IEC 61850 Makes Substations Smarter

01 IEC 61850 Substation Overview


Go from wire-crazy to wire-smart with IEC 61850

Since substation environments can be extremely harsh, the Introduction Why Invest in an IEC 61850 Substation?
equipment used at a substation must be able to operate over a Power substation technology has evolved considerably since the Whether you’re looking to retrofit an existing substation, or build
first power distribution system went into service in the late 1800’s. a new one from the ground up, the advantages of implementing
wide temperature range, and be designed to meet electromagnetic Today, several hundred thousand substations of various sizes and the IEC 61850 standard are the same:
compatibility (EMC) requirements. In addition, the products you varieties are in operation around the world, with both retrofit and
Simplified Architecture: The thousands of IEDs in a modern
use must be IEC 61850 certified, resistant to electromagnetic new substation projects being initiated with increasing frequency.
substation use localized intelligence to handle much of the
To get a better handle on the enormity of the situation, one study
interference (EMI), and be able to withstand periods of high decision making required at the local site, and communicate with
(Pike Research) estimates that 150,000 substations are expected
vibration. One of customers’ main concerns is that the devices are to be fully automated by the year 2020.
other devices via Ethernet switch, which themselves are
rugged and robust enough, since highly reliable, rugged solutions connected to the substation’s Ethernet network.

can reduce downtime, and minimize maintenance requirements Let's take a close look at the benefits and advantages offered by Greater Reliability: By design, the IEC 61850 standard places
the IEC 61850 standard. While the prospect of implementing such great emphasis on reliability. Not only are many of the devices
and wear-and-tear.
a complex set of rules, regulations, and stringent specification required to be rugged enough to withstand extreme
requirements may at first seem daunting, the advantages by far environmental conditions, you can expect the network itself to be
outweigh the disadvantages. For example, whereas the thousands redundant on many different levels.
of devices making up a traditional substation use hard-wired
device-to-device connections running relatively low speed serial Future-Proof Design: One of the major advantages of
connections over copper wiring, the IEDs (intelligent electronic implementing an Ethernet network is that it is easy to expand
devices) in a modern IEC 61850 substation connect to a when the need arises. In addition, any new products that
high-speed Ethernet bus, making it relatively easy to implement a connect to an existing IEC 61850 substation are required to be
comprehensive management, maintenance, and control strategy fully compatible with what’s already there.
via a centralized power SCADA system.
Vendor-Independence: The fact that IEC 61850 products
produced by different companies are all required to speak the
same language gives substation System Integrators (SIs) a huge
advantage, since they can pick and choose the best products
from different vendors.

1 2
www.moxa.com/SmartGrid www.moxa.com/substation
IEC 61850 Makes Substations Smarter

