Академический Документы
Профессиональный Документы
Культура Документы
Index 35
Fire Alarm Concepts is the second PACE Book in a series of prerequisite materials
designed to describe Fire Alarm Basics. The text and accompanying graphics within
this PACE Book are focused on the types of fire alarm systems, the specific services for
fire alarm control panels and finally, system architecture.
Objectives
l describe how the NFPA and listing requirements affect the equipment required in a
fire alarm system
l recognize the seven types of fire alarm systems
l recognize the six types of service for fire alarm control panels
l recognize the three types of system architecture.
The PACE Book format was designed so that you could review the technical content of
the graphics by reading through the accompanying text.
After you’ve completed the reading, complete the short quiz at the end of this text, and
review the answers provided in the Answer Key. If you answered any questions
incorrectly, go back to the individual sections and review the relevant information.
Types of Systems
l Household Fire Alarm Systems - NFPA 72 Chapter 2
l Protected Premises (Local) Systems - NFPA 72 Chapter 3
l Emergency Voice/Alarm Communication Systems - NFPA 72 Chapter 3
l Auxiliary (Municipal) Systems - NFPA 72 Chapter 4
l Remote Supervising Station Systems - NFPA 72 Chapter 4
l Central Station Systems - NFPA 72 Chapter 4
l Proprietary Supervising Station Systems - NFPA 72 Chapter 4
Figure 2-1
We’ll start the discussion of Fire Alarm Concepts by reviewing the seven (7) types of
systems and their NFPA listing categories as outlined in Figure 2-1 above. Refer to
each of the NFPA 72 chapter listings for specific relevant information regarding each
system type.
NFPA 72 defines a household fire alarm system as a system of devices that is intended
to notify the occupants of the presence of fire. Typically there will be detectors with an
integral horn, which may be interconnected so that one alarm will sound all the horns in
a facility or house. Household systems do not require a control panel.
Most commercial fire alarm control panels are not listed as a household fire alarm
system. These systems can, however, be used in a household and actually exceed the
requirements for a household system.
Smoke Detector
Manual Horn
Station
FACP
Figure 2-2
A local protective signaling system is defined as one which protects the premises with
detection and notification, but it does not automatically notify a remote supervising
station. Not every system is required to notify all occupants, as long as emergency
response personnel are notified.
HOSPITAL
n Live Voice Communications
n Prerecorded Tones
S
n Prerecorded Messages
Figure 2-3
Due to high-rise buildings and other structures where immediate evacuation of the entire
building was impractical, the use of this type of system allowed selective partial
evacuation or relocation of building occupants from fire-affected areas.
A one-way system permits emergency personnel to give live voice instructions on either
a selective or all-call basis via microphone and a system of loudspeakers. Prerecorded
tones and messages can also be selected and distributed manually or automatically.
Municipal
Fire Local
Alarm FACP
H.Q.
Figure 2-4
An auxiliary fire alarm system is one which is connected directly to a public fire alarm
reporting system to notify the fire department. This system’s main component is the
“master box” which is normally located on the outside of the protected facility. These
boxes are connected to the fire department receiving station with a pair of wires on what
is normally called a “municipal loop.” Many master boxes may be on the same loop.
When activated manually by a fire alarm system, master boxes will transmit a 3- or 4-
digit code which alerts the fire department of their exact location.
Auxiliary municipal systems are typically connected to one of three different types of
master boxes:
To
Fire Code 126
Dept. Code 123
H.Q.
Public System
Figure 2-5
Shunt master boxes are slowly fading from use because they no longer meet the
requirements of NFPA. The wires between the building’s control panel (FACP) and the
master box are unsupervised and utilize power from the municipal system, which places
the power for the loop in the protected building. In a fire situation, this power could be
accidentally connected to ground or shorted, preventing other boxes on the same loop
from reporting. In addition, any open circuit in the loop between the master box and the
FACP will cause the box to report a fire alarm. The NFPA now requires that an open
circuit report a Trouble. With a shunt system, there is no distinguishing between Alarm
or Trouble because an open circuit condition reports an alarm.
To
Fire Code 126
Dept. Code 123
H.Q.
Public System
Figure 2-6
In local energy master boxes, the wires between the FACP and the master box are
supervised. So if there is a wiring fault in that area, it is reported at the control panel.
Power for those wires also comes from the FACP at the facility rather than from the
municipal system.
FACP Auxiliary
System
Fire
Dept.
H.Q.
