Вы находитесь на странице: 1из 6

Operations and Maintenance

Copyright 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This
posting is by permission of ASHRAE Journal. This article may not be copied nor distributed in either paper
or digital form without ASHRAE’s permission. Contact ASHRAE at www.ashrae.org.

Because Temperature Matters

Maintaining
Cooling Towers
By Glenn A. Babcock, Member ASHRAE

T
he cooling tower is often the forgotten component of the wa- the coil section, again evaporating a
small percentage of the water in the
ter cooling system when it comes to maintenance. It’s a good process.
The temperature at which the cooled
example of the phrase “out of sight, out of mind.” A newly installed fluid is returned to the system measures
tower performance. This temperature
cooling tower reliably delivers the design fluid temperature and flow can vary depending upon the actual
cooling load, water flow, airflow, and the
rate. However, since its heat transfer operation creates a hurricane-
entering air conditions. Because tem-
like environment and is a natural air-washer, the cooling tower needs perature matters so much, owner confi-
dence in cooling tower performance will
routine inspection and maintenance to continue performing as de- be enhanced by selecting a tower model
whose performance is certified by the
signed. This article discusses routine maintenance and suggests ways Cooling Technology Institute (CTI).

to improve cooling tower performance. Preventive Maintenance


Performing routine preventive main-
Let’s take a moment to recall how a removes heat and cools the remaining tenance is paramount for consistently
cooling tower works. In an open-circuit water, which is collected in the tower’s achieving the desired temperature and
cooling tower, warm water from the heat cold water basin and returned to the flow rate, and plays an important role
source is evenly distributed via a gravity heat source (typically a water-cooled in maximizing cooling tower operat-
or pressurized nozzle system directly condenser or other heat exchanger). ing life. Manufacturers conscious of
over a heat transfer surface called fill Similarly, in a closed-circuit cooling the importance of maintenance offer
or wet deck, while air is simultane- tower or evaporative condenser, the
ously forced or drawn through the tower, heat is rejected indirectly from a fluid About the Author
causing a small percentage of the water or vapor flowing through the coil sec- Glenn A. Babcock is manager, marketing commu-
nications and training development for Baltimore
to evaporate. The evaporation process tion by spraying recirculated water over Aircoil Company, Baltimore.

46 ASHRAE Journal ashrae.org March 2005


Cooling towers away from the building can be subjected to the “out of sight, out of mind” principle.

many features that simplify these procedures, saving time condenser system water loop. Strainers in the cold water basin
and money. outlet prevent debris from reaching the pump.
To perform properly, all tower components must be kept Some towers feature low-pressure drop pre-strainers up-
clean and free of obstructions. The following sections describe stream of the hot water basin to prevent clogging of distribu-
standard maintenance procedures for optimized circulating tion nozzles. This simple cleaning procedure eliminates the
water system operation. These procedures can prevent loss of need to access the distribution nozzles. Both strainers should
efficiency in the heat transfer section by maintaining proper be routinely inspected and cleaned as necessary. Some tower
water flow and airflow, as well as preventing corrosion in the designs allow external access to the strainers, which enables
cooling tower. maintenance to take place without the need to
Maintenance frequency depends largely turn off the unit.
on the condition of the circulating water, the
cleanliness of the ambient air used by the tower, Water Distribution
and the environment where the tower is oper- The water distribution system should evenly
ating. More detailed information is provided distribute water over the fill package or coil
by the specific manufacturer’s operating and section via either a gravity distribution system
maintenance instructions. or a pressurized spray system, using an array
of nozzles. If water distribution is found to
Strainer Systems Cold water basin strainer. be uneven, the nozzles need to be checked.
Fundamentally important to the performance Clogged nozzles should be cleaned in ac-
of a cooling tower is a method to minimize contact between cordance with the manufacturer’s recommendations. Since
air- and water-borne debris and the system components. Strain- even water distribution is important to the performance of the
ers in the tower provide a means of keeping debris out of the tower, consideration should be given to the ease with which the

