Count Code No.

Alarm description
0 00 A00 (No error occurred)
1 01 A01 Engine hydraulics failure / Engine oil pressure trouble
2 02 A02 Engine oil failure
3 03 A03 Engine over speed failure
4 04 A04 Engine low speed failure
5 05 A05 Ignition power supply failure
6 06 A06 Engine start failure
7 07 A07 Fuel gas valve failure
8 08 A08 Engine stall / stop
9 09 A09 Engine overload
10 0A A10 High exhaust gas temperature
11 0B A11 Engine oil level trouble
12 0C A12 Throttle (stepping motor) failure
13 0D A13 Fuel gas adjustment valve failure
14 0E A14 Engine oil pressure switch failure
15 0F A15 Starter power supply output short-circuit
16 10 A16 Starter locked
17 11 A17 CT failure (starter current detection failure)
18 12 A18 ---
19 13 A19 Wax 3 way valve trouble
20 14 A20 High cooling water temperature
21 15 A21 Abnormal cooling water level
22 16 A22 Cooling water pump overload
23 17 A23 Crank angle sensor trouble
24 18 A24 Cam angle sensor trouble
25 19 A25 Clutch trouble
26 1A A26 Misfire
27 1B A27 Catalyst temp. trouble
28 1C A28 Generator trouble
29 1D A29 Converter trouble
30 1E A30 Fuel gas pressure low
31 1F A31 ---
32 20 C00 Unused
33 21 C01 Poor setting on Control Address (duplicated).
34 22 C02 Discord of number of units in central process control.
35 23 C03 Miswiring of central process control.
36 24 C04 Misconnection of central process control.
37 25 C05 Transmission error of central process control.
38 26 C06 Reception error of central process control.
39 27 C07 ---
40 28 C08 ---
41 29 C09 ---
42 2A C10 ---
43 2B C11 ---
44 2C C12 Lump / Batch alarm by local adapter.
45 2D C13 ---
46 2E C14 ---
47 2F C15 ---
48 30 C16 Poor transmission of the adapter to the unit.
49 31 C17 Poor reception of the adapter from the unit.
50 32 C18 Duplicate central address in adaptor
51 33 C19 Duplicate adaptor address
52 34 C20 PAC-, GHP- type mixed in Amy-adapter / communications adapter
53 35 C21 Non-volatile memory in the adapter is abnormal.
54 36 C22 Poor setting of adapter address.
Count Code No. Alarm description
55 37 C23 Host terminal failure (Software)
56 38 C24 Host terminal failure (Hardware)
57 39 C25 Host terminal transaction failure
58 3A C26 Communication failure in host terminal
59 3B C27 ---
60 3C C28 Reception error of S-DDC from host terminal
61 3D C29 Initialization failure of S-DDC
62 3E C30 ---
63 3F C31 Configuration change (detected by adaptor)
64 40 E00 Unused
65 41 E01 Poor reception of the signal on the remote controller / Remote controller is detecting
error signal from indoor unit.
66 42 E02 Poor transmission of the signal on the remote controller.
67 43 E03 Poor reception of the indoor unit from the remote controller(central process control)
68 44 E04 Poor reception of the indoor unit from the outdoor unit / When turning on the power
supply, the number of connected indoor units does not correspond to the number set.
(Except R.C. address is "0.")
69 45 E05 Poor transmission of the indoor unit to the outdoor unit.
70 46 E06 Poor reception of the outdoor unit from the indoor unit. / Error of the main outddor unit
in receiving serial communication signal from the indoor unit.
71 47 E07 Poor transmission of the outdoor unit to the indoor unit.
72 48 E08 Duplicated setting of indoor unit's address.
73 49 E09 Setting multiple master remote controllers.
74 4A E10 Indoor unit - 3-way + signal PCB serial transmission failure
75 4B E11 Poor reception of the indoor unit from the signal output P.C.B..
