HAZARDOUS AREA CLASSIFICATION WORK FLOW

EQUIPMENT OPERATING P & T SUBSTANCE CONTAINMENT VENTILATION CLASSIFY EXTENT

NON-ENCLOSED
/
OUTDOOR
START
GAS/VAPOR/LIQUID

ENCLOSED YES OIL & GAS NO


/ ADEQUATE? ?
INDOOR

NO/NOT SURE YES


1. Phase
2. Relativity of density
to air CHECK ZONE
VENTILATION OR
3. Flash Point ADEQUACY DIVISION
4. Auto-Ignition Point NFPA
497
5. Gas Group
6. Liquid Group
(optional) DIVISION ZONE
YES
ADEQUATE? YES
SUFFICIENT? FINISH

NO
NO
CONDUCT
DISPERSION
STUDY API 505

API 500

OUTDOOR UNCLASSIFIED

FIGURE:

ZONE
UNRESTRICTED/NO WALL ZONE
OR
DIVISION
DIVISION FIGURE:
DESCRIBE THE
1. Auto-Ignition Point
DESCRIBE THE
EQUIPMENT OPERATING DUST 2. Dust Group
CONDITION 3. Particle Density OPEN/SEMI-OPEN
(optional) WALL

FIGURE:
ZONE
ZONE
OR
WALLED-OFF DIVISION
DIVISION
FIGURE:
EQUIPMENT
INDOOR
ENCLOSURE

1. Operating Pressure YES


FIGURE: SUFFICIENT?
1. Tag No. 2. Operating ZONE
2. Equipment Temperature UNRESTRICTED/NO WALL ZONE
Name 3. Flow Rate (optional) OR
CONDUCT DIVISION NO
4. Capacity (optional)
DISPERSION DIVISION
STUDY FIGURE:

YES WALL
ENCLOSED
FIGURE:
ZONE
STILL ZONE
INSUFFICIENT OR
NO ? WALLED-OFF DIVISION
DIVISION
FIGURE:

REVIEW
CONDITION

FIBER/FLYINGS NFPA 70