Sr. No. Description Qty Unit Rate Amount

1.0 MV PANELS
1.01 11 KV WAPDA METERING PANEL
Supply of 11 KV sheet steel, floor mounting
cubical type totally enclosed indoor type MV
switch board as per latest WAPDA
specifications and requirement and suitable
for operation on 11 KV, 3 phase, 50 Hz. of
25 KA, BIL 95 KV. The MV panel shall be
conforming to the specifications -and
drawings and manufactured by any one of
the manufacturers specified in Annexure "B"
including cost of all necessary installing
material and termination kits make
Raychem/3M and comprising of:-

1-11 KV fully wired complete cubical housing


which will be metal clad sheet fabricated
totally enclosed 2.3mm thick indoor type
complete with copper bus bars 630Amps as
per WAPDA specifications P44:96(Amended
To-Date).

1-630 Amps triple pole , 15-KV , fully


enclosed Manual Operated Vacuum Circuit
Breaker DRAWOUT TYPE, 95KV BIL, BC-
25KA.
6-630 Amps, main isolating plugs and
sockets.
2-Sets of 3 Phase shutter, having facilities
for pad locking.
1-T/Pole copper bus bars rated at 630Amps.
3-Current Transformers epoxy cast ratio
(200/5Amps) 10VA class 0.5, M5, ITH=20
Insulation Level 95KV for Metering.
3-Current Transformers ( 400:200/5A )
Burden 15VA class 0.5, Insulation Level
12/36/95KV, 25KA for Protection.
3-1 Pole Voltage Transformers ratio
11000/√3/ 110V/√3, 100VA Class 0.5,
Insulation Level 12/36/95KV,25KA.
1-Digital Over Current & Earth Fault
Protection Relay.
1-Space only Combined KVARH + KWH
Meter with M.D.I.

P-2
INTERNATIONAL ENGINEERS

Sr. No. Description Qty Unit Rate Amount

1-Ammeter scaled (200/5A ) Class 1.5 of


size 96 x 96mm.
1-Voltmeter of scale ( 0–15KV ) Class 1.5 of
size 96 x 96mm.
1-Voltmeter selector switch (7-Position ).
1-Capacitor Trip Unit.
2-Indication Lamps for (OFF-RED/ON –
GREEN).
1-Set of MCB’s For Control Circuit.
1-Set of Terminal Blocks.
2-Set of cable gland for incoming/ outgoing
11 KV, 3 core XLPE cable. 1 Each -

1.02 OWNER PROTECTION PANEL


Conforming to same constructional
specifications as per Item No. 1 owner
supplied transformer protection panel MV
Switch Board to be installed in sub station
and comprising of:-

1-11 KV fully wired complete cubical housing


which will be metal clad sheet fabricated
totally enclosed 2.3mm thick indoor type
complete with copper bus bars 630Amps as
per WAPDA specifications P44:96
(Amended To-Date).

1-630 Amps triple pole , 15-KV , fully


enclosed Manual Operated Vacuum Circuit
Breaker DRAWOUT TYPE, 95KV BIL,BC-
25KA.

6-630 Amps, main isolating plugs and


sockets.
2-Sets of 3 Phase shutter, having facilities
for pad locking.
1-T/Pole copper bus bars rated at 630Amps.
3-Current Transformers epoxy cast ratio
(200/5Amps) 10VA class 0.5, M5, ITH=20
Insulation Level 95KV for Metering.
3-Current Transformers ( 400:200/5A )
Burden 15VA class 0.5, Insulation Level
12/36/95KV, 25KA for Protection.
3-1 Pole Voltage Transformers ratio
11000/√3/ 110V/√3, 100VA Class 0.5,
Insulation Level 12/36/95KV,25KA.
1-Digital Over Current & Earth Fault
Protection Relay.
1-Combined KVARH + KWH Meter with
M.D.I.

