Project Name: KINGS MOUNTAIN ENERGY
Location: , ,
Drawing Name: STEAM TURBINE GENERATOR BEARINGS HYDRO Calculation Date: 7/14/2017
Design
Remote Area Number: Manually Flowing
Remote Area Location: NA
Occupancy Classification: NA
Density: NA
Area of Application: NA
Coverage per Sprinkler: NA
Type of sprinklers calculated: NA
No. of sprinklers calculated: 12
Name of Contractor:
Address: ,
Phone Number: Name of designer: Josh Layton
Notes:
Water Supply
Summary Sheet
Node: 1
Supply Analysis
Static Residual Flow Available Total Demand Required Pressure
Node Name @ @
(psi) (psi) (gpm) (psi) (gpm) (psi)
Node Analysis
Node Number Elevation (Foot) Node Type Pressure at Discharge at Notes
Node Node
(psi) (gpm)
32 -6-0½ 121.9
44 -6-0½ 121.8
45 0-11½ 118.8
91 2-9 117.9
96 5-4½ 113.7
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Foot) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Foot) (Q) (psi) to (Pf) and shown as a
(Foot) Friction(Pf)
(Foot) negative value.
0.051717
189 31-1½ 25.0 1.380
7-8½ 0.4
1.741708
135 31-9½ 403.9 2.067
8-2½ 14.3
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Foot) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Foot) (Q) (psi) to (Pf) and shown as a
(Foot) Friction(Pf)
(Foot) negative value.
1 903.9
Total(Pt) Route 1
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Foot) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Foot) (Q) (psi) to (Pf) and shown as a
(Foot) Friction(Pf)
(Foot) negative value.
0.341368
161 28-7½ 69.3 1.380
8-0 2.7
0.096423
165 28-7½ 35.0 1.380
8-8½ 0.8
0.153296
142 31-9½ 108.6 2.067
17-5½ 2.7
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Foot) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Foot) (Q) (psi) to (Pf) and shown as a
(Foot) Friction(Pf)
(Foot) negative value.
0.020641
138 31-1½ 36.7 2.067
7-8½ 0.2
0.076664
164 28-7½ 74.7 2.067
8-0 0.6
0.021730
167 28-7½ 37.8 2.067
8-8½ 0.2
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Foot) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Foot) (Q) (psi) to (Pf) and shown as a
(Foot) Friction(Pf)
(Foot) negative value.
Fittings Legend