ADOPTED MANUFACTURER’S INSTALLATION STANDARD

FOR

INSTALLATION OF
EARLY STREAMER EMISSION
LIGHTNING ROD SYSTEMS

PROPOSED NFPA 781 - 1994


SUPPLEMENTARY

Report of the Committee on Lightning Protection Systems Using Early Streamer Emission Air Terminals

Andrew J. O’Connor, Chair


Science Applications Int’l. Corp., FL

Gerard M. Berger, CNRS-ESE, Gif-Sur-Yvette, France


Burt J. Bittner, Harris Corp., FL
Alexander L. Chaberski, Lightning Research, NY
Henry Diaz, MCI Telecommunications, TX
Thomas P. Dowling, Inst. of Makers of Explosives, DC
Rep. Inst. of Makers of Explosives
N. Floret, Helita SA, Paris, France
J.R. Gumley, International Protection Consultants, Hobart
TAS, Australia
Kenneth P. Heary, Heary Bros. Lightning Protection Co.,
NY NONVOTING
Rep. Lightning Preventor of America, Inc.
Bruce A. Kaiser, Lightning Master Corp., FL Salomon Blitstein, Proteccion Electricia Sa, Buenos Aires,
Edward A. Lobnitz, Tilden Lobnitz & Cooper Inc., FL Argentina
David E. McAfee, Westinghouse Savannah River Co., SC C.G. Invernizzi, E F Int’l SA, Geneva, Switzerland
Robert W. Rapp, National Lightning Protection Corp., CO Eduardo Mariani, Proteccion Electrica SA, Buenos Aires
Robert Allan Richardson, Reynolds, Smith & Hills, Inc., Argentina
FL
Michel Roubinet, Franklin France, Ozoir la Ferriere, Staff Liaison: John M. Caloggero
France
Timothy E. Russell, Underwriters Laboratories Inc., IL This list represents the membership at the time the
David E. Wilson, Wilson Electrical Sales, OH Committee was balloted the text of this edition. Since that
time, changes in the membership may have occurred.
ALTERNATES
Committee Scope: This Committee shall have primary
Marie Bakker, Franklin France, Ozoir la Ferriere, France responsibilities for documents on the protection from
(Alt. M. Roubinet) lightning of buildings and other structures and recreation
Max Goldman, CNRS-Ecole Superieure d’Electricite, Gif- and sports areas, other situations involving danger from
Sur-Yvette, France lightning to people or property, utilizing early streamer
(Alt. G. Berger) emission air terminals. The protection of electric
Dale A. Hallerberg, Underwriters Laboratories Inc., IL generating, power transmission and distribution systems
(Alt. T.E. Russell) is not within the scope of this Committee.
Frederick M. Heary, Lightning Preventor of America, Inc.,
NY The Supplementary Report of the Committee on Lightning
(Alt. K.P. Heary) Protection Systems Using Early Streamer Emission Air
Arnaud Lefort, Indelec, Douai, France Terminals is presented for adoption.
(Alt. N. Floret)
This Supplementary Report was prepared by the
MANUFACTURERS OF EARLY STREAMER Technical Committee on Lightning Protection Systems
EMISSION AIR TERMINALS Using Early Streamer Emission Air Terminals and
proposes for adoption a Supplementary Report which
Helita SA, Paris, France documents its action on the public comments received on
International Protection Consultants, Hobart TAS, the proposed NFPA 781-1994, Lightning Protection
Australia Systems Using Early Streamer Emission Air Terminals
Heary Bros Lightning Protection Co., Inc., NY published in the Technical Committee Reports for the
National Lightning Protection Corp., CO 1993 Fall Meeting.
Franklin France, Ozoir la Ferriere, France
Lightning Preventor of America, Inc., NY The results of the balloting will be found in the
British Lightning Preventor Ltd., Nottingham, England supplementary report.
DMC 2, Chennevisres, France
EFI, Geneva, Switzerland
ADOPTED MANUFACTURER’S INSTALLATION STANDARD

PROPOSED NFPA 781--F93 TCD

The following draft of proposed NFPA 781-1994 incorporates the Committee Actions on the Public Comments which make up the
Technical Committee Documentation and which appear on the preceding pages. The draft is presented only as an aid to the
reviewer.

Manufacturer’s Installation Standard proposed NFPA 781


Standard for Lightning Protection Systems Using Early Streamer Emission Air Terminals

1994 Edition

NOTICE: An asterisk (*) following the number or letter designating a paragraph indicates explanatory material on that paragraph
in Appendix A. Information on referenced publications can be found in Chapter 6 and Appendix H.

Chapter 1 Introduction

1-1 Scope. This standard covers protection from lightning for buildings, structures, recreation and sports
areas, and other situations subject to lightning that pose a danger to people or property by utilizing Early
Streamer Emission (ESE) air terminals. The protection of electric generating, transmission and distribution
systems and explosives manufacturing buildings and magazines is not within the scope of this standard.

1-2 Purpose. The purpose of this standard is the practical safeguard of persons and property from exposure
to lightning through the use of early streamer emission air terminals. This document covers a lightning
protection system that utilizes the influence of early streamer emission air terminals on the formation and
propagation of upward-connecting leaders. An ESE air terminal serves as a preferred strike point and acts to
offer an increased zone of protection from lightning.

1-3 Listed, Labeled and Approved Components. Where fittings, devices or other components required by this
standard are available as listed or labeled, such components shall be used. Otherwise, such components shall
be approved by the authority having jurisdiction.

Chapter 2 Terms and Definitions

2-1 General Terminology. General terms commonly used in describing lightning protection methods and
devices are defined as follows:

Early Streamer Emission Air Terminals. Air terminals that, by design, trigger the early initiation of an upward-
connecting leader as compared to a control air terminal under identical conditions. The ESE air terminal shall
exhibit a positive time advantage, and be qualified for listing as described in Chapter 5.

Lightning Protection System. A lightning protection system is a complete system of air terminal(s), conductors,
ground terminals, bonding conductors, surge suppression devices and other connections or fittings required to
complete the system.

2-2 Definitions.

Air Terminal. An air terminal is that component of a lightning protection system that is intended to intercept
lightning strokes.

Approved. Acceptable to the “authority having jurisdiction.”

NOTE: The National Fire Protection Association does not approve, inspect or certify any installations,
procedures, equipment or materials nor does it approve or evaluate testing laboratories. In determining the
acceptability of installations or procedures, equipment or materials, the authority having jurisdiction may
Proposed NFPA 781 -- F93 TCD Chapter 2

base acceptance on compliance with NFPA or other appropriate standards. In the absence of such
standards, said authority may require evidence of proper installation, procedure or use. The authority
having jurisdiction may also refer to the listings or labeling practices of an organization concerned with
product evaluations which is in a position to determine compliance with appropriate standards for the
current production of listed items.

Authority Having Jurisdiction. The “authority having jurisdiction” is the organization, office or individual
responsible for “approving” equipment, an installation or a procedure.

NOTE: The phrase “authority having jurisdiction” is used in NFPA documents in a broad manner since
jurisdictions and “approval” agencies vary as do their responsibilities. Where public safety is primary, the
“authority having jurisdiction” may be a federal, state, local or other regional department or individual such
as a fire chief, fire marshal, chief of a fire prevention bureau, labor department, health department, building
official, electrical inspector, or others having statutory authority. For insurance purposes, an insurance
inspection department, rating bureau, or other insurance company representative may be the “authority
having jurisdiction.” In many circumstances the property owner or his designated agent assumes the role of
the “authority having jurisdiction”; at government installations, the commanding officer or departmental
official may be the “authority having jurisdiction.”

Bonding. An electrical connection between an electrically conductive object and a component of a lightning
protection system that is intended to reduce significantly the potential differences created by lightning currents.

Cable. A conductor formed of a number of wires stranded together.

Chimney. A smoke or vent stack having a flue with a cross sectional area less than 500 sq. in. (0.3 sq. m) and
a total height less than 75 ft (23 m).

Conductor, Bonding. A conductor intended to be used for potential equalization between metal bodies and the
lightning protection system. Bonding conductors are not designed to carry the main lightning current.

Conductor, Main. A conductor intended to be used to carry lightning currents between air terminals and ground
terminals.

Control Air Terminal. The control air terminal shall be 13 mm to 20 mm (0.5 in. to 0.8 in.) diameter solid
copper or copper alloy. The conical tip shall have an included angle no greater than 90 degrees.

Copper-clad Steel. Steel with a coating of copper bonded to it.

Fastener. An attachment to secure the conductor to the structure.

First Return Stroke. After connection of the two opposite leaders (downward, upward), initial phase of high
current flow.

Grounded. Connected to earth or to some conducting body that is connected to earth.