March 2005 ASHRAE Journal 47


Operations and Maintenance

distribution nozzles can be accessed, inspected, cleaned and tower, which allows easy basin water depth inspection and
replaced when selecting a cooling tower model. adjustment without the need to turn off the unit. The tower
In a gravity distribution system, the nozzles can be externally water level should be set in accordance with the manufacturer’s
accessed and visually inspected and cleaned by removing the recommendations to ensure no air enters the pump suction,
hot water basin covers on the fan deck. Most pressurized spray but not so high that water is wasted through the overflow when
distribution systems use nozzles and branches held in place by the tower is shut down.
snap-in rubber grommets, which allow easy removal to clean
and flush debris if necessary. Bleed
To prevent the accumulation of solids in the recirculating
Cold Water Basin water, the tower should be equipped with a bleed line (includ-
Since some debris eventually will enter into the cooling ing a metering connection and globe valve) connected to a
tower, the unit design should facilitate debris removal. A nearby drain.
well-designed cold water basin is sloped toward the strainer In a closed circuit cooling tower or evaporative condenser
to keep dirt (which can accelerate corrosion) with a circulating pump, a metering valve
from accumulating throughout the cold water to control the bleed rate should be provided
basin. The basin should be kept clean by oc- at the pump discharge. While a manually
casionally flushing the dirt out of the system adjusted bleed valve is the simplest system,
through the tower drain. getting the proper bleed rate can be a prob-
Another way to accomplish this is to install lem as cooling tower loads vary throughout
sump sweeper piping in conjunction with the day. A conductivity meter connected
water filtration or separator devices. Water to a solenoid valve solves this problem by
filtration saves maintenance costs by reduc- Spray distribution nozzles. maintaining the proper cycles of concentra-
ing dirt in the cooling water system, which tion at all times. Also, it is recommended
reduces the time required to clean the cold that a separate meter be installed to measure
water basins. It also reduces water treatment bleed volume, since less water is discharged
cost, as water treatment chemicals tend to to drain than supplied to the cooling tower.
work more effectively in clean water. Foreign This can reduce sewer water charges.
particles in dirty water can absorb treatment The bleed rate should be adjusted to
chemicals, thus requiring the distribution of prevent an excessive buildup of impuri-
even more chemicals to properly treat the ties in the recirculating water. This largely
tower water. depends on the local water quality and
the evaporation rate. Constant bleed and
Makeup
Inspecting drift eliminator.
replacement with fresh water will prevent
Although most of the water in the system the accumulation of impurities. To obtain
is recirculated, some water must be added to replace what specific recommendations, contact a competent water treat-
is lost by evaporation and by bleed, which is the water that ment professional.
is discharged to prevent the accumulation of solids in the
cooling water. The makeup water system provides the means Mechanical Drive System
to replace the water via a mechanical float ball and valve The mechanical fan drive system has several components
assembly or an electronic water level probe assembly (with that should be checked regularly. Many of these components
solenoid valve), which measures water depth in the cold water operate at high speed. So, to maximize safety, follow proper
basin. The make-up water supply pressure typically should be lock-out/tag-out procedures, including locking out all mo-
maintained between 15 psig and 50 psig (103 and 345 kPa) to tor disconnect switches before working on the mechanical
ensure proper valve shut-off and avoid “chatter.” If the supply system.
pressure is higher than 50 psig (345 kPa), install a pressure Cooling tower fans typically are driven by belt- or gear-drive
reducing valve. systems. Both require routine maintenance to ensure reliable,
The operating water level of the cooling tower will vary with trouble-free performance. Belt-drive systems are popular, as
system thermal load (evaporation rate), the bleed rate used, they are inexpensive yet reliable, offer single point adjustment,
and the makeup water supply pressure. Some tower designs and have no limit on turndown capabilities for variable speed
offer access to the makeup assembly external to the cooling applications. If a problem occurs, a simple change of the belt

