SERVICE
INSTRUCTION
Models Indoor unit Outdoor unit
AS* A09LEC AO* R09LECN
AS* A12LEC AO* R12LECN
R410A
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY....................................................................................................... 02-01
2-1-1 INDOOR UNIT AND WIRED RMOTE CONTROLLER DISPLAY (OPTION)...... 02-01
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)..................................... 02-02
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................ 02-03
2-3 TROUBLE SHOOTING WITH NO ERROR CODE...................................................... 02-24
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-29
3. APPENDING DATA
3-1 FUNCTION SETTING................................................................................................. 03-01
3-1-1 INDOOR UNIT.................................................................................................... 03-01
3-1-2 Procedures to change the Function Setting for wireless RC.............................. 03-03
3-2 Thermistor Resistance Values.................................................................................... 03-05
1 . DESCRIPTION OF EACH
CONTROL OPERATION
F zone
When the compressor operates for 30 minutes continuously at over the maximum speed ,
the maximum speed is changed from Maximum speed to Maximum speed .
01-01
Downloaded from www.Manualslib.com manuals search engine
2. HEATING OPERATION
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature,
the compressor speed is controlled within the range shown in Table2.
However, the maximum speed is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
01-02
Downloaded from www.Manualslib.com manuals search engine
3. DRY OPERATION
Ts+1.5°C
X zone
Ts+0.5°C
Ts -0.5°C
J zone
Ts -1.5°C
Y zone
01-03
Downloaded from www.Manualslib.com manuals search engine
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.
1 When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outdoor temperature are sensed and the operation mode is
selected in accordance with the table below.
3 When HEATING was selected at 1 , the same operation as HEATING OPERATION of item 2
above is performed.
4 When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at 1 above, operation is switched
to MONITORING and the operation mode is selected again.
01-04
Downloaded from www.Manualslib.com manuals search engine
5. INDOOR FAN CONTROL
1. FAN SPEED
( Table 5 : Indoor fan speed )
ASYA09/12LEC
Operation mode Air flow mode Speed (rpm)
Heating Hi 1440
Me+ 1370
Me 1200
Lo 980
Quiet 700
Cool air prevention 600
S-Lo 480
Cooling Hi 1440
Me 1200
Lo 920
Quiet 680
Dry X zone: 680
J zone: 650
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 5.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table 5.
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts =
> 2.5 degC
HIGH mode
TR-Ts =
> 2 degC
2.5 degC > TR-Ts =
> 1.5 degC
MED mode
2 degC > TR-Ts =
> 1 degC
1.5 degC > TR-Ts
1 degC > TR-Ts LOW mode
When the room TR : Room temperature
temperature rises Ts : Setting temperature
When the room
temperature drops
4. DRY OPERATION
Refer to the Table 5.
During the dry mode operation, the fan speed setting can not be changed.
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 6.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow
of [HEAT] operation modes Quiet, Lo, Me, Hi, as shown in Table 5.
01-05
Downloaded from www.Manualslib.com manuals search engine
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 7, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.7 : Cool air prevention control)
<Before 7 minutes upon running the compressor>
Indoor heat exchanger Indoor heat exchanger
temperature rises temperature drops
Lower of "Hi" and "setting fan speed"
47°C
40°C
Lower of "Me+" and "setting fan speed"
40°C
35°C
Lower of "Lo" and "setting fan speed"
37°C
32°C
Cool air prevention
30°C
28°C
S-Lo
40°C
Lower of "Me+" and "setting fan speed"
40°C
35°C
Lower of "Lo" and "setting fan speed"
OFF
Indoor fan
(as shown in Table 6)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
(Table 6 : Indoor fan speed )
X zone J zone
ASYA09LEC 680rpm 650rpm
ASYA12LEC 680rpm 650rpm
01-06
Downloaded from www.Manualslib.com manuals search engine
6. OUTDOOR FAN CONTROL
ASYA09/ 12LEC
2. Fan Speed
( Table8 : Outdoor fan speed ) (rpm)
Zone Cooling Heating Dry
D 850/ 750/ 670/ 500 760/ 470
ASYA09LEC F 400/ 280 850/ 750/ 680/ 550/ 450 400/ 280
G 250/ 200 250/ 200
D 850/ 750/ 670/ 500 760/ 470
ASYA12LEC F 400/ 280 900/ 750/ 680/ 550/ 450 400/ 280
G 250/ 200 250/ 200
Refer to Fig.9
* The outdoor fan speed mentioned above depends on the compressor frequency.