Ground Terminal. The portion of a lightning protection system such as a ground rod, ground plate or ground
conductor that is installed for the purpose of providing electrical contact with the earth.

Initiation Distance. Distance separating the air terminal tip and the downward leader head at the time of the
upward connecting leader initiation.

Initiation Time. The time of inception of the continuous upward propagating leader issued from the air terminal.

Ionization. The multiplication of electric charge in high electric fields, due mostly to collisions of electrons with
air molecules.
Proposed NFPA 781--F93 TCD Chapter 2 (a)

Labeled. Equipment or materials to which has been attached a label, symbol or other identifying mark of an
organization acceptable to the “authority having jurisdiction” and concerned with product evaluation that
maintains periodic inspection of production of labeled equipment or materials and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.

Leader. An electrically conductive propagating channel carrying a high intensity current electric charge and
headed by filamentary discharge streamers.

Downward Leader. A precursor to the main lightning discharge that propagates by steps towards
ground from a cloud charge center.

Upward Leader. An upward propagating discharge commencing from a ground point in response to the
strong electric field created by an approaching down leader.

Lightning Strike. The entire lightning event, which can consist of one or more lightning strokes.

Lightning Stroke. Lightning strokes are classified according to the direction of development of the first leader
and the polarity of the cloud charge center that discharges. Ninety percent of all lightning strokes are negative
downward strokes from a negative cloud charge center.

Listed. Equipment or materials included in a list published by an organization acceptable to the “authority
having jurisdiction” and concerned with product evaluation, that maintains periodic inspection of production of
listed equipment or materials and whose listing states either that the equipment or material meets appropriate
standards or has been tested and found suitable for use in a specified manner.

NOTE: The means for identifying listed equipment may vary for each organization concerned with product
evaluation, some of which do not recognize equipment as listed unless it is also labeled. The “authority
having jurisdiction” should utilize the system employed by the listing organization to identify a listed product.

Loop Conductor. A conductor encircling a structure that is used to interconnect ground terminals, main
conductors or other grounded bodies.

Metal-Clad Structure. A structure with sides or roof or both covered with metal.

Metal Frame Structure. A structure with electrically continuous structural members of sufficient size to provide
an electrical path equivalent to that of the lightning conductors covered in this standard.

Point of Attachment. See “Strike Point.”

Shall. Indicates a mandatory requirement.

Should. Indicates a recommendation or that which is advised but not required.

Sideflash. An electrical spark, caused by differences of potential, occurring between conductive metal bodies
or between such metal bodies and a component of the lightning protection system.

Space Charge. Positive or negative charge, or both, distributed in volume due to corona or streamer
discharges.

Spark Gap. Any short air space between two conductors electrically insulated from, or remotely electrically
connected to each other.

Streamer. A low intensity current that is a filamentary electrical discharge propagating out of corona and
preceding a propagating leader.

Strike Point. The point from which the upward connecting leader originates (point of attachment).
Proposed NFPA 781 --F93 TCD Chapter 2 (b)

Striking Distance. The distance over which final breakdown of the initial stroke to ground or to a grounded
object occurs.

Subsequent Stroke. Repeated discharges that originate at 30 millisecond to 200 millisecond intervals from
alternate cloud charge centers, which utilize the initial lightning path.

Surge Suppresser. A protective device for limiting surge voltages and preventing continued flow of follow
current while sustaining the ability to repeat these functions.

Test Joint. A disconnecting device used to permit isolated resistance measurements.

Time Advantage. The gain in length of the upward connecting leader of the early streamer emission air
terminal. A calculated numerical assignment used to determine a zone of protection.

Zone of Protection. The zone of protection is the space adjacent to a lightning protection system that is
substantially immune to direct lightning flashes.

Metric Units of Measurement. Metric units of measurement in this standard are in accordance with the
modernized metric system known as the International System of Units (SI). If a value for a measurement as
given in this standard is followed by an equivalent value in other units, the first stated value is to be regarded
as the requirement. A given equivalent value may be approximate.
Proposed NFPA 781-F93 TCD

Chapter 3 System Design

3-1 General Design Requirements. A lightning protection system using a ESE air terminal(s) shall be
designed with provisions for inspection and maintenance. Its design should be specified whenever possible
before the building is constructed.

Every installation shall be reviewed by a prior study to determine the level of protection needed. (Appendix D
provides guidance.)

3-2 Zone of Protection. The positioning of ESE air terminals is determined by the radius of protection, Rp, as a
function of the height, h, of the early streamer emission air terminal above the area to be protected.

The zone of protection is determined by the volume of the cone of the height, h, which has its apex at the top
of the ESE air terminal and the radius of which is Rp. (See Figure 3-2.1.)

3-2.1 Radius of Protection. The positioning of the ESE air terminal is determined by the radius of protection,
Rp, as a function of the height, h, of the ESE air terminal above the area to be protected.

All structures and buildings that are to be protected shall be located in the zone under a cone of height, h,
having its apex at the top of the ESE air terminal and a radius of protection, Rp.

The radius of protection is determined as follows:

Figure 3-2.1 Positioning of the ESE air terminal.

h: Height of the early streamer emission air terminal above the area to be protected.

Rp: Radius of protection of the ESE as function of h obtained using Figures 3-2.2(a), (b) and (c).

3-2.2 Determination of the Radius of Protection, Rp.

The position of the ESE air terminal depends on the radius of protection it provides. The radius of protection
can be determined by the use of Figures 3-2.2(a), (b) and (c). The figure used depends upon the level of
protection determined for the structure to be protected as follows:

Level I, structure with low risk: See Figure 3-2.2(a).


Level II, standard level of protection: See Figure 3-2.2(b).
Level III, structure with high risk: See Figure 3-2.2(c).
Proposed NFPA 781-F93 TCD Chapter 3(a)

Rp is the intersection of the horizontal scale (x axis) by the height at which the ESE air terminal is to be
installed (y axis), and the curve of Delta L corresponding to the ESE air terminal.

The value of h shall be determined using the equation that follows. The radius of protection, Rp, shall be
permitted to be obtainedby calculation, where h is greater than 16.4 ft (5 m).
Proposed NFPA 781-F93 TCD Chapter 3(b)
Proposed NFPA 781--F93 TCD Chapter 3 (c)
Proposed NFPA 781--F93 TCD Chapter 3 (d)
Proposed NFPA 781--F93 TCD

Chapter 4 Installation of a Lightning Protection System Using ESE Air Terminals

4-1 An ESE lightning protection systems installation consists of the following interconnected parts (See
Figure 4-1):

(a) One or more ESE air terminal(s)


(b) Bonding conductors
(c) Down conductor(s)
(d) Test joint
(e) Grounding system
(f) Equipotential bondings
(g) Surge voltage suppressors, if applicable.

4-1.1 Materials. Table 4-4.3A and Table 4-4.3B provide minimum sizes and weights for use in early streamer
emission system installations.

4-2 Air Terminal. ESE air terminals shall be sufficiently rigid to withstand mechanical damage. They shall be
of copper, copper alloy, aluminum or stainless steel. The main conductive parts of an ESE air terminal shall
have minimum dimensions in accordance with Table 4-4.3A and Table 4-4.3B.

4-2.1 Installation. Air terminals and their supports shall be mounted in such a way as to withstand the
lightning currents, electromotive force, corrosion and effects of weather, heat, humidity, snow and wind.

NOTE: Wind design criteria should be consistent with local building code requirements.
Proposed NFPA 781--F93 TCD Chapter 4 (a)
Proposed NFPA 781--F93 TCD Chapter 4 (b)
Proposed NFPA 781--F93 TCD Chapter 4 (c)
Proposed NFPA 781--F93 TCD Chapter 4 (d)

4-2.2 Where an air terminal or mast is supported by conductive guys, the guys shall be connected from their
points of anchorage to the closest down conductor(s) by a conductor equivalent in size to that of the down
conductor(s).

4-2.3 The tip of any ESE air terminal shall not be less than 6.6 ft (2 m) above protected open areas and
protected structures including antennas, cooling towers, tanks, roofs and masts.

4-2.4 Open Area. For sports grounds, golf courses, public parks, camping sites, swimming pools and race
tracks, the ESE air terminals shall be permitted to be mounted on top of pylons, flagpoles, or lamp standards
or on dedicated supports selected to protect the area best.

4-3 Storage Areas for Flammable and Combustible Liquids or Flammable Gases. Structures containing these
materials shall be grounded, but grounding alone does not constitute sufficient protection against atmospheric
discharges.

4-4 General. This section is concerned with equalizing potential differences that occur when lightning currents
flow through separately grounded metal bodies and conductors. Proper bonding, grounding and application of
surge suppression minimizes the possibility of flashover and arcing and their destructive results.

