Synco™ 200

Universal Controllers RLU2...

With programmed standard applications


Freely programmable controller, for optimum adaptation to the relevant
type of plant
P-, PI, or PID mode
Menu-driven operation

Use

For use on basic to complex ventilation, air conditioning and chilled water plant.
The universal controllers are designed to handle the following controlled variables:
Temperature, relative/ absolute humidity, pressure/ differential pressure, airflow,
indoor air quality and enthalpy.

CE1N3101en
2016-03-22 Building Technologies
Functions

Operating modes Selection of operating mode via status inputs: Comfort, Economy, Protection
Display of current operating mode (Comfort, Economy, Protection)
Setpoints With each sequence controller: Individually adjustable heating and cooling
setpoints (or maximum and minimum setpoints) for the Comfort and Economy
modes
Predefined room temperature setpoint with room unit or setpoint readjuster
(passive)
With each sequence controller: Predefined setpoint with remote setpoint adjuster
(active or passive)
Room temperature setpoint with summer and/ or winter compensation
With each sequence controller: Setpoint shift depending on sensor signal,
selectable start and end points
Universal inputs Universal inputs for:
Passive or active analog input signals of various measured values (°C, %, ---)
Digital input signals (potential-free contacts)
Control functions Universal controller (sequence controller) for 2 heating sequences (reverse
acting) and 2 cooling sequences (direct acting), can be used as a controller
providing P-, PI or PID mode, or as a differential controller
Controller can be configured as a room / supply air temperature cascade
controller with limitation of the supply air temperature
Each sequence can be assigned modulating control (modulating output, step
switch, mixed air damper/ heat recovery equipment) and a pump. 2 sequences
can act on the same modulating control (e.g. priority cooling/ dehumidification)
General limitation (minimum/maximum with PI mode per sequence controller,
either as absolute limitation, e.g. for the supply air temperature or supply air
humidity), or as relative temperature limitation (e.g. maximum limitation of the
room / supply air temperature differential). Limitation acts on all sequences.
Minimum limitation can be set to a lower setpoint while cooling is on (e.g cooling
with DX cooler battery)
Sequence limitation with PI mode per universal controller, can be defined as
minimum or maximum limitation. Limitation acts on a single sequence (e.g. heat
recovery anti-icing protection or maximum limitation of the heating coil’s return
temperature)
The mixed air temperature controller controls the mixed air temperature via the
air dampers
Locking of individual sequences
Digital input (heating limit switch, from a heating controller) for changing the
control strategy (room-supply air temperature cascade control), configurable

2 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Switching and 2-stage frost protection (modulating/ 2-position) or frost protection thermostat
supervisory functions (heating sequences delivering 100 % output, fault relay for switching off the
fans) (with RLU220 only indication)
Control of pumps, constantly ON at low outside temperatures, ON according to
load sequence controller (not with RLU220); periodic activation of pump (pump
kick)
Control of an analog output (not with RLU202). Configurable external presetting
(controller used as a pure signal converter). Minimum and maximum position,
invertible.
Minimum limitation at low outside temperatures
Control of mixed air dampers or heat recovery equipment with maximum econ-
omy changeover (not with RLU202), startup function at low outside temperatures
Control of a multistage aggregate with a step switch, with a maximum of 6 steps
and a modulating output.
The switching on/off points of each step can be adjusted. Adjustable delay
times. Configurable external presetting (controller used as a pure step switch).
Modulating output with minimum and maximum position, invertible (only with
RLU236)
Control of a multistage aggregate with a step switch, with a maximum of 2 steps
and a modulating output.
Functions as described above (not with RLU220)
Control of a linear multistage aggregate with a step switch, with a maximum of 6
steps and a modulating output.
Fixed assignment of switching on/off points to the load. Adjustable delay times
and priority changeover. Configurable external presetting (controller used as a
pure step switch). Modulating output for load assignment to the steps, with min-
imum and maximum position, invertible (only with RLU232 and RLU236)
Control of a binary multistage aggregate with a step switch, with a maximum of 4
relays for 15 steps and a modulating output.
Fixed switching on/off points with binary switching logic. Adjustable delay times.
Configurable external presetting (controller used as a pure step switch). Modu-
lating output for load assignment to the steps, with minimum and maximum posi-
tion, invertible (only with RLU232 and RLU236)
Control of a modulating 3-position actuator. Configurable presetting (controller
used as a pure analog/3-position converter) (only with RLU202 and RLU222)
Delivery of a passive measuring signal as an active signal for use by other con-
trollers

Type summary

Type Universal Digital Positioning Switching Number of


reference inputs inputs outputs outputs control loops
RLU202 4 1 0 2 1
RLU220 4 1 2 0 1
RLU222 4 1 2 2 2
RLU232 5 2 3 2 2
RLU236 5 2 3 6 2

Accessories Name Type reference


Mounting frame for flush panel mounting ARG62.201
(consisting of 1 small frame, 1 large frame,
2 hexagonal spacers, 4 fixing screws,
Mounting Instructions)

3 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Ordering

When ordering, please give name and type reference of the controller, e.g.:
Universal controller RLU236.
The products listed under "Accessories" must be ordered as separate items.

Equipment combinations

For equipment combinations, refer to the Basic Documentation P3101 or to the


document covering the selected application.

Product documentation

Document type Document


number
Basic Documentation: Universal Controllers RLU2… CE1P3101en
Instructions Set (mounting, commissioning, operation) 74 319 0424 0
Declaration of Conformity (CE): RLU2… CE1T3101xx
Environmental Declaration: RLU202, RLU220, RLU222 CE1E3101en01
Environmental Declaration: RLU232 and RLU236 CE1E3101en02

Technical design

Each controller offers up to 45 ready programmed applications. When


commissioning a plant, the relevant basic type must be entered. All associated
functions, terminal assignments, settings and displays will then automatically be
activated and parameters that are not required will be deactivated.

In addition, each type of universal controller has 2 empty applications loaded:


1 for basic type A (ventilation controller)
1 for basic type U (universal controller)

With the help of the built-in operation or the OCI700.1 service tool, the controller
affords:
Activation of a programmed application (refer to "Programmed standard applica-
tions")
Modification of a programmed application
Free configuration of applications
Optimization of the controller settings

For operating actions of the functions, refer to the Basic Documentation.

4 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Mechanical design

The universal controller consists of terminal base and controller insert with built-in
operation.
The terminal base can be fitted to a DIN mounting rail or is screwed directly on a
flat surface. It consists of a plastic housing with 2 terminal levels.
The controller insert engages in the terminal base. It consists of a plastic housing
which accommodates the printed circuit boards.
Controller operation is fully integrated.

Operating, display and

3101Z06
connecting elements
1
2

3
4

9 8 7 6 5

Legend 1 OK button for confirming the selected menu line or the value entered
2 Navigation button, upward (+) for selecting the menu line or changing the value
3 Navigation button, downward (–) for selecting the menu line or changing the value
4 ESC button for returning to the previous menu or for rejecting the value entered
5 Connection facility for the service tool (RJ45 connector)
6 Display
7 Catch for fitting the controller to a top hat rail
8 Fixing facility for a cable tie (cable strain relief)
9 Rest for the terminal cover

Engineering notes

The controller operates on AC 24 V. Operating voltage must conform to the re-


quirements of SELV/ PELV (safety extra low-voltage)
The transformers used must be safety isolating transformers featuring double
insulation to EN 60 742 or EN 61 558-2-6; they must be suited for 100 % duty
Fuses, switches, wiring and earthing must be in compliance with local
regulations
Sensor wires should not be run parallel to mains carrying wires that power fans,
actuators, pumps, etc.
It is recommended to use the standard applications provided. Specific plant
situations may require certain adaptations however

5 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Mounting and installation notes

Controllers and extension modules are designed for:


Mounting in a standard cabinet to DIN 43 880
Wall mounting on an existing top hat rail (to EN 60715-TH35-7.5)
Wall mounting with 2 fixing screws
Flush panel mounting with ARG62.201 mounting frame
Not permitted are wet or damp spaces. The permissible environmental
conditions must be observed
Disconnected the system from the power supply prior to mounting the controller
The controller insert must not be removed from the terminal base!
Low-voltage side All connection terminals for protective extra low-voltage are located in the upper
half of the unit, those for mains voltage at the bottom
Each terminal (spring cage terminal) can accommodate only 1 solid wire or 1
stranded wire. For making the connections, the cables must be stripped for 7 to
8 mm. To introduce the cables into the spring cage terminals and to remove
them, a screw driver size 1 is required. Cable strain relief can be provided with
3101Z07en

the help of the fixing facility for cable ties


Mains-voltage side The controller is supplied complete with Installation and Operating Instructions

Commissioning notes

The configuration and parameters of the standard applications offered by the


controller can be changed any time by service staff who have been trained by
HVAC Products and who have the required access rights, either locally or
online/offline with the service tool
During the commissioning process, the application is deactivated and the
outputs are in a defined off state
On completion of the configuration, the controller automatically makes a new
start
When leaving the commissioning pages, the peripheral devices connected to the
universal inputs (including the extension modules) are automatically tested and
identified. If a peripheral device is missing, a fault status message will be
delivered
If adaptions to specific plants are required, they must be recorded and the
documentation kept inside the control panel
For the procedure to be followed when starting up the plant for the first time,
refer to the Installation Instructions

Disposal notes

The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the devices through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.

Warranty

Technical data on specific applications are valid only together with Siemens prod-
ucts listed under "Equipment combinations". Siemens rejects any and all warran-
ties in the event that third-party products are used.

