Вы находитесь на странице: 1из 13

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO.

5, MAY 2014 2139

An Adaptive Prefiltering Method to Improve the


Speed/Accuracy Tradeoff of Voltage Sequence
Detection Methods Under Adverse Grid Conditions
José Matas, Miguel Castilla, Jaume Miret, Member, IEEE, Luis García de Vicuña, and Ramon Guzman

Abstract—This paper deals with the improvement of the tran- produce visual flicker in the range between 0.5 Hz and 30 Hz
sient response and harmonic, subharmonic, and dc-offset voltage [6]. The grid voltage can also contain dc-offset due to saturation
rejection capability of a grid voltage sequence detection scheme in current transformers or to grid faults [7]. In this scenario, the
based on a second-order generalized integrator (SOGI). To per-
form that, the SOGI structure is first analyzed in deep, empha- power converters connected to the grid should provide stable
sizing both its tradeoff limits between settling time and harmonic operation even during faults and network disturbances. One
attenuation and the sensitivity to grid subharmonics and dc-offset of the most severe conditions that a power inverter must face
voltage. Then, a study of the effect of grid voltage harmonics and is the operation during voltage sags [8]–[10]. Most sags are
subharmonics in SOGI and in the SOGI-FLL and MSOGI-FLL unbalanced and produce ripple and harmonics in the delivered
structures is introduced. Hence, to overcome these problems, a
new structure based on the use of the SOGI filter as prefilter power, deteriorating the power quality of the system [11]–[13].
for the previous structures is proposed to achieve a faster time Different control schemes can be found in literature to over-
response and higher harmonic rejection. This structure is used in come these problems in which the current controller and the
a sequence detection scheme for the detection of the grid voltage employed synchronization technique play an important role
components in the αβ-frame and it is applied in a three-phase [14]–[21]. In these controllers a fast and accurate detection
PV system. Experimental and comparative results are shown to
validate this proposal. of the positive and negative sequence components of the grid
voltage is a crucial issue during unbalanced voltage sags.
Index Terms—Distributed generation, generalized integrators, Several methods for synchronization and grid-voltage monitor-
grid offset voltage rejection, grid voltage sequence detection,
power quality, subharmonic rejection, voltage sags. ing under polluted and variable-frequency environments have
been presented [22]–[34]. Usually phase-locked loop (PLL)
I. I NTRODUCTION in a synchronous reference frame is used to detect the phase
angle, amplitude, and frequency of the grid voltage [24]–[42].

T HE electrical networks are becoming more distributed


due to the necessity of more clean, reliable, and flexible
ways to produce and deliver energy. The increasing penetra-
However, its performance is deteriorated when the utility grid
is unbalanced. To overcome this obstacle, an enhanced PLL
(EPLL) [24], [25], a quadrature PLL (QPLL) [26], and a PLL
tion of nonlinear loads is creating a growing concern for the based on a generalized integrator (GI) [38]–[40] and named as
quality of the ac supply system. Nonlinear loads such as cy- “second-order generalized integrator” SOGI-PLL [41], [42] had
cloconverters, arc furnaces, integral cycle controlled furnaces, been reported. The EPLL consists of a frequency-adaptive filter
pulse-burst-modulation power conditioners, rectifiers supplying whose frequency follows the fundamental frequency of the grid.
cyclic loads, motors driving cyclic loads, and adjustable speed The QPLL is designed by using the estimation of the in-phase
drives can produce interharmonic or subharmonic voltage fluc- and quadrature-phase amplitudes and the frequency of the fun-
tuations [1]–[4]. Subharmonics can also be produced by wind damental input signal. Finally, the SOGI-PLL has a GI as main
generators that deliver low frequency power due to wind speed block that generates in-phase and quadrature-phase sinusoidal
variations, the wind gradient, and the tower shadow effect [5]. components of the input signal. A comparative study of these
The frequency of these subharmonics can be very low and structures was reported in [43] and [44] for single-phase and
three-phase systems. In [45] a structure simplification of the
SOGI-PLL that replaces the PLL by a frequency-adaptive loop
Manuscript received October 18, 2012; revised February 7, 2013 and SOGI-FLL was introduced. The FLL estimates the frequency
April 12, 2013; accepted May 26, 2013. Date of publication July 23, 2013; date of the input signal and was used to tune the SOGI, or GI, with
of current version October 18, 2013. This work was supported by the Ministerio the grid voltage frequency. In [46] a multiple SOGI (MSOGI-
de Economía y Competitividad of Spain under Project ENE2012-37667-
C02-02. FLL) is proposed that uses a cross-feedback network consisting
J. Matas, M. Castilla, J. Miret, and L. García de Vicuña are with the De- of multiple SOGIs to reject the harmonics from the grid. The
partment of Electronic Engineering, Technical University of Catalonia (UPC), MSOGI-FLL is designed to achieve a fast response, but its
08800 Vilanova i la Geltrú, Spain (e-mail: jose.matas@upc.edu).
R. Guzman is with the Department of Signal Theory and Communications, response can be distorted by interhamonics in the input signal.
Technical University of Catalonia (UPC), 08800 Vilanova i la Geltrú, Spain. This paper first analyzes in detail the relationship between
Color versions of one or more of the figures in this paper are available online damping factor, harmonic attenuation, and settling time of the
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TIE.2013.2274414 SOGI structure, which restricts the SOGI performance when

0278-0046 © 2013 IEEE


2140 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

In this system, the power flow is balanced through the control


of the dc-link voltage, vdc . The inverter is connected to the
point of common coupling (PCC) by a LCL filter to reduce the
amount of high frequency harmonics injected to the grid.
The grid voltage can be affected by the fault produced some-
where in the distribution network.

