Вы находитесь на странице: 1из 44

SSR-125/150/200 H.P.
SSR-250/300 H.P.
SSR-E300/350/400/450 H.P.
OPERATORS MANUAL
INSTALLATION
MAINTENANCE
Includes NEMA 4/12

INGERSOLL-RAND­
AIR COMPRESSORS

• APDD 202 D-89


5th Edition
April 1989
.•
OPERATORS MANUAL
ALL SSR MODELS
ROTARY SCREW AIR COMPRESSOR Warranty
The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects m material and
workmanship !or a period of twelve months (see extended airend warranty) from the date of placing the Equipment in operation or
This unit was purchased from eighteen months (see extended airend warranty) from the date of shipment from Davidson, N�. whichever shall first occur. The
Purchaser shall be obligated to promptly report any failure to conform to. t his warranty, in wri�1ng to the Company in said pe.riod,
,
whereupon the Company shall, af its option, correct such nonconform1ty, by suitable repair to such equipment or, furnish a
replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or
equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the manufacturers have
conveyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs,
replacements. or adjustments to the Equ1pmenl or any costs of labor performed by the Purchaser or others without the Company's
prior written approval.
The eflects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are limited to those
specifically stated within the Company's proposal. Unless responsibility !or meeting such _performance warranties are limited to
specified tests, the Company's obligation shalt be to correct in the manner and tor the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR
IMPLIED, EXCEPT THAT OF TITLE. AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED
Correction by the Company of nonc�nformit1es whether patent or latenl, in the mannE:r and for the period of time provided above,
shall const1tule fulfillment of all liabilities of the Company lor such nonconformil1es whether based on contract, warranty
negligence, indemnity, strict liability or otherwise with respect to or arising out ol such Equipment
The Purchaser shatl not operate Equipment which is considered to be defective. without first notifying the Company in writing of
its intention to do so. Any such use of Equipment will be at Purchaser's sole risk and liability.
Limitation of Liabilily
The remedies of the Purchaser set forth herein are exclusive, and the total liability of the Company with respect to this contract or
!he Equipment and services furnished hereunder, in connection with the performance or breach thereof, or from the manufacture,
sale, delivery, installation, repair or technical direction covered by or furnished under this contract. whether passed on contract.
Ingersoll-Rand Company reserves the warranty negligence, indemnity, strict liability or otherwise, shall not exceed the purchase price of the unit of Equipment upon
which such liability is based
right to make changes or add improve­ The Company and its suppliers shall in no event be liable to the Purchaser, any successors in interest or any beneficiary or
assignee ol this contracl for any consequential, incidental. indirect, special or punitive damages arising out of this contract or any
breach thereol. or any delect m. or failure of, or malfunction of the Equipment hereunder, whether based upon loss of use, �est
ments without notice and without in­ profits or revenue, interest, lost goodwill, work stoppage, impairment cl other goods, loss by reason of shutdown or non-operation,
curring any obligation to make such increased expenses of operation, cost of purchase of replacement power or claims of Purchaser or customers of Purchaser for
service interruption whether or not such !ass or damage is based on contract, warranty. negligence. indemnity. strict liability or
changes or add such improvements to
products sold previously. a�:;:;·t-rn000I·I·le·H·!·!·l�·ll:lt:>l·!·!·K·i:i

Model: ____________

No. of units on order: _______

Customer order No.:

Ingersoll-Rand Co. Order No.:


EXTENDED Al REND WARRANTY
For ready reference:
Record the serial number and model The Ingersoll-Rand Company Rotary Screw Air Compressor that has been filled
number of your unit here. prior to its original shipment from Ingersoll-Rand Company with ULTRA
COOLANT and which has been operated solely on ULTRA COOLANT there­
after shall have its AIREND warranted for twenty-four (24) months from the date
of placing the COMPRESSOR in operation or thirty ( 30) months from the date of
Serial number: ________ _ shipment. whichever occurs first.