6 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Technical data

Power supply (G, G0) Rated voltage AC 24 V 20 % (SELV)


Requirements for external safety isolating trans- EN 60 742 / EN 61 558-2-6,
former to min. 10 VA, max. 320 VA
Frequency 50/ 60 Hz
Power consumption
RLU202, RLU220, RLU222 5 VA
RLU232, RLU236 6 VA
Supply line fusing Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D accord-
ing to EN 60898
or
Power source with current
limitation of max. 10 A

Universal inputs Number refer to "Type summary"


Measured value inputs Sensors
(X...) Passive LG-Ni 1000, T1, Pt 1000
2x LG-Ni 1000 (averaging)
Active DC 0...10 V
Signal sources
Passive 0...1000 / 1000...1175
Active DC 0...10 V

Digital inputs (X..., D...) Contact sensing


Voltage DC 15 V
Current 5 mA
Requirements for status and impulse contacts
Signal coupling potential-free
Type of contact maintained or impulse con-
Insulating strength against mains potential tacts
AC 3750 V to EN 60 730
Perm. resistance
Contacts closed max. 200
Contacts open min. 50 k

Outputs Number of positioning and switching outputs refer to "Type summary"


Positioning outputs Y... Output voltage DC 0...10 V
Output current 1 mA
Max. load continuous short-circuit

Switching outputs External supply line fusing


AC 230 V Non-renewable fuse (slow) max. 10 A
Automatic line cutout max. 13 A
(Q1x...Q6x)
Release characteristic B, C, D to EN 60 898
Cable length max. 300 m
Relay contacts
Switching voltage max. AC 265 V
min. AC 19 V
AC current max. 4 A ohm.,
3 A ind. (cos = 0.6)
At 250 V min. 5 mA
At 19 V min. 20 mA
Switch-on current max. 10 A (1 s)
Contact life at AC 250 V guide values:

7 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
At 0.1 A res. 2 x 107 cycles
At 0.5 A res. 4 x 106 cycles (NO)
2 x 106 cycles (changeover)
At 4 A res. 3 x 105 cycles (NO)
1 x 105 cycles (changeover)
Red. factor at ind. (cos = 0.6) 0.85
Insulating strength
Between relay contacts and system electronics
(reinforced insulation) AC 3750 V, to EN 60 730-1
Between neighboring relay contacts (operational
insulation)
Q1 Q2; Q3 Q4; Q5 Q6 AC 1250 V, to EN 60 730-1
Between relay groups (reinforced insulation)
(Q1, Q2) (Q3, Q4) (Q5, Q6) AC 3750 V, to EN 60 730-1

Power supply external Voltage AC 24 V


devices (G1) Current max. 4 A

Interfaces Service tool connection facility RJ45 connector

Perm. cable lengths For passive measuring and positioning signals (measuring errors can be
Type of signal corrected)
LG-Ni 1000, T1 max. 300 m
Pt 1000 max. 300 m
0...1000 max. 300 m
1000...1235 max. 300 m
Contact sensing max. 300 m
For DC 0...10 V measuring and control signals refer to Data Sheet of the
signal delivering device

Electrical connections Connection terminals spring cage terminals


For wires 0.6 mm dia....2.5 mm2
For stranded wires without ferrules 0.25...2.5 mm2
For stranded wires with ferrules 0.25...1.5 mm2

Degrees of protection Degree of protection of housing to IEC 60 529 IP 20 (when mounted)


Safety class to EN 60 730 device suited for use with
equipment of safety class II

Environmental Operation to IEC 60 721-3-3


conditions Climatic conditions class 3K5
Temperature (housing and electronics) 0...50 °C
Humidity 5...95 % r.h. (non-condensing)
Mechanical conditions class 3M2
Transport to IEC 60 721-3-2
Climatic conditions class 2K3
Temperature 25... 70 °C
Humidity < 95 % r.h.
Mechanical conditions class 2M2

Classifications to Mode of operation, automatic controls type 1B


EN 60 730 Degree of contamination, controls’ environment 2
Software class A
Rated surge voltage 4000 V
Temperature for ball-pressure test of housing 125 °C

8 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Materials and colors Terminal base Polycarbonate, RAL 7035
(light-grey)
Controller insert Polycarbonate, RAL 7035
(light-grey)
Packaging corrugated cardboard

Standards, directives Product standard EN 60730-1


and approvals Automatic electrical controls
for household and similar use
Electromagnetic compatibility (Applications) For use in residential, com-
mercial and industrial
environments
EU conformity (CE) CE1T3101xx *)
UL certification UL916
http://database.ul.com
RCM-conformity (EMC) CE1T3110en_C1*)
EAC conformity Eurasia conformity
Environmental Product environmental declarations: CE1E3101de01 *)
compatibility contain data on environmentally compatible CE1E3101de02 *)
product design and assessments (RoHS compli-
ance, materials composition, packaging, envi-
ronmental benefit, disposal)

Weight, RLU202 0,334 kg


excl. packaging RLU220 0,292 kg
RLU222 0,334 kg
RLU232 0,437 kg
RLU236 0,481 kg
*)
Documents can be downloaded at http://www.siemens.com/bt/download

9 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Connection diagrams

Internal diagrams
RLU202

3101G08
G X1 M X2 M G1 X3 M X4 M G1 D1 M Q11 Q23

G0 N1 Q12 Q14 N2 Q24

RLU220

3101G09
G X1 M X2 M G1 X3 M X4 M G1 D1 M

G0 G1 Y1 G0 G1 Y2 G0

RLU222

3101G02
G X1 M X2 M G1 X3 M X4 M G1 D1 M Q11 Q23

G0 G1 Y1 G0 G1 Y2 G0 N1 Q12 Q14 N2 Q24

RLU232

3101G03
G X1 M X2 M G1 X3 M X4 M G1 X5 M D1 M D2 M Q11 Q33

G0 G1 Y1 G0 G1 Y2 G0 G1 Y3 G0 Q12 Q14 Q34

RLU236

3101G04
G X1 M X2 M G1 X3 M X4 M G1 X5 M D1 M D2 M Q11 Q23 Q33 Q41 Q53 Q63

G0 G1 Y1 G0 G1 Y2 G0 G1 Y3 G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

Legend G, G0 Rated voltage AC 24 V


G1 Output voltage AC 24 V for powering external active sensors, signal sources, monitors or
setting units
M Measuring neutral for signal input
G0 System neutral for signal output
X... Universal signal inputs for LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000,
DC 0...10 V, 0...1000 (= REM), 1000…1175 (= REL)
X..., D... Contact sensing (potential-free)
Y... Control or status outputs, analog DC 0...10 V
Q... Potential-free relay outputs for AC 24...230 V
N1, N2 Neutral conductor connection for radio interference suppression elements

Notes Each terminal (spring cage terminal) can only accommodate 1 solid wire or 1 stranded wire. Double
terminals are internally interconnected
If a 3-position AC 230 V actuator is used, the radio suppression element must be activated:
Connect terminal N1 to the neutral conductor and fit a wire link between N1 and N2 (see connection
diagram 5)

10 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Connection diagrams Examples:
Connections on the Connection diagram 1: Measuring section with passive main and auxiliary sensors
measuring side and passive signal source
G

3101A01
(3) (1)
B M B1 B M B5 B2 M R5

AC 24 V
G X... M X... M X... M
G0 N1
G0

Connection diagram 2: Measuring section with active sensor and active signal
source
G

3101A02
(1) (2) (3) (4)
B M G B3 GL GN out in R2
AC 24 V

G X... M G1 G1 M X...
G0 N1
G0

Connection diagrams 3 and 4:


Measuring section with CO2/VOC- and CO2-evaluation
G G
3101A03

3101A04
G (CO2/
(CO2) VOC) G (CO2 )
M U1 U2 B4 M U1
B4
AC 24 V

AC 24 V

G G1 M X... G G1 M X...

G0 G0 N1
N1
G0 G0

Connections on the
control and monitoring Connection diagram 5:
side
L
G
3101A 05_A
1 L M D1 Q11
S7
2 4 F3 N Q12 Q14 S5

G M X... M D1 M D2 Q11 Q33 Q11 Q23


AC 230 V
AC 24 V

G0 G0 G1 Y1 Q12 Q14 Q34 N1 N1 Q12 Q14 N2 Q24 N2

G Y Y1 Y2
G0 N
Y3 Y
G0
H1 K1 K2
N

Legend to the connection N1 Universal controller RLU2... K1 Fan release relay


N2 Universal controller RLU222 K2 Pump release relay
diagrams 1 through 5 B1 Supply air temperature sensor QAM2120.040 R2 Setpoint adjuster BSG61
B3 Frost sensor QAF63.2/QAF63... R5 Setpoint readjuster BSG21.5
B4 CO2/VOC sensor QPA2002/2002D S4 On/off switch "Locking signal"
B4 CO2 sensor QPA2000 S5 Digital time switch SEH62.1
B5 Room temperature sensor QAA24 S7 Manual switch "On/Standby"
F3 Frost unit QAF81... Y Actuating device with 3-position control
H1 Horn for fault status message from fan Y3 Actuating device for heating

11 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Preprogrammed standard applications

Note The plant diagrams / connection diagrams assigned to the basic types are only
examples.

Controller- / Application no. / description Plant diagram / connection diagram


basic type
RLU202 ADA006 LU0 HQ

S01
A01 Extract air (room) temperature control with electric air heater T
B2
battery. N. X1

Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
ture B9 E1 B1
N.X4

N.Q1
Outside temperature-dependent functions N.X3
N.Q2
N. X2

Remote setpoint readjuster S5


2-stage electric air heater battery N. D1

Comfort / Protection Mode changeover (time switch)


RLU202 ADA012 LU0 HQ

S01
B5
A02 Supply air temperature control with electric air heater battery. T
N.X2
Cascade
Options:
Room temperature cascade control
Outside temperature-dependent functions T T T R5
Remote setpoint readjuster B9 E1 B1
N.X4

N.Q1
2-stage electric air heater battery N.X3
N.Q2
N.X1

Comfort / Protection Mode changeover (time switch) S5


N. D1

RLU202 ADA014 LU0 HQ

S01
B5
A03 Supply air temperature control with hot water heating coil. T
N.X2
Cascade
Options:
Room temperature cascade control
Outside temperature-dependent functions T T T R5
Remote setpoint readjuster B9 B1
N.X4

Comfort / Protection Mode changeover (time switch) N.X3 N.X1

Y3 M
N.Q1 S5
N.Q2
N.D1

RLU202 ADB003 LU0 HQ

S01
A04 Extract air (room) temperature control with DX cooler battery. T

Options: B2
N.X1
Minimum and maximum limitation of the supply air tempera-
ture T T T R5
Outside temperature-dependent functions B9 M7 B1
N.X4

N.X2
Remote setpoint readjuster N.X3 N.Q 1
N.Q 2

2-stage DX cooler battery S5


Comfort / Protection Mode changeover (time switch) N.D1

RLU202 ADB007 LU0 HQ


S01

B5
T
A05 Supply air temperature control with DX cooler battery. N.X2
Cascade
Options:
Room temperature cascade control
Outside temperature-dependent functions T T T R5
Remote setpoint readjuster B9 M7 B1
N.X4