NOTE: For basic theory and design information regarding grounding, bonding and shielding for equipment
and facilities, see Department of Defense (D.O.D.) Military Handbook 419A, Volume 1 of 2, Grounding,
Bonding and Shielding for Electronic Equipment and Facilities.

4-4.1 Surge Suppression. Devices suitable for protection of the structure shall be installed on electric and
telephone service entrances and on radio and television antenna lead-ins.

NOTE: Electrical systems and utilization equipment within the structure might require further surge
suppression. Such protection is not part of this standard. NFPA 70, National Electrical Code, and
ANSI/IEEE C-62.1, Surge Arrestors for Alternating Current Systems, provide additional information.

4-4.2 General. In determining the necessity of bonding a metal body to a lightning protection system, the
following factors shall be considered:

(a) Bonding is required only if there is likely to be a sideflash between the lightning protection system and
another grounded metal body.

(b) The influence of a nongrounded metal body, such as a metal window frame in a nonconductive medium,
is limited to its effectiveness as a short circuit conductor if a sideflash occurs and therefore, does not
necessarily require bonding to the lightning protection system

(c) Bonding distance requirements depend on a technical evaluation of the number of down conductors and
their location, the interconnection of other grounded systems, the proximity of grounded metal bodies to the
down conductors, and the flashover medium (e.g., air or solid materials).

(d) Metal bodies located in a steel frame structure shall be permitted to be inherently bonded through
construction and further bonding shall not be required.

(e) Metal antenna masts or supports located on a protected structure shall be bonded to the lightning
protection system using main size conductors and listed fittings unless they are within a zone of protection.
Proposed NFPA 781--F93 TCD Chapter 4 (e)

4-4.3 Materials. Conductors used for the bonding of grounded metal bodies, or isolated metal bodies,
requiring connection to the lightning protection system shall be sized in accordance with the bonding conductor
requirements in Table 4-4.3A and Table 4-4.3B

Table 4-4.3A Class I Material Requirements Under 60 ft. in Height

Type of Conductor
Copper Aluminum
Standard Metric Standard Metric

Air Terminal, Solid Min. Diameter 3/8 in. 9.5 mm 1/2 in. 12.7 mm
Air Terminal, Tubular Min. Diameter 5/8 in. 15.9 mm 5/8 in. 15.9 mm
Min. Wall Thickness 0.033 in. 0.8 mm 0.064 in. 1.6 mm
Min. Size ea. Strand 17 AWG 14 AWG
Main Conductor, Cable Wgt. per Length 187 lb/1000 ft 278 g/m 95 lb/1000 ft 141 g/m
Cross Sect. Area 57,400 CM 29 mm 98,600 CM 50 mm
Main Conductor, Thickness 0.051 in. 1.30 mm 0.064 in. 1.63 mm
Solid Strip Width 1 in. 25.4 mm 1 in. 25.4 mm
Bonding, Conductor, Min. Size ea. Strand 17 AWG 14 AWG
Cable (solid or stranded) Cross Sect. Area 26,240 CM 41,100 CM
Bonding, Conductor, Thickness 0.051 in. 1.30 mm 0.064 in. 1.63 mm
Solid Strip Width 1/2 in. 12.7 mm 1/2 in. 12.7 mm

Table 4-4.3B Class II Material Requirements Over 60 ft. in Height

Type of Conductor Copper Aluminum


Standard Metric Standard Metric

Air Terminal, Solid Min. Diameter 1/2 in. 12.7 mm 5/8 in. 15.9 mm
Min. Size ea. Strand 15 AWG 13 AWG
Main Conductor Cable Wt. per Length 375 lb/1000 ft 558 g/m 190 lb/1000 ft 283 g/m
2 2
Cross Sect. Area 115,000 CM 58 mm 192,000 CM 97 mm
Solid Strip Thickness 0.078 in. 2 mm
Width 1/2 in. 12.7 mm
Bonding Conductor, Min. Size ea. Strand 17 AWG 14 AWG
Cable (solid or stranded) Cross Sect. Area 26,240 CM 41,100 CM
Bonding Conductor, Thickness 0.051 in 1.30 mm 0.064 in. 1.63 mm
Solid Strip Width 1/2 in. 12.7 mm 1/2 in. 12.7 mm

4-4.4 Materials. Horizontal loop conductors used for the interconnection of lightning protection system
downlead conductors, ground terminals or other grounded media shall be sized no smaller than that required
for the main lightning conductor. (See Table 4-4.3A and Table 4-4.3B).

4-4.5 Ground Level Potential Equalization. All grounded media in and on a structure shall be connected to the
lightning protection system within 12 ft (3.6 m) of the base of the structure in accordance with 4-7.6. For
structures exceeding 60 ft (18 m) in height, the interconnection of the lightning protection system ground
terminals and other grounded media shall be in the form of a ground loop conductor.

NOTE: For structures 60 ft (18 m) or less in height a loop conductor should be provided for the inter-
connection of all ground terminals and other grounded media. Regardless of the building height, ground
loop conductors should be installed underground in contact with earth. Ground level potential equalization
allows use of a ground ring electrode as a ground loop conductor. A ground ring electrode conforming to
4-7.4 may be permitted to be utilized for the ground loop conductor.
Proposed NFPA 781--F93 TCD Chapter 4 (f)

4-5 Metal Bodies. Certain metal bodies located outside or inside a structure contribute to lightning hazards,
because they are grounded or assist in providing a path to ground for lightning currents. Such metal bodies
shall be bonded to the lightning protection system in accordance with this section and the following two
sections. (See Appendix B for a technical discussion of lightning protection potential equalization bonding.)

4-5.1 Long, Vertical Metal Bodies

(a) Steel Frame Structure. Grounded and ungrounded metal bodies exceeding 60 ft (18 m) in vertical
length shall be bonded to structural steel members as near as practical to their extremities, unless inherently
bonded through construction at these locations.

(b) Reinforced Concrete Structures where the Reinforcement is Interconnected and Grounded in
Accordance with 4-7.10. Grounded and ungrounded metal bodies exceeding 60 ft (18 m) in vertical length
shall be bonded to the lightning protection system as near as practical to their extremities, unless inherently
bonded through construction at these locations.

(c) Other Structures. Bonding of grounded or ungrounded long, vertical metal bodies shall be as specified in
4-5.2

4-5.2 Grounded Metal Bodies. This paragraph covers the bonding of grounded metal bodies not covered in
4-5.1. Where grounded metal bodies have been connected to the lightning protection system at only one
extremity, the formula that follows shall be used to determine if additional bonding is required. Branches of
grounded metal bodies connected to the lightning protection system at their extremities shall require bonding to
the lightning protection system in accordance with the formula that follows if they change vertical direction
more than 12 ft (3.6 m).

Exception: Where such bonding has been accomplished either inherently through construction or by physical contact between
electrically conductive materials, no additional bonding connection shall be required.

(a) Structures Over 40 ft (12 m) in Height. Grounded metal bodies shall be bonded to the lightning protection
system where located within a distance, D, as determined by the following formula:

D = h/6n . Km

Where “h” is the vertical distance between the bond being considered and the nearest lightning protection
system bond.

The value of “n” is related to the number of down conductors that are spaced at least 25 ft (7.6 m) apart and
located within a zone of 100 ft (30 m) from the bond in question and is calculated as follows:

(1) Where bonding is required within 60 ft (18 m) from the top of any structure:

n = 1, where there is only one down conductor in this zone

n = 1.5, where there are only two down conductors in this zone

n = a minimum of 2.25, where there are three or more down conductors in this zone.

Km = 1.0 if flashover is through air or 0.50 if flashover is through dense material such as concrete,
brick, wood, etc.
Proposed NFPA 781--F93 TCD Chapter 4(g)

(2) Where bonding is required below a level 60 ft (18 m) from the top of a structure, n is the total number of
down conductors in the lightning protection system.

(b) Structures 40 ft (12 m) and Less in Height. Grounded metal bodies shall be bonded to the lightning
protection system where located within a distance, D, as determined by the formula:

D = h/6n . Km

Where “h” is either the height of the building or the vertical distance from the nearest bonding connection
from the grounded metal body to the lightning protection system and the point on the down conductor
where the bonding connection is being considered.

The value of “n” is related to the number of down conductors that are spaced at least 25 ft (7.6 m) apart and
located within a zone of 100 ft (30 m) from the bond in question and is calculated as follows:

n = 1, where there is only one down conductor in this zone

n = 1.5, where there are only two down conductors in this zone

n = a minimum of 2.25, where there are three or more down conductors in this zone

Km = 1.0 if the flashover is through air or 0.50 if flashover is through dense material such as concrete,
brick, wood, etc.