Model number: _________


Except for the above warranty period. the standard warranty provisions shall
apply and the conditions outlined herein are understood to be a supplement to the
standard Ingersoll-Rand Company warranty.

This EXTENDED AIREND WARRANTY applies to all COMPRESSORS


operating on ULTRA COOLANT after February I. I987.

@ Ingersoll-Rand Company 1989 •


1
• SAFETY PRECAUTIONS
READ CAREFULLY BEFORE INSTALLING THE COMPRESSOR.

WARNING 6. A safety valve is located on the


receiver-separator. Whenever
COMPRESSED AIR AND ELECTRI­ pressure is released through this
CITY ARE DANGEROUS. valve, it is due to excessive pressure
BEFORE DOING ANY WORK ON THIS in the system. The cause for the ex­
UNIT, BE SURE THE ELECTRICAL cessive pressure should be in­
SUPPLY HAS BEEN CUT OFF AND vestigated immediately.
THE ENTIRE COMPRESSOR SYSTEM
7. Before doing any mechanical work
HAS BEEN VENTED OF ALL
on the compressor:
PRESSURE.
a.) Shut the unit down.

SAFETY PRECAUTIONS b.) Electrically isolate the compressor


by use of the manual disconnect
1. Do not remove the covers or switch in the power line to the unit.
loosen or remove any fittings, connec­ Lock and tag the switch so that it
tions or devices when this unit is in cannot be operated.
operation. Hot liquid and air under
pressure that are contained within c.) Make sure the unit has blown
this unit can cause severe injury. down, and close the unit isolation
valve to prevent possible backflow in­


2. The compressor has high and to the unit from the air system.
dangerous voltage in the motor,
the starter, and control box. All in­ 8. There can be bad effects if com­
stallations must be in accordance pressor lubricants are allowed to
with recognized electrical codes. enter plant air systems.
Before working on the electrical Air line separators, properly selected
system, be sure to remove voltage and installed, can reduce any liquid
from the system by use of a manual­ carryover close to zero.
disconnect switch. A circuit breaker
or fused safety switch must be pro­ The use of plastic bowls on line
vided in the electrical supply line filters without metal guards can be
leading to the compressor. hazardous. Their safety can be af­
fected by either synthetic lubricants,
Those responsible for installation of or the additives used in mineral oils.
this equipment must provide suitable From a safety standpoint, metal
grounds, maintenance clearance and bowls should be useci on any
lightning arrestors for all electrical pressurized system. Review of your
components as stipulated in O.S.H.A. plant air line system is recommended.
1910.308 through 1910.329.
9. When a receiver is installed, it is
3. Do not operate the compressor at recommended that occupational safe­
higher discharge pressures than ty and health standards as covered in
those specified on the Compressor the Federal Register, volume 36
Nameplate, or motor overload will oc­ number 105 Part II paragraph
cur. This condition will result in 1910.169 be adhered to in the installa­
motor and compressor shutdown. tion and maintenance of this receiver.
4. Use only safety solvent for clean­ 10. Before starting the compressor,
ing the compressor and auxiliary its maintenance instructions should
equipment. be throughly read and understood.
5. Install a manual shut off valve
(isolation type) in the discharge line


as close to the compressor as
possible.

FAILURE TO HEED THIS WARNING MAY RESULT IN AN


ACCIDENT CAUSING PERSONAL INJURY OR PROPERTY DAMAGE.