N.X1
2-stage DX cooler battery N.X3 N.Q 1
N.Q 2

Comfort / Protection Mode changeover (time switch) S5


N.D1

RLU202 AEC001 LU0 HQ


S01

A06 Extract air (room) temperature control with hot water heating T

coil and DX cooler battery. B2


N.X1
Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
N.X4
ture B9 B1
M3 M7
Outside temperature-dependent functions N.X3
N.Q1 N.Q2
N.X2

Remote setpoint readjuster S5


Comfort / Protection Mode changeover (time switch) N.D1

12 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU202 AEC002 LU0 HQ

S01
B5
A07 Supply air temperature control with hot water heating coil and T
N.X2

DX cooler battery. Cascade

Options:
Room temperature cascade control T T T R5
N.X4
Outside temperature-dependent functions B9 B1
M3 M7
Remote setpoint readjuster N.X3
N.Q 1 N.Q 2
N.X1

Comfort / Protection Mode changeover (time switch) S5


N.D1

RLU202 ADKA02 LU0 HQ

S01
U01 Extract air (room) humidity control (r.h.) with spray humidifier.
Options: B12
N.X1
Maximum limitation of the air humidity [%]

Remote setpoint adjuster R5


T
2-stage spray humidifier M
B11
N.X3

N.X2
Comfort / Protection Mode changeover (time switch) [%]
M8
N.Q 1 S5
N.Q2 N.D1

RLU202 ADI003 LU0 HQ

S01
B5
U02 Extract air (room) humidity control (r.h.) with DX cooler battery. T
N.X3

Options: B12
N.X1
Additional maximum selection from internal and external [%]

signal R5
T
Room temperature-dependent shifting of humidity setpoint N.X4
M7
Remote setpoint adjuster N.Q1
N.Q2
2-stage DX cooler battery S5
N. X2
Comfort / Protection Mode changeover (time switch) N.D1

RLU202 ADI005 LU0 HQ

S01
B5
U03 Extract air (room) humidity control (a.h.) with DX cooler battery. T T
T
N.X3

Options: B18
Additional maximum selection from internal and external N.X1
[g/kg]

signal R5
T
Room temperature-dependent shifting of humidity setpoint M7
N.X4

Remote setpoint adjuster N.Q1


N.Q2
2-stage DX cooler battery S5
Comfort / Protection Mode changeover (time switch) N.D1 N.X2

RLU202 ADZA01 LU0 HQ

S01
U04 Extract air (room) humidity control (r.h.) with spray humidifier
B12
and DX cooler battery. N.X1
Options: [%]

Maximum limitation of the supply air humidity T R5


Additional maximum selection from internal and external M
B11
N.X4

M7 N.X2
signal N.Q2 [%]
M8
Remote setpoint adjuster N.Q1 S5
N.D1 N. X3
Comfort / Protection Mode changeover (time switch)
RLU202 AZZ001 LU0 HQ
S01

B4
U05 Indoor air quality control with fan control. AQ
N.X1
[ppm]
Options:
Additional maximum selection from internal and external
signal T T R5
Outside temperature-dependent functions B9 M1
N.Q1
N.X4

N.X3
Remote setpoint adjuster N.Q2

2-speed fan S5
Comfort / Protection Mode changeover (time switch) N.D1 N .X2

RLU202 HZC001 LU0 HQ T B9


S01

U06 Temperature control of mixing heating circuit. N.X3 B1 T


Options: N.X1

Minimum limitation of the return temperature Y3 S5


N.D1
Outside temperature-dependent functions N.Q1
N.Q2 M
Remote setpoint adjuster
Comfort / Protection Mode changeover (time switch) T R5
N.X4

T B7
N.X2

13 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU202 HZC002 LU0 HQ

S01
U07 Boiler temperature control (substitute for RCA12.2)
Application:
Minimum limitation of the boiler return temperature Y3 S5
Options: N.Q1 N.D1
N.Q2 M
Remote setpoint adjuster (absolute)
Comfort / Protection Mode changeover (time switch) T R5
N.X2

T B7
N.X1

RLU202 ADC019 LU0 HQ

S01
U08 Universal control (substitute for RKN2 / RKN22) T

B2
Application: N.X1

Temperature control (on/off pump control)


Options:
T R5
Remote setpoint adjuster (absolute) N.X2
M3 M4
Comfort / Protection changeover N.Q1 N.Q 2

S5
N.D1

RLU202 SA0001 LU0 HQ B6


T N.X1
U09 Differential temperature control (substitute for RSA24)
Application:
Solar heat storage plant
Options:
Maximum limitation of the boiler temperature
Minimum limitation of the charging temperature
M3 T B3
Comfort / Protection Mode changeover (time switch) N.Q1 N.X2

S01
RLU202 ZZZ001 LU0 HQ DC 0 ... 10 V

U10 3-position actuator

A01
G X1 M G1 D1 M Q11 Q23
RLU202
G0 N1 Q12 Q14 N2 Q24
3P

RLU202 ZZZ002 LU0 HQ DC 0 ... 10 V

U11 Variable 2-step switch

A01
G X1 M G1 D1 M Q11 Q23
RLU202
G0 N1 Q12 Q14 N2 Q24

2Q VAR.

RLU220 ADA001 LU2 HQ


S01

A01 Extract air (room) temperature control with hot water heating T

coil. B2
N.X1
Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
ture B9 B1
N.X4

Remote setpoint readjuster N.X3 N.X2

M
Outside temperature-dependent functions Y3 S5
Comfort / Protection Mode changeover (time switch) N.Y1 N.D1

RLU220 ADA008 LU2 HQ


S01

B5
A02 Supply air temperature control with hot water heating coil. T
N.X2
Cascade
Options:
Room temperature cascade control
Remote setpoint readjuster T T T R5
Outside temperature-dependent functions B9 B1
N.X4

N.X3 N.X1
Comfort / Protection Mode changeover (time switch)
M

Y3 S5
N.Y1 N.D1

14 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU220 ADA003 LU2 HQ

S01
A03 Extract air (room) temperature control with hot water heating T

coil and frost protection. B2


N. X1
F3
Options: N.X3

Minimum and maximum limitation of the supply air tempera- T T


T
ture B9 B1
N.X4
Outside temperature-dependent functions N.X2

M
Comfort / Protection Mode changeover (time switch) Y3 S5
N.Y1 N.D1

RLU220 ADA010 LU2 HQ

S01
B5
T
A04 Supply air temperature control with hot water heating coil and N.X2
Cascade
frost protection.
F3
Options: N.X3

Room temperature cascade control T T


T
Outside temperature-dependent functions B9 B1
N.X4 N.X1
Comfort / Protection Mode changeover (time switch)
M

Y3 S5
N.Y1 N.D1

RLU220 ADA017 LU2 HQ

S01
1

A05 Extract air (room) temperature control with hot water heating T
B2
coil, frost protection. N.X1
Options: F3
N.X3

Minimum and maximum limitation of the supply air tempera- 1


T R5
T T
ture B1
N.X4

Remote setpoint readjuster N.X2

M
Comfort / Protection Mode changeover (time switch) Y3 S5
N.Y1 N.D1

RLU220 ADB001 LU2 HQ

S01
A06 Extract air (room) temperature control with chilled water cooling T
B2
coil. N.X1
Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
ture B9 B1
N.X4

N.X3 N.X2
Remote setpoint readjuster
M
Outside temperature-dependent functions Y4 S5
Comfort / Protection Mode changeover (time switch) N.Y1 N.D1

RLU220 ADB005 LU2 HQ

S01
B5
A07 Supply air temperature control with chilled water cooling coil. T
N.X2
Cascade
Options:
Room temperature cascade control
Remote setpoint readjuster T R5
T T
Outside temperature-dependent functions B9 B1
N.X4

Comfort / Protection Mode changeover (time switch) N.X3 N.X1

M
Y4 S5
N.Y1 N.D1

RLU220 ACAD01 LU2 HQ


S01

A08 Extract air (room) temperature control with mixed air dampers M
T
Y2 B2
and outside temperature-dependent functions. M N.X1
Y1
Options: N.Y1 M
Y6

Additional maximum selection from internal and external


T
signal B9
Comfort / Protection Mode changeover (time switch) N.X3

S5
N.D1 N.X2

RLU220 ABC001 LU2 HQ


S01

A09 Supply air temperature control with heating / cooling coil and
frost protection.
Options: F3
N.X3

Outside temperature-dependent functions T T


T
Comfort / Protection Mode changeover (time switch) B9 B1
N.X4 N.X1

M
T F16
Y5 N.X2 S5
N.Y1 N.D1

15 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU220 ADC021 LU2 HQ

S01
A10 Extract air (room) temperature control with hot water heating T
B2
coil and chilled water cooling coil. N.X1
Options:
Room temperature cascade control T T T R5
Outside temperature-dependent functions B9 B1
N.X4

Remote setpoint readjuster N.X3 N.X2

M M
Comfort / Protection Mode changeover (time switch) Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU220 ADC023 LU2 HQ

S01
B5
A11 Supply air temperature control with hot water heating coil and T
N.X2
Cascade
chilled water cooling coil.
Options:
Room temperature cascade control T T T R5
N.X4
Outside temperature-dependent functions B9 B1
N.X1
Remote setpoint readjuster N.X3

M M
Comfort / Protection Mode changeover (time switch) Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU220 ADC022 LU2 HQ

S01
1

A12 Extract air (room) temperature control with hot water heating T
B2
coil, frost protection, chilled water cooling coil. N.X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- T
1
T
T
ture B9 B1
N.X4 N.X2
Outside temperature-dependent functions
M M
Comfort / Protection Mode changeover (time switch) Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU220 ADC024 LU2 HQ

S01
B5
A13 Supply air temperature control with hot water heating coil, frost T
N.X2
Cascade
protection, chilled water cooling coil.
Options: F3
N.X3
Room temperature cascade control T T
T
Outside temperature-dependent functions B9 B1
Comfort / Protection Mode changeover (time switch) N.X4 N.X1

M M

Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU220 AEAF03 LU2 HQ

S01
A14 Extract air (room) temperature control with closed-circuit heat T

recovery system and hot water heating coil. B2


N.X1
Options:
Minimum and maximum limitation of the supply air tempera-
R5
ture T T T
N.X4
B1
Outside temperature-dependent functions B9
N.X3
Y11
N.Y2
N.X2