B. Voltage Sag
Fig. 1. Block diagram of a grid connected PV system.
A voltage sag is an abnormal short-time reduction in one or
applied to the detection of the sequence components of the more phases of the grid voltages produced mainly by short-
grid voltage. This analysis reveals the high sensitivity of the circuits between phase and ground, between phase to phase
SOGI quadrature-phase output to input subharmonics and dc- (to ground), and the start-up of large motors [8]. The most
offset voltage, because the transfer function of this output widely accepted classification of voltage sags is presented in
behaves like a low-pass filter. The subharmonic sensitivity [10]. Voltage sags in a three-wire system can be characterized
produces an important deterioration of the SOGI performance in the stationary reference frame (SRF) as
and noticeable errors in its output signals. In the case of dc- vα = vα+ + vα− (1)
offset its effect is dangerous because produces the failure of
the SOGI system and the malfunction of the sequence detection vβ = vβ+ + vβ− (2)
system. This analysis is extended to the FLL, SOGI-FLL, and
MSOGI-FLL structures to evaluate the scope of the problem. where vα+ and vβ+ are the positive sequence voltages in the
To solve these problems, this paper proposes a simple new SRF and vα− and vβ− are the negative ones. These positive and
structure based on the use of the SOGI filter as prefilter for the negative voltage sequences can be represented as
previous structures. This structure can reject grid subharmonics
and grid dc-offset voltage and it has a faster settling time and vα+ = V + cos(wt + ϕ+ ) (3)
better filtering capability. Hereafter, as an application example, vβ+ =V +
sin(wt + ϕ ) +
(4)
this solution is proposed in a double SOGI-FLL (DSOGI-FLL)
in the αβ-frame for the grid voltage sequence detection in a vα− = V − cos(−wt − ϕ− ) (5)
three-phase photovoltaic (PV) system. Experimental results of vβ− −
= V sin(−wt − ϕ ) −
(6)
this structure are presented and compared with the sequence
detection scheme proposed in [45]. where V + and V − are the amplitudes of the positive and
This paper is organized as follows. Section II describes the negative sequences respectively, ϕ+ and ϕ− are their respective
power system. Section III analyzes in detail the SOGI structure initial phase angles, and w is the grid frequency. The grid fault
and reveals its limitations and problems with subharmonics and can be characterized by the voltage unbalance factor (V U F )
dc-offset. Section IV proposes an analysis of the harmonic and [51], which describes the amount of unbalance in the system as
subharmonic influence on the FLL, SOGI-FLL, and MSOGI- the ratio between negative and positive voltage amplitudes
FLL structures. Section V proposes the use of a SOGI prefilter    2
as a solution. Section VI proposes the application of this (vα− )2 + vβ−

structure as a voltage sequence detection block of the grid V
V UF = =  2 . (7)
voltage components on a three-phase PV system. This section V+  2
also presents the experimental and comparative results of this vα+ + vβ+
structure in a PV system. Section VII is the conclusion of
this work.
C. Three-Phase Inverter Control Under Grid Faults

II. S YSTEM D ESCRIPTION The behavior of an inverter during a fault is determined


by the injected currents at the PCC. A fast reference current
This paper deals with an enhanced grid voltage sequence generator is required to react properly to the fault. Fig. 2 depicts
detection method, which reveals its superior performance dur- the block diagram of the grid fault controller. The controller
ing adverse grid conditions. A PV application is chosen to inputs are the measured phase voltages v at the PCC, the current
introduce the proposed sequence detection method in a practical i flowing through the Li inductors, and the dc-link voltage. Volt-
environment. age v and current i are transformed into SRF values. Voltages vα
and vβ are then decomposed into symmetric components using
a sequence detection block. The dc-link voltage regulator is in
A. PV Three-Phase Inverter System
charge of setting the active power reference P ∗ that keeps the
Fig. 1 depicts the configuration of a PV system, which is power balance. The symmetric components of the grid voltage
composed by a PV source, a dc-link capacitor, a three-phase and P ∗ are conveyed to the reference generator to build the
three-wire inverter, and an LCL filter. reference currents i∗α and i∗β . This generator determines the
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2141

Fig. 3. SOGI block diagram.


Fig. 2. Control diagram of the grid fault controller.

control strategy to operate with the fault [16], [17]. The next
block corresponds to the current control and space vector pulse
width modulator (SVM) to commute the inverter switches, u1
to u6 .
Reactive power injection is not considered in this application
in agreement with the international standards for interconnect-
ing low rated power PV systems with the utility grid [49].
The positive sequence voltages are obtained from the grid
voltage by
 +  π  
vα 1 1 −e−j 2 vα
= . (8)
2 e−j 2
π
vβ+ 1 vβ

There are several control strategies for setting the current


references to operate the three-phase inverter during voltage
sags [16], [17]. For this study, a control strategy that consists of
following the positive sequence of the grid voltage is adopted Fig. 4. Magnitude plots of Hd(s) and Hq(s) for ξ = 0.707.
[17]. This strategy generates sinusoidal and balanced currents
during the fault. The expressions of the current references when A. SOGI Tradeoff Relationship Between Bandwidth and
using this strategy are Settling Time

2 P ∗ vα+ Fig. 3 depicts the block diagram of a SOGI structure. The


i∗α = 2   2 (9)
3
SOGI is a frequency-adjustable resonator that is damped by an
vα+ + vβ+ outer loop [38], [39]. This external loop introduces the error e
between resonator output and the input signal in the resonator
2 P ∗ vβ+ input through a gain 2ξ. The parameter ξ is the damping factor
i∗β =  2 . (10)
3 
+ 2 of the system.
vα + vβ+
The SOGI outputs are vd and vq , which are, respectively, in-
phase and quadrature-phase with the input signal vin . From the
The dynamics of the controller shown in Fig. 2 are mainly de-
input-to-output point of view, the SOGI behaves as a bandpass
termined by the sequence detection block. In fact, the transient
filter (BPF) for vd , and as a low-pass filter (LPF) for vq , with
response of this block must be fast enough to ensure the absence
the following closed-loop transfer functions
of overshoots in the injected current that may cause converter
damage. In this paper, the SOGI algorithm [39] is chosen as a vd (s) 2ξwo · s
Hd (s) = = 2 (11)
basic sequence detector block for comparison purposes. In the vin (s) s + 2ξwo · s + wo2
next section, the limitations of the SOGI algorithm are analyzed
in detail. vq (s) 2ξwo2
Hq (s) = = 2 (12)
vin (s) s + 2ξwo · s + wo2

III. P ROBLEM I DENTIFICATION : SOGI L IMITS AND where wo is the SOGI input frequency. The Bode magnitude
S UBHARMONIC AND DC-O FFSET P ROBLEMS plots of (11) and (12) are depicted in Fig. 4 for ξ = 0.707.
According to (11) and (12), the main parameters related
As described above, there are several detection methods with the SOGI time response and filter selectivity are the
reported in literature to extract voltage sag information at run- settling time
time. These methods share a practical limitation to be able
to achieve a fast time response to voltage sags. This issue is 4
ts ≈ (13)
discussed here in detail using the SOGI structure. ξwo
2142 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

Fig. 6. Structure of the SOGI-FLL.

Fig. 5. Time response of the SOGI vd and vq outputs for an input signal (vin
of 50 Hz/220 Vrms and 1 Hz/10% of vin subharmonic, and wo = win ).

and the SOGI bandpass filter gain at a given harmonic h of the


fundamental frequency wo

2ξ · h
|Hd (jhwo )| = (14)
(1 − h2 )2 + (2ξ · h)2

where 0 < ξ < 1 and h is an odd integer number. Taking into


account the typical h values 3, 5, 7, and so on, then (14) can be
further simplified to


|Hd (jhwo )| ≈ . (15)
h

From (13)–(15) it can be seen that the SOGI has a tradeoff


relationship between harmonic attenuation and settling time,
i.e., for small values of ξ(ξ  1) it has a strong harmonic
attenuation, but at an expense of a very long settling time.

