Вы находитесь на странице: 1из 1

KFD2-UFC-Ex1.

D
Technical Data
POWER SUPPLY Power Rail or terminals 23+, 24- 1-Channel
Rated voltage 20-30 VDC Frequency Converter
Rated current ≤ 100 mA
INPUT (intrinsically safe) Terminals 1+, 3-
Nominal data NAMUR, ≈ 8 VDC; ≈ 8 mA Model Number
Input pulse length/interval ≥ 50 µs/≥ 50 µs KFD2-UFC-Ex1.D
OUTPUT (not intrinsically safe)
• 1-channel
Output 1, 2 (SPDT relay) Terminals 10, 11, 12; 16, 17, 18
• 24 VDC supply/Power Rail compatible
Contact load 250 VAC/2 A/cos ø ≥ 0.7; 40 VDC/2 A
Mechanical life 5 x 107 switching cycles
• Analog and digital outputs
Energizing/de-energizing ≈ 20 ms/≈ 20 ms • Current source output: allowable .
Output 3 (passive transistor) Terminals 19+, 20
load ≤ 650 Ω
Logic 1 (L+) - 2.5 V (50 mA, short-circuit/overload proof) • Start-up override
Logic 0 Switched off (off-state current ≤ 10 µA) • Lead breakage (LB) and short-circuit (SC)

K-System Logic Controls/Trip Amplifiers


Output 4 (current source) Terminals 8+, 7- monitoring
Open circuit voltage ≤ 24 VDC • Operating range 0.001-5,000 Hz
Output current 0-20 mA or 4-20 mA • Push button and PC programmable
Error signal Downscale ≤ 3.6 mA, upscale ≥ 21.5 mA • SIL 2 according to IEC 61508; SIL 3 in a
Load ≤ 650 Ω redundant structure
CERTIFICATES See page 232 for entity parameters
This universal frequency converter converts a digital
No. 116-0200
input signal into an analog output signal for connection
No. 116-0202 to standard current input devices. A passive transistor
Zone 0, 1, 2 TÜV 99 ATEX 1471, II (1) G D [EEx ia] IIC output isolates and transfers the digital input signal. Two
relay outputs can be programed to actuate at desired
Zone 2 TÜV 02 ATEX 1885 X, II 3 G EEx nAC IIC T4 frequencies. The unit is programmable by using push
Exida P+F 04/03-15 R016 buttons on the front panel or with a PC and the PACTware
configuration software. A debounce circuit eliminates
MECHANICAL
extraneous signals from relay bounce. Lead breakage and
Housing Type C3 see page 454
short circuits in the sensor are indicated by a red LED and
Dimensions 4.65" x 1.57" x 4.53" (118 x 40 x 115 mm) through the collective error output via Power Rail.
Weight 10.6 oz. (≈ 300 g)
Note: For information about programming, refer to our
AMBIENT TEMPERATURE -4°F to +140°F (-20°C to +60ºC)
website at www.am.pepperl-fuchs.com

Engineer's Guide (page 7)


Accessories (page 443)
Power Supplies (page 401)
Surge Suppression (page 413)
Connection Diagram Lastest Info. Avail. Online

Class I; Div 1, 2 Front View


Zone 0, 1, 2 Removable terminal
blue
Hazardous Area Safe Area, Div 2 or Zone 2
Housing type C3 LED green:
KFD2-UFC-Ex1.D (see system description) Power supply
11
Input 1 10 Output 1
(+) 1 12
R2 17 LED yellow/red: Control panel
R1 16 Output 2 Input pulses/
R1 18 Fault signal
(–) 3 19 (+) Keypad
Output 3
20 (–) LED yellow:
LB/SC LB/SC LB RxD 8 (+) Output 4 Output 1-3
TxD Programming 0/4-20 mA
Jack 7 (–)
GND
13 (+) Start Up
R1 = 10 kΩ 14 (–) Override
400Ω ≤ R2 ≤ 2 kΩ 23 (+)
Supply
24 (–) 24 VDC
Programming jack
Collective Error Messaging
Power Rail Connection

Removable terminals
green

USA Headquarters web: www.am.pepperl-fuchs.com


phone: 330 486-0002 • email: sales@us.pepperl-fuchs.com
Worldwide Headquarters web: www.pepperl-fuchs.com
phone: +49 621 776-0 • email: pa-info@de.pepperl-fuchs.com
Asia Pacific Headquarters web: www.pepperl-fuchs.com
phone: +65 67799091 • email: sales@sg.pepperl-fuchs.com 221