Remote setpoint readjuster M

Comfort / Protection Mode changeover (time switch) Y3


N.Y1
S5
N.D1

RLU220 AEAF04 LU2 HQ


S01

B5
A15 Supply air temperature control with closed-circuit heat recovery T
N.X2
Cascade
system and hot water heating coil.
Options:
Room temperature cascade control
R5
Outside temperature-dependent functions T T
T
N.X4
B9 B1
Remote setpoint readjuster N.X3
Y11
N. Y2 N.X1

Comfort / Protection Mode changeover (time switch) M


Y3 S5
N.Y1 N.D1

RLU220 AEAD03 LU2 HQ


S01

A16 Extract air (room) temperature control with mixed air dampers, M
T
Y2
hot water heating coil, frost protection. M
B2
N.X1
Options: Y1
N.Y2 M
Y6 F3
N.X3

Minimum and maximum limitation of the supply air tempera- T


1
T
T
ture B9 B1
Outside temperature-dependent functions N.X4 N.X2

M
Comfort / Protection Mode changeover (time switch) Y3 S5
N.Y1 N.D1

16 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU220 AEAD04 LU2 HQ

S01
1 B5
A17 Supply air temperature control with mixed air dampers, hot M
T
N.X2
Y2 Cascade
water heating coil, frost protection. M

Options: Y1
N.Y2 M
Y6 F3
N.X3

Room temperature cascade control T


1
T
T
Outside temperature-dependent functions B9 B1
N.X1
Comfort / Protection Mode changeover (time switch) N.X4

Y3 S5
N.Y1 N.D1

RLU220 ADB012 LU2 HQ

S01
A18 Extract air (room) temperature control with chilled water cooling T
B2
coil and 2 cooling towers. N.X1

Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
N.X4
ture B9 f1
f2
G1 f1
f2
G2 B1
N.X3 N.Y1 N.Y2
Outside temperature-dependent functions N.X2

Remote setpoint readjuster S5


Comfort / Protection Mode changeover (time switch) N.D1

RLU220 ADKA01 LU2 HQ

S01
U01 Extract air (room) humidity control (r.h.) with spray humidifier.
Options: B12
N. X1
Maximum limitation of the supply air humidity [%]

Remote setpoint adjuster R5


T
Comfort / Protection Mode changeover (time switch) M
B11
N.X3

N.X2
Y8 [%]
N.Y1
S5
N.D1

RLU220 ADI001 LU2 HQ

S01
U02 Extract air (room) humidity control (r.h.) with chilled water
cooling coil. B12
N. X1
Options: [%]

Additional maximum selection from internal and external R5


T
signal N.X3

Remote setpoint adjuster


M
Comfort / Protection Mode changeover (time switch) Y4 S5
N.Y1 N. D1 N.X2

RLU220 ADI002 LU2 HQ

S01
U03 Extract air (room) humidity control (a.h.) with chilled water T T

cooling coil. B18


Options: N.X1
[g/kg]

Additional maximum selection from internal and external T R5


signal N.X3

Remote setpoint adjuster


M
Comfort / Protection Mode changeover (time switch) Y4 S5
N.Y1 N.D1 N. X2

RLU220 PB0001 LU2 HQ B23


T B22
U04 Differential pressure control of water with speed-controlled N.X2
p
N.X1
p
B9 [bar]
pump. N.X4
S01

Options:
f1
T R5
Minimum and maximum limitation of the differential pressure f2
N.X3
Remote setpoint adjuster G1
N.Y1
Comfort / Protection Mode changeover (time switch)
S5
N.D1

RLU220 PB0004 LU2 HQ B23 p B22 p

U05 Differential pressure control of water with speed-controlled N.X2 N.X1


[bar]
pumps.
S01

Options: f1
f2
f1
f2

Minimum and maximum pressure limit controller G1


N.Y1
G2
N.Y2
Outside temperature-dependent functions T R5
N.X4
Remote setpoint adjuster
Comfort / Protection Mode changeover (time switch) T

B9 S5
N.X3 N.D1

17 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU220 AZL001 LU2 HQ B25 B24
p p
U06 Differential pressure control of air with speed-controlled fan. N.X2 N.X1
[Pa]
Options:

S01
Minimum and maximum limitation of the differential pressure R5
f1 T
Remote setpoint adjuster f2 N.X3

Comfort / Protection Mode changeover (time switch) G1


N.Y1

S5
N.D1

RLU220 AZL004 LU2 HQ B25 B24

U07 Differential pressure control of air with speed-controlled fans.


Options:
Minimum and maximum pressure limit controller
Outside temperature-dependent functions
Remote setpoint adjuster
Comfort / Protection Mode changeover (time switch)

S5

RLU220 AAZD01 LU2 HQ

S01
B4
U08 Indoor air quality control with mixed air dampers. M
AQ
N.X1
Y2 [ppm]
Options: M
Y1
Additional maximum selection from internal and external N.Y1 M
Y6

signal T R5
Remote setpoint adjuster N.X3

Comfort / Protection Mode changeover (time switch)


S5
N.D1 N.X2

RLU220 CZC002 LU2 HQ


U09 Temperature control of chilled ceilings.
Options:
Setpoint compensation depending on humidity
Deviation alarm B16
M
Comfort / Protection Mode changeover (time switch)
Y4

S5

RLU220 ADC025 LU2 HQ

S01
U10 Universal control (substitute for RKN8 / RKN88) T

Application: B2
N. X1

Temperature control (modulating valve control)


Options:
T R5
Remote setpoint adjuster (absolute) N.X2

Comfort / Protection Mode changeover (time switch)


Y3 M Y4 M
N.Y1 N.Y2 S5
N.D1

RLU222 ADA006 LU2 HQ


S01

A01 Extract air (room) temperature control with electric air heater T
B2
battery. N. X1

Options:
Minimum and maximum limitation of the supply air tempera- T T T R5
N.X4
ture B9 E1 B1
N.X3 N.Q1
Outside temperature-dependent functions N.Q2
N.Y1
N. X2

Remote setpoint readjuster S5


2-stage electric air heater battery N. D1

Comfort / Protection Mode changeover (time switch)


RLU222 ADA012 LU2 HQ
S01

B5
A02 Supply air temperature control with electric air heater battery. T
N.X2
Cascade
Options:
Room temperature cascade control
Outside temperature-dependent functions T T T R5
Remote setpoint readjuster B9 E1 B1
N.X4

N.Q1
2-stage electric air heater battery N.X3
N.Q2
N.Y1
N.X1

Comfort / Protection Mode changeover (time switch) S5


N. D1

18 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 ADA014 LU2 HQ

S01
B5
A03 Supply air temperature control with hot water heating coil. T
N.X2
Cascade
Options:
Room temperature cascade control
Outside temperature-dependent functions T T T R5
Remote setpoint readjuster B9 B1
N.X4

N.X1
Comfort / Protection Mode changeover (time switch) N.X3

Y3 M
N.Q1 S5
N.Q2
N.D1

RLU222 ADA004 LU2 HQ N.Q 1

S01
1
A04 Extract air (room) temperature control with hot water heating T

coil, frost protection and fan release. B2


N. X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T
ture B9
T
B1
M3
Outside temperature-dependent functions N.X4
N. Q2
N.X2

Comfort / Protection Mode changeover (time switch) M

Y3 S5
N.Y1 N.D1

RLU222 ADA005 LU2 HQ N.Q1

S01
1
A05 Extract air (room) temperature control with hot water heating T

coil, frost protection and fan release. B2


N.X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T R5
ture T
B1
N.X4

M3
Remote setpoint readjuster N.Q2
N.X2

Comfort / Protection Mode changeover (time switch) M


S5
Y3
N.Y1 N.D1

RLU222 ADA0011 LU2 HQ N.Q1

S01
1 B5
A06 Supply air temperature control with hot water heating coil, frost T
N.X2

protection and fan release. Cascade

Options: F3
N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions B9
T
B1
M3
Comfort / Protection Mode changeover (time switch) N.X4
N.Q2
N.X1

Y3 S5
N.Y1 N.D1

RLU222 ADB003 LU2 HQ


A07 Extract air (room) temperature control with DX cooler battery.
Options:
Minimum and maximum limitation of the supply air tempera-
ture
Outside temperature-dependent functions Y7
Remote setpoint readjuster
2-stage DX cooler battery M7 S5
Comfort / Protection Mode changeover (time switch) N.Q1
N.Q 2

RLU222 ADB007 LU2 HQ


A08 Supply air temperature control with DX cooler battery.
Options:
Room temperature cascade control
Outside temperature-dependent functions
Remote setpoint readjuster Y7
2-stage DX cooler battery
Comfort / Protection Mode changeover (time switch) M7 S5
N.Q1
N.Q2

RLU222 ADC002 LU2 HQ


S01

A09 Extract air (room) temperature control with hot water heating T

B2
coil and chilled water cooling coil. N.X1

Options:
Room temperature cascade control T T T R5
Outside temperature-dependent functions B9 B1
N.X4

M3 M4
Remote setpoint readjuster N.X3
N.Q1 N.Q2
N.X2

M M
Comfort / Protection Mode changeover (time switch) Y3 Y4 S5
N.Y1 N.Y2 N.D1

19 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 ADC010 LU2 HQ

S01
B5
A10 Supply air temperature control with hot water heating coil and T
N.X2
Cascade
chilled water cooling coil.
Options:
Room temperature cascade control T T T R5
Outside temperature-dependent functions B9 B1
N.X4

M3 M4 N.X1
Remote setpoint readjuster N.X3
N.Q 1 N.Q2
M M
Comfort / Protection Mode changeover (time switch) Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU222 ADC004 LU2 HQ

S01
A11 Extract air (room) temperature control with electric air heater T

B2
battery and chilled water cooling coil. N.X1

Options:
Minimum and maximum limitation of the supply air tempera- T R5
T T
ture B9 E1 B1
N.X4

N.Q1 N.X2
Outside temperature-dependent functions N.X3
N.Q2
N.Y1
M
Remote setpoint readjuster Y4 S5
2-stage electric air heater battery N.Y2 N.D1

Comfort / Protection Mode changeover (time switch)