2

FOREWORD
CJINGERSOLL-RAND®
The SSR data plate on the compressor Davidson, North Carolina
is affixed to the compressor housing
inside the cabinet. (See Figure 1.)
HP ·--- VOLTS ···················
It lists the rated operating pressure KW••···••·--- PHASE/HZ·-­
and the maximum discharge SER. FAC.····-··­ NEMA DES.·······-·­
pressure along with the compressor RPM---­
capacity, the electric motor charac­ FRAME---­
teristics and power. KVA CODE-··-­ MODEL--­
AMPS ····-····-··· TIME/HRS. ····-•·
Information has been prepared in

this manual to assist an operator to INS. CLASS········ MAX. AMBIENT-


understand, maintain and operate DRIVE END BEARING········--­
this compressor within the power OPPOSITE DRIVE END BEARING······-····-
limits shown on the name plate. CODE··-···-----------
Before installation or starting the
compressor for the first time, this
manual should be studied carefully
39519137
to obtain a clear knowledge of the
unit and of the duties to be
performed.
Take pride in your compressor-keep Figure 1
it clean and in good mechanical Compressor Data
condition.


3

SSR


Figure 2
Typical SSR Compressor

i
�;;;;;
El 1· \
\

Figure 2A
Typical SSR NEMA 4/12 Compressor


4

TABLE OF CONTENTS
General Information ..............6 Operation .....................30
Lubricant Circulation System .......8 Lubrication ....................31
Lubricant/ Air Safety Shutdown Checks .........32
Separation System ............12 Trouble Investigation.............32
Aircooled Compressors ..........13 Maintenance ...................33
Watercooled Compressors ........ 14 Lubricant Time Change ..........34
Installation Details............... 15 Drive Motor Bearing
Electrical System ...............18 Maintenance Stored Units.......35
Instrumentation .................23 Long Term Storage ..............35
Dual Slowdown Valve Compressor Change/
System .....................24 Lubricant Procedure ...........36
Capacity Control ................24 Prelube Procedure
Regulation Adjustment 304mm Airend (Only) ..........37
Instructions ..................27

&WARNING&


Failure to adhere to these recommendations can result in mechanical failure, property damage and serious injury or death.

"All air and water inlet, and air and water discharge pipework to and from the inlet and discharge port connections must take
into account vibration, pulsations, temperature, maximum pressure applied, corrosion and chemical resistance. In addition,
it should also be noted that lubricated compressors will discharge some oil into the air stream; therefore, compatability
between discharge piping, system accessories, and software must be assured.

"For the foregoing reasons, the use of plastic piping, soldered copper fittings, and rubber hose as discharge piping is not
recommended. In addition, flexible joints and/or flex lines can only be considernd for such purposes if their specifications fit
the operating parameters of the system.

It is the responsibility of the installer and owner to provide the appropriate service pipework to and from the machine."

&WARNING&
STATEMENT CONCERNING THE USE OF THIS EQUIPMENT FOR BREATHING AIR AND/OR AQUA LUNG SERVICE
If the model number on this air compressor contains the letters "BAP", the compressor is suitable for use in breathing air
services. In the absence of such a designation, the compressor is NOT considered as capable of producing air of breathing
quality. For a compressor to be capable of use in breathing air services, it must be fitted with additional specialized equip­
ment to properly filter and/or purify the air to meet all applicable federal, state and local laws, rules, regulations and
codes, such as, but not limited to, OSHA 29 CFR 1910.134, Compressed Gas Association Commodity Specification
G-7, 1-1966, Grade D Breathing Air, and/or Canadian Standards Association. Should the Purchaser and/or User fail to add
such specialized equipment and proceeds to use the compressor for breathing air service, the Purhcaser/User assumes all
liability resulting therefrom without any responsibility or liability being assumed by Ingersoll-Rand Company.
The Purchaser is urged to include the above provision in any agreement for any resale of this compressor.