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
* After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
as table9 without relating to the compressor frequency.
( Table9 : Outdoor fan speed after the defrost )
ASYA09LEC 850rpm
ASYA12LEC 900rpm
01-07
Downloaded from www.Manualslib.com manuals search engine
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
(Operation Range)
Cooling / Dry mode
Heating mode
Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow
Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during
defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( ) for long period of time, since water vapor many condense near the outlet louvers and
drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow
Direction Louvers are left in the heating range for more than 30minutes, they will automatically
return to position .
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically
becomes , and it cannot be adjusted.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
Cooling mode / Dry mode / Fan mode( )
Heating mode / Fan mode( )
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted
and the louver stops at the memorized position.
01-08
Downloaded from www.Manualslib.com manuals search engine
8. COMPRESSOR CONTROL
119rps
108rps
97rps
87rps
74rps
56rps
Time
80sec 60sec 60sec 180sec 60sec 60sec
01-09
Downloaded from www.Manualslib.com manuals search engine
9. TIMER OPEARTION CONTROL
Operation mode
Stop mode
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting.
The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
01-10
Downloaded from www.Manualslib.com manuals search engine
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
+2°C
+1°C Stop of operation
Ts
Set 60min
Ts
- 1°C
- 2°C
- 3°C
- 4°C
Stop of operation
01-11
Downloaded from www.Manualslib.com manuals search engine
9-2 WIRED REMOTE CONTROLLER (OPTION)
The table12 shows the available timer setting based on the product model.
( Table12 : Timer Setting )
ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
ASYA09/ 12LEC
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week.
All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
ON OFF
Set back tmp.
Normal tmp.
01-12
Downloaded from www.Manualslib.com manuals search engine
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor,
and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 60 to 480 pulses.
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
[ Release ]
Perform the test operation for 60 minutes.
Pressing the Start/Stop button will stop the test operation.
OFF
7°C
5°C
ON
01-14
Downloaded from www.Manualslib.com manuals search engine
19. 10°C HEAT OPERATION
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller.
The 10°C HEAT operation is almost the same operation as below settings.
( Table16 )
Mode Heating
Setting temperature 10°C
Fan mode AUTO
OFF
5°C
2°C
ON
01-15
Downloaded from www.Manualslib.com manuals search engine
22. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects
the temperature lower than the values shown in Table18.
( Table 18 : Condition of starting Defrost Operation )
1 ST time defrosting Compressor integrating operation time
after starting operation Less than 20 min. 20 to 60 min. More than 60 min.
Release Condition
01-16
Downloaded from www.Manualslib.com manuals search engine
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Compressor OFF
Outdoor fan motor OFF
50 sec later four - way valve OFF
55 sec later compressor ON
Base heater maintains the same status
as before the compressor stops.
Defrost end
01-17
Downloaded from www.Manualslib.com manuals search engine
23. OFF DEFROST OPEARTION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
Defrost start
Defrost Indicater:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost end
01-18
Downloaded from www.Manualslib.com manuals search engine
24. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge discharge thermistor will detect discharge gas temperature.
1-1. When the discharge temperature becomes higher than Temperature , the compressor speed
is decreased 20rps, and it continues to decrease the speed for 20rps every 120seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the protection control of
the compressor speed is released.
However, if this protection repeats and the instruction speed of the compressor falls below 18rps,
the compressor will be stopped.
1-2. When the discharge temperature becomes higher than Temperature , the compressor is stopped.
If the above protection stop repeats 2 times, system will be stopped permanently, and the indoor unit
LED starts error indication.