(c) Isolated (Nongrounded) Metallic Bodies. An isolated metallic body, such as a metal window frame in a
nonconducting medium, that is located close to a lightning conductor and to a grounded metal body influences
bonding requirements only if the total of the isolated distances between the lightning conductor and the
isolated metal body, and between the isolated metal body and the grounded metal body, is equal to or less
than the calculated bonding distance.

A bonding connection is required where the total of the shortest distance between the lightning conductor and
the isolated metal body and the shortest distance between the isolated metal body and the grounded metal
body is equal to or less than the bonding distance as calculated in accordance with 4-5.2 Bondings shall be
made between the lightning protection system and the grounded metal body and shall not be required to run
through or be connected to the isolated metal body.

NOTE: In addition to the bonding of metal bodies, surge suppression should be provided to protect power,
communications and data lines from dangerous overvoltages and sparks caused by lightning strikes.

4-5.3 Use of Aluminum. Aluminum systems shall be installed in accordance with other applicable sections
and with the following requirements.

(a) Aluminum lightning protection equipment shall not be installed on copper roofing materials or other
copper surfaces or where exposed to the runoff from copper surfaces.

(b) Aluminum materials shall not be used where they come into direct contact with earth. Fittings used for
the connection of aluminum down conductors to copper or copper clad grounding equipment shall be of the
bimetallic type. Bimetallic connectors shall be installed not less than 18 in. (457 mm) above earth level.
Proposed NFPA 781--F93 TCD Chapter 4(h)

(c) Connectors and fittings shall be suitable for use with the conductor and the surfaces on which they are
installed. Bimetallic connectors and fittings shall be used for splicing or bonding dissimilar metals.

(d) An aluminum conductor shall not be attached to a surface coated with alkaline-base paint, embedded in
concrete or masonry, or installed in a location subject to excessive moisture.

4-5.4 Corrosive Protection. Precautions shall be taken to provide the necessary protection against any
tendency towards deterioration of any lightning protection components due to environmental conditions.

4-5.5 Mechanical Damage or Displacement. Any part of a lightning protection system that is subject to
mechanical damage or displacement shall be protected with a protective molding or covering. If metal pipe or
tubing is used around the conductor, the conductor shall be connected electrically to the pipe or tubing at both
ends.

4-5.6 Substitution of Metals. Metal parts of a structure such as eave troughs, down spouts, ladders, chutes, or
other metal parts shall not be substituted for the main lightning conductor. Likewise, metal roofing or siding
having a thickness of less than 3/16 in. (4.8 mm) shall not be substituted for main lightning conductors.

4-5.7 “U” or “V” Pockets. Conductors shall maintain a horizontal or downward coursing, free from “U” or “V”
(down and up) pockets or shall not rise at a rate exceeding 3 ft (76.2 mm) to connections with ground
terminals.

4-5.8 Conductor Bends. No bend of a conductor shall form an included angle of less than 90 degrees, nor
shall it have a radius of bend less than 8 in. (203 mm).

4-5.9 Conductor Supports. Conductors shall be permitted to be coursed through the air without supports for a
distance of 3 ft (0.9 m) or less. Conductors that are coursed through air for longer distances shall be provided
with a positive means of support that prevents damage or displacement of the conductor.

4-5.10 Down Conductors Entering Corrosive Soil. Down conductors entering corrosive soil shall be protected
against corrosion by a protective covering beginning at a point 3 ft (0.9 m) above grade level and extending for
its entire length below grade.

4-6 Down Conductors

4-6.1 A single down conductor shall be permitted to be used where the length of run does not exceed 65.5 ft
(20 m).

4-6.2 If the horizontal length is greater than the vertical length, two down conductors shall be required and
separated as far apart as is possible.

(a) For lengths greater than 65.5 ft (20 m), two conductors shall be required.

(b) For masts, a single down conductor only shall be required.

(c) If electrically conductive, the mast shall be permitted to be used as the down conductor.

(d) If electrically continuous, structural components shall be permitted to be used as the down conductor.

(e) Test joints shall be provided for each down conductor. They shall be accessible and located as near as
practicable to the ground termination. [See Figure 4-6.2(c)].

4-6.3 Masonry Anchors. Masonry anchors used to secure lightning protection materials shall have a minimum
outside diameter of 1/4 in. (6.4 mm) and shall be set with care. Holes made to receive the body of the anchor
Proposed NFPA 781--F93 TCD Chapter 4(i)

shall be of the correct size, made with the proper tools and preferably made in brick, stone or other masonry
unit rather than in mortar joints. When the anchors are installed, the fit shall be tight against moisture, thus
reducing the possibility of damage due to freezing.

4-6.4 Connector Fittings. Connector fittings shall be used at all “end-to-end,” “tee,” or “Y” splices of lightning
conductors. They shall be attached so as to withstand a pull test of 200 lb (890 N). Fittings used for required
connections shall be of the bolted, welded or high compression type.

4-6.5 Conductor Fasteners. Conductors shall be fastened securely to the structure upon which they are placed
at intervals not exceeding 3 ft (1 m). The fasteners, attached by nails, screws, bolts or adhesives, as
necessary, shall not be subject to breakage and shall be of the same material as the conductor or of a material
as resistant to corrosion as that of the conductor. No combination of materials shall be used that forms an
electrolytic couple of such nature that, in the presence of moisture, corrosion is accelerated.

4-7 Grounding. A study shall be conducted to engineer a grounding system to a maximum of 10 ohms
resistance in accordance with IEEE fall of potential ANSI/IEEE 141, Recommended Practice for Electric Power
Distribution for Industrial Power Plants, method. The material for the grounding system shall be selected to be
suitable for the soil conditions and other side factors such as cathodic protection.

4-7.1 Ground Electrodes. Ground electrodes shall be of copper, copper-clad steel, electrolytic and stainless
steel, or both, or galvanized steel and shall be utilized so as to achieve the 10 ohm maximum resistance to
ground.

4-7.2 Ground Rod Terminations. The down conductor shall be attached to the ground rod by welding
(including exothermic welding), brazing or clamping. Clamps shall be suitable for direct soil burial.

(a) Each down conductor shall terminate at a ground terminal. The design, size, depth and number of ground
terminals used shall comply with 4-7.1.

(b) Ground terminals located under slabs or in crawl spaces shall be installed as near as practicable to the
outside perimeter of the structure.

(c) Electrical system grounding electrodes shall not be used in lieu of lightning ground rods. This provision
shall not prohibit the required bonding together of grounding electrodes of different systems.

NOTE 1: For further information, see NFPA 70, National Electrical Code which contains detailed information
on the grounding of electrical systems.

NOTE 2: Research demonstrates that stainless steel is very susceptible to corrosion in many soil conditions.
It is critical that a proper soil analysis be performed before this type of rod is used.

NOTE 3: The ground rod material should be selected only after thorough investigation of soil type, corrosive
effects on various metals and other factors to ensure longevity of the rod system.

NOTE 4: Ground rod or ground ring electrodes should be installed below the frost line, where practicable.

4-7.3 Concrete-encased Electrodes. Concrete-encased electrodes shall be used only in new construction.
The electrodes shall be located near the bottom of a concrete foundation or footing that is in direct contact with
the earth and shall be encased by not less than 2 in. (50.8 mm) of concrete. The encased electrode shall
consist of the following:

(a) Not less than 20 ft (6.1 m) of No. 2 AWG bare copper conductor.
Proposed NFPA 781--F93 TCD Chapter 4(j)

(b) An electrode consisting of at least 20 ft (6.1 m) of one or more steel reinforcing bars or rods not less
than 1/2 in. (12.7 mm) in diameter that have been effectively bonded together by either welding or overlapping
20 diameters and that are securely wire-tied.

4-7.4 Ground Ring Electrode. A ground ring electrode encircling a structure shall be in direct contact with
earth at a depth of not less than 2-1/2 ft (762 mm) or encased in a concrete footing in accordance with 4-7.3. It
shall consist of not less than a continuous length of 20 ft (6.1 m) of No. 2 AWG bare copper conductor.

4-7.5 Concrete-encased Electrode Terminations. The down conductors(s) shall be permanently attached to
the concrete-encased electrode system by welding ( including exothermic welding), brazing or clamps.

4-7.6 Common Grounding. All grounding media in or on a structure shall be interconnected to provide a
common ground potential. This shall include lightning protection, electric service, and telephone and antenna
system grounds, as well as underground metallic piping systems. Such piping systems include water service,
well casings located within 25 ft (7.6 m) of the structure, gas piping, underground conduits, underground
liquefied petroleum gas piping systems, etc. Interconnection to a gas line shall be made on the customer’s
side of the meter. Main size lightning conductors shall be used for interconnecting these grounding systems to
the lightning protection system.