RLU222 ADC012 LU2 HQ

S01
B5
A12 Supply air temperature control with electric air heater battery T
N.X2
Cascade
and chilled water cooling coil.
Options:
Room temperature cascade control T R5
T T
Outside temperature-dependent functions B9 E1 B1
N.X4

N.Q1 N.X1
Remote setpoint readjuster N.X3
N.Q2
N.Y1
M
2-stage electric air heater battery Y4 S5
Comfort / Protection Mode changeover (time switch) N.Y2 N.D1

RLU222 ADC003 LU2 HQ


A13 Extract air (room) temperature control with hot water heating
coil and DX cooler battery.
Options:
Minimum and maximum limitation of the supply air tempera-
ture Y7
Outside temperature-dependent functions
M
Remote setpoint readjuster Y3 M7 S5
2-stage DX cooler battery N.Q1
N.Q2

Comfort / Protection Mode changeover (time switch)


RLU222 ADC011 LU2 HQ
A14 Supply air temperature control with hot water heating coil and
DX cooler battery.
Options:
Room temperature cascade control
Outside temperature-dependent functions Y7
Remote setpoint readjuster
2-stage DX cooler battery M
M7
Y3 S5
Comfort / Protection Mode changeover (time switch) N.Q1
N.Q 2

RLU222 ADC006 LU2 HQ N.Q1


S01

A15 Extract air (room) temperature control with hot water heating 1
T

coil, frost protection, chilled water cooling coil and fan release. B2
N.X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T
ture B9
T
B1
Outside temperature-dependent functions N.X4 M3
N.Q2
N.X2

Comfort / Protection Mode changeover (time switch) M M

Y3 Y4 S5
N.Y1 N.Y2 N.D1

RLU222 ADC014 LU2 HQ N.Q1


S01

B5
A16 Supply air temperature control with hot water heating coil, frost 1
T
N.X2

protection, chilled water cooling coil and fan release. Cascade

Options: F3
N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions B9
T
B1
Comfort / Protection Mode changeover (time switch) N.X4 M3
N.Q2
N.X1

M M

Y3 Y4 S5
N.Y1 N.Y2 N.D1

20 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 ADC007 LU2 HQ N.Q1

S01
A17 Extract air (room) temperature control with hot water heating 1
T

coil, frost protection, DX cooler battery and fan release. B2


N.X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T
ture B9
T
B1
Y7
Outside temperature-dependent functions N.X4 N.Y2 N. X2

Comfort / Protection Mode changeover (time switch) M

Y3 M7 S5
N.Y1 N.Q2 N.D1

RLU222 ADC016 LU2 HQ N.Q1

S01
B5
A18 Supply air temperature control with hot water heating coil, frost 1
T
N.X2

protection, DX cooler battery and fan release. Cascade

Options: F3
N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions B9
T
B1
Y7
Comfort / Protection Mode changeover (time switch) N.X4 N.Y2 N.X1

Y3 M7 S5
N.Y1 N.Q2 N.D1

RLU222 AEAG01 LU2 HQ

S01
A19 Extract air (room) temperature control with closed-circuit heat T
M6
recovery system and hot water heating coil. N.Q2
B2
N.X1
Options: M
Y6
Minimum and maximum limitation of the supply air tempera- N.Y2
R5
ture T T T
N.X4
B1
Outside temperature-dependent functions B9
N.X3
M3 N.X2
N.Q1
Remote setpoint readjuster M

Comfort / Protection Mode changeover (time switch) Y3


N.Y1
S5
N.D1

RLU222 AEAG02 LU2 HQ

S01
B5
A20 Supply air temperature control with closed-circuit heat recovery T
N.X2
M6 Cascade
system and hot water heating coil. N.Q2

Options: M
Y6
Room temperature cascade control N.Y2
R5
Outside temperature-dependent functions T T T
N.X4
B1
Remote setpoint readjuster B9
N.X3
M3 N.X1
N. Q1
Comfort / Protection Mode changeover (time switch) M
Y3 S5
N.Y1 N.D1

RLU222 AEAD01 LU2 HQ N.Q1

S01
A21 Extract air (room) temperature control with mixed air dampers, 1
T
M
Y2
hot water heating coil, frost protection and fan release. M
B2
N.X1
Options: Y1 Y6 F3
N.Y2 M N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T
ture B9
T
B1
Outside temperature-dependent functions N.X4 M3
N.Q 2
N.X2

Comfort / Protection Mode changeover (time switch) M

Y3 S5
N.Y1 N.D1

RLU222 AEAD02 LU2 HQ N.Q1


S01

B5
A22 Supply air temperature control with mixed air dampers, hot 1
T
N.X2
M
Y2
water heating coil, frost protection and fan release. Cascade
M
Options: Y1 Y6 F3
N.Y2 M N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions T
B1
B9
Comfort / Protection Mode changeover (time switch) N.X4 M3
N.Q 2
N.X1

Y3 S5
N.Y1 N.D1

RLU222 ADB009 LU2 HQ


S01

A23 Extract air (room) temperature control with chilled water cooling T
B2
coil and 2 cooling towers. N.X1
Options:
Minimum and maximum limitation of the supply air tempera- T N.Q1 N.Q2 T T R5
N.X4
ture B9 f1
f2
G1 f1
f2
G2 B1
N.Y1 N.Y2
Outside temperature-dependent functions N.X3 N.X2

Remote setpoint readjuster S5


Comfort / Protection Mode changeover (time switch) N.D1

21 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 AECD01 LU2 HQ

S01
A24 Extract air (room) temperature control with mixed air dampers, M
T
Y2
hot water heating coil and DX cooler battery. M
B2
N.X1
Y1
Options: N.Y2 M
Y6

Minimum and maximum limitation of the supply air tempera- T T T R5


N.X4
ture B9 B1
M3 M7
Outside temperature-dependent functions N.X3
N.Q1 N.Q2
N.X2

M
Remote setpoint readjuster Y3 S5
Comfort / Protection Mode changeover (time switch) N.Y1 N.D1

RLU222 AECD04 LU2 HQ

S01
B5
A25 Supply air temperature control with mixed air dampers, hot M
T
N.X2
Y2
water heating coil and DX cooler battery. M
Cascade

Options: Y1
N.Y2 M
Y6

Room temperature cascade control T T T R5


N.X4
Outside temperature-dependent functions B9 B1
M3 M7
Remote setpoint readjuster N.X3
N.Q 1 N.Q 2
N.X1

M
Comfort / Protection Mode changeover (time switch) Y3 S5
N.Y1 N.D1

RLU222 AECD02 LU2 HQ

S01
A26 Extract air (room) temperature control with mixed air dampers, M
T
Y2
hot water heating coil and DX cooler battery. M
B2
N.X1
Options: Y1
N.Y2 M
Y6

Minimum and maximum limitation of the supply air tempera- T T T R5


N.X4
ture B9 B1
M7
Outside temperature-dependent functions N.X3
N.Q1
N.Q2
N.X2

M
Remote setpoint readjuster Y3 S5
2-stage DX cooler battery N.Y1 N.D1

Comfort / Protection Mode changeover (time switch)


RLU222 AECD05 LU2 HQ

S01
B5
A27 Supply air temperature control with mixed air dampers, hot M
T
N.X2
Y2
water heating coil and dx cooler battery. M
Cascade

Options: Y1
N.Y2 M
Y6

Room temperature cascade control T T T R5


N.X4
Outside temperature-dependent functions B9 B1
M7 N.X1
Remote setpoint readjuster N.X3
N.Q1
N.Q2
M
2-stage DX cooler battery Y3 S5
Comfort / Protection Mode changeover (time switch) N.Y1 N.D1

RLU222 AECD03 LU2 HQ

S01
A28 Extract air (room) temperature control with mixed air dampers, M
T
Y2
B2
electric air heater battery and chilled water cooling coil. M N.X1
Options: Y1
N.Y1 M
Y6

Minimum and maximum limitation of the supply air tempera- T T T R5


N.X4
ture B9 E1 B1
N.Q1
Outside temperature-dependent functions N.X3
N.Q 2
N.X2

M
Remote setpoint readjuster Y4 S5
2-stage electric air heater battery N.Y2 N.D1

Comfort / Protection Mode changeover (time switch)


RLU222 AECD06 LU2 HQ
S01

B5
A29 Supply air temperature control with mixed air dampers, electric M
T
N.X2
Y2 Cascade
air heater battery and chilled water cooling coil. M
Y1
Options: N.Y1 M
Y6

Room temperature cascade control T T T R5


Outside temperature-dependent functions B9 E1 B1
N.X4

N.Q1
Remote setpoint readjuster N.X3
N.Q2
N.X1

M
2-stage electric air heater battery Y4 S5
Comfort / Protection Mode changeover (time switch) N.Y2 N.D1

RLU222 ADKA02 LU2 HQ


S01

U01 Extract air (room) humidity control (r.h.) with spray humidifier.
Options: B12
N.X1

Maximum limitation of the air humidity [%]

Remote setpoint adjuster R5


T
2-stage spray humidifier Y8 M
B11
N.X3

N.X2
Comfort / Protection Mode changeover (time switch) N.Y1 [%]
M8
N.Q 1 S5
N.Q2 N.D1

22 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 PB0002 LU2 HQ B23 p B22 p

U02 Differential pressure control of water with speed-controlled N.X2 N.X1


[bar]
N.Q1 N.Q2
pumps.