P-3
INTERNATIONAL ENGINEERS

Sr. No. Description Qty Unit Rate Amount

1-Ammeter scaled ( 200/5A ) Class 1.5 of


size 96 x 96mm.
1-Voltmeter of scale ( 0–15KV ) Class 1.5 of
size 96 x 96mm.
1-Voltmeter selector switch ( 7-Position ).
1-Capacitor Trip Unit.
2-Indication Lamps for (OFF - RED / ON –
GREEN).
1-Set of MCB’s For Control Circuit.
1-Set of Terminal Blocks.
2-Set of cable gland for incoming / outgoing
11 KV, 3 core XLPE cable. 1 Each -

1.03 11 KV,TRANSFORMER CONTROLLING


SWITCH BOARD
Supply of 11 KV sheet steel, floor mounting
cubical type totally enclosed indoor type MV
switch board as per specifications and
requirement and suitable for operation on 11
KV, 3 phase, 50 Hz. of 25 KA, BIL 95 KV.
The MV panel shall be conforming to the
specifications -and drawings and
manufactured by any one of the
manufacturers specified in Annexure "B"
including cost of all necessary installing
material and termination kits make
Raychem/3M and comprising of:-

INCOMING
1-Arrangement of one incoming and
common busbar on incoming side of both
MV panel and having incoming cable
connection box on side of one of the panel.
OUTGOING MV PANELS (2 NOS.)
2-11 KV fully wired complete cubical housing
which will be metal clad sheet fabricated
totally enclosed 2.3mm thick indoor type
complete with copper bus bars 630Amps.
2-630 Amps triple pole , 15-KV , fully
enclosed motorized Vacuum Circuit Breaker
DRAWOUT TYPE, 95KV BIL, BC-25KA.
12-630 Amps, main isolating plugs and
sockets.
4-Sets of 3 Phase shutter, having facilities
for pad locking.
4-T/Pole copper bus bars rated at 630Amps.

P-4
INTERNATIONAL ENGINEERS

Sr. No. Description Qty Unit Rate Amount

6-Current Transformers epoxy cast ratio


(100/5/5Amps) 10VA class 0.5, M5, ITH=20
Insulation Level 95KV for Metering.
6-1 Pole Voltage Transformers ratio
11000/√3/ 110V/√3, 100VA Class 0.5,
Insulation Level 12/36/95KV,25KA.
2-Digital Over Current & Earth Fault
Protection Relay (ABB/MIKRO).
1-Digital Energy Meter (ELSTER/BLUE
STAR).
2-Ammeter scaled ( 100/5A ) Class 1.5 of
size 96 x 96mm (LUMEL).
2-Ammeter Selector Switch (GGT).
2-Voltmeter of scale (0–15KV ) Class 1.5 of
size 96 x 96mm (LUMEL).
2-Voltmeter Selector Switch (GGT).
2-Capacitor Trip Unit (E-LAB).
4-Indication Lamps for (OFF - RED / ON –
GREEN) (GGT).
4-Push Button (OFF - RED / ON – GREEN)
GGT).
2-Bucholz Relay Tripping Contact &
annunciator.
2-Anti-Condensate Heater with Thermostat.
2-Set of MCB’s For Control Circuit.
2-Set of Terminal Blocks.
3-Set of cable gland for incoming/outgoing
11 KV, 3 core XLPE cable.
1 Each -
SUB TOTAL SECTION (1.0) -

2.0 POWER TRANSFORMER


2.01 Supply of 2500 KVA transformer, complete
for outdoor installation with oil conservator,
filling hole & plug, lifting lugs, Bi-directional
roller wheels, oil level gauge, silica gel
breather, termometer for oil, pressure relief
device, double float BUCHHOLZ relay, drain
valve, earthing terminal, all complete as per
following details:-

Rated Power KVA 2500


Rated Frequency HZ 50
Static Shielding .
between HT & LT winding.
to avoid voltage surdges.
Impulse withstand KV 95 -
50 HZ withstand KV28 - 2.5

P-5
INTERNATIONAL ENGINEERS

Sr. No. Description Qty Unit Rate Amount

Cooling - ONAN - ONAN


MV-Bushings No. 3 4
Connection - Cable - Bus Tie Duct
Vector Group - DY 11
Iron losses 3000W
Copper losses 35000W
Impedence 6.5%
Permissible temperature:
Ambient C˚ 45
Winding temperature rise of C˚ 55
Temperature rise of oil C˚ 50
Tape Changer
- Type - Off Load
- Tappings % +2.5+ 5 - 7.5 2 Each -
SUB TOTAL SECTION (2.0) -
3.0 HT CABLE
3.01 HT CABLE
Supply and laying of 3 core XLPE insulated
copper tape screened PVC/SWA/PVC
15/0.635 KV aluminium conductor cable.
i) 3 core 150mm2 XLPE insulated copper tape
screened PVC/SWA/PVC 15/0.635 KV
aluminium conductor cable. 200 Rft -
SUB TOTAL SECTION (3.0) -
Total Rs:- -