76 4C E12
No auto address setting. (Auto address is in setting) / Inhibit starting automatic address
setting (in automatic address setting) / This alarm message shows that the auto address
connector CN100 is shorted while other RC line is executing auto address operation.
77 4D E13 Poor transmission of indoor unit to the remote controller.
78 4E E14 Duplicated address of master indoor unit in group processing control.
79 4F E15 Alarm for auto address setting.(Number of indoor units is too small.)
80 50 E16 Alarm for auto address setting.(Number of indoor units is too large.)
81 51 E17 Poor transmission from indoor unit to indoor unit.
82 52 E18 Poor communication of group processing control caused by miswiring / Error of main
indoor unit in receiving serial communication signal from sub indoor units.
83 53 E19 3 or more master units (Individual twin multi type) in one system
84 54 E20 No indoor unit in automatic address
85 55 E21 PCB (outdoor control board) trouble
86 56 E22 Thermistor (outdoor control board sensor) trouble
87 57 E23 Poor transmission of CCU to outdoor sub bus.
88 58 E24 Poor reception of CCU from outdoor sub bus / Outdoor unit (INV or Main) failed to
receive communications from another outdoor unit (constant-speed or sub).
89 59 E25 Poor setting of outdoor sub bus address. (duplicated)
90 5A E26 Discord of number of outdoor sub bus units / Outdoor unit sub bus number mismatch /
Mismatch in outdoor unit quantity
91 5B E27 Miswiring of outdoor sub bus.
92 5C E28 Misconnection of outdoor units.
93 5D E29 Outdoor unit serial reception failure / Outdoor unit failed to receive communication from
relay control unit / Error of sub outdoor unit in receiving serial communication signal from
main outdoor unit.
94 5E E30 Poor transmission of outdoor serial / Outdoor unit serial transmission failure
95 5F E31 Outdoor unit Unit internal communications failure
96 60 F00 Unused
Count Code No. Alarm description
97 61 F01 Abnormal sensor for the inlet temp. E1 on the heat exchanger of the indoor unit. / Water
heat exchanger unit refrigerant inlet temp. sensor trouble
98 62 F02 Abnormal sensor for mid-point temp. E2 on the heat exchanger of the indoor unit. /
Water heat exchanger unit freezing sensor trouble
99 63 F03 Abnormal sensor for the outlet temp. E3 on the heat exchanger of the indoor unit /
Water heat exchanger unit outlet temp. sensor trouble
100 64 F04 Abnormal sensor for the outlet temperature of the PC compressor (comp. No.1)
101 65 F05 Abnormal sensor for the outlet temperature of the AC compressor (comp. No.2)
102 66 F06 Abnormal sensor for the inlet temp. on the heat exchanger 1 of the outdoor unit.
103 67 F07 Abnormal sensor for the outlet temp. on the heat exchanger 1 of the outdoor unit.
104 68 F08 Abnormal sensor for outdoor temperature.
105 69 F09 Actuation of scroll compressor protective thermostat.
106 6A F10 Abnormal sensor for intake temperature of indoor unit / WHE: Cold/hot water inlet
sensor trouble
107 6B F11 Abnormal sensor for discharge temperature of indoor unit / WHE Cold/hot water outlet
sensor trouble
108 6C F12 Compressor inlet temperature sensor failure
109 6D F13 Abnormal sensor for cooling water temperature.
110 6E F14 Abnormal sensor for engine room temperature.
111 6F F15 Outdoor unit heat exchanger intermediate temperature sensor failure
112 70 F16 Compressor inlet/outlet pressure sensor failure / High-pressure sensor trouble
113 71 F17 Low-pressure sensor trouble
114 72 F18 Abnormal sensor for exhaust gas temperature.
115 73 F19 Abnormal sensor for compressor bottom surface temperature.
116 74 F20 ICE sensor / Clutch coil temp. sensor trouble
117 75 F21 Abnormal sensor for compressor 3 current.
