YES
REPLACE / CM
STEP-2 NO
OCV CHECK
Voltage is 12.4V or above
NO
RECHARGE After recharge,
Refer to charging voltage is 12.4V
section or above
STEP-3
LOAD TEST
Volt at 15 seconds is higher
than 9.8 V at 21° C and
above. NO
NO
REPLACE / CM
YES
STEP-4
RETURN TO
SERVICE
TEST CHART FOR CONVENTIONAL BATTERY (LM)
YES
REPLACE / CM
NO
ELECTROLYTE
STEP-2
LEVEL CHECK
Electrolyte level above top of If electrolyte level below top of plates
Plates in all cells in one or more cells
ADD WATER
Add water to just above separators.
Charge for 15 MIN @15-25
amperes. Proceed to step 3
STEP-3
OCV CHECK
Voltage is 12.4V or above
STEP-4
LOAD TEST
Volt at 15 seconds is higher YES
than 9.8 V at 21° C and
above.
NO
REPLACE / CM
YES RETURN TO
SERVICE