4-7.7 Common Ground Bonding. If electric, telephone, or other systems are bonded to a metallic water pipe,
only one connection from the lightning protection system to the water pipe system shall be required, provided
that the water pipe is electrically continuous between all systems. If the water pipe system is not electrically
continuous due to the use of plastic pipe sections or for other reasons, the nonconductive sections shall be
bridged with main size conductors, or the connection shall be made at a point where electrical continuity is
ensured.
Proposed NFPA 781--F93 TCD Chapter 4(k)
Proposed NFPA 781--F93 TCD Chapter 4

4-7.8 Structural Steel Systems

4-7.8.1 General. The steel framework of a structure shall be permitted to be utilized as the main conductor of
a lightning protection system if it is electrically continuous or is made electrically continuous.

(a) Steel Structure Terminals. Ground terminals shall be connected to approximately every other steel
column around the perimeter of the structure at intervals averaging not more than 60 ft (18 m). Connections
shall be made near the base of the column, with a surface contact area of not less than 8 sq. in. (5200 mm2),
or by welding or brazing the ground terminal conductor directly to the column. Bonding plates shall have bolt
tension cable connectors and shall be bolted, welded or brazed securely to the column so as to maintain
electrical continuity.

(b) Connections to Framework. Conductors shall be connected to cleaned areas of the structural steel
framework by the bonding of plates having a surface contact area not less than 8 sq. in. (5200 mm2) or by
welding or brazing. Bonding plates shall have bolt pressure cable connectors and shall be bolted, welded
or brazed securely to the structural steel framework so as to maintain electrical continuity.

4-7.8.2 Air Terminals. Air terminals shall be connected to the structural steel framing by direct connection,
by use of individual conductors routed through the roof or parapet walls to the steel framework, or by use of an
exterior conductor that interconnects all air terminals and that is connected to the steel framework. Where
such an exterior conductor is used, it shall be connected to the steel framework of the structure at intervals not
exceeding 100 ft (30m).

4-7.9 Metal Bodies. Certain metal bodies located outside or inside a structure contribute to lightning hazards
because they are grounded or assist in providing a path to ground for lightning currents. Such metal bodies
shall be bonded to the lightning protection system in accordance with 4-5.2.

4-7.10 Concealment in Steel Reinforced Concrete. Conductors or other components of the lightning protection
system concealed in steel reinforced concrete units shall be connected to the reinforcing steel. Concealed
down conductors shall be connected to the vertical reinforcing steel. Roof conductors or other concealed
horizontal conductor runs shall be connected to the reinforcing steel at intervals not exceeding 100 ft (30 m).

4-7.11 Down Conductors and Structural Columns. Down conductors coursed on or in reinforced concrete
columns or on structural steel columns shall be connected to the reinforcing steel or the structural steel
member at its upper and lower extremities. In the case of long, vertical members, an additional connection
shall be made at intervals not exceeding 200 ft (60 m). Such connections shall be made using listed clamps or
listed bonding plates or by welding or brazing. The use of PVC conduit or other nonmetallic chase does not
negate the need for these interconnections unless sufficient separation is provided to satisfy the bonding
requirements of Sections 4-4 and 4-5. Where this is not the case, provisions shall be made to ensure the
required interconnection of these parallel vertical paths.
PROPOSED NFPA 781--F93 TCD

CHAPTER 5 ESE AIR TERMINAL QUALIFICATIONS

5-1 General. These tests evaluate the ESE air terminal in comparison to a control air terminal of the same
height under the same ambient conditions. This evaluation provides a value for the “Delta T” of the ESE air
terminal, which then is used in the calculation of the Delta L and radius of protection.

5-2 Required Tests. The following tests shall be performed:

(a) 100 Operation test


(b) Field confirmation test.

5-3 100 Operation Test. Two alternate methods are acceptable for the 100 operation test, single rod test, or
dual rod test, one of which shall be used. The following conditions shall apply to both methods:

(a) The ambient temperature in the test cell shall not vary more than 9oF (5oC) during the test.

(b) The absolute humidity shall be not less than 10 g/m3 throughout the test and shall not very by more
than 10 percent during the test.

(c) The control air terminal shall be 18 mm to 20 mm (0.7 in. to 0.8 in.) diameter solid copper or copper alloy
freestanding, 1 meter (39 in.) in length. The conical tip shall have an included angle of not greater than 90
degrees.

(d) Each air terminal shall be mounted vertically under a horizontal upper plate.

(e) The tip of each air terminal shall be located not less than 1 m (39 in.) above the floor of the test cell.
The distance between the air terminal tip and the upper plate shall be not less than 2 m (79 in.).

(f) The upper plate shall be solid, mesh or interconnected conductors. Suitable preparation of the upper
plate (such as polishing) shall be made so that no down leader initiates from it during the test. It shall
overhang the air terminal(s) by a distance not less than the distance between the air terminal tip and the
upper plate.

(g) Each air terminal shall be grounded.

(h) With the air terminal removed, the upper plate shall be negatively biased at 10 kV/m to 20 kV/m.
Distance for this bias is from the upper plate to the floor of the test cell. The bias voltage shall not vary
by more than 5 percent during the test.

Exception: Proper biasing of the upper plate shall be permitted to be determined with the air terminal in place by producing a
negative air terminal corona current of 0.1 to 10 microamperes. The bias voltage shall not vary by more than 5 percent during
the test.

(i) One hundred switching impulses shall be applied to the upper plate. The rate of rise of the voltage
8 9
immediately before the breakdown shall be 10 V/m/s to 10 V/m/s. Breakdown shall occur when the
electric field is 100 kV/m to 500 kV/m. The rate of impulses shall not exceed one per minute and shall
remain as constant as practical.

(j) The tip of the air terminal(s) shall be positioned at the same height ± 0.00787 in. (± 0.2 mm) for each
shot.
Proposed NFPA 781--F93 TCD Chapter 5(a)

5-3.1 Single Rod Test. Both the ESE air terminal and the control air terminal shall be tested independently,
25 shots at a time, then exchanged, for a total of 100 shots on each air terminal.

The upward leader initiation time shall be determined for each breakdown and averaged for the 100 shots.
The Delta T for the ESE air terminal is calculated as follows:

Delta T = [Tic-Tiese]

Delta L = 106 m/s x [Delta T]

106 m/s = the velocity of lightning

Tic = Average initiation time for the control air terminal

Tiese = Average initiation time for the ESE air terminal

The result shall be rounded to the nearest whole number and reduced by 3.

5-3.2 Dual Rod Test. * The dual rod test shall be preceded by a check of the parallelism of the upper plate.
For the dual rod test, both the ESE air terminal and the control air terminal shall be mounted in the test cell,
separated by a distance not less than either of their heights. The air terminals shall be grounded identically
and interconnected. Fifty shots shall be made and then the air terminal positions shall be exchanged for the
remaining 50 shots. The difference in upward leader initiation time shall be determined for each impulse and
averaged for the 100 shots. The Delta T for the ESE air terminal is calculated as follows:

Delta T = [Tic - Tiese]

Tic = Average initiation time for the control air terminal

Tiese = Average initiation time for the ESE air terminal

Delta L = 106 m/s x Delta T  Formula B

Delta T = Average difference in initiation time

The result shall be rounded to the nearest whole number and reduced by 3.

5-4 Field Confirmation Test. This controlled, instrumented, 20-event field test is performed to confirm the
Delta L determined during the 100 operation lab test. Due to the length of time necessary for outdoor tests,
this test shall not be required for initial qualification of the ESE air terminal but shall begin at that time.

The upward leader initiation time shall be compared for the ESE air terminal and a control air terminal for a
minimum of 20 events. The Delta L for the ESE air terminal shall be determined in accordance with 5-3.2.
The Delta L determined at the conclusion of the field confirmation test shall supersede the Delta L determined
from the 100 operation lab test.

The following conditions shall apply to this test:

(a) The ESE air terminal and control air terminal shall be mounted vertically outdoors.
(b) The ESE air terminal and control air terminals shall be the same height with their tips not less than
8 m (26 ft.) above the ground.
(c) The control air terminal shall be the same as specified in Section 5-3 (c).
Proposed NFPA 781--F93 TCD Chapter 5 (b)

(d) Each air terminal shall be grounded identically and interconnected.


(e) Upward emission currents in excess of 10 amperes shall be indicative of upward leader initiation.
When both ESE and control air terminals create upward leaders, Delta T shall be the time advantage
measured at the points where each achieves emission levels of 10 amperes. In cases where the control
air terminal does not initiate an upward leader, Delta T shall be the difference in time between
commencement of the return stroke and the prior achievement of 10 ampere emission from the ESE
terminal. Delta L is obtained by inserting Delta T in formula B.

Chapter 6 Referenced Publications

6-1 The following documents or portions thereof are referenced within this standard for informational purposes
only and thus are not considered part of the requirements of this document. The edition indicated for each
reference is the current edition as of the date of the NFPA issuance of this document.

