European
definition of de-energized work); 2- live working; Some activities are sensitive to unexpected
and 3- working in the vicinity of live parts, very sources and in these cases, depending on the
similar to NFPA 70E [2]. These procedures are electrical energy available, these sources can cause
founded on the use of protective measures against injury or death. EN 50110-1 highlights, as sensitive
to unexpected sources, work where the actIvIty potential between conductors and ground to a safe
requires conductors to be broken or joined. These level; or by equipotential bonding at the work
operations request a direct contact of workers with location in order to avoid the possibility of workers
bare conductors and not by insulated devices. inserting themselves as conductors in an induction
Under these circumstances there is a risk that loop.
potential differences will appear on the installation, For the problem related to induction, NFPA 70E
in which case suitable measures such as bonding [2], sub clause 2-1.1.3 (f) recommends: where the
and/or grounding must be taken at the work location possibility of induced voltages (Figure I) or where
before the conductors are broken or joined as line stored electrical energy exists, ground the phase
conductors or grounding conductors in HV/MV/LV conductors or circuit parts before touching them.
systems. A hazard is presumed to exist if the induced
These conductors are grounded or short circuited by voltage is 50 volts (rms) or more that is sufficient to
proper or mobile equipment that avoid the risk of cause the threshold current of perception (1 rnA)
electric shock for direct contact when potential through the body resistance of a person (0.5 kQ) not
differences will surge. protected from injury due to involuntary reactions
Unexpected power sources can appear on dead or de from electric shock [5].
energized lines. Depending on the electrical energy
available, these voltages can cause injury or death. Ground-leakage currents and ground fault
These unexpected sources are generally: [1], [2], [4]: currents.
- induced voltages and capacitive recharging A risk of potential differences could appear on
- ground-leakage currents and ground fault grounding conductors that are to be broken or joined.
currents A special case can be considered the grounding
- accidental contact with other circuits and conductors in a data center, because of the grounded
penetrating an "unknown" space. leakage currents that are as higher than multiple
Unexpected power sources can appear particularly servers are connected to the same power source.
when working on component disconnections and on For this paper we assume that for bare overhead
overhead lines ( Figure I). lines and bare conductors, grounding and short
circuiting will be carried out on all sides of the work
location on all conductors entering this location. Note
that this grounding creates closed loops that make
possible circulating currents in the working circuits,
derived by ground faults or by induction. Ground
fault currents generally have a short duration since a
protective device clears the circuit. The steady
induced currents could be dangerous because they
may introduce overvoltages in conductors being
disconnected.
requirements for worker safety and service exposure these systems often have due to their length
continuity. and location.
The new generation of very compact HVIMV/LV Many industrial facilities and utilities require
components doesn't have to cause an higher temporary personal protective grounding as measures
induction among adjacent equipment and systems in essential for all aerial power line works and not
stations (Figure 3) and transmission lines. simply as additional protection in relation to the risk
The compact execution of components has to assessment of each specific work (see 10.4.3
contribute to reduce the electrical interferences and to Temporary personal protective grounding [4]).
increase the ergonomic safe distances than to reduce Additional requirements can be applied
the total space size of the sub stations. effectively not only to the personal protective
equipment and to passive protection (like additional
This paragraph touches on significant design temporary grounding and equipotential bonding at
considerations that apply prior to installation, but are the work location) but also to active protection
not usually suitable for existing installations. against energy from unexpected sources by de
energizing all sources of induction, disconnecting by
ADDITIONAL REQUIREMENTS OF MAXIMAL CAUTION isolated devices the paths for current circulation, or
by adopting live working procedures. Frequently in
A key element in the success of any safety practice, however, situations are such that de
program is employee awareness that no violation of energizing all sources of induction is not possible
the program is acceptable, implying that the program because of the impact on other electrical services.
addresses all situations that can be foreseen within Standard IEEE C2-NESC [6], part 4 Sec.422
reason. Generally, the program highlights minimum Overhead line operating procedures, sub clause C 5
safety measures that are realistic for several Installing and removing wires or cables, recommends
situations. To be effective, a program for safe "Employees working on or in the vicinity of
working practices should be written in specific, equipment or lines exposed to voltages higher than
rather than general, terms. Ultimately the degree of those guarded against by the safety appliances
caution or safety that is required will be a decision provided shall take steps to be assured that the
made in the field, entrusted to the wisdom and equipment or lines on which the employees are
scrupulousness of the person performing the work working are free from dangerous leakage or
who will base decisions on safety instructions and on induction or have been effectively grounded". Before
perceptions of conditions in the field. starting work, the canonical requirements (''the five
Without clearly defined safety procedures for safety rules" of EN 50110-1 or the equivalent "six
such situations, resorting to additional requirements safety rules" of the NFPA70E) ensure that the
based on intuition or "guesses" can obviate the electrical installation at the work location is
validity of the program. It is not reasonable for the meticulously de-energized and secure for the
person performing the work to be saddled with duration of the work ([1],[2],[5],[6]). In other words,
decisions involving additional protection that are after the work zone has been identified it is not
based on judgments that have subjective and variable sufficient to disconnect completely and to secure
threshold values. Additional requirements determined against re-connection; the rules require verification
in the course of the work may be irrelevant or that the installation is actually de-energized.
inappropriate, unwittingly imposing exaggerated Absence of objective tests to verify the levels of
requirements of maximal caution or worse still, unexpected sources of energy and the adequacy of
jeopardizing the entire safety procedure. Operators related additional protection measures expose the
are not incompetent; nevertheless it is well known worker to risk of electrocution [8]. Specific
that very many workers involved in accidents were instructions on how to determine and cope with
skilled, experienced, and mature. unexpected sources should be part of the safety
Without question, carefully defined safety instructions given to the worker.
requirements for unexpected sources of energy must The shortcoming today is that standard procedures
become a mandatory part of safety procedures. don't recommend conventional tests to assess the
Additional requirements for maximum caution exposure and to improve decision-making regarding
usually are established for aerial power line work on additional measures for the safety program.
power systems over 1kV because of the increased
REFERENCES