B. DC-Offset and Subharmonic Impact on SOGI


Quadrature-Phase Output Signal Fig. 7. Structure of the MSOGI-FLL.

The presence of subharmonics and dc-offset in the input B. MSOGI-FLL


signal have a direct impact on the SOGI quadrature-phase
output, since this output behaves has a LPF with gain 2ξ; Fig. 7 shows a Multi-SOGI-FLL scheme [46]. This structure
see Fig. 4. To evaluate this problem, Fig. 5 shows the SOGI is able to extract fundamental and multiple harmonic compo-
response to a subharmonic of 1 Hz and a 10% of vin amplitude. nents using multiple SOGI filters connected in parallel. The
As seen in Fig. 5, this subharmonic is directly translated to extracted signals are cross-feedback canceled from the inputs
the output vq and can produce problems and distortion in all of the multiple SOGIs to obtain fundamental and harmonic
the SOGI-based structures such as the SOGI-FLL and MSOGI- components without harmonic distortion. The MSOGI-FLL
FLL. Moreover, when vin contains dc-offset it causes the failure can be used to obtain the amplitude, frequency, fundamental
of these structures, so they cannot be used in this situation. and harmonic components, and positive and negative sequence
components of the grid voltage. However, this structure has a
high sensitivity to unknown, or spurious, interhamonics and
IV. H ARMONICS AND S UBHARMONIC E FFECTS subharmonics in the input signal. Moreover, the accuracy in
ON FLL, SOGI-FLL AND MSOGI-FLL the obtained components can be affected when the input signal
harmonics are in a narrow range [46]. For instance, an extracted
A. SOGI-FLL
second-harmonic component (100 Hz) can be partially influ-
Fig. 6 shows the scheme of the SOGI-FLL [45]. The FLL enced by the fundamental component (50 Hz) of vin , because
block is used to tune the SOGI filters with the grid frequency. both frequency components are very close each other. To avoid
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2143

these collateral interferences, the damping factor should be low


to set a very narrow bandwidth, which would make the system’s
response too slow [46].

C. Ideal Phase-Detector Operation


As can be seen in Fig. 6, the kernel of the FLL is a phase
detector (PD), which consists of the product of the error, e =
vin − vd , with vq . The PD can be analyzed as in a conven-
tional PLL. Assuming that vin , vd and vq are pure sinusoidal
signals, that is vin = A sin(wt + θ), vd = A sin(ŵt + θ̂) and
vq = −A cos(ŵt + θ̂), where we = w − ŵ and θe = θ − θ̂ are
the frequency and phase errors between the input and the
estimated signals, respectively. Then, the PD output can be
written as


e · vq = − A sin(wt + θ) − sin(wt + θ̂) A cos(ŵt + θ̂)
 
A2 (we t + θe )
=− sin(we t + θe ) + 2 · sin
2 2 Fig. 8. Steady-state response of the FLL to a 50 Hz input signal for the SOGI-
 FLL and MSOGI-FLL: (a) with a third-harmonic and 15% of vin ; (b) with a
1 Hz subharmonic and 10% of vin . (ξ = 0.707 and γ = 0.4 rad/V2 ).
· sin(2ŵt + φ) (16)

distortion in the PD produces ripple in the estimated frequency,


which, assuming that the FLL is locked in steady state (ŵ ≈
which causes additional distortion in the SOGI outputs.
w), can be simplified to
  
A2 θe
e · vq = − sin(θe ) + 2 · sin · sin(2wt + φ) (17) E. Harmonics and Subharmonics Effects on the SOGI-FLL
2 2
and MSOGI-FLL
where φ = tg −1 (sin(θe )/(cos(θe ) − 1)). This last expression The SOGI-FLL and MSOGI-FLL have been simulated to
shows that the PD generates a small dc signal and a second determine the impact of harmonics and subharmonics on the
harmonic term of the input frequency. FLL outputs. The simulations are for an input signal with
a 15% of a third-harmonic and also for 10% of a 1 Hz
D. Harmonics and Subharmonics in Phase-Detector subharmonic. The filter parameters are ξ = 0.707 and γ =
0.4 rad/v2 . The MSOGI-FLL is designed to reject fifth, sev-
Now, considering that the input signal contains odd enth, and 11th-harmonics. However, the third-harmonic is also
harmonics considered, in this case, as it was an unknown interharmonic
to test the MSOGI-FLL and SOGI-FLL behavior to spurious
vin = A sin(wt + θ) + f (3w, 5w, 7w, . . .) (18)
interhamonics.
the PD output when the system is locked in steady state can be Fig. 8(a) shows the results for the case of a third-harmonic.
written as Note in this figure that the ripple distortion in MSOGI-FLL
is higher than in SOGI-FLL. This phenomenon is due to the
A2 ripple in the FLL output that distorts the outputs of all the
e · vq = − [sin(θe ) + fm (3we , 5we , 7we , . . .)
2 SOGI blocks (inside of the MSOGI-FLL), which are feedback
+ fn (2w, 6w, 8w, . . .)] . (19) again to the cross-feedback network. Notice that the maximum
ripple in the FLL output is of 1.62 Hz for the SOGI-FLL and of
From (19), it can be seen that the PD generates even harmon- 1.73 Hz for the MSOGI-FLL.
ics of w and odd multiples of we . These harmonics distort the Fig. 8(b) shows the FLL response for the case of 1 Hz
PD output, but their impact is attenuated by the SOGI BPF and subharmonic. In this figure, it can be seen that the steady-
LPF behavior for frequencies that are among wo . Therefore, the state response of the SOGI-FLL and MSOGI-FLL are almost
SOGI should be very selective if a strong rejection to harmonics identical and that the ripple is very important. Note that the
is required, which in turns implies a longer settling time. A maximum ripple is of 3.88 Hz and the distorted waveform has
detailed expression of the PD output for an input signal with a 50 Hz carrier frequency modulated by a 2 Hz subharmonic.
a third-harmonic is shown in the Appendix. In the case of To assess the impact of the FLL ripple at the SOGI outputs
subharmonics a similar expression to (19) can be obtained. we propose the method shown in Fig. 9. This method consists
However, as shown in Fig. 4, the subharmonics go directly of subtracting the outputs of a SOGI that works at constant
to the PD due to the flat response of the LPF vq output for frequency from the outputs of the SOGI-FLL distorted by
frequencies below wo . Then, the harmonic and subharmonic its own FLL ripple. This method has been also applied to
2144 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

Fig. 9. Block diagram used to measure the voltage distortion caused in the
orthogonal outputs of the SOGI-FLL by ripple in the FLL output.