(Table 20 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature Temperature Temperature
[ Cooling ]
ASYA09LEC ASYA12LEC
01-19
Downloaded from www.Manualslib.com manuals search engine
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor speed is decreased on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than 4°C .
Then, the anti-freezing control is released when it becomes higher than Release temperature A.
(Table 22 : Anti-freezing protection operation / Release temperature)
Outdoor temperature zone Release temperature A
A, B , C, D 7°C
E, F 13°C
50°C
It returns to the normal operation
Refer to below
55°C
52°C
It returns to the normal operation
[ ASYA09LEC ]
Compressor operation
57rps or more 55rps
35 ~ 55rps Rotational speed down every 120 sec
28 ~ 33rps 23rps
18 ~ 23rps OFF
[ ASYA12LEC ]
Compressor operation
48rps or more 45rps
39 ~ 45rps Rotational speed down every 120 sec
27 ~ 36rps 25rps
18 ~ 25rps OFF
01-20
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
R410A
2 . TROUBLE SHOOTING
CT error 3 times 18 13
5 times
Compressor location ditection error 5 times 1A 14
02-01
Downloaded from www.Manualslib.com manuals search engine
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
When "EE" in Temperature Display is displayed, inspection of the air conditioning system is necessary.
Please consult authoilzed service personnel.
Error code
Error history number
SU MO TU WE TH FR SA
3. Press the SET TEMPERATURE button to select the error history number.
Lower Raise
0 1 2ı 3 4 5 6 7
F E d c b A 9 8
02-02
Downloaded from www.Manualslib.com manuals search engine
2-2 TROUBLE SHOOTING WITH ERROR CODE
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit Fan motor failure
YES
Check Point 2 : Check connection Check Point 1-2 : Check external cause such as noise
Check any loose or removed connection line of Check if the ground connection is proper.
between indoor unit and outdoor unit. Check if there is any equipment that causes harmonic wave
>> If there is an abnormal condition, correct it by near the power cable (Neon light bulb or any electronic
referring to Installation Manual or Data & equipment which causes harmonic wave).
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
OK
OK
+
BLACK L -
WHITE N
RED 3
02-03
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 2 Indicate or Display:
INDOOR UNIT Error Method:
Serial Error Refer to error code table.
(Serial Forward Transfer Error)
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure 4. Outdoor unit Main PCB
YES
Check Point 2 : Check connection Check Point 1-2 : Check external cause such as noise
Check any loose or removed connection line of Check if the ground connection is proper.
between indoor unit and outdoor unit. Check if there is any equipment that causes harmonic wave
>> If there is an abnormal condition, correct it by near the power cable (Neon light bulb or any electronic
referring to Installation Manual or Data & equipment which causes harmonic wave).
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
OK
OK
BLACK L
WHITE N +
-
RED 3
02-04
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 3 Indicate or Display:
INDOOR UNIT Error Method:
Refer to error code table.
Wired Remote Controller Error
Forecast of Cause:
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
OK
02-05
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 4 Indicate or Display:
INDOOR UNIT Error Method:
Refer to error code table.
Room Temperature Thermistor Error
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
OK
Resistance value (k ) 58.2 44.0 33.6 25.9 20.2 15.8 12.5 10.0
Temperature (°C ) 30 35 40 45
OK
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK THERMISTOR
1 1
2 2
BLACK ( PIPE TEMP. )
CN4 BLACK
3 3
BLACK THERMISTOR
4 4
( ROOM TEMP. )
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-06
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 5 Indicate or Display:
INDOOR UNIT Error Method:
Indoor Heat Exchanger Temperature Refer to error code table.
Thermistor (Middle) Error
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
OK
Temperature (°C ) -5 0 5 10 15 20 25 30
Resistance value (k ) 233.2 176.0 134.2 103.3 80.3 62.9 49.7 39.6
Temperature (°C ) 35 40 45 50 55 60 65
Resistance value (k ) 31.7 25.6 20.8 17.1 14.1 11.6 9.7
OK
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
1 1
BLACK THERMISTOR
2 2
BLACK ( PIPE TEMP. )
CN4 3 3
BLACK
4 4
BLACK THERMISTOR
( ROOM TEMP. )
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-07
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 6 Indicate or Display:
OUTDOOR UNIT Error Method:
Outdoor Discharge Pipe Temperature Refer to error code table.