S01
Options: f1
f2
f1
f2

Minimum and maximum pressure limit controller G1


N.Y1
G2
N.Y2
Outside temperature-dependent functions T R5
N.X4
Remote setpoint adjuster
Comfort / Protection Mode changeover (time switch) T

B9 S5
N.X3 N.D1

RLU222 AZL002 LU2 HQ B23 B22


U03 Differential pressure control of air with speed-controlled fans. [bar]
N.Q1 N.Q2
Options:
Minimum and maximum pressure limit controller
Outside temperature-dependent functions
Remote setpoint adjuster
Comfort / Protection Mode changeover (time switch)
S5

RLU222 ADI003 LU2 HQ

S01
B5
U04 Extract air (room) humidity control (r.h.) with DX cooler battery. T
N.X3
B12
Options: N. X1

Additional maximum selection from internal and external [%]

signal R5
T
Room temperature-dependent shifting of humidity setpoint N.X4

Y7
Remote setpoint adjuster N.Y1

2-stage DX cooler battery M7 S5


N.D1 N .X2
Comfort / Protection Mode changeover (time switch) N.Q1
N.Q2

RLU222 ADI005 LU2 HQ

S01
B5
U05 Extract air (room) humidity control (a.h.) with DX cooler battery. T T
T
N.X3

Options: B18
Additional maximum selection from internal and external N.X1
[g/kg]

signal R5
T
Room temperature-dependent shifting of humidity setpoint Y7
N .X4

Remote setpoint adjuster N.Y1

2-stage DX cooler battery M7 S5


Comfort / Protection Mode changeover (time switch) N.Q1
N.Q2
N.D1 N.X2

RLU222 AAZD02 LU2 HQ

S01
B4
U06 Indoor air quality control with mixed air dampers and fan con- M
AQ
N.X1
Y2 [ppm]
trol. M
Y1
Options: N.Y1 M
Y6

Additional maximum selection from internal and external T T R5


signal B9 M1
N.Q1
N.X4

N.X3
Outside temperature-dependent functions N.Q2

Remote setpoint adjuster S5


2-speed fan N.D1 N .X2

Comfort / Protection Mode changeover (time switch)


RLU222 ADZA01 LU2 HQ
S01

U07 Extract air (room) humidity control (r.h.) with spray humidifier
B12
and DX cooler battery. N.X 1
Options: [%]

Maximum limitation of the supply air humidity T R5


Additional maximum selection from internal and external Y8 M Y7 B11
N .X4

N.X2
signal N.Y1 N.Y2
[%]
M8
Remote setpoint adjuster N.Q1
M7 S5
N.D1 N.X3
Comfort / Protection Mode changeover (time switch) N.Q2

23 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 CZC001 LU2 HQ
U08 Temperature control of chilled ceilings.
Options:
Setpoint compensation depending on humidity
M4
Deviation alarm B16
M
Comfort / Protection Mode changeover (time switch)
Y4

S5
N.Q1

RLU222 HZC001 LU2 HQ


U09 Temperature control of mixing heating circuit.
Options:
Minimum limitation of the return temperature
Y3 S5
Outside temperature-dependent functions N.Q1
Remote setpoint adjuster N.Q2 M
Comfort / Protection Mode changeover (time switch)

RLU222 ZZZ001 LU2 HQ DC 0 ... 10 V

U10 3-position actuator

A01
G X1 M G1 D1 M Q11 Q23
RLU222
G0 N1 Q12 Q14 N2 Q24
3P

RLU222 ZZZ002 LU2 HQ DC 0 ... 10 V

U11 Variable 2-step switch

A01
G X1 M G1 D1 M Q11 Q23
RLU222
G0 N1 Q12 Q14 N2 Q24

2Q VAR.

RLU222 ADC019 LU2 HQ


S01
U12 Universal control (substitute for RKN2 / RKN22) T

Application: B2
N.X1
Temperature control (on/off pump control)
Options:
T R5
Remote setpoint adjuster (absolute) N.X2
M3 M4
Comfort / Protection Mode changeover (time switch) N.Q1 N.Q2

S5
N.D1

RLU222 ADC020 LU2 HQ


S01

U13 Universal control (substitute for RKN8 / RKN88) T

B2
Application: N. X1

Temperature control (modulating valve control)


Options:
T R5
Remote setpoint adjuster (absolute) N.X2

Comfort / Protection Mode changeover (time switch)


Y3 M Y4 M
N.Y1 N.Y2 S5
N.D1

24 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU222 HZC002 LU2 HQ
U14 Boiler temperature control (substitute for RCA12.2)
Application:
Minimum limitation of the boiler return temperature
Options: Y3 S5
N.Q1
Remote setpoint adjuster (absolute) N.Q2 M
Comfort / Protection Mode changeover (time switch)

RLU222 SA0001 LU2 HQ B6


N.X1
T
U15 Differential temperature control (substitute for RSA24)
Application:
Solar heat storage plant
Options:
Maximum limitation of the boiler temperature
Minimum limitation of the charging temperature
M3 T B3
N.Q1 N.X2

S01
RLU222 ABL001 LU2 HQ
U16 Supply air differential pressure control
Options:
Switching via external time switch F1
Differential pressure monitor p

p
G1 S5
N.Y1 B7 N.D1
N.X1

RLU222 ADZ001 LU2 HQ F1


p

U17 Supply air differential pressure control, Extract air volume


control
Options: G2
N.Y1
V
B2
Switching via external time switch N.X1

F1
Setpoint shift through volumetric supply air flow p

Differential pressure monitor


S5
N.D1
V p
G1
N.Y2 B1 B7
N.X2 N.X3

RLU222 ADL001 LU2 HQ F1


p

U18 Supply air and room differential pressure control


Options:
Switching via external time switch G2
N.Y1
p
Differential pressure monitor B81
F1 N.X2

S5
N.D1
G1 p
N.Y2 B7
N.X1

RLU222 ADZA02 LU2 HQ


U19 Extract air (room) humidity control
Options:
B12
Maximum limitation of supply air humidity N.X1

Comfort / Protection Mode changeover (time switch)

N.X3

Y8 M
S5
N.Y2 B11
N.X2 N.D1
Y4 M M8
N.Y1 N.Q1

25 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU232 AEAF01 LU3 HQ N.Q1

S01
A01 Extract air (room) temperature control with heat recovery, hot T
1
T

water heating coil, frost protection and fan release. B10 B2


N.X4 N.X1
Options: F3
N.X3
Minimum and maximum limitation of the supply air tempera- 1
T T
ture B9
T
B1
Outside temperature-dependent functions N.X5 Y11
N.Y2
M3
N.Q3
N.X2
S5
Anti-icing protection for heat recovery M
N.D1
Y3 S6
Comfort / Economy changeover N.Y1 N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 AEAF02 LU3 HQ N.Q1

S01
1 B5
A02 Supply air temperature control with heat recovery, hot water T
T
N.X2

heating coil, frost protection and fan release B10 Cascade


N.X4
Options: F3
N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions B9
T
B1
Anti-icing protection for heat recovery N.X5 Y11
N.Y2
M3
N.Q3
N.X1
S5
Comfort / Economy changeover M
N.D1
Y3 S6
Comfort / Protection Mode changeover (time switch) N.Y1 N.D2

RLU232 ADC015 LU3 HQ N.Q 1

S01
B5
A03 Supply air temperature control with hot water heating coil, frost 1
T
N.X2

protection, chilled water cooling coil and fan release Cascade

Options: F3
N.X3
Room temperature cascade control 1
T T
Outside temperature-dependent functions B9
T
B1
Comfort / Economy changeover N.X4 M3
N.Q 3
N.X1
S5
Comfort / Protection Mode changeover (time switch) M M
N.D1
Y3 Y4 S6
N.Y1 N.Y2 N.D2

RLU232 AECG01 LU3 HQ

S01
A04 Extract air (room) temperature control with closed-circuit heat T
T M6
recovery system, hot water heating coil and chilled water cool- B21 N.Q3
B2
N. X1
N.X4
ing coil. M
Y6
Options: N.Y2
R5
Minimum and maximum limitation of the supply air tempera- T T T
N.X5
B9 B1
ture N.X3
M3 N.X2
S5
N.Q1
Outside temperature-dependent functions M M
N.D1
S6
Anti-icing protection for heat recovery N.Y1
Y3 Y4
N.Y3
N.D2

Remote setpoint readjuster


Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU232 AECG02 LU3 HQ
S01
B5
A05 Supply air temperature control with closed-circuit heat recovery T
N.X2
T M6
system, hot water heating coil and chilled water cooling coil. B21 N.Q3
Cascade

Options: N.X4 M
Y6
Room temperature cascade control N.Y2
R5
Outside temperature-dependent functions T T T
N.X5
B9 B1
Anti-icing protection for heat recovery N.X3
M3 N.X1 S5
N.Q1
Remote setpoint readjuster M M
N.D1
S6
Comfort / Economy changeover N.Y1
Y3 Y4
N.Y3
N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 AECF01 LU3 HQ
S01

A06 Extract air (room) temperature control with heat recovery, hot T T
B10 B2
water heating coil and chilled water cooling coil. N.X4 N.X1

Options:
Minimum and maximum limitation of the supply air tempera- T T
R5
ture B9 B1
T
N.X5
N.X3 Y11 M3 M4
Outside temperature-dependent functions N.Y2 N.Q1 N.Q3
N.X2
S5
M M
Anti-icing protection for heat recovery Y3 Y4
N.D1
S6
Remote setpoint readjuster N.Y1 N.Y3 N.D2

Comfort / Economy changeover


Comfort / Protection Mode changeover (time switch)

26 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU232 AECF03 LU3 HQ

S01
B5
A07 Supply air temperature control with heat recovery, hot water T T
N.X2
B10
heating coil and chilled water cooling coil. N.X4
Cascade

Options:
Room temperature cascade control T T
R5
Outside temperature-dependent functions B9 B1
T
N.X5
N.X3 Y11 M3 M4 N.X1
Anti-icing protection for heat recovery N.Y2 N.Q1 N.Q3
S5
M M
Remote setpoint readjuster Y3 Y4
N.D1
S6
Comfort / Economy changeover N.Y1 N.Y3 N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 AECF02 LU3 HQ N.Q1

S01
A08 Extract air (room) temperature control with heat recovery, hot T
1
T

water heating coil, frost protection, chilled water cooling coil B10 B2
N.X5 N.X1
and fan release. F3
N.X3
Options: 1
T T
Minimum and maximum limitation of the supply air tempera- B9
T
B1
ture N.X4 Y11
N.Y2
M3
N. Q3
N.X2
S5
Outside temperature-dependent functions M M
N.D1
Y3 Y4 S6
Anti-icing protection for heat recovery N.Y1 N. Y3 N.D2

Comfort / Economy changeover


Comfort / Protection Mode changeover (time switch)
RLU232 AECF04 LU3 HQ N.Q1

S01
B5
A09 Supply air temperature control with heat recovery, hot water T
1
T
N.X2

heating coil, frost protection, chilled water cooling coil and fan B10 Cascade
N.X5
release. F3
N.X3
Options: 1
T T
Room temperature cascade control B9
T
B1
M3
Outside temperature-dependent functions N.X4 Y11
N.Y2 N.Q 3
N.X1
S5
Anti-icing protection for heat recovery M M
N.D1
Y3 Y4 S6
Comfort / Economy changeover N.Y1 N.Y3 N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 ADC009 LU3 HQ