6-1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101,
Quincy, MA 02269-9101.

NFPA 70, National Electrical Code, 1993 edition.

NFPA 780, Lightning Protection Code, 1992 edition.

6-1.2 ANSI/IEEE Publications. Institute of Electrical and Electronic Engineers, Inc., 345 East 47th St.,
New York, N Y.

ANSI/IEEE C-62.1-1984, Surge Arrestors for Alternating Current Systems

ANSI/IEEE 141-1986, Recommended Practice for Electric Power Distribution for Industrial Power Plants

6-1.3 U.S. Government Publication. Superintendent of Documents, U.S. Government Printing Office,
Washington, D C 20401.

MIL-HDBK 419A, Volume 1 of 2, Grounding, Bonding and Shielding for Electronic Equipment and Facilities,
Naval Publications and Forms Center, 700 Robbius Ave., Philadelphia, PA 19111.
Proposed NFPA 781--F93 TCD Appendix A

Appendix A Explanatory Material

This appendix is not a part of the requirements of this NFPA document, but is included for informational purposes only.

A-5-3.2 The check of the parallelism of the upper plate may be permitted to be performed by mounting two
identical control air terminals in the test cell and subjecting them to a minimum of 20 impulse shots. When the
breakdown is divided equally between the two air terminals, the upper plate is considered to be parallel to the
tips of the air terminals.

Appendix B Guide for Personal Safety during Thunderstorms with Suggestions


for Appropriate Medical Response in the Event of a Lightning Strike

The purpose of this appendix is to furnish a guide for personal safety during thunderstorms. A review of
common medical problems initially encountered with a lightning strike and appropriate and basic resuscitative
therapy are discussed.

B-1 Personal Conduct.

B-1.1 Do not go outdoors or remain outside during thunderstorms unless it is necessary. Seek shelter in the
following locations:

(a) Dwellings of other buildings that are protected against lightning


(b) Underground shelters such as subways, tunnels and caves
(c) Large metal frame buildings
(d) Large unprotected buildings
(e) Enclosed automobiles, buses and other vehicles with metal tops and bodies
(f) Enclosed metal trains and street cars
(g) Enclosed metal boats and ships
(h) Boats that are protected against lightning
(I) City streets that are shielded by nearby buildings.

B-1.2 If possible, avoid the following locations, which offer little or no protection from lightning:

(a) Small, unprotected buildings, barns, sheds, etc.


(b) Tents and temporary shelters
(c) Automobiles (nonmetal top or open)
(d) Trailers (nonmetal or open).

B-1.3 Certain locations are extremely hazardous during thunderstorms and should be avoided if at all possible.
Approaching thunderstorms should be anticipated and the following locations and situations should be avoided
when storms are in the immediate vicinity:

(a) Hilltops and ridges


(b) Areas on tops of buildings
(c) Open fields, athletic fields, golf courses
(d) Parking lots and tennis courts
(e) Swimming pools, lakes and seashores
(f) Areas near wire fences, clotheslines, overhead wires and railroad tracks
(g) Standing beneath isolated trees
(h) Use of or contact with electrical appliances, telephones and plumbing fixtures
(i) Wearing metal spiked shoes; if wearing them, remove them.
Proposed NFPA 781--F93 TCD Appendix B

B-1.4 In the locations specified above, it is especially hazardous to be riding in or on any of the following
during lightning storms:

(a) Open tractors or other farm machinery operated in open fields


(b) Golf carts, scooters, bicycles or motorcycles
(c) Automobiles (nonmetal top or open).

B-1.5 It might not always be possible to choose a location that offers good protection from lightning. Follow
these rules when there is a choice in selecting locations:

(a) Seek depressed areas; avoid hilltops and high places.


(b) Seek dense woods; avoid isolated trees.
(c) Seek buildings, tents and shelters in low areas; avoid unprotected buildings and shelters in high areas.
(d) If hopelessly isolated in an exposed area and hair stands on end, indicating that lightning is about to
strike, squat down with feet close together, and extend arms to the side (90 degrees at the shoulder).
Proposed NFPA 781--F93 TCD Appendix C

Appendix C Modeling of the Zone of Protection for Lightning Protection Systems


Using ESE Air Terminals

C-1 Attachment Process.

C-1.1 Determination of the Lightning Strike Point. The overhead arrival of a thunder cloud produces an
increase in the electric field observed at ground level. This electric field can exceed 5kV/m (5kV/3.3 ft), giving
rise to corona discharges [see Figure C-1.1(a)] on ground point irregularities.

The lightning stroke is initiated by the formation within the storm cloud of a downward leader that advances
in steps towards the ground.

The downward leader carries electric charges causing the field observed at the ground to increase in an
exponential manner. The result is that ground points start to exhibit coronas [see Figure C-1.1(b)] that
progressively convert into streamers and into upward propagating leaders [see Figure C-1.1(c)] until the two
leaders meet [see Figure C-1.1(d)].

As the upward leader progresses, it influences the path of the downward leader [see Figure C-1.1(c)]. Both
downward and upward leaders converge until interception occurs [see Figure C-1.1(d)]. The electrical
conducting path between cloud and ground then is completed, and the main discharge or return stroke
occurs, followed sometimes by one or several subsequent strokes.

Several upward leaders might be initiated from structural projections. The first upward leader to meet the
downward leader designates the strike point.

C-1.2 Leader Velocity. Experimental data from nature show that the mean values of the velocities of the
upward leader, Vu, and downward leader, Vd, are comparable during the attachment process.

The ratio of the velocities, Vu/Vd, of this natural phenomenon generally is close to 1 (between .9 and 1.1).

We assume Vu = Vd = V = 106 m/s:

Where:

Vu = Velocity of the upward leader


Vd = Velocity of the downward leader
6
V = Velocity of lightning 10 m/s.
Proposed NFPA 781--F93 TCD Appendix C(a)

C-2 Advantage in Protection of the ESE Air Terminal.

C-2.1 Gain in Time of Initiation. An ESE air terminal is designed to reduce significantly the statistical time
lag associated with the upward leader attachment process. It displays a time advantage when tested in
comparison with a pointed vertical rod under identical conditions.

The upward connecting leader issued from the ESE air terminal is the first one to meet the downward leader.
The difference in time of initiation is expressed by Delta T, determined during the ESE qualification tests.
(See Chapter 5.)

C-2.2 Gain in Length of the Upward Leader. At the moment of initiation of the upward leader at the tip of a
pointed vertical rod, the head of the downward leader is positioned at a certain height above the ground. At
that same moment, in the case of an ESE air terminal, the head of the upward leader, traveling at velocity, Vu,
is at the distance Vu. Delta T, Delta T being the proper gain in time of initiation of the ESE air terminal. Delta
L is the gain in length of the upward connecting leader of the ESE air terminal.

The increase in zone of protection is determined from the model of protection outlined in the following
paragraphs.

C-3 Model of Protection: The Volume of Capture. The calculation of the volume of capture of incident
downward leaders is adapted from the rolling sphere concept.

The termination of a flash to a specified point depends upon the dual requirements of approach by the
descending leader to within at least the initiation distance together with entry by the downward lead (or
of a branch of the downward leader) into an effective collection (capture) volume within which interception
of the two leaders can take place.

C-3.1 Radius of Protection of a Single Vertical Rod. For a given value of peak current, a spherical surface, S,
centered at point A, can be drawn with a radius equal to the initiation distance, D.

Point B is part of S and another surface, S, locus of points such as AB = BC. Any downward leader entering
S between verticals passing through A and B will terminate at point A.
Proposed NFPA 781--F93 TCD Appendix C(b)

Where:
Proposed NFPA 781--F93 TCD Appendix C(c)

C-3.2 Radius of Protection of an ESE air terminal. In the case of an ESE air terminal, point B is created from
a similar geometric construction as shown in Figure C-3.2(a).

Where:

D = Initiation distance
∆L = Gain in length of the upward leader, defined by ∆L = V x ∆T
h = Height of the tip of the ESE air terminal above the area to be protected
Rp = Radius of protection of the ESE air terminal

h = Height between the tip of the ESE air terminal and the areas to be protected.
D = Initiation distance from 4-2.3
∆L = The assigned numerical value for the ESE air terminal
Rp = Radius of protection
Proposed NFPA 781--F93 TCD Appendix C(d)

Where elevated structures penetrate the electric field below a thunderstorm, they, in effect, raise the ground.
This creates a nonlinearity in the electric field strength near the upper surfaces of the structure. Lines of equal
potential are compressed severely in such cases.