Thermistor Error
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
OK
Resistance value (k ) 1013.1 531.6 292.9 221.1 168.6 129.8 100.9 79.1 62.5
Resistance value (k ) 40.0 26.3 17.8 12.3 8.7 6.3 4.6 3.4 2.0
OK
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK THERMISTOR
1 1
2 2
BLACK ( HEAT EXCHANGER )
CN71 3 3
BLACK
BLACK THERMISTOR
4 4
( DISCHARGE PIPE )
BLACK
1 1
THERMISTOR
CN70 2 2
3 3
BLACK ( OUTDOOR TEMP. )
02-08
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 7 Indicate or Display:
OUTDOOR UNIT Error Method:
Outdoor Heat Exchanger Temperature Refer to error code table.
Thermistor Error
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
OK
Resistance value (k ) 95.6 50.3 27.8 21.0 16.1 12.4 9.6 7.6 6.0 4.8
Temperature (°C ) 30 35 40 45 50 60 70 80
Resistance value (k ) 3.8 3.1 2.5 2.1 1.7 1.2 0.8 0.6
OK
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK THERMISTOR
1 1
2 2
BLACK ( HEAT EXCHANGER )
CN71 BLACK
3 3
BLACK THERMISTOR
4 4
( DISCHARGE PIPE )
BLACK
1 1
THERMISTOR
CN70 2 2
3 3
BLACK ( OUTDOOR TEMP. )
02-09
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 8 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
Outdoor Temperature Thermistor Error
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
OK
Resistance value (k ) 224.3 115.2 62.3 46.6 35.2 26.9 20.7 16.1
Temperature (°C ) 20 30 40 50 60 70 80
OK
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK THERMISTOR
1 1
2 2
BLACK ( HEAT EXCHANGER )
CN71 3 3
BLACK
BLACK THERMISTOR
4 4
( DISCHARGE PIPE )
BLACK
1 1
THERMISTOR
CN70 2 2
3 3
BLACK ( OUTDOOR TEMP. )
02-10
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 9 Indicate or Display:
INDOOR UNIT Error Method:
Refer to error code table.
Manual Auto Switch Error
Forecast of Cause :
1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
OK
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB
and execute the check operation again.
02-11
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 10 Indicate or Display:
OUTDOOR UNIT Error Method:
INDOOR UNIT
Refer to error code table.
Main relay welded error
Forecast of Cause :
1. Power code assy*1 2. Main PCB failure 3. Controller PCB failure
OK
OK
If Check Point 2 do not improve the symptom, replace Power code assy.
*1: Power code assy consists of Terminal, Relay, Thermal fuse, and Power code.
02-12
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 11 Indicate or Display:
INDOOR UNIT Error Method:
Power Supply Frequency Refer to error code table.
Detection Error
Indoor unit Controller PCB When power frequency is not detected by 4 seconds after power-on.
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure
YES
Check Point 2 : Check connection Check Point 1-2 : Check external cause such as noise
Check any loose or removed connection line of Check if the ground connection is proper.
between indoor unit and outdoor unit. Check if there is any equipment that causes harmonic wave
>> If there is an abnormal condition, correct it by near the power cable (Neon light bulb or any electronic
referring to Installation Manual or Data & equipment which causes harmonic wave).
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring.)
OK
OK
02-13
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 12 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
Over Current Protection
Forecast of Cause :
1. Connection failure 2. Outdoor fan operation failure 3. Outdoor heat exchanger clogged
4. Compressor failure 5. Main PCB failure
OK
OK
OK
OK
02-14
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 13 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
CT Error
Forecast of Cause :
1. Connection failure 2. External cause 3. Main PCB failure
YES
Check Point 2 :
Check Point 1-2 : Check external cause such as noise
Check connections condition in control unit
Check if the terminal connection is loose. Check if the ground connection is proper.
