www.bsria.co.uk
BSRIA Limited
has tested a sample of the product described below in accordance with the test methods contained
within HVCA DW/143‘A practical guide to ductwork leakage testing’ and have determined the item
met the leakage requirements for duct joints at Class A (500 Pa) and Class B (1000 pa) as described in
HVCA DW/144, when using the criteria within Clause 1.2 of DW/TM1. For further details see page 2
of this certificate.
TEST RESULTS
Requirements
Duct Details
Kingspan Koolduct PreInsulated Ductwork, 22 mm thick with internal dimensions of 1000 mm (W) x
1000 mm (H) x 2950 mm (L) [2 Nos.]. Ducts fitted with reinforcing bars, 2 bars at 600 as defined by
Kingspan Fabrication Manual (issue 3). Joined with Doby IDF 40 Flange Profiles, incorporating
0120/572 gasket material, and retained by EP13S clips.
Instrumentation
Results
2 of 2