Вы находитесь на странице: 1из 9

For 3 phase motor

Power in Power Derating Derated Resistance( Reactance(


kW Voltage Factor Effiicency Current Factor Current ohms/km ohms/km

55 415 0.86 0.935 95.157693 0.612 155.486426 0.13 0.071

90 415 0.87 0.942 152.77899 0.612 249.63887 0.265 0.072

132 415 0.86 0.954 223.83004 0.612 365.735367 0.162 0.072

110 415 0.86 0.951 187.11344 0.612 305.740922 0.13 0.071

147.2 415 0.9 0.95 239.51514 0.612 391.364608 0.162 0.072

160 415 0.85 0.956 273.92675 0.612 447.592724 0.162 0.072


%
Voltage V drop
% Voltage
Length in No. of Drop during Drop % starting
Impedance metres V drop during running runs running starting starting current

0.14803088 500 12.199073421 1 2.93953576 87.83333 21.1646575 7.2

0.26604972 150 10.5603504088 1 2.54466275 76.03452 18.3215718 7.2

0.17606117 260 8.8733159448 2 2.13814842 63.88787 15.3946686 7.2

0.14803088 225 10.794448248 1 2.60107187 77.72003 18.7277174 7.2

0.17718407 208 7.6445445711 2 1.84205893 55.04072 13.2628243 7.2

0.17562835 296 12.3325082099 2 2.97168873 88.79406 21.3961588 7.2


Load Description & Doc No
S. No.1 of Doc No TPL-1044-37100-
EE-DC-7183
S. No.10 of Doc No TPL-1044-
37100-EE-DC-7183
S. No. 74 of TPL-1044-37100-EE-DC-
7184
S. No. 5 of TPL-1044-37100-EE-DC-
7184
S. No. 3 of TPL-1044-37100-EE-DC-
7188
S. No. 17 of TPL-1044-37100-EE-DC-
7188
Power in Power Derating Derated Resistance( Reactance(
kW Factor Efficiency Voltage Current Factor Current ohms/km ohms/km Impedance

0.2 1 1 240 0.833333 0.612 1.361656 8.87 0.0985 8.87

0.2 1 1 240 0.833333 0.612 1.361656 8.87 0.0985 8.87

0.9 1 1 240 3.75 0.612 6.127451 2.44 0.0808 2.44


%
Length in V drop during Voltage Load Description & Doc
metres running Drop No

S. No.2 of Doc No TPL-


500 7.391666667 3.07986111 1044-37100-EE-DC-7183
S. No. 40 of TPL-1044-
285 4.21325 1.75552083 37100-EE-DC-7184
S. No. 7 of TPL-1044-
208 3.8064 1.586 37100-EE-DC-7188
Power in Power Derating Derated Resistance(o Reactance(o
KVA Factor Effiicency Voltage Current Factor Current hms/km hms/km Impedance

100 0.9 0.95 415 146.4427 0.612 239.2854 0.325 0.072 0.32388407

518.3 1 1 415 721.0618 0.612 1178.206 0.0648 0.082 0.0648

132 0.86 0.954 415 192.4938 0.612 314.5324 0.162 0.072 0.17606117

295.78 1 1 415 411.4908 0.612 672.3705 0.162 0.072 0.162

180 1 1 415 250.417 0.612 409.1781 0.13 0.071 0.13


84 1 1 415 116.8613 0.63 185.4941 0.41 0.072 0.41
V drop
Length in during % Voltage No.of Load Description & Doc
metres running Drop Runs No
S. No.62 of Doc No TPL-
50 4.107598 0.98978256 1 1044-37100-EE-DC-7183
S. No. 2 of TPL-1044-
125 3.372072 0.81254754 3 37100-EE-DC-7184
S. No. 41 of TPL-1044-
285 8.364807 2.01561607 2 37100-EE-DC-7184
S. No. 1 of TPL-1044-
56 3.232911 0.77901471 2 37100-EE-DC-7188
S. No. 31 of TPL-1044-
80 4.510843 1.08695021 1 37100-EE-DC-7188
152 12.61417 3.03955872 1
Voltage 220

Resistance at 20°C in ohms/km 0.253

Temperature coeffcient of
resistance for copper at 20°C 0.004041

Resistance at 90°C in ohms/km Err:501

Length of cable in meters 15

no. of runs 1

Power in kW/kVA 28.18

Current 128.090909

efficiency of motor 0.95

current considering
efficiency 134.8325

If resistance considered is
20deg resistance
Voltage drop 1.24721904 Err:501 1.3128621502

% V drop 0.56691775 0.4419136364 0.5967555228

Starting current for DC motors is


200% Irated
Resistance at 20°C 0.32

Temperature coeffcient of resistance


for Aluminium at 20°C 0.004308

Resistance at 90°C 0.416499

Length of cable in meters 350

no. of runs 1

Power in kW/kVA 9.3

Current 42.27273

efficiency of motor 0.85

current
considering
efficiency 49.73262

If resistance considered is
20deg resistance
Voltage drop 12.32459 9.4690909091 14.499517604

% V drop 5.602086 4.3041322314 6.5906898201

Вам также может понравиться