There is a rapid return to linear conditions as height increases above the structure. In positioning an ESE air
terminal, its mounting height should be such that it substantially penetrates the area of nonlinearity. For this
reason, a minimum mounting height of 2m (0.61M) is specified, with a return to more natural conditions at
heights above 5m (1.525M). The protected radii for the various protection levels and Delta L ratings have been
modified accordingly.

C-3.3 Examples of typical installations using ESE air terminals.


Proposed NFPA 781--F93 TCD Appendix C(e)
Proposed NFPA 781--F93 TCD

Appendix D Risk Assessment Guide

D-1 Introduction. This lightning risk assessment guide is prepared to assist in the analysis of various criteria
to determine the risk of loss due to lightning and the need for protection. As a guide, it is not possible to cover
every special design element that might render a structure more or less susceptible to lightning damage.

In special cases, personal or economic factors can be very important and should be considered in addition to
the assessment made using this guide.

Structures with inherent risks usually warrant the highest possible class of lightning protection system, and
recommendations for protecting such structures might be provided in this appendix.

For all other structures, the level of protection required by this standard is applicable and the only question
remaining is whether protection is necessary.

The need for protection is often self-evident, as in the following examples:

(a) Where large numbers of people congregate.


(b) Where essential public services are concerned.
(c) Where the area is one in which lightning is prevalent.
(d) Where there are very tall or isolated structures.
(e) Where there are structures containing explosive or flammable contents.

However, there are many cases in which the need for protection is not always clear or obvious. The various
factors affecting the risk of being struck and the consequences of a strike are discussed in this guide and
should help address such situations. Some factors cannot be assessed, and these may override all other
considerations. For example, the desire to avoid all risk to life or to provide the occupants of a building with
complete assurance of safety might require the use of protection , even though there is no compelling need.
No guidance can be provided in such matters, but an assessment can be made that considers the exposure
risk and the following factors:

(a) Nature of the structure’s construction


(b) Value of its contents
(c) Life occupancy
(d) Environment of the structure location
(e) External consequences of possible damage to the structure.

The location of the structure in its environment and its overall height are taken into account in the calculation of
the exposure risk.

D-2 Collection Area and Estimation of Exposure Risk. The probability of a structure being struck by lightning
during any one year is the product of the “lightning flash density” and the “collection area” of the structure.
2
The lightning flash density, Ng, is the number of flashes to ground per km per year. Values of Ng can vary
significantly. The recent site survey network provides more detailed and current data on ground strike density
for the U.S. and its territories.
Proposed NFPA 781--F93 TCD Appendix D(a)

Figure D-1 Statistics for continental United States showing mean annual number of days with thunderstorms.
The highest frequency is encountered in south central Florida. Since 1894, the criteria for recording of
thunderstorms has been defined as the local calendar day during which thunder was heard. A day during
which thunderstorms occur is so recorded, regardless of the number occurring on that day. The occurrences of
lightning without thunder is not recorded as a thunderstorm. (Data supplied by the Environmental Science Service
Administration, U.S. Department of Commerce.)

Lik 5 10 20 30 40 50 60 70 80 90 100
Ng .3 .7 1.7 2.8 4.0 5.3 6.7 8.1 9.6 11.1 12.6

Where:

Lik = The lightning frequency isoceraunic level


Ng = Lightning flash density

The collection area of a building is the area of the plan of the structure extending in all directions to account for
its height. The edge of the collection area is displaced from the edge of the structure by an amount equal to
double the height of the structure at that point. Therefore, for a simple rectangular building of length, L, width,
W, and height, H, the collection area has length (L + 4H) and width (W +4H) with four rounded corners formed
by quarter circles of radius, H. All dimensions are expressed in meters.

Therefore, calculation of the collection area is as follows:


2
Ca = (L x W) + (4L x H) + (4W x H) + 4(πH )

Where:

(π = 3.14)

NOTE: Where the collection area of a structure fully covers the collection area of another structure, the latter is
not taken into account. Where collection areas of several structures overlap, the corresponding common areas
are taken into account only once. Three typical examples follow.
Proposed NFPA 781--F93 TCD Appendix D (b)

The probable number of strikes to the structure per year, Ps, is as follows:

Ps = Ca x Ng x 10-6

Ng is derived directly from survey networks maps.

The result of this equation then is weighted by a factor, C1, taking into account the environment of the structure.
(See Table D-2.)

The exposure risk then is expressed as the probability:

P = Ps x C1 per year.

Table D-2 Determination of Environmental Coefficient C1

This table takes into account the relative location of the structure.

Relative Location C1

Structure located in a large area of structures or trees 0.5


of the same or greater height (tower, forest)

Structure located in areas of few structures of similar height 1.0

Structure located in isolated site or surrounded by small structures 2.0

Structure is isolated on a hilltop or a knoll 3.0

D-3 Overall Assessment of Risk Pr.

Having established the value of P, the probable number of strikes to the structure per year, the “weighting
factors,” as specified in Tables D-3, D-4, D-5 and D-6 then are applied.

Multiply P by the appropriate factors to determine whether the result, the overall risk factor, exceeds the
acceptable risk R0 = 5.10-4. The result is Pr, the overall risk probability.

Thus, Pr = P x C2 x C3 x C4 x C5

Tables D-3 through D-6 provide the weighting factors for the relative degree of importance of risk in each case.

Table D-3

Roof Metal Metal


Structural Electrically Not
Framework Continuous Continuous Composition Wood
s
Nonmetallic 1.0 1.7 1.4 3.0
(other than wood)
Wood 2.0 1.7 1.4 3.0
Reinforced 0.5 1.7 1.4 3.0
concrete
Structural steel 0.5 1.7 1.4 2.0
Proposed NFPA 781--F93 TCD Appendix D(c)

Table D-4 Determination of Contents Coefficient C3

Content of the structure C3


Noncombustible materials 0.3
Residential furnishings or equipment 0.5
Cattle and livestock 0.8
Combustible materials 1
High value materials or equipment 2
Materials of exceptional or irreplaceable nature 5

Table D-5 Determination of Occupancy Coefficient C4

Occupancy of the structure C4


Unoccupied 0.3
Normally low occupancy 0.5
Normally occupied 1
Occasionally occupied by many persons 1.5
Occupied by immobile or bedridden persons 2.5
Risk of panic or very difficult access 3

Table 6 Determination of Environmental Consequences Coefficient C5

Consequential effects C5
Building with no service continuity necessities 1
Building with a necessary service continuity 1.5
Building containing hazardous materials 5

D-4 Interpretation of Overall Risk Probability. The risk factor method provided in this appendix is intended to
assist in solving the difficult problem of risk assessment. If the determined risk is less than 5 X 10-4, then, in
the absence of other overriding considerations, protection is optional. If the risk is greater, the following
recommendations for protection should be considered:

< 5 X 10
-4
If Pr ----> Protection optional

5 X 10-4 < 5 X 10-3 ----> Level I protection recommended

5 X 10-3 < 5 X 10-2 ----> Level II protection recommended

If Pr > 5 X 10-2 ----> Level III protection recommended

D-5 Levels of Protection. As a function of the intensity, I, of the current of the lightning strikes and of the
distance, R, correlated to I, a lightning stroke is relatively easy to capture for a LPS.
Proposed NFPA 781--F93 TCD Appendix D(d)
Proposed NFPA 781--F93 Appendix D(e)

Table D-7 provides the three levels of protection that ensure severe (Level III) to standard (Level I) protection.

Table D-7

Levels of Protection R (m) I (ka)

Level I 60 16.00
Level II 45 10.00
Level III 20 3.00

D-6 Examples of Calculation.

D-6.1 For a rectangular structure, the collection area is calculated as follows:

S = L x W + 4 LH + 4 WH = 4 π H2

D-6.2 For high structures, the radius of which will include the collection of another part of the structure.
(See Figure D-6.2)

D-6.3 For high structures of which only a part of the collection area is common to the other part of the
structure.

In the case of a high stack near a smaller building, a factor of 3/4 is added in the formula in order to avoid
taking into account one quarter of the collection area of the stack that is superimposed on the collection area of
the building. ( See Figure D-6.2)

2 2 2
S = L x W + h (L + W) + 4 x p x h + 3/4 x 4 x p H = 8869 m

Figure D-6.2
Proposed NFPA 781--F93 Appendix E

Appendix E Lightning Parameters

E-1 Lightning parameters are widely variable and generally are treated in a statistical manner. Table E-1
provides the frequency distributions of the main characteristics of the lightning ground flash.

E-1.2 Current Wave Shape. It should be understood that it is not possible for two similar currents of first
negative strokes to exist. However, similarities have been established. A mean wave shape was computed by
Kroninger in 1974 and is reproduced in Figure E-1.2.

Figure E-1.2 Mean current wave shape of negative stroke (Berger etal., 1975). A. Full record length.
B. Expanded front. (Reproduced from R.H. Golde, Lightning, Vol. 1, Academic Press, 1977.)