Box 4 Code 126
Public System
Figure 2-7
Radio master boxes are identical to local energy boxes except that they use a radio
frequency to transmit the signal to the fire department. There is a requirement that these
systems have two repeaters, so that if one fails, the other one will still report that signal
to the fire department. Additionally, radio boxes must transmit periodically for
supervision purposes and must report when their standby batteries are being depleted.
Individual
1 2 3 Remote Leased
Central Telephone
4 5 6 Station Lines
Annunciator
Figure 2-8
A remote supervising station is a system or group of systems that has the authority to
monitor facilities of different ownership within a municipality. Their primary business
is to receive signals from individual facilities and then call the fire department with the
location of the fire. In some cases, the remote facility is the fire department.
The key to these systems is that they use individual leased telephone lines to report
alarms or troubles. Because this is costly, these systems are decreasing in popularity. A
term used in conjunction with remote station systems is reverse polarity. To report an
alarm, these systems reverse the polarity on the leased lines which, in turn, light up the
appropriate location at the remote station’s annunciator. Remote Supervising Stations
are not required to provide runner service and reports as required by Proprietary
Supervising Stations and Central Station systems.
A central station system’s primary business is also to receive signals from individual
facilities and notify the fire department with the location of the fire. The central station
must meet certain construction, equipment, and service criteria. NFPA 72 lists all the
requirements for this kind of station. There are a lot of security central stations
Phone
Line #1
Supervised Wiring
Figure 2-9
The unavailability of dedicated wire between facilities drove the need for a different
technology to notify central stations. The Digital Alarm Communicator Transmitter
(DACT) allows central station notification over standard telephone lines. Two (2) phone
lines are required as a redundancy measure for fire alarms. A fire alarm DACT has to
be capable of transmitting to either line—if one fails, it will call up on the other. These
lines are supervised by a test signal transmitted to the Digital Alarm Communicator
Receiver (DACR) once every 24 (twenty-four) hours.
Central stations are required to provide a number of services. The stations must record
signals and retransmit signals to the appropriate public fire communications center.
They must also provide protected premise communications and runner service —
meaning that a “runner” will investigate the problem if an alarm, supervisory, or trouble
condition exists for longer than a specified amount of time (reference: NFPA 72).
Scheduled maintenance and testing are required for central stations. Finally, central
stations must also provide written reports to the owner and the Authority Having
Jurisdiction (AHJ).
CRT/Keyboard Printer
Connection to
Fire Department
FACP
Central Supervising Station
Figure 2-10
A proprietary supervising station system looks much like a central station. The key
difference is that a central station monitors facilities of different ownership, while a
proprietary system monitors the facilities of one ownership. A typical proprietary
system would be a very large company or university with many buildings. A company
or university might even have its own fire department or may call the local municipal
department to respond to fire emergencies.
Proprietary supervising stations are also required to have a visual annunciator and a
hardcopy printer. And, like central station systems, they are required to provide a runner
service, scheduled maintenance and testing, as well as written reports and notices to the
owner and the AHJ.
Services actually refer to the type of devices connected to the fire alarm control panel.
To reinforce what we discussed in Fire Alarm Components and Operations, these
include:
l Manual Alarm Service - utilizes manual stations that are physically operated by
pulling a lever for alarm activation.
l Automatic Alarm Service - involves devices which report an alarm upon
detecting smoke, heat, flame, or a particular gas.
l Waterflow Alarm Service - utilizes either paddle or pressure switches to monitor
waterflow caused by an activated sprinkler head.
l Sprinkler Supervisory Service - involves monitoring five specific categories:
water supply valves, line and tank pressure, tank water level, exposed tank water
temperature, and pump abnormal conditions. The panel itself must be listed for
each of the individual categories it is capable of monitoring.
l Guards Tour Supervisory Service - essentially, is a facilities management
protection service against building losses and destruction. Normally, it is
operational only when buildings are unoccupied.
l Releasing Service (Underwriters’ Laboratories [UL] & Factory Mutual [FM]) -
is for fire alarm panels used to control the release of water and/or agents for fire
prevention (suppression). They are specifically listed by UL and/or FM for this
service. FM has two different categories: 1) pre-action and/or deluge sprinkler
system, and 2) fixed extinguishing systems.