48 ASHRAE Journal ashrae.org March 2005


is usually all that is required, and replacement components Importance of Clean Operation
are readily available. Cooling tower components must be kept clean and free of
Gear drives provide reliable operation as well, and perform obstructions, because temperature matters. Neglecting the
consistently when properly maintained. If a problem occurs, cooling tower will lead to higher than desired return water
resolution may be more involved if a gear box rebuild or re- temperatures to the system, which will result in higher energy
placement is required. Some manufacturers offer both systems use from two perspectives. First, the system (chiller) will
to meet user needs or preferences. To ensure proper operation consume more energy because it must operate at a higher
of a belt-drive system, tighten drive belts to manufacturer’s than necessary condensing pressure (head) to satisfy the load,
specifications. In gear drive systems, the oil level and quality, due to the higher fluid temperatures provided by the cooling
as well as shaft alignment should be checked regularly in ac- tower. As little as 2°F (1°C) higher temperature can result in
cordance with the manufacturer’s recommendations. 6% more energy being consumed by the chiller. Second, the
When starting up a new unit, lubrication of the fan shaft tower must operate longer at higher fan horsepower while
bearings is typically not necessary, since most units leave the trying to attain the design cold water temperature.
factory already greased. However, for seasonal startup, purge
the fan shaft bearings with new grease (per manufacturer’s Common Problems: Causes, Effects, and Solutions
recommendations). Fan shaft bearings should be lubricated Regardless of how often routine maintenance is performed,
after every 2,000 hours of operation or every three months like any other mechanical component, problems with cooling
(whichever occurs sooner). Motor bearings should be lubri- towers may materialize unexpectedly. These include elevated
cated as recommended by the manufacturer’s instructions. leaving water temperatures, drift, and corrosion. Should any of
For maximum life, it is best to install motors with a “cooling these problems occur, contact the cooling tower manufacturer’s
tower duty” rating. representative or water treatment supplier for assistance.

Advertisement formerly in this space.

March 2005 ASHRAE Journal 49


Operations and Maintenance

High leaving water temperature will cause a drop in pro- help save energy, do a better job of following the load, and
cess cooling efficiency, increasing system power consumption, help reduce wear and tear on the drive system.
creating physical discomfort to people within an air-condi- Check ambient conditions. Cooling towers are selected to
tioned area, and have a detrimental effect on other system produce the required leaving water temperature at the design
components. Major factors affecting cooling tower leaving cooling load and entering wet-bulb temperature. Whenever
water temperatures are cooling load, water flow, airflow, enter- the actual entering wet-bulb temperature is higher than design
ing air conditions, and the condition of the tower itself. conditions, the leaving water temperature also will be higher.
Check cooling load. If the actual cooling load exceeds the The result is decreased energy efficiency and possible downtime
design load for which the tower was selected or surpasses for the system.
the certified thermal performance of the tower, the leaving Drift occurs as air flows through the cooling tower and carries
water temperature will exceed the design specifications for water droplets out of the tower. Drift eliminators are installed in
the towers. the discharge stream to strip entrained water droplets from the air.
Check water flow and distribution. Visually inspect the In a properly maintained system, efficient eliminators will reduce
water distribution system to ensure the spray distribution drift loss to a negligible percentage of the design flow rate.
nozzles are clean and correctly installed and are distribut- If excess drift occurs, check drift eliminators for proper
ing a uniform spray pattern over the wet deck surface. The installation, spacing, and overall condition. Examine the wet
cooling tower circulating water flow rate can be measured deck surface for even spacing, inspect the wet deck surface or
by either the pressure differential between the circulating water distribution system to ensure no clogging or blockage,
pump discharge and suction or by measuring the pressure and check water and airflow as described previously. Repair or
drop across the condenser, which should be relatively free replace eliminators as necessary.
of scale and fouling, and comparing it to the manufacturer’s Corrosion is always a concern with cooling towers because
specifications. In counterflow towers, measure the pressure of their ability to wash the air of impurities, leaving them on
at the cooling tower inlet connection and compare it to the the wet deck surface or in the cold water basin. This can cause
design pressure provided by the cooling tower manufacturer. scale, corrosion, and eventually damage to system components
For towers with a gravity distribution system, the operating after long-term exposure to these impurities.
level in the hot water basin (typically between 2 and 5 in.) (51 Historically, galvanized steel construction has been com-
and 127 mm) can be correlated to a specific flow rate based monly used for factory-assembled cooling towers. Its structural
upon the manufacturer’s information. rigidity and corrosion-resistant properties are needed in the
Check airflow. Cooling towers should be located where an corrosive environment where recirculating water becomes
unimpeded supply of fresh air is available to the air inlets. The oxygenated. Current industry standards use G-235 galvanized
cooling tower air discharge also should be at least as high as steel, which has 2.35 ounces of zinc galvanized coating per ft2
any surrounding walls to reduce the possibility of hot, moist (717 g per m2) of steel.
discharge air being recirculated into the air inlets, creating The formation of white rust is a type of corrosion that may be
artificially elevated entering wet-bulb and leaving water promoted because of recent changes in water quality and water
temperatures. To ensure full design airflow, the cooling tower treatment programs. White rust appears as a white and waxy
drive system must be adjusted according to the manufacturer’s adherent, non-protective deposit on steel surfaces. White rust
operating and maintenance instructions. forms on a new tower if it is operated at high pH levels (above
The cooling tower and surrounding area should be examined 8.0) for an extended period of time before the zinc galvanizing
for airflow restrictions that may cause blockage of the air can form a protective passivation layer. If white rust remains
inlets. Check for clogging or improper distribution of water unchecked, the galvanized steel coating will continue to cor-
across the tower fill surface and check for proper operation of rode, eventually leading to an early failure.
capacity control dampers in centrifugal fan towers to ensure Many additional cost effective construction options are
proper airflow. The dampers, airfoil blades located in the available to provide increased cooling tower protection and
discharge of the fan housing, help achieve tight temperature equipment longevity. For example, fuse-bonded thermosetting
control and energy savings by matching cooling tower airflow polymers that are electrostatically applied on galvanized steel
to actual load requirements. can provide enhanced protection from corrosion. They also
Although you may encounter dampers in older existing serve as a deterrent to white rust.
units, today’s towers tend to take advantage of variable fre- Stainless steel construction offers the ultimate in corrosion
quency drive technology (VFDs) to control capacity. VFDs protection. Options of entire stainless steel units or units with only