Fig. 11. Steady-state amplitude distortions in the outputs of the SOGI-FLL


and MSOGI-FLL due to ripple in the FLL output frequency for an input signal
with a 10% of 1 Hz subharmonic.

A. Use of SOGI Filter as Prefilter as Solution for


Subharmonics and Harmonics
In Fig. 12 appears the proposed solution to overcome sub-
harmonic and dc-offset voltage problems in the vq output. The
idea consists of the series connection of two SOGI structures.
The first one is used as a bandpass prefilter. The second one is
a SOGI-FLL that allows obtaining the estimated frequency of
the input signal. The first SOGI is adaptively tuned using the
frequency provided by the second SOGI-FLL. This structure
will be referred as SOGI-FLL with prefilter (SOGI-FLL-WPF)
from now on.
The SOGI-FLL-WPF alleviates the negative effect of grid
Fig. 10. Steady-state amplitude distortions in the outputs of the SOGI-FLL subharmonics and improves the system response in relation to
and MSOGI-FLL due to ripple in the FLL output frequency for an input signal
with of a 3rd-harmonic and 15% of vin . grid harmonics. It is worth remarking that the main characteris-
tics of this structure are as follows.
the MSOGI-FLL using a second MSOGI block operating at 1) The estimated frequency ripple is much lower than a
constant frequency. The measured results are shown in Figs. 10 SOGI-FLL or MSOGI-FLL, allowing a fine-tuning of
and 11. SOGI filters.
Fig. 10 shows the measured voltage distortions in vd and 2) The quadrature-phase signal is much less affected by input
vq for the case of a third-harmonic. It can be seen that the subharmonics than a simple SOGI-FLL, or MSOGI-FLL.
distortion in vd reaches 7.6 V for the SOGI-FLL and 7.4 V for A considerable improvement in the quadrature-phase out-
the MSOGI-FLL. For vq the distortion reaches 11.6 V for the put signal is obtained.
SOGI-FLL and 10.2 V for the MSOGI-FLL. 3) It enhances the harmonic rejection of the system and
Fig. 11 shows the distortion induced for the case of 1 Hz reduces the amplitude distortion in the in-phase and
subharmonic. Notice that the SOGI-FLL and MSOGI-FLL quadrature-phase output signals.
distortions are identical. The maximum distortion in vd is of 4) It can be used as a prefilter connected in series to the
30 V and in vq is of 40 V. As it can be seen these distortions are MSOGI-FLL to obtain a better behavior in front of input
very important and deteriorate the response of these systems. subharmonics or harmonics.
All these distortions are summarized in Table I. To analyze the benefits of the SOGI-FLL-WPF structure in
comparison with the SOGI-FLL and MSOGI-FLL, the same
previous simulations of Section IV have been performed for
V. P ROPOSED S OLUTION : U SE OF SOGI P REFILTER
1 Hz subharmonic in the input signal. For this case, it is im-
The aim of this section is to present the use of a SOGI filter portant to highlight that the obtained frequency ripple is of only
as a system prefilter, which can overcome the limitations of a 0.11 Hz, which is much lower than the previous ones. Besides,
single SOGI and is not influenced by grid dc-offset voltage or the maximum amplitude distortion in vd and vq has been greatly
by subharmonics. reduced to less than 1 V.
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2145

TABLE I
S UMMARY OF H ARMONIC AND S UBHARMONIC D ISTORTIONS P RODUCED IN D IFFERENT SOGI-BASED S TRUCTURES

all win are fixed to wo , can be approximated by


n
∼ 2ξ
|Hdn (jhwo )| = (21)
h
4 4 2
ts ≈ = · (22)
ξwo hwo |Hdn (jhwo )|1/n

where |Hdn (jhwo )| is the gain of the n-order SOGI system at


the harmonic h. Note that (21) implies that the attenuation at a
given harmonic has been increased by an “n” factor, (i.e., n ·
Fig. 12. Proposed SOGI-FLL structure with SOGI prefilter. 20 log(2ξ/h) dB).

C. Design of n-Order SOGI System


The SOGI has a tradeoff between settling time and atten-
uation. In this point, an n-order SOGI system is designed to
overcome this limitation. The main objective in this design is to
achieve a faster time response of an n-order SOGI than a single
Fig. 13. Cascade connection of several SOGIs.
SOGI with the same harmonic attenuation.
The unique option to reduce the settling time of an n-order
In the case of harmonics, the maximum frequency ripple SOGI is to increase the damping factors of the system at
obtained in Fig. 8(a) has been reduced from 1.62 Hz to 0.77 Hz expenses of achieve less harmonic attenuation, see (22). These
for the SOGI-FLL and from 1.73 Hz to 0.87 Hz for the MSOGI- damping factors can be increased until obtaining the same
FLL. The distortion in the vd and vq outputs of these structures harmonic attenuation as a single SOGI. In this situation, the
have also been reduced, see Table I. settling time of the n-order SOGI is faster than the single SOGI.
It is important to emphasize that the use of a prefilter consti- From this point of view, the design of the n-order SOGI has
tutes in fact a connection in cascade of two SOGI filters, which been changed in favor of achieving a faster transient response
produces an increase in the filter-order of the system. Then, the that a single SOGI, but with similar harmonic attenuation.
series connection of multiple SOGI is analyzed and proposed As a design example, Fig. 14 depicts the Bode magnitude
in next subsection as a way to overcome the mentioned tradeoff plot of a first-, second-, and third-order cascaded SOGIs for
relationship of a single SOGI filter, enhancing the features of a small damping factor of 0.11, where the attenuations at the
the system. fifth-hamonic are −26.8 dB, −53.6 dB, and −80.4 dB, respec-
tively. We have chosen the desired attenuation of −26.8 dB for
B. Analysis of Harmonic Attenuation and Settling Time a fifth-harmonic as a starting point in the design of the filter.
This damping factor would lead to the same settling time for all
The study of the cascade connection of two SOGI filters can these filters of 0.115 s.
be extended to n-SOGI filters as shown in Fig. 13. As it can be seen in Fig. 14, the gains of the first- and
The n-order system of Fig. 13 achieves higher harmonic third-orders SOGIs can be increased 26.8 dB and 53.6 dB,
attenuation and a similar settling time than a single SOGI for respectively, to achieve the same attenuation of −26.8 dB as
equal damping factors (ξ1 = ξ2 = . . . = ξn ). In this case, the the single SOGI. Now, the damping factors of the second-
damping factors should be equal to avoid the predominance of and third-order SOGI should be 0.53 and 0.89, respectively,
any SOGI with respect to the others. The transfer function of which supposes that the settling times of these filters have been
this system is reduced from 0.115 s to 0.024 s and 0.014 s, respectively.
n Notice that these settling times represent an important time
vdn (s) 2ξwo · s
Hdn (s) = = . (20) reduction for the second- and third-orders SOGIs systems.
vin (s) s2 + 2ξwo · s + wo2 The following expression is derived using (21):
The gain and the settling time of this system at a given h
ξ≈ · |Hdn (jhwo )|1/n (23)
harmonic h of the fundamental frequency wo , considering that 2
2146 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