5

GENERAL The air-lubrication mixture
discharges from the compressor into
The lubricant system consists of a
sump, a cooler, thermostatic lubri­
INFORMATION the separation system. This system, cant control valve and a filter. When
self-contained in the receiver tank, the unit is operating the lubricant is
The SSA compressor is an electric removes all but a few PPM of the pressurized and forced to the
motor driven, single stage, screw lubricant from the discharge air. The compressor bearings.
compressor - complete with lubricant is returned to the system
accessories piped, wired and and the air passes to the aftercooler. Panel instrumentation is provided to
baseplate mounted. It is a totally indicate the compressor operating
self-contained air compressor The aftercooling system consists of conditions, control power availability,
package. a heat exchanger, a condensate load control mode, a push-button
separator, and a drain trap. By start-stoo station, condition of air
A standard compressor is composed cooling the discharge air, much of and lubricant filters, and. optionally,
of the following: the water vapor naturally contained a shutdown annunciation section.
Inlet air filtration in the air is condensed and
eliminated from the downstream Safety of operation is provided for
Compressor and motor assembly as the compressor will shut down
Pressurized lubricant system plant-piping and equipment.
due to excessive discharge
with cooler The compressor capacity is temperature, excessive bearing
Separation system governed by the load control scavenge temperature, and elec­
Load control system system. In the standard control trical overload.
Motor starting control system mode, the compressor will operate
Instrumentation "On-Off Line". Air filtration is handled by a large,
Safety provisions highly efficient, dry-type air cleaner.
Air cooled aftercooler The compressor will operate to Optional types of prefilters are
(Moisture separator and drain trap) maintain discharge line pressure at available, and pre-engineered to
or slightly above the rated pressure. handle virtually any type of
Compression in the screw-type air
compressor is created by the Optional accessories can provide for installation.
meshing of two helical rotors (male such things as upper range modula­ Effective lubricant filtration is pro­
and female) on parallel shafts, tion and automatic starting and vided by use of heavy duty
enclosed in a heavy-duty cast iron stopping. This may be desirable in


hydraulic type filters.
housing, with air inlet and outlet a plant with widely varying air de­
ports located on opposite ends. The mand. The field proven control All of the above features are
grooves of the female rotor mesh system is basically solid state for described in greater detail and
with, and are driven by, the male long term, trouble-free operation. discussed in the pertinent sections
rotor. Tapered roller bearings at the of this manual.
discharge end prevent axial All service connections are on the
movement of the rotors. back of the unit to provide ease of
connection and a clean looking
installation


6

COMPRESSION
If one thinks of the female rotor
grooves and the compressor hous­
ing acting as a conventional
cylinder, and the sliding action of
the male rotor lobe as a piston, the
positive displacement nature of a
rotary screw compressor becomes
apparent.
As rotation of the compressor
begins, air is drawn into the
pockets opened between the male
rotor lobes and the female rotor
grooves at the intake end of the
compressor. This is illustrated in °
:·Figure 3-1. (A,·rnatihg··m�le�fo_bei '·1 1 - Intake Inlet air flow
and female-groove are marked with
dots to show the relative positions
of the rotors.)
With further rotation, the leading
strip of the male lobe reaches the
contour of the female groove, and
traps the air in the pocket Female rotor
previously formed. This air is mov­
ed down the female rotor groove
and is compressed.
Lubricant is injected during the


compression phase and takes up
heat of compression, lubricates the
rotors, and seals the rotor­
clearances against leakage. This
phase is illustrated in Figure 3-2.
When the male rotor lobe reaches
the end of the groove, the trapped
air is discharged along with the
lubricant. Figure 3-3. The mixture 2 - Compression
is piped through a check valve to
the receiver. In the receiver, the
lubricant will be separated from
the air and returned to the system.
The air will flow to the aftercooler
and then to the plant system. Discharge port


3 - Discharge

Figure 3
Rotor Compressor

7

The thermostatic oil control valve The compressor injection minimum
LUBRICANT controls the quantity of lubricant temperature is controlled to preclude
CIRCULATION SYSTEM necessary to provide a suitable the possibility of water vapor
compressor injection temperature. condensing in the receiver. By
Refer to Figures 4A and 4B for the When the compressor starts cold, injecting lubricant at a sufficiently
Aircooled Circulation System part of the lubricant will by-pass the high temperature, temperature of
Schematics. cooler. As the system temperature the discharge air and lubricant
rises above the valve setting, the mixture will be kept above the dew
Lubricant flows from the receiver­ lubricant will be directed to the point.
separator to the inlet port of the cooler. During periods of operation
lubricant cooler and the bypass in higher ambient temperatures, all The controlled-temperature lubricant
port of the thermostatic control the lubricant flow will be directed passes through a filter to the air end
valve. through the cooler. under constant pressure.