50 ASHRAE Journal ashrae.org March 2005


stainless steel cold water basins are effec- Performance Improvements
tive in negating corrosion damage. How- Product improvements (retrofit kits) can
ever, stainless steel is not “maintenance improve the performance of yesterday’s
free.” Submerged surfaces must be kept cooling towers with today’s technology.
reasonably clean to prevent under-deposit Older, structurally sound cooling towers
oxygen deprivation and rapid pitting. For can be retrofitted with upgrade kits to:
areas of the cooling tower which do not pro- conserve energy; restore or improve per-
vide structural support, such as the casing formance; and facilitate maintenance.
walls, fiberglass reinforced polyester (FRP) To conserve energy, two-speed motors,
panels provide a non-corroding, cost-effec- VFDs and/or pony motors can be added
tive material of construction. to the mechanical drive system to take
If a constant bleed of the system is advantage of moderate operating condi-
ineffective to combat scale or corrosion, tions with lower horsepower. VFDs offer
chemical treatment may be necessary. A a range of speeds to more closely parallel
successful chemical or water treatment operating requirements, and pony motors
program should satisfy the specific guide- provide the added benefit of redundancy
lines set by the manufacturer, provide in the event of a motor failure. A popular
effective microbiological control, and be energy conservation approach uses a
compatible with the system’s materials pony motor system with a VFD control-
of construction as an integral part of the ling the lower horsepower motor.
total water treatment program. To improve performance on water
Potential airborne impurities and distribution systems, kits are available to
biological contamination (such as Le- replace older, smaller distribution nozzles Advertisement formerly in this space.
gionella) should be controlled through or troughs with large-orifice, clog-free
the use of biocides, and such treatment design replacements. Retrofit fill kits
should be initiated at system startup and easily replace the original fill that may
continued regularly. ASHRAE has taken be clogged with scale or airborne debris.
proactive steps to understand and deal Access platforms also can be added to
with Legionella through its publication, existing cooling towers to facilitate main-
ASHRAE Guideline 12-2000, Minimiz- tenance and improve worker safety.
ing the Risk of Legionellosis Associated
with Building Water Systems. To obtain Conclusion
specific recommendations of water treat- Paying regular attention to the cooling
ment programs, contact a competent tower, through a regular, comprehensive
water treatment supplier. maintenance program can save time,
Although basic cooling tower problems money and energy while increasing the
can either be alleviated or avoided altogeth- tower’s life expectancy. A well-main-
er by using the recommended maintenance tained tower is a viable candidate for
procedures, the process of servicing and retrofit kits designed to enhance perfor-
maintaining the factory-assembled cooling mance and lengthen its life.
tower is by no means a simple, one step op- Owners and operators with a working
eration. Many interrelated factors must be knowledge of cooling tower preventive
considered, including periodic inspections maintenance and upgrade technology
and use of a competent specialist such as can take advantage of cost-saving ideas
a water treatment service engineer. These and procedures. If you are not regularly
factors serve as a valuable resource in the performing routine maintenance on your
total service program and may represent the cooling, implement a comprehensive
margin of success throughout the lifespan maintenance program today—because
of the cooling tower. temperature matters.

March 2005 ASHRAE Journal 51

Вам также может понравиться