Main Control Valve Internal Pump

Parameter Inlet Outlet Flow Satuan


Flows 619,5569 619,5569 619,5569 kg/s
Pressure 192,08 211,288 192,08 bar
Temperature 362,3764 365,455 362,3764 C
Enthalpy 1786,772 1791,1705 1786,7724 kJ/kg
Vapor Fraction on a weight
basis 0 0 0 fraction

REHEATER
Steam
Gas inlet Gas Outlet Steam Inlet Outlet
Flows kg/sec 141,4926 141,4926 88,2307 88,2307
Pressure bar 1,0124 1,0124 35 34,3
Temperatur
e C 683,2614 510,5351 300,6927 440,0001
3316,040
Enthalphy kJ/kg 759,4493 549,9917 2980,2269 2
Vapor
Fraction fraction 0 0 1 1

RIVER PUMP

Control valve
Main Inlet outlet Internal pump flow
Flows kg/sec 3516,5299 3516,5299 3516,5299
Pressure bar 1,7237 3 1,7237
Temperature C 30 30,0082 30
Enthalphy kJ/kg 125,8985 126,0493 125,8985
Vapor Fraction fraction 0 0 0
STACK

Inlet
Flows kg/sec 141,4926
Pressure bar 1,0124
Temperature C 155,4015
Enthalphy kJ/kg 148,0557
Molecular Weight 29,4739
Lower Heating Value kJ/kg 0
Oxygen,O2 fraction 0,0174
Nitrogen,N2 fraction 0,7172
Water,H2O fraction 0,1086
Carbon Monoxide,CO fraction 0
Carbon Dioxide,CO2 fraction 0,1481
Methane,CH4 fraction 0
Hydrogen,H2 fraction 0
Argon,AR fraction 0,0085
Carbonyl Sulfide,COS fraction 0
Hydrogen Sulfide,H2S fraction 0
Sulfur Dioxide,SO2 fraction 0,0002
Main
Primary Main Water Steam
Return Outlet Main Boiler Feed Water Inlet Outlet
Flows kg/sec 619,5569 619,5569 88,2307 88,2307
Pressure bar 211,288 192,08 192,08 192,08
Temperature C 370,3391 362,3764 245,85 362,3764
Enthalphy kJ/kg 1984,4484 1786,7724 1067,0875 2455,1708
Vapor
Fraction fraction 0,2 0 0 1

Superheater
Steam
Gas Inlet Gas Outlet Steam Inlet Outlet
Flows kg/sec 141,4926 141,4926 88,2307 88,2307
Pressure bar 1,0124 1,0124 192,08 188,2384
Temperature C 973,34 683,2614 362,3764 440,0001
Enthalphy kJ/kg 1128,0625 759,4493 2455,1708 3046,3033
Vapor
Fraction 0 0 1 1
Molecular
Weight 29,4739 29,4739
Lower
Heating
Value kJ/kg 0 0
Oxygen,O2 fraction 0,0174 0,0174
Nitrogen,N2 fraction 0,7172 0,7172
Water,H2O fraction 0,1086 0,1086
Carbon
Monoxide,CO fraction 0 0
Carbon
Dioxide,CO2 fraction 0,1481 0,1481
Methane,CH4 fraction 0 0
Hydrogen,H2 fraction 0 0
Argon,AR fraction 0,0085 0,0085
Carbonyl
Sulfide,COS fraction 0 0
Hydrogen
Sulfide,H2S fraction 0 0
Sulfur
Dioxide,SO2 fraction 0,0002 0,0002