1S01
A10 Extract air (room) temperature control with hot water heating T
B2
coil and 2 chilled water cooling coils. N.X1

Options:
Minimum and maximum limitation of the supply air tempera- T T
R5
ture B9 M3 M4 B1
T
N.X4
N.X3
Outside temperature-dependent functions N. Q1 N.Q 3 N.X2
S5
M M M
Remote setpoint readjuster Y3 Y4 Y15
N.D1
S6
Comfort / Economy changeover N.Y1 N.Y2 N.Y3 N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 ADC018 LU3 HQ

S01
B5
A11 Supply air temperature control with hot water heating coil and 2 T
N.X2
Cascade
chilled water cooling coils.
Options:
Room temperature cascade control T T
R5
Outside temperature-dependent functions B9 M3 M4 B1
T
N.X4
N.X1
Remote setpoint readjuster N.X3 N.Q1 N.Q3
S5
M M M
Comfort / Economy changeover Y3 Y4 Y15
N.D1
S6
Comfort / Protection Mode changeover (time switch) N.Y1 N.Y2 N. Y3 N.D2

RLU232 AEDK01 LU3 HQ


S01

A12 Supply air temperature control and room humidity control (r.h.) T T

B15 B5
with heat recovery, hot water heating coil and spray humidifier. N.X3 N.X2

Options: Cascade

Room temperature cascade control T T


Maximum limitation of the supply air humidity B9 Y8 M
B1 B11
N.X5 Y11 M3 N.X1 N.X4
Outside temperature-dependent functions N.Y2 N. Q1
N.Y3
S5
M M8
Comfort / Economy changeover Y3 N.Q3
N.D1
S6
Comfort / Protection Mode changeover (time switch) N.Y1 N.D2

27 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU232 ADE001 LU3 HQ N.Q1

S01
1
A13 Extract air (room) temperature control and dewpoint control T

with hot water preheating coil, frost protection, chilled water B2


N.X1
cooling coil, hot water reheating coil and fan release. F3
N.X4
Options: 1
T T T
Minimum and maximum limitation of the supply air tempera- B9
T
B27 B1
ture N.X5 N.X3 N.X2
S5
Outside temperature-dependent functions M M M
N.D1
Y3 Y4 Y10 S6
Comfort / Economy changeover N.Y2 N.Y3 N.Y1 N.D2

Comfort / Protection Mode changeover (time switch)


RLU232 ADFA01 LU3 HQ N.Q1

S01
1
A14 Supply air temperature and extract air (room) humidity control T

(r.h.) with hot water heating coil, frost protection, spray humidi- B2
N.X1
fier, chilled water cooling coil and fan release. F3
N.X4
Options: 1
T T T
Maximum limitation of the supply air humidity B9
T
B27 B1
Outside temperature-dependent functions N.X5 N.X3 N.X2
S5
Comfort / Economy changeover M M M
N.D1
Y3 Y4 Y10 S6
Comfort / Protection Mode changeover (time switch) N.Y2 N.Y3 N.Y1 N.D2

RLU232 ADFA02 LU3 HQ N.Q1

S01
1
A15 Extract air (room) temperature control and dew point control T

with hot water preheating coil, frost protection, spray humidifi- B2


N.X1
er, chilled water cooling coil, hot water reheating coil and fan F3
N.X5
release. 1
T T
Options: T
B27 B1
Minimum and maximum limitation of the supply air tempera- N.X4 N.X2
S5
ture M M M
N . X 3 ( 0. . .10 V ) N.D1
Y3 Y4 Y10 S6
Additional maximum selection from internal and external N.Y3 N.Y2 N.Y1 N.D2

signal
Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU232 AEFH01 LU3 HQ N.Q1

S01
A16 Supply air temperature and room humidity control (r.h.) with M
1
T T
Y2
mixed air dampers, hot water heating coil, frost protection, M
B15 B5
N.X4 N.X2
chilled water cooling coil, spray humidifier and fan release. Y1
N.Y2 M
Y6 F3 Cascade
N.X3
Options: 1
T T
Room temperature cascade control B9
T
B1
Outside temperature-dependent functions N.X5 N.X1
S5
Comfort / Economy changeover M M
N.Q3
M8 N.D1
Y3 Y4 S6
Comfort / Protection Mode changeover (time switch) N.Y1 N.Y3 N.D2

RLU232 AECD01 LU3 HQ


A17 Extract air (room) temperature control and mixed air tempera- M
Y2
ture control Y6 M

Options:
Minimum and maximum limitation of supply air temperature
Outside temperature-dependent functions Y1
M
B31 M
F4
M
S5
Comfort / Economy changeover Y3
M1
Y4
S6
N.Q1

Comfort / Protection Mode changeover (time switch)


RLU232 ABA001 LU3 HQ
U01 2 independent supply air temperature control systems with hot T T
S01

M3.1 B1.1 M3.2 B1.2


water heating coils. N.Q1 N.X1 N.Q3 N.X3
T R5.1 T R5.2
Options: T
Y3.1
N.X2
Y3.2
N.X4

B9 S5
2 independent remote setpoint adjusters N.X5
N.Y1 N.Y2
N.D1

Outside temperature-dependent functions


Comfort / Protection Mode changeover (time switch)
RLU232 ADL001 LU3 HQ
S01

U02 Supply and extract air volume control with fan control. p
f1
G2
Options: N.Q2
f2 B8
N.X3
N.Y2
2 independent remote setpoint adjusters
Outside temperature-dependent functions T p
Comfort / Protection Mode changeover (time switch) B9 G1
f1
f2 B7
N.X5 N.Q1 N.X1
N.Y1

T
R5.1 T
R5.2 S5
N.X4 N.X2 N.D1

28 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU232 ZZZ003 LU3 HQ DC 0 ... 10 V

U03 Linear 2-step switch

A01
G X1 M G1 D1 M Q11 Q33
RLU232
G0 Q12 Q14 Q34

2Q LIN.

RLU232 ZZZ004 LU3 HQ DC 0 ... 10 V

U04 Binary 2-step switch

A01
G X1 M G1 D1 M Q11 Q33
RLU232
G0 Q12 Q14 Q34

Q1
2Q BIN.
Q2
Q1

RLU232 ZZZ005 LU3 HQ DC 0 ... 10 V

U05 Variable 2-step switch

A01
G X1 M G1 D1 M Q11 Q33
RLU232
G0 Q12 Q14 Q34

2Q VAR.

RLU236 ADA007 LU3 HQ

S01
A01 Extract air (room) temperature control with electric air heater T
B2
battery. N.X1

Options:
Min. and max. limitation of the supply air temperature T T T R5
Outside temperature-dependent functions B9 E1 N.Q4 B1
N.X4

N.Q1 N.Q5
Remote setpoint readjuster N.X3
N.Q2 N.Q6
N.X2
S5
N.Q3 N.Y1
6-stage electric air heater battery N.D1
S6
Comfort / Economy changeover N.D2

Comfort / Protection Mode changeover (time switch)


RLU236 ADA013 LU3 HQ
A02 Supply air temperature control with electric air heater battery.
Options:
Room temperature cascade control
Outside temperature-dependent functions
Remote setpoint readjuster E1 N.Q4
N.Q1 N.Q5
6-stage electric air heater battery N.Q2 N.Q6
N.Q3 N.Y1 S5
Comfort / Economy changeover S6
Comfort / Protection Mode changeover (time switch)
RLU236 ADB004 LU3 HQ
A03 Extract air (room) temperature control with DX cooler battery.
Options:
Min. and max. limitation of the supply air temperature
Outside temperature-dependent functions
Remote setpoint readjuster Y7
6-stage dx cooler battery S5
Comfort / Economy changeover N.Q4
N.Q5
M7
S6
N.Q1
N.Q6
Comfort / Protection Mode changeover (time switch) N.Q2
N.Q3

RLU236 ADB008 LU3 HQ


A04 Supply air temperature control with DX cooler battery.
Options:
Room temperature cascade control
Outside temperature-dependent functions
Remote setpoint readjuster Y7
6-stage DX cooler battery S5
Comfort / Economy changeover N.Q4
N.Q5
M7
S6
N.Q1
Comfort / Protection Mode changeover (time switch) N.Q6 N.Q2
N.Q3

29 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU236 ADC005 LU3 HQ
A05 Extract air (room) temperature control with electric air heater
battery and DX cooler battery.
Options:
Minimum and maximum limitation of the supply air tempera-
ture E1 Y7
Outside temperature-dependent functions N.Q1
N.Q2 S5
N.Q3
Remote setpoint readjuster N.Q4
N. Y1 M7 S6
4-stage electric air heater battery N.Q5
N.Q6

2-stage DX cooler battery


Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU236 ADC013 LU3 HQ
A06 Supply air temperature control with electric air heater battery
and DX cooler battery.
Options:
Room temperature cascade control
Outside temperature-dependent functions E1 Y7
N.Q1
Remote setpoint readjuster N.Q2
S5
N.Q3
4-stage electric air heater battery N.Q4
N.Y1 M7 S6
2-stage DX cooler battery N.Q5
N.Q6

Comfort / Economy changeover


Comfort / Protection Mode changeover (time switch)
RLU236 ADC008 LU3 HQ N.Q1

A07 Extract air (room) temperature control with hot water air heat-
ing coil, frost protection, DX cooler battery and fan release.
Options: F3

Minimum and maximum limitation of the supply air tempera-


ture
Y7
Outside temperature-dependent functions M3
N.Q2
S5
Remote setpoint readjuster M

Y3 M7 S6
4-stage DX cooler battery N.Q3
N.Q4
Comfort / Economy changeover N.Q5
N.Q6

Comfort / Protection Mode changeover (time switch)


RLU236 ADC017 LU3 HQ N.Q1

A08 Supply air temperature control with hot water heating coil, frost
protection, DX cooler battery and fan release.
Options: F3

Room temperature cascade control


Outside temperature-dependent functions
Y7
Remote setpoint readjuster M3
N.Q2
S5
4-stage DX cooler battery M

Y3 M7 S6
Comfort / Economy changeover N.Q3
N.Q4
Comfort / Protection Mode changeover (time switch) N.Q5
N.Q6