Supervisory Sprinkler
H S
Gate Valve
AV Automatic Fire Detectors
Notification Appliance NFPA 72
NFPA 72
Waterflow Paddle
Switch
Building Wiring
NFPA 70 PIV Supervisory Post
Fire Alarm (National Electrical Code) Indicator Valve
Control Panel
OPEN
NFPA 72
120 VAC
Figure 2-11
Supervisory Sprinkler
Gate Valve
H S
AV Automatic Fire Detectors
Water Solenoid
Notification Appliance NFPA 72
NFPA 72
Valve
Waterflow Pressure
Switch
Building Wiring
NFPA 70 PIV Supervisory Post
Fire Alarm (National Electrical Code) Indicator Valve
Control Panel
OPEN
NFPA 72
120 VAC
Figure 2-12
Pre-action systems have closed sprinkler heads. When the FACP goes into alarm, the
FACP activates and opens the water solenoid valve. This action causes the sprinkler
pipes to be filled with water. As soon as a sprinkler head activates due to high
temperature, water is released.
Supervisory Sprinkler
Gate Valve
H S
AV Automatic Fire Detectors
Water Solenoid
Notification Appliance NFPA 72
NFPA 72
Valve
Waterflow Pressure
Switch
Building Wiring
NFPA 70 PIV Supervisory Post
Fire Alarm (National Electrical Code) Indicator Valve
Control Panel
OPEN
NFPA 72
120 VAC
Figure 2-13
Deluge systems have open sprinkler heads and require careful design to be effective and
efficient. When the water solenoid valve is activated and opened by the FACP, the water
is released from every sprinkler head. Usually, the FACP is programmed to activate the
water upon activation of a single heat detector or only after multiple smoke detectors go
into alarm. This requirement of more than one smoke detector in alarm before
activating the water release valve is called “dual detector” or “cross zoning.” It is
generally not desirable to release water on a single smoke detector alarm.
Supervisory Pressure
Switch
H S
AV Automatic Fire Detectors
Notification Appliance NFPA 72 Agent Solenoid
NFPA 72 Valve
Supervisory Post
Indicator Valve
120 VAC
Figure 2-14
Fixed extinguishing systems are basically like any other system that releases agents for
fire suppression. These systems are usually of the deluge type, but release fire
suppression agents instead of water. Some examples of these agents are: CO2, FM200,
Halon and AFFF foam. Some agents pose a health hazard to occupants and, if there is a
release, a large volume of chemical will be expelled. Consequently, it is a good design
practice not to release chemicals until the occupants are notified and had an opportunity
to evacuate the hazard area.
The two FM categories have different requirements. Under FM, pre-action or deluge
systems must use Style D (Class A) wiring on their IDC circuits and have 90 hours of
standby power. It can be batteries, or generators, but it must be acceptable to the
Authority Having Jurisdiction (AHJ). Sometimes a standalone charger and batteries
from an outside vendor may have to be used to meet the 90-hour standby requirements.
In these instances, you must confirm whether or not the control panel is capable of
operating with stand-alone battery chargers.
NFPA 13 contains a complete list of the requirements for these types of systems. STRM
Section A1.1 also provides additional information concerning Releasing Services.
System Architecture
Hardwired
1/2” EMT
Multiplexed or Networked with
Voice & Phone
Figure 2-15
Stand-Alone Systems
Wiring
for 3rd Signal
Signal
F Floor F
E
E I
I
R
R O
O E
E
L
L
E
O
Detectors L
FIRE
E Waterflow
O Switch
L Manual Wiring
Station for 2nd
Floor
Signal Signal
F
F E
E I
I
O
R
O R E L
E
L
E
O
Detectors L
FIRE
E Waterflow
O Wiring Switch
L Manual
Station for 1st
Floor
City Connect
FACP
Conventional
(Hardwired) Devices 120 VAC
Figure 2-16
This system is a conventional hardwired system. Note that the large number of wires
from the peripherals on each floor go directly back to the control panel. This requires
large conduits and lots of wire.
Multiplex Systems
Signal F
I
E
F
E I R O
E L
O R
E
L Signal
System
Transponder E
Detectors 102 O
E FIRE L
O Data Lines
L Waterflow
Switch
Manual
Station
Signal F
I
E
F
E I R O
E L
O R
E
L Signal
System
Transponder E
Detectors 101 O
E FIRE L
O Data Lines
L Waterflow
Switch
Manual
Station
City Connect
FACP
Conventional
(Hardwired) Devices
120 VAC
Figure 2-17
This system uses multiplex technology. Note that a single pair leaves the control panel
and goes to a device called a transponder located on each floor. The communications
between panels is in a digital format, while conventional peripherals are connected on a
standard IDC circuit in the transponder. This was the initial use of multiplex technology
in buildings as it significantly reduced the cost of the vertical riser wire.