DIFFERENTIAL
PRESSURE SWITCH (3DP)
OPERATES WARNING LIGHT (3Ll)
ON INSTRUMENT PANEL

COMBINATION MINIMUM PRESSURE


(60PSIG) CHECK VALVE MAINTAINS
PRESSURE IN TANK WHEN UNIT IS
LOADED AND PREVENTS CUSTOMER
AIR ENTERING SEPARATOR TANK.
ENSURE PROPER OIL FLOW.

• •

AIR/OIL
DISCHARGE DUMP TO
FROM A RE D OMPRESSOR INLET
�L SUMP �
AREA J

I
,,.,- -:
-)
' I I
, ..... _',..,:

- ENERGIZED
- - - -- DE-ENERGIZED

LOAD SOLENOID


VALVE (1SV)

Figure 4A
Lubricant Circulation System
Aircooled with Integral Coolers
8
COOLER VENT SOLENOID (7SV)
VENTS ANY PRESSURE
IN COOLER AT SHUTDOWN #'.

DIFFERENTIAL
PRESSURE SWITCH
OPERATES LIGHT ON
INSTRUMENT PANEL

COOLANT
FILTER

INLET VALVE


POSITIONER

DUMP TO
OMPRESSOR INLET

i
' ' )
''-'< ... fI

l...�---- 1,,
..,..,____....,_.,.. ENERGIZED
- - - -- DE-ENERGIZED


LOAD SOLENOID
VALVE (1SV)

Figure 4B
Lubricant Circulation System
Aircooled with Remote Coolers

9

BLOWOOWN SOLENOID VALVE ilSV) COMBINATION COLD START/BLOWDOWN
VENTS SEPARATOR TANK WHEN SOLENOID 8SV. WORKS IN PARALLEL
UNIT UNLOADS OR IS SHUTDOWN. WITH 3SV WHEN INJECTED OIL
IS OPERATED BY AIR PRESSU RE TEMPERATURE IS 120' F. OR HIGHER.
SWITCH 1PS. REMAINS CLOSED WHEN INJECTED OIL
TEMPERATURE IS LOWER THAN 120' F.
TO CREATE HIGHER UNLOADED SUMP
PRESSURE FOR COLD OIL FLOW.

L R TCH l1PS)
:!ilt�i ���
�g�mt� fo�i/ 1.
VACUUM SWITCH I1VAC) OPERATES
WARNING LIGHT i4LT) ON
INSTRUMENT PANEL WHEN AIR
FILTER BECOMES FOULED.

COMBINATION MINIMUM PRESSURE


(60 PSIG)/CHECK VALVE MAINTAINS · ·

1
PRESSURE IN TANK WHEN UNIT IS LOADED ·.
AND PREVENTS CUSTOMER AIR ENTE RING : ---���- SCAVENGE LINE
SEPA RATOR TANK. ORIFICE

6d'j
rt �·
FLANGE MOUNTED 1:; Ulf

I
SEPARATOR �l _

7
HIGH DISCHARGE AI R TEMPERATURE


:::::::E RELIE SWITCH (HAS) OPENS ON RISING
VALVE �I TEMPERATU RE TD SHUT UNIT DOWN.