maximum of two SOGI prefilters in its input stage to obtain a


faster transient response in relation to a single SOGI-FLL.
The step-by-step design procedure for this system consists
of defining first the attenuation for a specific harmonic. This
attenuation determines the filtering capability of the system
and its robustness to harmonic distortion in the event of fast
transient disturbances (for instance, voltage sags). Second,
the corresponding damping factors and settling times can be
obtained using (21) and (22) for a single SOGI, n = 1, and
for higher orders, n = 2 and n = 3. And third, the order of
the system should be chosen according to the desired time
reduction.
In view of the above results, it can be stated that the cascaded
SOGIs can achieve a faster transient response to voltage sags
Fig. 14. Bode magnitude plot of a first-, second-, and third-order SOGI for than a single SOGI when their damping factors are designed
ξ = 0.11.
to achieve the same harmonic attenuation. This response over-
comes the design tradeoff of a single SOGI, which means that
this proposal can lead to a faster response of three-phase PV
systems if it is used for the grid voltage positive sequence
extraction as proposed in next section.
Finally, Table II summarizes the main features of the SOGI-
FLL, MSOGI-FLL, and the proposed one with prefilter. This
table also considers the sequence detection algorithms exposed
in next section. These algorithms are compared in terms of com-
putational load, subharmonics sensitivity, interharmonic sen-
sitivity, dc-offset voltage rejection, required knowledge of the
grid harmonic content, and tradeoff between settling time and
harmonic attenuation. The computational load has been eval-
uated for a floating-point TMS320F28335 DSP at 150 MHz.
In the case of MSOGI-FLL the computational load depends on
the number of grid harmonics to be considered. As a typical
situation, the grid voltage harmonics to cancel in this case are
3, 5, 7, 9, and 11.

Fig. 15. (a) Settling time versus gain at h = 5 for first-, second-, and third- VI. E XPERIMENTAL R ESULTS
order SOGI system. (b) Time response reduction of second- and third-order
SOGI with respect to the single one. Experimental results were obtained for a PV system that
delivers active power to the grid. These results validate the
and allows us to derive the relationship between the settling proposed DSOGI-FLL-WPF structure in a practical grid with
time and the harmonic attenuation for h = 5 which is depicted voltage distortion and faults.
in Fig. 15. It is worth to see in this figure that ts increases
as the gain for h = 5 decreases. Observe that the longest ts
A. Experimental Setup
always correspond to the first-order SOGI. Fig 15(b) depicts a
comparison between the settling times of the second and third- The experimental setup of the grid-connected PV system
order SOGIs with respect the first-order SOGI to highlight the considered in this work is shown in Fig. 1. It includes a dc-
improvement achieved by the cascaded SOGIs. The comparison source configured to emulate the PV array (Amrel SPS-800-
is made in terms of percentage of achieved time reduction. 12-D013), a 4.5 kVA Semikron three-phase inverter and an
Observe that these time reductions are always above a 50%. In ac programmable three-phase voltage source (Pacific AMX-
the case of −50 dB the time reduction arrives to 88% for n = 2 360 12 kVA) to emulate the grid and get repetitive unbalanced
and to 94% for n = 3. faults. The setup uses a digital control platform based on the
According to Fig. 15(b), it is clear that the best relation floating-point TMS320F28335 DSP. The setup parameters are
between time response reduction and system order is always shown in Table III.
achieved by the second-order SOGI, n = 2. Note that the
increase in performance of the system for n = 3 with respect
B. Proposed Sequence Detection Block in αβ-Frame
to n = 2 is small, about a 10% more. Therefore, it can be stated
that n = 3 is the maximum number of cascaded SOGI that it is The use of the proposed SOGI prefilter to detect the sequence
worth to use to obtain a better ts for the same filter attenuation. of the grid voltage to obtain in-phase and quadrature-phase
The proposed prefilter structure shown in Fig. 12 can have a components of the αβ-frame is shown in Fig. 16.
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2147

TABLE II
C OMPARISON OF D IFFERENT SOGI-BASED S TRUCTURES

TABLE III
PARAMETERS OF S YSTEM S ETUP

Fig. 17. Measured grid voltages under a type C fault and strong harmonic
distortion. (Top) 100 V/div, 100 ms/div. (Bottom) 100 V/div, 10 ms/div.

TABLE IV
Fig. 16. Proposed sequence detection block based on a DSOGI-FLL with S YSTEM C ONTROL AND S EQUENCE D ETECTION PARAMETERS
prefilter structure in the αβ-frame.

In this scheme, the FLL is used only in the α-frame to make


the sequence detection adaptive to the grid frequency. For the
β-frame a second-order SOGI is used with the grid frequency
provided by the FLL of the upper α-frame. The positive
sequences, vα+ and vβ+ , are obtained by simple addition and
subtraction of the in-phase and quadrature-phase components distortions turn to 7.8% and 21.7% during the fault. The gains
of the grid αβ-voltages. This structure can be named “Double of the sequence detection methods of the proposed DSOGI-
SOGI-FLL with prefilter” (DSOGI-FLL-WPF) from now on. FLL-WPF and the DSOGI-FLL were designed to have an
The same structure can be used with a MSOGI scheme if the attenuation at the fifth-harmonic of −28 dB to avoid distortion
SOGI-2 blocks of Fig. 16 are replaced by the MSOGI block and ensure a high-quality waveform in the generated reference
of Fig. 7. currents. The parameters of these sequence detection methods
The experimental results of this sequence detection scheme are shown in Table IV.
were experimentally compared with those obtained using the Fig. 18(a) and (b) shows the grid injected currents when
DSOGI-FLL [45]. using the DSOGI-FLL and the proposed DSOGI-FLL-WPF,
respectively. Note that the proposed scheme with prefilter
presents a faster response than the DSOGI-FLL. This point
C. Experimental and Comparative Results
can be clearly observed during the current transition intervals
The programmed voltage sag is of type C (single-phase-to- shown in this figure. See also in Fig. 18(c) and (d) that the
ground fault) with V U F = 0.3. The pre-fault grid voltages are injected currents are sinusoidal and balanced despite the dis-
Va = 1∠0◦ (pu), Vb = 1∠ − 120◦ (pu), and Vc = 1∠120◦ (pu). torted and unbalanced grid voltage, achieving a current THD of
The grid voltages during the fault are Va = 0.8∠0◦ (pu), Vb = only 2% during the fault. Fig. 19(a) and (c) shows the measured
0.6∠ − 137◦ (pu), and Vc = 0.6∠137◦ (pu), see Fig. 17. The positive sequence voltages in the αβ-frames, vαβ +
. Fig. 19(b)
grid voltage has a high harmonic content (fifth and seventh and (d) shows the generated reference currents, i∗αβ .
harmonics) that lead to a measured voltage THD in the pre-fault In Fig. 18 it can be seen that the settling times of the DSOGI-
of 7.8% and 11.68% for the α and β frames, respectively. These FLL-WPF and of DSOGI-FLL are of 0.039 s and 0.11 s,
2148 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