Multiplex Systems
To Additional
Transponders
2nd Floor Addressable Data Lines
System
Transponder
102
Addressable FIRE
Module Addressable Addressable
105 Module Module
102 101
104 106
Manual Addressable
Detectors E
E F Station O
I E F
O R L
O
I
R
E
L L E
Signal Waterflow
Signal
Switch
Signal F
E
E I
F
1st Floor O I
R
E
O
R L
L E Signal
System
Transponder E
101 O
E FIRE L
O Data Lines
L Waterflow
Manual Switch
Station
City Connect
FACP
Conventional and
Addressable Devices 120 VAC
Figure 2-18
Digital communications were then expanded to all the peripheral devices. As in the
figure above, addressable devices were installed over a pair of wires to the transponder
electronics on each floor, further reducing installation costs.
Stand-Alone Systems
Wiring
for 3rd
Signal
Floor Signal
F
Conventional and
F E
E
O
L
I
R
E
I
R
E
O
L
Addressable Devices
E
O
Detectors
L
FIRE
E
Wiring Waterflow
O
L
Manual for 2nd Switch
Station Floor
Signal
F F
E I I E
R R O
O E E
L L
E
O
Detectors
L
FIRE
E
Waterflow
O Wiring
L
Manual Switch
Station for 1st
Floor
Basement Data Lines
City Connect
FACP Addressable
FIRE Addressable Addressable
Module Module Module
104 105 106
Detectors
Manual
Station E
O F
120 VAC E I E F
I
L O R O R
E E
L L
Waterflow
Signal Signal
Switch
Figure 2-19
When using distributed system technology, the two different types of communication
you may use include: master/subordinate or peer-to-peer.
Master/Subordinate
Transponder
Transponder
Master
Figure 2-20
Token
. . . until the
end and then
they reverse.
Figure 2-21
Token
X
. . . for any two
or more panels
still connected FAULT
together.
Figure 2-22
What happens when there are two breaks in the wire? As shown above, the result is two
independent networks. How then does the network communicate with only one token?
Each node is aware of how frequently it should receive the token. If a node ends up on
a disconnected network without a token, it recognizes the condition and creates a new
token. This node then starts to pass the new token to the nodes on its network allowing
them to communicate with each other. As mentioned earlier, all Trouble conditions are
transmitted to the network, so each node will display the indication of the troubles on its
operator panel.
It must be noted that this is considered a degraded mode of operation since the two
separate networks are unable to communicate with each other. However, considering
there are two fault conditions, the system survivability is maximized compared with that
of a master/subordinate system.
Style 7 maintained
even with failed
Token
node
Figure 2-23
Each node has a Network Interface Card (NIC), and is designed to allow
communications to pass through the unit in a failure provided the total distance of the
wiring between the failed node and each of its adjacent nodes is less than the maximum
distance allowed. If the total distance of the wiring between the failed node and its
adjacent nodes is greater than the maximum distance, then the token will be reversed as
if the failed node was an open line.
Directions: Below are several multiple choice items for each statement or question.
Circle the appropriate letter that best matches each item.
1. Which of the following fire alarm systems is not connected to an external monitoring
facility?
2. Which of the following fire alarm systems is able to monitor multiple sites?
a. wires between the control panel and local energy master box are supervised by
the control panel
b. wires between the control panel and shunt master box are supervised by the
control panel
c. wires between the control panel and radio master box are unsupervised
d. all of the above
e. a and c
6. Which of the following categories does sprinkler supervisory service not include:
a. FM has two categories for fire alarm panel releasing service: pre-action and
deluge sprinkler systems
b. FM has one category for fire alarm panel releasing service: extinguishing
systems
c. releasing service is designed to provide an electrically supervised releasing
system and both the wiring and releasing device must be supervised
d. a and c
e. b and c
a. coded
b. multiplex
c. Digital Alarm Communicator System
d. a and b
e. b and c
a. a master-subordinate relationship
b. a peer-to-peer relationship
c. style B or D signaling line circuits
d. a and b
e. all of the above
10. What is the major operational difference between what a peer-to-peer network
provides that a master-subordinate does not?
1. b 2. e 3. d 4. a 5. d
6. a 7. c 8. c 9. d 10. c