118 76 F22 Abnormal sensor for discharge gas temperature from compressor 3.
119 77 F23 Abnormal sensor for refrigerant gas temperature in the heat exchanger 2 (In).
120 78 F24 Abnormal sensor for liquid refrigerant temperature in the heat exchanger 2 (Out).
121 79 F25 Abnormal sensor for heat exchanger coil 1 temperature.
122 7A F26 Abnormal sensor for heat exchanger coil 2 temperature.
123 7B F27 Abnormal sensor for compressor 1 current.
124 7C F28 Abnormal sensor for compressor 2 current.
125 7D F29 Abnormal non-volatile memory (EEPROM) in indoor unit.
126 7E F30 Abnormal timer (RTC).
127 7F F31 Abnormal non-volatile memory (EEPROM) in outdoor unit.
128 80 H00 unused
129 81 H01 Incorrect current value for compressor 1 .(over current)
130 82 H02 Incorrect current value for compressor 1 .(locked compressor)
131 83 H03 CT sensor is dislocated from compressor 1, Short circuited / Current is not detected
when comp. No. 1 is ON.
132 84 H04 Protective thermostat for scroll compressor 1.
133 85 H05 Protective thermostat for compressor 1 is slipped off / not installed
134 86 H06 Activation of low pressure switch.
135 87 H07 No oil in compressor 1. Low oil level
136 88 H08 Incorrect connection of oil sensor 1.
137 89 H09 Chattering of magnet switch 1 .(Multi)
138 8A H10 Defective sensor for crank case heater 1.
139 8B H11 Incorrect current value for compressor 2 .(over current)
140 8C H12 Incorrect current value for compressor 2 .(locked compressor)
141 8D H13 CT sensor is dislocated from compressor 2, short circuit / Current is not detected when
comp. No.2 is ON.
142 8E H14 Protective thermostat for scroll compressor 2.
143 8F H15 Protective thermostat for scroll compressor 2 is dislocated.
144 90 H16 No oil in compressor 2.
Count Code No. Alarm description
145 91 H17 Sensed unbalanced power voltage.
146 92 H18 Chattering of magnet switch 1 (Espacio).
147 93 H19 Chattering of magnet switch 2 .
148 94 H20 Defective sensor for crank case heater 2.
149 95 H21 Incorrect current value for compressor 3 .(over current)
150 96 H22 Incorrect current value for compressor 3 .(locked compressor)
151 97 H23 CT sensor is dislocated from compressor 3, short circuited.
152 98 H24 Protective thermostat for scroll compressor 3.
153 99 H25 Protective thermostat for scroll compressor 3 is slipped off / Compressor 3 discharge
temperature sensor disconnected
154 9A H26 No oil in compressor 3.
155 9B H27 Incorrect connection of oil sensor 2.
156 9C H28 Incorrect connection of oil sensor 3.
157 9D H29 Chattering of magnet switch 3.
158 9E H30 Defective sensor for crank case heater 3.
159 9F H31 HIC trouble alarm / IPM trip (IPM current or temperature)