Fig. 18. Measured grid currents using (plots a and c) the DSOGI-FLL and (plots b and d) the proposed DSOGI-FLL-WPF sequence detection blocks. Plots (a)
and (b) 2.5 A/div, 100 ms/div. Plots (c) and (d) are a detail of currents inside boxes in (a) and (b) (2.5 A/div, 10 ms/div).

Fig. 19. Experimental results of DSOGI-FLL (plots a and b) and of DSOGI-FLL-WPF (plots c and d). Plots (a) and (c) are the αβ positive sequence voltages
and its magnitude. Plots (b) and (d) are the generated current reference and its magnitude.

respectively, which implies a time reduction in the time re- estimated frequency arrives to 0.9 rad/s, while for the DSOGI-
sponse of a 64%. This time reduction agrees with the theoretical FLL-WPF is reduced to 0.2 rad/seg.
prediction of Section V. This fact points out again the better
performance of the proposed solution.
VII. C ONCLUSION
Finally, the grid frequency was subjected to a step perturba-
tion from 50 Hz to 45 Hz to compare the behavior of the FLL in This paper presents an analysis of the SOGI structure show-
both methods. The estimated frequency is shown in Fig. 20(a). ing the problems with grid dc-offset voltage and subharmonics
In this figure, the response of the DSOGI-FLL and the DSOGI- and emphasizing the design tradeoff between damping factor,
FLL-WPF appears with and without overshoot, respectively. settling time, and harmonic attenuation. The use of a SOGI
This response is due to the lower damping factor of the DSOGI- prefilter in the SOGI-FLL structure is proposed to overcome
FLL with respect to the DSOGI-FLL-WPF, which leads to these problems and to achieve a faster settling time.
a slower time response in the sequence detector and thus to In addition, this structure is used in the detection of the
an overshoot in the estimated frequency. Moreover, Fig. 20(b) sequence components of the grid voltage to react faster to volt-
depicts a detail of the estimation at steady state. Note that age sags, provide clean current references, reject grid dc-offset
the ripple produced by harmonics in the DSOGI-FLL-WPF is voltage, reject grid subharmonics, and have less sensitivity to
lower than in DSOGI-FLL. For the DSOGI-FLL the error in the grid harmonics. This configuration has been finally applied with
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2149

Fig. 20. (a) Estimated frequency obtained by the FLL of the DSOGI-FLL and DSOGI-FLL-WPF for a frequency step perturbation from 50 Hz to 45 Hz.
(b) Detail of harmonics at steady state.

the DSOGI-FLL-WPF structure for the grid sequence detection A3
in a three-phase PV system. Experimental and comparative X1 = (cos(we t)−1)+ (cos(3we t)−B) (34)
(A+A3 L)
results of this DSOGI-FLL-WPF during voltage faults have 
been presented. The reported results validate the proposals A3
X2 = sin(we t) + sin(3we t) (35)
presented in this paper as a solution to improve the PV system (A + A3 L)

response to voltage sags and its rejection to grid subharmonics 1
and dc-offset voltage. Y1 = (cos(we t) − 1) + (cos(3we t) − B) (36)
L

1
Y2 = sin(we t) + sin(3we t) (37)
A PPENDIX L
Considering an input signal with a third-harmonic vin = Z1 = cos(we t) − B (38)
A sin(wt) + A3 sin(3wt) and vq = −A cos(wt),
the PD output
Z2 = sin(3we t) (39)
can be formulated as
B = |Hd (j3w)| (40)
A2
e · vq = − [sin(we t) + fm (3we ) + fn (2w, 4w, 6w)] (24) L = |Hq (j3w)| . (41)
2

where
R EFERENCES
[1] J. P. G. de Abreu and A. E. Emanuel, “The need to limit subharmonics
fm (3we ) = m sin(3we t) (25) injection,” in Proc. 9th ICHQP, Oct. 2000, vol. 1, pp. 251–253.
[2] Z. Leonowicz, “Analysis of sub-harmonics in power systems,” in Proc.
fn (2w, 4w, 6w) = ma sin(2wt + φa ) + mb sin(4wt + φb ) Int. Conf. EEIC, 2010, pp. 125–127.
[3] D. Gallo, R. Langella, A. Testa, and A. Emanuel, “On the effects of
+ mc sin(6wt + φc ) (26) voltage subharmonics on power transformers: A preliminary study,” in
Proc. ICHQP, 2004, pp. 501–506.
and [4] F. De Rosa, R. Langella, A. Sollazzo, and A. Testa, “On the interharmonic
components generated by adjustable speed drives,” IEEE Trans. Power
Del., vol. 20, no. 4, pp. 2535–2543, Oct. 2005.
A3 L [5] S. Brownlees, B. Fox, D. Flynn, and T. Littler, “Wind farm induced
m= (27) oscillations,” in Proc. Int. UPEC, 2006, pp. 118–122.
A2
[6] M. M. Morcos and J. C. Gomez, “Flicker sources and mitigation,” IEEE
 1
ma = (1 + A3 L/A) · X12 + X22 2 (28) Power Eng. Rev., vol. 22, no. 11, pp. 5–10, Nov. 2002.
[7] N. Soon-Ryul, P. Jong-Young, K. Sang-Hee, and M. Kezunovic, “Phasor