RLU236 AEDL01 LU3 HQ N.Q1


S01

B5
A09 Supply air temperature and supply air humidity control (r.h.) 1
T T
N.X2

with closed-circuit heat recovery system, hot water heating coil, M6


N.Q3
B15
N.X4
Cascade

frost protection, spray humidifier and fan release. M


F3
Options: Y6
N.Y2 N.X3
1
Room temperature cascade control T
T
T

Outside temperature-dependent functions B9


M3
Y8 M B1
N.X5 N.Y3 N.X1 S5
Comfort / Economy changeover N.Q2
N.D1
M M8 S6
Comfort / Protection Mode changeover (time switch) Y3 N.Q4 N.D2
N.Y1

RLU236 AEFL01 LU3 HQ N.Q1


S01

B5
A10 Supply air temperature and supply air humidity control (r.h.) 1
T T
N.X2
B15
with closed-circuit heat recovery system, DX cooler battery, hot M6
N.Q 3 N.X4
Cascade

water heating coil, frost protection, spray humidifier and fan M Y6


N.Y2
F3
release. N.X3
1
Options: T
T
T

Room temperature cascade control B9 M Y8 B1


N.X5 M7 M3 N.Y3 N.X1 S5
Outside temperature-dependent functions N.Q 4
M
N.Q2
M8
N.D1
N.Q 5 S6
2-stage DX cooler battery Y3 N.Q 6
N.D2
N.Y1
Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)

30 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU236 AECD02 LU3 HQ
A11 Extract air (room) temperature control and mixed air tempera- M
Y2
ture control Y6 M

Options: S5

Minimum and maximum limitation of supply air temperature S6

Outside temperature-dependent functions Y1


M

B31 E2 E1

Remote setpoint readjuster


N.Q3 N.Q1
N.Q4 N.Q2

2-stage electric air heater battery


2-stage direct expansion cooler battery
Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU236 AEZD01 LU3 HQ
A12 Extract air (room) temperature and mixed air temperature M
Y2
control and supply air differential pressure control Y6 M
F1
Options:
Minimum and maximum limitation of supply air temperature
Outside temperature-dependent functions M
Y1 B31 E2 E1
N.Q3 N.Q1

2-stage electric air heater battery N.Q4 N.Q2 S5

S6
2-stage direct expansion cooler battery
Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU236 AEGD01 LU3 HQ
A13 Extract air (room) temperature and mixed air temperature M
Y2 B12
control and humidity control Y6 M

Options:
Minimum and maximum limitation of supply air temperature
Outside temperature-dependent functions M
Y1 B31 E2 E1
N.Q3 N.Q1 S5
2-stage electric air heater battery N.Q4 N.Q2
S6

2-stage direct expansion cooler battery


Comfort / Economy changeover
Comfort / Protection Mode changeover (time switch)
RLU236 AECD03 LU3 HQ
A14 Supply air temperature control M
Y2
Options: M

Room temperature cascade control Y1


M
Y6

Outside temperature-dependent functions


Remote setpoint readjuster E1
Y7
4-stage electric air heater battery N.Q1
N.Q2 S5
N.Q3
2-stage direct expansion cooler battery N.Q4
S6
M7
Comfort / Economy changeover N.Q5
N.Q 6
Comfort / Protection Mode changeover (time switch)
RLU236 ADKA03 LU3 HQ

S01
U01 Extract air (room) humidity control (r.h.) with spray humidifier.
B12
Options: N.X1

Maximum limitation of the supply air humidity [%]

Outside temperature-dependent functions T T R5


Remote setpoint adjuster B9 Y8 M
B11
N.X4
N.Q4 N.X2
6-stage spray humidifier N.X3 N.Q5 N.Q1
N.Q6 N.Q2
[ %]
S5
Comfort / Economy changeover N.Y1 N.Q3 N.D1
S6
Comfort / Protection Mode changeover (time switch) N.D2

RLU236 PB0003 LU3 HQ B23


p
B22
p
N.X2 N.X1
U02 Differential pressure control of water with load-dependent [bar]

pump control.
S01

Options: N.Q1 N.Q2 N.Q3 N.Q 4 N.Q5 N.Q6

Minimum and maximum pressure limit controller T R5


N.X4
Outside temperature-dependent functions T
Remote setpoint adjuster B9 S5
N.D1
Comfort / Economy changeover N.X3
S6
Comfort / Protection Mode changeover (time switch) N.D2

31 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU236 AZL003 LU3 HQ B25 B24

U03 Differential pressure control of air with load-dependent fan


control.
Options: N.Q1 N.Q2 N.Q3 N.Q4 N.Q5 N.Q6
Minimum and maximum pressure limit controller
Outside temperature-dependent functions
Remote setpoint adjuster S5
Comfort / Economy changeover S6
Comfort / Protection Mode changeover (time switch)
RLU236 ADI004 LU3 HQ

S01
B5
U04 Extract air (room) humidity control (r.h.) with DX cooler battery. T
N.X3

Options: B12
N.X1
Additional maximum selection from internal and external [ %]

signal R5
T
Room temperature-dependent shifting of humidity setpoint Y7
N.X4

Remote setpoint adjuster N.Y1


N .X 2 S5
6-stage DX cooler battery N.Q2 M7
N.D1
S6
N.Q3 N.Q1
Comfort / Economy changeover N.Q4
N.Q5
N.D2

Comfort / Protection Mode changeover (time switch) N.Q6

RLU236 ADI006 LU3 HQ

S01
B5
U05 Extract air (room) humidity control (a.h.) with DX cooler battery. T T
T
N.X3

Options: B18
Additional maximum selection from internal and external N.X1
[g/kg]

signal R5
T
Room temperature-dependent shifting of humidity setpoint Y7
N.X4

Remote setpoint adjuster N.Y1


N.X2 S5
6-stage DX cooler battery N.Q2 M7 N.D1
S6
N.Q3 N.Q 1
Comfort / Economy changeover N.Q4
N.Q5
N.D2

Comfort / Protection Mode changeover (time switch) N.Q6

RLU236 AAZD03 LU3 HQ

S01
B4
U06 Indoor air quality control with mixed air dampers and fan con- M
AQ
N.X1
Y2 [ppm]
trol. M
Y1
Options: N.Y1 M
Y6

Additional maximum selection from internal and external T T R5


N.X4
signal B9
N.Q2 M1
N.Q3 N.Q1
N.X3
Outside temperature-dependent functions N.Q4
N.Q5
N .X 2 S5
N.Q6
Remote setpoint adjuster N.D1
S6
6-speed fan N.D2

Comfort / Economy changeover


Comfort / Protection Mode changeover (time switch)
RLU236 ADZA02 LU3 HQ

S01
U07 Extract air (room) humidity control (r.h.) with spray humidifier
B12
and DX cooler battery. N.X1
Options: [%]

Maximum limitation of supply air humidity R5


T
Additional maximum selection from internal and external Y8 M Y7 B11
N.X4

N.X2
signal N.Y 1 N.Y2
[%]
S5
M8
Remote setpoint adjuster N.Q1 M7
N.D1
S6
N.Q2
2-stage spray humidifier N.Q3
N.Q4
N.D2

N.Q5
4-stage DX cooler battery N.Q6 N.X3

Comfort / Economy changeover


Comfort / Protection Mode changeover (time switch)
RLU236 ZZZ006 LU3 HQ DC 0 ... 10 V

U08 Linear 3-step switch


A01

G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63


RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

3Q LIN.

32 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU236 ZZZ007 LU3 HQ DC 0 ... 10 V

U09 Linear 4-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

4Q LIN.

RLU236 ZZZ008 LU3 HQ DC 0 ... 10 V

U10 Linear 5-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

5Q LIN.

RLU236 ZZZ009 LU3 HQ DC 0 ... 10 V

U11 Linear 6-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

6Q LIN.

RLU236 ZZZ010 LU3 HQ DC 0 ... 10 V

U12 Variable 3-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

3Q VAR.

RLU236 ZZZ011 LU3 HQ DC 0 ... 10 V

U13 Variable 4-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

4Q VAR.

RLU236 ZZZ012 LU3 HQ DC 0 ... 10 V

U14 Variable 5-step switch


A01

G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63


RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

5Q VAR.

33 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Controller- / Application no. / description Plant diagram / connection diagram
basic type
RLU236 ZZZ013 LU3 HQ DC 0 ... 10 V

U15 Variable 6-step switch

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

6Q VAR.

RLU236 ZZZ014 LU3 HQ DC 0 ... 10 V

U16 Binary step switch with 7 steps (3 relays)

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

3Q BIN.
Q1

Q2
Q1

Q1
Q3
Q2
Q1

RLU236 ZZZ015 LU3 HQ DC 0 ... 10 V

U17 Binary step switch with 15 steps (4 relays)

A01
G X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63
RLU236
G0 Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64

Q1

Q2
Q1
4Q BIN.
Q1
Q3
Q2
Q1

Q1

Q2
Q1
Q4

Q1
Q3
Q2
Q1

RLU236 CZZ001 LU3 HQ


Condensation pressure control M11
U18 B21 M7
Options:
Switching via external time switch

S5

34 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
Dimensions (dimensions in mm)

RLU202, RLU220, 86 123


RLU222 5 3 3
3

2
ø5
ø 10,5

=
44,5

66,4
50

90
35

=
44

3
= =

3101M02
EN 60 715-TH 35-7.5 97

RLU232, RLU236
86 176
5 3
3

2
ø5
ø 10,5

=
44,5

66,4
50

90
35

=
44

3
= =

3101M01
EN 60 715-TH 35-7.5 153

35 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22
ARG62.201

Mounting frame for RLU202, RLU220 Mounting frame for RLU232 and RLU236:
and RLU222:

45
87

45
87
113 168
3101M11

3101M10
143 5,6 199

5,6
24

24
Panel cutout if controller shall be wired prior to Panel cutout if controller shall be wired after mounting:
mounting:
L3

3101M09
4,4
4,4
66,4
45

66,4
82

45

4,4 4,4
18,5

18 L1 L3
10,7

7,8
3101M08

L2 18 L1
L2

Type L1 L2 Type L1 L2 L3
RLU202, RLU220, 97 133 RLU202, RLU220, 97 133 107
RLU222 RLU222
RLU232, RLU236 153 189
RLU232, RLU236 153 189 163

Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd 2000
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change

36 / 36

Siemens Universal Controllers CE1N3101en


Building Technologies 2016-03-22