160 A0 J00 Not used
161 A1 J01 ---
162 A2 J02 ---
163 A3 J03 ---
164 A4 J04 ---
165 A5 J05 ---
166 A6 J06 ---
167 A7 J07 ---
168 A8 J08 ---
169 A9 J09 ---
170 AA J10 ---
171 AB J11 ---
172 AC J12 ---
173 AD J13 ---
174 AE J14 ---
175 AF J15 ---
176 B0 J16 ---
177 B1 J17 ---
178 B2 J18 ---
179 B3 J19 ---
180 B4 J20 ---
181 B5 J21 ---
182 B6 J22 ---
183 B7 J23 ---
184 B8 J24 ---
185 B9 J25 ---
186 BA J26 ---
187 BB J27 ---
188 BC J28 ---
189 BD J29 ---
190 BE J30 ---
191 BF J31 ---
192 C0 L00 Unused
193 C1 L01 Incorrect address for indoor unit. (No master indoor unit.)
194 C2 L02 Mismatch of indoor and outdoor units. (Non-GHP device present)
195 C3 L03 Setting plural master indoor units for group control.
196 C4 L04 Duplicate setting of system address (outdoor unit).
197 C5 L05 Duplicate setting of priority indoor unit. (for priority indoor unit)
198 C6 L06 Duplicate setting of priority indoor unit. (for other than priority indoor unit.)
Count Code No. Alarm description
199 C7 L07 Group control wiring to individually controlled indoor unit.
200 C8 L08 No Setting of indoor unit address.
201 C9 L09 No Setting of indoor unit capacity.
202 CA L10 No Setting of outdoor unit capacity.
203 CB L11 Mis-wiring of group control wire. (Espacio)
204 CC L12 Discord of indoor unit's capacity. (Multi)
205 CD L13 Poor setting of indoor unit's type.
206 CE L14 Discord of power frequency. (50,60Hz)
207 CF L15 Defective double duct bearing.
208 D0 L16 Water heat exchanger unit setting failure
209 D1 L17 Mis-matched connection of outdoor units that have different kinds of refrigerant.
210 D2 L18 4-way valve operation failure.
211 D3 L19 Water heat exchanger unit duplicate parallel address
212 D4 L20 Duplicated central control addresses of indoor units at local adaptor
213 D5 L21 Gas type setting failure
214 D6 L22 ---
215 D7 L23 ---
216 D8 L24 ---
217 D9 L25 ---
218 DA L26 ---
219 DB L27 ---
220 DC L28 ---
221 DD L29 ---
222 DE L30 ---
223 DF L31 ---
224 E0 P00 Unused
225 E1 P01 Abnormal indoor fan motor / Thermal protector in indoor unit fan motor is activated
226 E2 P02 Actuation of outdoor fan motor, protective thermostats for CM and AC. / Power supply
voltage is unusual. (The voltage is more than 260 V or less than 160 V between L and N
phase.)
227 E3 P03 High discharge temperature of compressor 1.
228 E4 P04 Actuation of high refrigerant pressure switch.
229 E5 P05 Reversed phase (or missing phase) of the power source detected, capacity mismatch
230 E6 P06 Mismatching of Model type or Capacity in outdoor unit
231 E7 P07 DC-current overload, heat radiator temperature abnormal in outdoor unit
232 E8 P08 ---
233 E9 P09 Poor connection of ceiling panel connector for indoor unit.
234 EA P10 Actuation of indoor unit float switch.
235 EB P11 Water heat exchanger unit freezing trouble
236 EC P12 Operation of protective function of fan inverter / Indoor unit DC fan trouble
237 ED P13 ---
238 EE P14 O2 sensor (detects low oxygen level) activated.
239 EF P15 No refrigerant gas.
240 F0 P16 Compressor 1 overcurrent
241 F1 P17 Abnormal discharge gas temperature from compressor 2.
242 F2 P18
Abnormal discharge gas temperature from compressor 3 / GHP: Bypass valve trouble
243 F3 P19 4 way valve lock trouble
244 F4 P20 Abnormally high refrigerant gas pressure.
245 F5 P21 Abnormal pressure difference in compressor oil.
246 F6 P22 Fan motor trouble / Outdoor unit fan motor is unusual.
247 F7 P23 Water heat exchanger unit interlock trouble
248 F8 P24 ice storage tank unit abnormaly
249 F9 P25 ice storage tank unit abnormaly
250 FA P26 Inverter compressor high-frequency overcurrent alarm
Count Code No. Alarm description
251 FB P27 Protective alarm for freezing of coolant water
252 FC P28 Alarm: Out of range for coolant water set temperature
253 FD P29 Inverter compressor missing phase or lock alarm
254 FE P30 Abnormal sub indoor units in group control. (Centralized processing control detected
the abnormality.)
255 FF P31 Abnormal group control.