A3 L  1 estimation in the presence of DC offset and CT saturation,” IEEE Trans.
mb = · Y12 + Y22 2 (29) Power Del., vol. 24, no. 4, pp. 1842–1849, Oct. 2009.
A [8] M. McGranagham, D. Mueller, and M. Samotyj, “Voltage sags in in-
2 dustrial systems,” IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. 397–403,
A3  1 Mar./Apr. 1993.
mc = L · Z12 + Z22 2 (30) [9] G. Yalcinkaya, M. H. Bollen, and P. A. Crossley, “Characterization of
A voltage sags in industrial distribution systems,” IEEE Trans. Ind. Appl.,
 vol. 34, no. 4, pp. 682–688, Jul./Aug. 1998.
−1 X2 [10] M. H. Bollen, “Algorithms for characterizing measured three-phase unbal-
φa = tg (31)
X1 anced voltage dips,” IEEE Trans. Power Del., vol. 18, no. 3, pp. 937–944,
 Jul. 2003.
Y2 [11] H. Song and K. Nam, “Dual current control scheme for PWM converter
φb = tg −1 (32) under unbalanced input voltage conditions,” IEEE Trans. Ind. Electron.,
Y1 vol. 46, no. 5, pp. 953–959, Oct. 1999.
 [12] S. Bruno, S. Lamonaca, G. Rotondo, U. Stecchi, and M. La Scala, “Un-
Z2
φb = tg −1 (33) balanced three-phase optimal power flow for smart grids,” IEEE Trans.
Z1 Ind. Electron., vol. 58, no. 10, pp. 4504–4513, Oct. 2011.
2150 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 5, MAY 2014

[13] Y. A.-R. I. Mohamed, “Mitigation of dynamic, unbalanced, and harmonic provement in a polluted utility grid,” IEEE Trans. Ind. Electron., vol. 59,
voltage disturbances using grid-connected inverters with LCL filter,” no. 6, pp. 2718–2731, Jun. 2012.
IEEE Trans. Ind. Electron., vol. 58, no. 9, pp. 3914–3924, Sep. 2011. [35] Z. Qi, S. Xiang-Dong, Z. Yan-Ru, M. Matsui, and B.-Y. Ren, “Analysis
[14] A. V. Timbus, M. Liserre, R. Teodorescu, P. Rodriguez, and F. Blaabjerg, and design of a digital phase-locked loop for single-phase grid-connected
“Evaluation of current controllers for distributed power generation sys- power conversion systems,” IEEE Trans. Ind. Electron., vol. 58, no. 8,
tems,” IEEE Trans. Power Electron., vol. 24, no. 3, pp. 654–664, pp. 3581–3592, Aug. 2011.
Mar. 2009. [36] T. Thacker, D. Boroyevich, R. Burgos, and F. Wang, “Phase-locked
[15] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla, loop noise reduction via phase detector implementation for single-phase
“Hierarchical control of droop-controlled AC and DC microgrids—A systems,” IEEE Trans. Ind. Electron., vol. 58, no. 6, pp. 2482–2490,
general approach toward standardization,” IEEE Trans. Ind. Electron., Jun. 2011.
vol. 58, no. 1, pp. 158–172, Jan. 2011. [37] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “A new single-phase PLL
[16] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview structure based on second order generalized integrator,” in Proc. IEEE
of control and grid synchronization for distributed power generation PESC, Jun. 2006, pp. 1–6.
systems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, [38] U. Nuß, “Blindleistungskompensation mit selbsgeführtem stromrichter
Oct. 2006. und kapazitivem energiespeicher,” Ph.D. dissertation, Institut der Univer-
[17] M. Castilla, J. Miret, J. L. Sosa, J. Matas, and L. García de Vicuña, sität Karlsruhe, Karlsruhe, Germany, 1989.
“Grid-fault control scheme for three-phase photovoltaic inverters with [39] B. Burger and A. Engler, “Fast signal conditioning in single phase
adjustable power quality characteristics,” IEEE Trans. Power Electron., systems,” in Proc. Eur. Conf. Power Elect. Appl., 2001, pp. P1–P10.
vol. 25, no. 12, pp. 2930–2940, Dec. 2010. [40] X. Yuan, W. Merk, H. Stemmler, and J. Allmeling, “Stationary-frame
[18] C.-I. Chen, “A phasor estimator for synchronization between power grid generalized integrators for current control of active power filters with zero
and distributed generation system,” IEEE Trans. Ind. Electron., vol. 60, steady-state error for current harmonics of concern under unbalanced and
no. 8, pp. 3248–3255, Aug. 2013. distorted operating conditions,” IEEE Trans. Ind. Appl., vol. 38, no. 2,
[19] S. Gomez Jorge, C. A. Busada, and J. A. Solsona, “Frequency-adaptive pp. 523–532, Mar./Apr. 2002.
current controller for three-phase grid-connected converters,” IEEE Trans. [41] P. Rodriguez, R. Teodorescu, I. Candela, A. V. Timbus, and
Ind. Electron., vol. 60, no. 10, pp. 4169–4177, Oct. 2013. F. Blaabjerg, “New positive-sequence voltage detector for grid synchro-
[20] C. A. Busada, S. Gomez Jorge, A. E. Leon, and J. A. Solsona, “Current nization of power converters under faulty grid conditions,” in Proc. IEEE
controller based on reduced order generalized integrators for distributed PESC, 2005, pp. 2474–2481.
generation systems,” IEEE Trans. Ind. Electron., vol. 59, no. 7, pp. 2898– [42] M. Ciobotaru, V. G. Agelidis, R. Teodorescu, and F. Blaabjerg, “Accu-
2909, Jul. 2012. rate and less-disturbing active anti-islanding method based on PLL for
[21] S. Golestan, M. Monfared, F. D. Freijedo, and J. M. Guerrero, “Dynamics grid-connected converters,” IEEE Trans. Power Electron., vol. 25, no. 6,
assessment of advanced single-phase PLL structures,” IEEE Trans. Ind. pp. 1576–1584, Jun. 2010.
Electron., vol. 60, no. 6, pp. 2167–2177, Jun. 2013. [43] A. Nagliero, R. A. Mastromauro, M. Liserre, and A. Dell’Aquilla, “Mon-
[22] S. K. Chung, “A phase tracking system for three phase utility interface itoring and synchronization techniques for single-phase PV systems,” in
inverters,” IEEE Trans. Power Electron., vol. 15, no. 3, pp. 431–438, Proc. SPEEDAM, 2010, pp. 1404–1409.
May 2000. [44] A. Nicastri and A. Nagliero, “Comparison and evaluation of the PLL
[23] J. Svensson, “Synchronization methods for grid-connected voltage source techniques for the design of the grid-connected inverter systems,” in Proc.
converters,” Proc. Inst. Elect. Eng.—Gener. Transm. Distrib., vol. 148, ISIE, Jul. 2010, pp. 3865–3870.
no. 3, pp. 229–235, May 2001. [45] P. Rodriguez, A. Luna, M. Ciobotaru, R. Teodorescu, and F. Blaabjerg,
[24] M. Karimi-Ghartemani and M. R. Iravani, “A nonlinear adaptive filter for “Advanced grid synchronization system for power converters under un-
online signal analysis in power systems applications,” IEEE Trans. Power balanced and distorted operating conditions,” in Proc. IECON, 2006,
Del., vol. 17, no. 2, pp. 617–622, Apr. 2002. pp. 5173–5178.
[25] M. Karimi-Ghartemani and M. R. Iravani, “A method for synchroniza- [46] P. Rodriguez, A. Luna, I. Candela, R. Mujal, R. Teodorescu, and
tion of power electronic converters in polluted and variable-frequency F. Blaabjerg, “Multiresonant frequency-locked loop for grid synchroniza-
environments,” IEEE Trans. Power Syst., vol. 19, no. 3, pp. 1263–1270, tion of power converters under distorted grid conditions,” IEEE Trans.
Aug. 2004. Ind. Electron., vol. 58, no. 1, pp. 127–138, Jan. 2011.
[26] M. Karimi-Ghartemani, H. Karimi, and M. R. Iravani, “A magnitude [47] M. Mojiri, M. Karimi-Ghartemani, and A. Bakhshai, “Estimation of
phase-locked loop system based on estimation of frequency and in-phase power system frequency using an adaptive notch filter,” IEEE Trans.
quadrature-phase amplitudes,” IEEE Trans. Ind. Electron., vol. 51, no. 2, Instrum. Meas., vol. 56, no. 6, pp. 2470–2477, Dec. 2007.
pp. 511–517, Apr. 2004. [48] A. Isidori, Nonlinear Control Systems, 3rd ed. New York, NY, USA:
[27] M. Karimi-Ghartemani, S. A. Khajehoddin, P. Jain, and A. Bakhshai, Springer-Verlag.
“Comparison of two methods for addressing DC component in phase- [49] Characteristics of the Utility Interface for Photovoltaic (PV) Systems,
locked loop (PLL) systems,” in Proc. ECCE, 2011, pp. 3053–3058. IEC Std. 61 727-2002, 2002.
[28] H. Karimi, M. Karimi-Ghartemani, and M. R. Iravani, “Estimation of [50] IEEE Guide for Monitoring, Information Exchange, and Control of Dis-
frequency and its rate of change for applications in power systems,” IEEE tributed Resources Interconnected With Electric Power Systems, IEEE
Trans. Power Del., vol. 19, no. 2, pp. 472–480, Apr. 2004. Std. 1547.3-2007, 2007.
[29] D. Yazdani, A. Bakhshai, and P. K. Jain, “A three-phase adaptive notch [51] A. von Jouanne and B. Banerjee, “Assessment of voltage unbalance,”
filter-based approach to harmonic/reactive current extraction and har- IEEE Trans. Power Del., vol. 16, no. 4, pp. 782–790, Oct. 2001.
monic decomposition,” IEEE Trans. Power Electron., vol. 25, no. 4,
pp. 914–923, Apr. 2010.
[30] F. D. Freijedo, J. Doval-Gandoy, O. López, and E. Acha, “Tuning of
phase-locked loops for power converters under distorted utility con-
ditions,” IEEE Trans. Ind. Appl., vol. 45, no. 6, pp. 2039–2047,
Nov./Dec. 2009.
[31] N. Hoffmann, R. Lohde, M. Fischer, F. W. Fuchs, L. Asiminoaei, and
P. B. Thogersen, “A review on fundamental grid-voltage detection meth-
ods under highly distorted conditions in distributed power-generation net-
works,” in Proc. IEEE ECCE, 2011, pp. 3045–3052. José Matas received the B.S., M.S., and Ph.D. de-
[32] E. Robles, J. Pou, S. Ceballos, J. Zaragoza, J. L. Martin, and P. Ibañez, grees in telecommunications engineering from the
“Frequency-adaptive stationary-reference-frame grid voltage sequence Technical University of Catalonia, Barcelona, Spain,
detector for distributed generation systems,” IEEE Trans. Ind. Electron., in 1988, 1996, and 2003, respectively.
vol. 58, no. 9, pp. 4275–4287, Sep. 2011. Since 1990, he has been an Associate Professor in
[33] M. A. Perez, J. R. Espinoza, L. A. Moran, M. A. Torres, and the Department of Electronic Engineering, Technical
E. A. Araya, “A robust phase-locked loop algorithm to synchronize static- University of Catalonia, Barcelona, where he teaches
power converters with polluted AC systems,” IEEE Trans. Ind. Electron., courses of digital signal processors and power elec-
vol. 55, no. 5, pp. 2185–2192, May 2008. tronics. His research interests are in the areas of
[34] F. Gonzalez-Espin, E. Figueres, and G. Garcera, “An adaptive power electronics, nonlinear control, and renewable
synchronous-reference-frame phase-locked loop for power quality im- energy systems.
MATAS et al.: PREFILTERING METHOD TO IMPROVE SPEED/ACCURACY OF VOLTAGE SEQUENCE DETECTION 2151