What is IEC 61850? The Architecture of an IEC 61850 IEC 61850 Communication
The non-proprietary IEC 61850 standard uses modern object Substation IEC 61850 is a substation automation standard that is part of The example in the following figure illustrates how
oriented programming principles to define a complete virtual The IEC 61850 standard divides substation operation into three the International Electrotechnical Commission's (IEC) Technical the three protocols contribute to substation
model of the substation, which can be tested and tweaked in a distinct levels: Committee 57 (TC57) reference architecture for electric power communication.
computer model before being implemented with actual systems. The transmission protocols used to handle specific
devices. Since the standard is open, any hardware vendor can Process Level: The process level comprises devices such as types of data transfer are one of the main aspects of the Step 5.
provide IEC 61850 compliant products, giving substation circuit breakers and data acquisition equipment used to IEC 61850 standard. The abstract data models defined in ALARM
ALARM
engineers the freedom to pick and choose the best products measure the current, voltage, and other parameters in different IEC 61850 can be mapped to a number of protocols, including ALARM
Power SCADA Server
for their particular project. Highlights of the standard include: parts of the substation. MMS (Manufacturing Message Specification), Step 4.
MMS The line has been
Bay Level: The bay level consists of the IEDs that collect the GOOSE (Generic Object Oriented Substation Events), and cut!
The main data pathways use Ethernet-based communication, measurements provided by the process level. The IEDs can SMV (Sampled Measured Values). These protocols can run
Step 3.
with high bandwidth trunk lines used to transmit data packets make local control decisions, transmit the data to other IEDs, over high speed TCP/IP networks to ensure the fast response Okay, I tripped the
circuit breaker.
sent from multiple devices connected to the network. or send the data to the substation SCADA system for further time (< 4 ms) needed for protective relays. SMV Protection GOOSE Step 2.
Relay It's over the limit!
processing and monitoring. Trip the circuit breaker!
Guaranteed compatibility with IEC 61850 compliant products Station Level: The station level is where you’ll find SCADA MMS: Substation status information used for monitoring
from different vendors, making it much easier to expand a servers and HMIs, as well as the human operators (if needed) purposes is sent using the Manufacturing Messaging
POWER LINE
substation’s operation when the need arises. who monitor the status of the substation. Specification protocol. Merging Unit Intelligent Control Unit
GOOSE: Critical data such as control signal and warnings are Step 1.
Current
The IEC 61850 standard makes heavy use of the XML-based Station Level Equipment sent using the Generic Object Oriented Substation Event Current
Current
substation configuration language (SCL) to define the protocol. Current overload!!
Station Level
configuration parameters of the multitudes of IEDs used in the Station Bus SMV: Power line current and voltage measurements are sent
substation. using the Sampled Measured Values protocol.
Station Level Equipment
Bay Control Bay Protection Step 1: After sensing that the current in the power
High speed IED-to-IED communication with transfer times line is too high, a merging unit sends a
Bay Level
guaranteed using priority tagging of the Ethernet frames. Process Bus message using the SMV protocol to a
MMS Traffic For monitoring substation status
protection relay.
The transfer time requirements for Current/Voltage
Station Level Equipment
Transformer
Circuit Breaker
different types of transfers Step 2: The protection relay uses the GOOSE
Process Level
protocol to notify the intelligent control unit
Transfer Transfer time
Type of transfer For status updates and sending to trip the circuit breaker.
time class (ms) GOOSE Traffic command requests
Furthermore, the IEC 61850 standard defines a Process Bus
TT0 >1000 Files, events, log contents Step 3: After switching the power off, the intelligent
and Station Bus, as illustrated in the following diagram. The
TT1 1000 Events, alarms Process Bus handles communication between the Process control unit uses the GOOSE protocol
Level and the Bay Level, and the Station Bus handles to notify the protection relay that the power
TT2 500 Operator commands For transmitting power line
communication between the Bay Level and Station Level. SMV Traffic current and voltage values has been cut.
TT3 100 Slow automatic interactions

TT4 20 Fast automatic interactions Station Level Equipment Step 4: The protection relay uses the MMS protocol to
notify the power SCADA server that the power
TT5 10 Releases, status changes Station Level
Station Bus line has been cut.
TT6 3 Trips, blockings
Bay Control Bay Protection Step 5: The power SCADA server issues an alarm.
Reference: IEC 61850-5
Bay Level
Process Bus

Instrument Transformer Circuit Breaker

Process Level

3 4
www.moxa.com/SmartGrid www.moxa.com/substation
IEC 61850 Makes Substations Smarter

The Evolution of Substation


Automation

Conventional Substation Automation Substation Automation with Substation Automation with PRP/HSR: The Next Wave of IEC 61850
IEC 61850 Station Bus IEC 61850 Station and Process Bus

SCADA Server HMI SCADA Server HMI SCADA Server HMI

Station Cubicles Station Cubicles Station Cubicles


SCADA Cubicle HMI

IEC 61850 IEC 61850


Station Bus Station Bus LAN A LAN B

PRP PRP

Coupling Coupling

Point-to-Point Protection Relays


Hard-Wired
Protection
Protection Relays Relays
Point-to-Point IEC 61850
Hard-Wired HSR
Process Bus

Protection Cubicles Control Cubicles

Digital Sensor and Digital Sensor and Digital Sensor and


Bay Cubicles Control Units Bay Cubicles Control Units Bay Cubicles Control Units

Point-to-Point
Copper Wire

Gas Insulated Substation

Gas Insulated Substation Gas Insulated Substation Gas Insulated Substation

In the 1960’s a conventional substation was rather The release of the IEC 61850 Station Bus protocol in the In 2005, the IEC 61850 standard was greatly improved by The latest development in the IEC 61850 standard was the
bulky, with copper or fiber wiring used to hard-wire 1980’s was a big first step forward on the way to implementing defining a Process Bus to connect the Process Level with inclusion of the PRP/HSR protocol in 2010. PRP/HSR (parallel
one device to another. a substation-wide all-purpose network. the Bay Level. redundancy protocol / high-availability seamless redundancy)
specifies how to use two Ethernet networks to ensure
seamless failover if one of the redundant networks fails.

5 6
www.moxa.com/SmartGrid www.moxa.com/substation