Check if connector is removed. Check if there is any equipment that causes harmonic wave
Check if connector is erroneous connection. near the power cable (Neon light bulb or any electronic
Check if cable is open. equipment which causes harmonic wave).
>> Upon correcting the removed connector or mis-wiring,
reset the power.
OK
02-15
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 14 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
Compressor Location Detection Error
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
OK
OK
If Check Point 1,2 do not improve the symptom, replace Main PCB.
OK
02-16
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 15 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
Outdoor Unit Fan Error
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
OK
OK
OK
RED
1
2 FAN MOTOR
3
BLACK
CN800 4
WHITE
FM
5
YELLOW
6
BROWN
7
02-17
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 16 Indicate or Display:
INDOOR UNIT Error Method:
Indoor Fan Motor Lock Error Refer to error code table.
Indoor Fan Motor Rev. Error
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
OK
OK
OK
02-18
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 17 Indicate or Display:
OUTDOOR UNIT Error Method:
Discharge Temperature Error Refer to error code table.
Forecast of Cause : 1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Check Point 1 : Check if 3-way valve(gas side) is open. Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(gas side) was closed, open the If the 3-way valve(liquid side) was closed, open the
3-way valve(gas side) and check operation. 3-way valve(liquid side) and check operation.
OK OK
Check Point 2 : Check the EEV, strainer Check Point 2 : Check the EEV, strainer
OK
OK
OK
Leak check
OK
02-19
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 18 Indicate or Display:
OUTDOOR UNIT Error Method:
Excessive High Pressure Refer to error code table.
Protection On Cooling
Forecast of Cause :
1. Connection failure 2. Outdoor fan operation failure
3. Outdoor heat exchanger clogged 4. Thermistor failure 5. EEV failure 6. Main PCB failure
OK
OK
OK
OK
OK
02-20
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 19 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
4-way valve error
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure
OK
OK
OK
02-21
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 20 Indicate or Display:
OUTDOOR UNIT Error Method:
Refer to error code table.
PFC circuit error
Forecast of Cause :
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
02-22
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 21 Indicate or Display:
INDOOR UNIT Error Method:
Refer to error code table.
Model Distinction Error (Indoor)
Forecast of Cause:
1. External cause 2. Defective for connection of electric components 3. Controller PCB failure
YES
Check Point 2 : Check Point 1-2 : Check external cause such as noise
Check indoor unit electric components
Check if the ground connection is proper.
Check all connectors. Check if there is any equipment that causes harmonic wave
(loose connector or incorrect wiring) near the power cable (Neon light bulb or any electronic
Check any shortage or corrosion on PCB. equipment which causes harmonic wave).
OK
02-23
Downloaded from www.Manualslib.com manuals search engine
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
OK
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
02-24
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 23 Forecast of Cause:
OK
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
OK
OK
02-25
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 24 Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON) 3. Electrical Component defective
Indoor unit - Check incorrect wiring between Indoor unit - Remote control.
Or, check if there is an open cable connection.
Are these Indoor unit, Outdoor unit, and Remote control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
02-26
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 25 Forecast of Cause:
OK
OK
02-27
Downloaded from www.Manualslib.com manuals search engine
Trouble shooting 26 Forecast of Cause :
1. Abnormal installation(Indoor unit / outdoor unit)
Abnormal Noise 2. Fan failure(Indoor unit / outdoor unit)
3. Compressor failure (Outdoor unit)
Is main unit installed in stable condition? Is main unit installed in stable condition?
Is the installation of air suction grille and Is Fan Guard installed normally?
front panel normal?
OK
OK
Is Fan broken or deformed?
Is Fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation? OK
Is Compressor locked?
>> Check Compressor
Diagnosis method when water leak occurs Diagnosis method when water is spitting out.
Is main unit installed in stable condition? Is the filter clogged?
Is main unit broken or deformed at the time of
transportation or maintenance? OK MPa MPa
OK
Check gas pressure and correct it
if there was a gas leak.