Table E-1: Summary of the Frequency Distribution of the Main Characteristics


of the Lightning Flash to Ground

Lightning Characteristics Percentage of events having value of characteristic greater than value shown Unit
below ( see Note 1).

99 90 75 50 25 10 1
1 max
First stroke peak current 3 12 20 30 50 80 130 kA
First stroke (di/dt) max 6 10 15 25 30 40 70 GA/s
1 max
Continuing current 30 50 80 100 150 200 400 A
Overall duration of flash 50 100 250 400 600 900 1500 ms
2 3 3 4 5 5 2
Action integral 10 3.10 10 5.10 3.10 10 5.10 A .s

Note 1: The values shown in this table have been taken from information compiled by CIGRE and have been
rounded in accordance with the known accuracy of these data. Values at the 1 percent and 99 percent levels
are very uncertain and are provided only to indicate an order of magnitude.
2
Note 2: The action integral, defined as i dt for the whole flash, is equivalent to the energy deposited in a 1
ohm resistor by the passage of the entire current for the duration of the flash.
Proposed NFPA 781--F93 TCD Appendix F

Appendix F System Design

F-1 The following factors should be considered in the system design.

(a) Dimensions of the building


(b) Form and pitch of the roofs
(c) Nature of the roofing
(d) Metal parts of the roof and the major external metal
(e) Items, such as gas conduits, antennas, ventilators and stairways
(f) Rainwater gutters and downpipes
(g) Projecting parts of the building and the nature of their materials (metallic and nonconductive)
(h) Most vulnerable parts of the building
(I) Arrangement of the metal pipes (water, electric, gas) of the building
(j) Any nearby obstacles that might have an effect upon the trajectory of the lightning, such as
overhead electricity lines, metal railings and trees
(k) Nature of any atmosphere liable to be particularly corrosive (petrochemical plants, cement works)
(l) Presence of any explosive or inflammable materials
(m) Presence of any sensitive equipment, such as computers, electronic systems.

Appendix G Maintenance and Inspection of ESE Lightning Protection Systems

G-1 Maintenance and Inspection of ESE Lightning Protection Systems. The effectiveness of a lightning
protection system is maintained most effectively by a quality control program designed to ensure that the
system in not degraded by age, mechanical damage, or modifications to the protected structure. Many system
components tend to lose their effectiveness over the years because of corrosion factors, weather related
damage and stroke damage. The physical as well as electrical characteristics of the lightning protection
system should be inspected and maintained in order to guarantee compliance with design requirements. A
maintenance and inspection plan should be developed to provide for periodic evaluations and timely repairs.
To the extent practical, all necessary repairs should be made immediately upon detection. This ensures that
the system can be depended upon to deliver adequate and reliable protection against lightning activity.

G-1.1 Frequency of Inspections. All new lightning protection systems should be inspected following
completion of their installation. Similarly, existing systems should receive periodic inspections to detect and
correct for deterioration, damage or inadvertent modifications having detrimental effects on the system’s
effectiveness. A lightning protection system should be inspected whenever any alterations or repairs are made
to a protected structure and following a known lightning discharge to the system. To ensure that the protection
system is properly maintained, inspections should be performed based on the following minimum criteria:

(a) A lightning protection system should be inspected visually and electrically once a year.
(b) Complete in-depth inspections of all systems should be completed every 3 to 5 years.
(c) Critical systems should be inspected visually twice a year and inspected electrically once a year.
(d) Critical systems should be inspected in-depth every 1 to 3 years, depending on the occupancy or the
environment in which the protected structure is located.

G-1.2 Inspection Cycles. To ensure the systems are tested during all four seasons over a 6 year period, 7
month and 14 month inspection cycles are suggested.
Proposed NFPA 781--F93 TCD Appendix G

G-1.2.1 Visual (7 Month) Inspection. The lightning protection system should be inspected visually every 7
months for evidence of corrosion, broken wires and changes detrimental to the efficiency of the system, among
other problems. Visual inspections are made to ascertain the maintenance requirements of the system and to
ensure that:

(a) The system is in good repair.


(b) There are no loose connections that might result in high resistance joints (bonds).
(c) No part of the system is weakened by corrosion or vibration.
(d) All down conductors and ground terminals are intact (nonsevered).
(e) All down conductors are routed smoothly and contain acceptable bend radii.
(f) All conductors are fastened securely to their mounting surfaces and are protected against accidental
mechanical displacement as required.
(g) There are no new additions or alterations to the protected structure that need further protection.
(h) There is no visual indication of damage to surge suppression (overvoltage) devices.
(i) The system complies in all respects with this 1994 edition of NFPA 781.

G-1.2.2 Grounding Systems (14 Month) Test. The lightning protection system should be tested electrically
every 14 months. The test should be conducted in accordance with the appropriate test equipment
manufacturer’s instructions by personnel familiar with lightning protection system testing. Only those
instruments designed for earth ground system testing are acceptable for use in ground resistance testing.
Such instruments should be capable of measuring 10 ohms ± 10 percent. The instrument used to measure
bonding resistance should be capable of measuring 1 ohm ± 10 percent.

G-1.3 Complete (In-depth) Testing and Inspection. In-depth testing and inspection should include the visual
inspections described in G-1.2.1 in addition to the following:

(a) Perform tests to verify continuity of those parts of the system that were concealed (built-in) during
the initial installation and that are now accessible for visual inspection.
(b) Conduct ground resistance tests of the ground termination system and its individual electrodes, if
adequate disconnecting means have been provided. The results of these tests should be compared with
previous, or original, results and/or current accepted values for the soil conditions involved. If it is found
that the test values differ substantially from previous values obtained under the same test procedures,
additional investigations should be made to determine the reason for the difference.
(c) Perform continuity tests to determine if suitable equipotential bonding has been established for any new
services or construction that has been added to the interior of the structure since the last inspection.

G-1.4 Inspection Guides and Records. Inspection guides or forms should be filled out and maintained by the owner.

These guides should contain sufficient information to aid in the inspection process so that documenting is done on
all areas of importance relating to the methods of installation, the type and condition of system components, the test
methods and the proper recording of the test data obtained.

Existing system documentation such as records of previous inspections and test results, as-built drawings, and
historical maintenance records should be located for convenient review.

G-1.5 Maintenance and Repairs. The mechanical and electrical integrity of the lightning protection system is
dependent upon frequent intervals of scheduled maintenance and immediate corrective action on observed
discrepancies. Care should be exercised to ensure that replacement parts or components and installation
procedures meet the applicable requirements of this standard.
Proposed NFPA 781--F93 TCD Appendix G(a)

G-1.5.1 Maintenance. Preventative maintenance should be performed as an integral part of the inspection
process. The frequency of inspections, in effect, determines how often maintenance should be performed.

G-1.5.2 Repairs. Repairs needed to correct discrepancies noted during casual observation, or resulting from a
known lightning or physical event, should not be delayed until the next scheduled inspection. All repairs should
be performed as the need is detected in order to maintain system integrity.

G-1.5.3 Special Considerations. Some ESE air terminals contain low levels of radioactive material. Labeling
should conform to federal requirements. Replacement of certain ESE parts and/or system components can
require special attention to the legal disposal of radioactive substances, lead, or other materials deemed to be
environmental hazards. It is recommended that the manufacturer be consulted before disposing of any
system components.

G-1.6 Records and Test Data. The inspecting personnel should compile and maintain records pertaining to:

(a) Past inspection results as detailed in the completed inspection guides and forms.
(b) Detailed maintenance records specifying scheduled replacements, repairs and modifications
to the lightning protection system.
(c) Updated as-built drawings of the lightning protection system.
(d) Resistance measurements of the various parts of the ground termination system.
(e) Known deviations from the requirements contained in this standard.

Appendix H Referenced Publications

H-1 The following documents or portions thereof are referenced within this standard for informational purposes
only and thus are not considered part of the requirements of this document. The edition indicated for each
reference is the edition dated as noted below:

H-1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101,
Quincy, MA 02269-9101.
NFPA 70, National Electrical Code, 1993 edition.
NFPA 780, Lightning Protection Code, 1992 edition.

H-1.2 ANSI/IEEE Publications. Institute of Electrical and Electronic Engineers, Inc.


345 East 47th St., New York, NY
ANSI/IEEE C-62.1-1984, Surge Arrestors for Alternating Current Systems
ANSI/IEEE 141-1986, Recommended Practice for Electric Power Distribution for Industrial Power Plants

H-1.3 U.S. Government Publication. Superintendent of Documents, U.S. Government Printing Office,
Washington, DC 20401.
MIL-HDBK 419A, Volume 1 of 2, Grounding, Bonding and Shielding for Electronic Equipment