Miguel Castilla received the B.S., M.S., and Ph.D. Luis García de Vicuña received the M.S. and Ph.D.
degrees in telecommunication engineering from the degrees in telecommunications engineering from
Technical University of Catalonia, Barcelona, Spain, the Universitat Politècnica de Catalunya, Barcelona,
in 1988, 1995, and 1998, respectively. Spain, in 1980 and 1990, respectively, and the Dr.Sci.
Since 2002, he has been an Associate Professor in degree from the Université Paul Sabatier, Toulouse,
the Department of Electronic Engineering, Technical France, in 1992.
University of Catalonia, where he teaches courses on From 1980 to 1982, he was an Engineer with
analog circuits and power electronics. His research control applications company. Currently, he is a Pro-
interests are in the areas of power electronics, non- fessor in the Department of Electronic Engineering,
linear control, and renewable energy systems. Technical University of Catalonia, Barcelona, where
he teaches power electronics. His research interests
include power electronics modeling, simulation and control, active power
filtering, and high-power-factor ac/dc conversion.

Ramon Guzman received the B.S. and M.S. degrees


Jaume Miret (M’98) received the B.S. degree in in telecomunications engineering from the Univer-
telecommunications, the M.S. degree in electronics, sitat Politècnica de Catalunya, Barcelona, Spain in
and the Ph.D. degree in electronics from the Tech- 1999 and 2004, respectively. He is currently working
nical University of Catalonia, Barcelona, Spain, in toward the Ph.D. degree in the Power and Control
1992, 1999, and 2005, respectively. Electronics Systems (SEPIC) group.
Since 1993, he has been an Assistant Professor in Since 2001, he is an Associate Professor of the
the Department of Electronic Engineering, Technical Comunications and Signal Theory Department at
University of Catalonia, where he teaches courses the Technical University of Catalonia, Barcelona,
on digital design and circuit theory. His research Spain. His current research interests are in the area of
interests include dc-to-ac converters, active power nonlinear and adaptive control for three phase power
filters, and digital control. converters.

Вам также может понравиться