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OK
Is Fan rotating?
>> Check Fan Motor
02-28
Downloaded from www.Manualslib.com manuals search engine
2-4 SERVICE PARTS INFORMATION
Compressor
Diagnosis method of Compressor (If outdoor unit LED displays error, refer to Trouble shooting )
Is there open or loose connection Is there open or loose connection Check if vibration noise by
cable? cable? loose bolt or contact noise
of piping is happening.
Replace Compressor
Check if Strainer is clogged.
(PARTS INFORMATION 3)
Replace Compressor
Replace Compressor
02-29
Downloaded from www.Manualslib.com manuals search engine
SERVICE PARTS INFORMATION 2
Inverter Compressor
W7 W8 W9
Inverter PCB
BLACK
RED WHITE
Compressor
R(U) (RED)
R(U)
C(W) S(V)
02-30
Downloaded from www.Manualslib.com manuals search engine
SERVICE PARTS INFORMATION 3
Outdoor unit Electronic Expansion Valve
( EEV )
EXPANSION
1 RED VALVE COIL
2 BLUE
3
CN40 4 ORANGE EV
YELLOW
5
WHITE
6
Check Point 2 : Check Coil of EEV Check Point 3 : Check Voltage from Main PCB.
Remove connector, check each winding Remove Connector and check Voltage (DC12V) DC
resistance of Coil. If it does not appear, replace Main PCB.
Read wire Resistance value
White - Red Check Point 4 : Check Noise at start up
Yellow - Red 46 4 Turn on Power and check operation noise.
Orange - Red at 20°C
If an abnormal noise does not show,
replace Main PCB.
Blue - Red
02-31
Downloaded from www.Manualslib.com manuals search engine
SERVICE PARTS INFORMATION 4
Indoor unit fan motor
02-32
Downloaded from www.Manualslib.com manuals search engine
SERVICE PARTS INFORMATION 6
Heater Unit
CN10
1 2 3 4 5
1 2 3 4 5 THERMOSTAT
(55°C)
BLACK FUSE 250V5A
BLACK 3 3 BLACK
2 2 BLACK
WHITE WHITE 1 1 WHITE
FUSE 250V5A HEATER
02-33
Downloaded from www.Manualslib.com manuals search engine
R410A
3 . APPENDING DATA
03-01
Downloaded from www.Manualslib.com manuals search engine
1-4. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by
Wired remote controller temperature sensor.
( Factory setting)
Setting Description Function Number Setting Value
No 00
42
Yes 01
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01" : Room temperature is controlled by remote controller unit sensor.
03-02
Downloaded from www.Manualslib.com manuals search engine
3-1-2 Procedures to change the Function Setting for wireless RC
This procedure changes to the function settings used to control the indoor unit according to
the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation
conditions using the remote controller.
Settings will not be changed if invalid numbers or setting values are selected.
(2) Press the SET TEMP. ( ) ( ) buttons to select the Function Number.
Function Number
(Press the MODE button to switch between the left and right digits.) Setting Value
(3) Press the FAN button to proceed to Setting Value. 10°C HEAT
(Press the FAN button again to return to the Function Number selection.)
(4) Press the SET TEMP. ( ) ( ) buttons to select the Setting Value.
(Press the MODE button to switch between the left and right digits.)
(5) Press the TIMER MODE button. It makes a signal to indoor unit.
(Indoor unit recognize the setting.)
(7) Press the RESET button to cancel the function setting mode.
(8) After completing the FUNCTION SETTING, be sure to turn of the 10°C HEAT
CAUTION
After turning off the power, wait 10 seconds or more
before turning on it again.
The FUNCTION SETTING doesn't become effective
if it doesn't do so.
03-03
Downloaded from www.Manualslib.com manuals search engine
Custom code setting for remote controller
(2) Press the SET TEMP. ( ) ( ) buttons to change the signal code between .
Match the code on the display to the air conditioner signal code. (initially set to )
CAUTION
03-04
Downloaded from www.Manualslib.com manuals search engine
3-2. Thermistor Resistance Values