�- Q
Oil FILL CHECK VALVE TO PREVENT BAC K
CONNECTION FLOW INTO AIREND AT SHUTDOWN

7 AIR/Oil MIXTURE DISCHARGE


OIL SUMP AREA FROM AIRENO

DISCHARGE AIR
TO PLANT SYSTEM
CONDENSATE
TO DRAIN
l�
j!'� ',7\) SINGLE NEEDLE AI R PR ESSURE GAUGE
LINE/SUMP PRESSURE SELECTOR VALVE. (MOUNTED ON INSTR UMENT PANEL)
USED TO DETERMINE DIFFERENTIAL
ACROSS SEPARATOR ELEMENT WHEN
UNIT IS FULLY LOAOEO
(MOUNTED ON INSTR UMENT PANEL)

Figure SA
Air Flow System
With Internal Aircooled Aftercooler


10

SLOWDOWN SOLENOID VALVE IJSV)
VENTS SEPARATOR TANK WHEN COMBINATION COLD START/BLOWDOWN
UNIT UNLOADS OR IS SHUTDOWN. SOLENOID esv. WORKS IN PARALLEL
IS OPERATED BY AIR PRESSURE WITH JSV WHEN INJECTED OIL
SWITCH 1PS. TEMPERATURE IS 120' F. OR HIGHER.
REMAINS CLOSED WHEN INJECTED OIL
TEMPERATURE IS LOWER THAN 120' F.
TO CREATE HIGHER UNLOADED SUMP
PRESSURE FOR COLD OIL FLOW.
ADJUSTABLE AIR PRESSURE SWITCH 11PS)
CONTROLS LOAD/UNLOAD POINT.
VACUUM SWITCH 11YAC) OPERATES
CONDENSATE WARNING LIGHT 14LT) ON
SEPARATOR• INSTRUMENT PANEL WHEN AIR
TRAP FILTER BECOMES FOULED.
REMOTE

INLET AIR CONTROL VALVE


!BUTTERFLY TYPE)
>"
DISCHARGE AIR / /
TO PLANT SYSTEM
COMBINATION MINIMUM PRESSURE
CONDENSATE 160 PSIG)/CHECK VALVE MAINTAINS
DRAIN

1:: b,,.,,
PRESSURE IN TANK WHEN UNIT IS LOADED
ANO PREVENTS CUSTOMER AIR ENTERING
SEPARATOR TANK.
I I� A f1
<
FLANGE MOUNTED� • e::.

),{1.I�•, ·
SEPARATOR ,
ELEMENT �


PRESSURE RELIEF I
VALVE
I
,,.�',
:·�
OIL FILL
CONNECTION

7 AIR/OIL MIXTURE DISCHARGE


OIL SUMP AREA FROM AIREN0

SINGLE NEEDLE AIR PRESSURE GAUGE


LINE/SUMP PRESSURE SELECTOR VALVE (MOUNTED ON INSTRUMENT PANEL)
USED TO DETERMINE DIFFERENTIAL
ACROSS SEPARATOR ELEMENT WHEN
UNIT IS FULLY LOADED
(MOUNTED ON INSTRUMENT PANEL)

Figure Sb
Air Flow System
Aircooled with Remote Aftercooler


11

LUBRICANT/ AIR
SEPARATION
SYSTEM
The lubricant/air separation system
is composed of a receiver or
separator tank with specially
designed internals, a two-stage,
coalescing-type separator element,
and provision for return of the
separated fluid back to the com­
pressor.
OPERATION
The lubricant and air discharging
from the compressor flow into the
receiver where the mixture is
directed along the ir:,ner cir­
cumference, allowing the lubricant
stream to collect and drop to the
receiver sump.
The internal baffle maintains the
circumferential flow of remaining
lubricant droplets and air. In an
almost continuous change of direc­
tion of flow, more and more


droplets are removed from the air
by inertial action and then returned
to the sump.
The air stream, now a very fine
mist, is directed to the separator
element.
Figure 6
The separator element is con­ Separator Tank Internals
structed with two concentric­
cylindrical-sections of closely
packed fibers, each held in steel
mesh. It is flange mounted at the
receiver outlet cover.
The air stream enters the separator
element and the mist coalesces to
form droplets. The droplets col­
lected on the outer first stage fall
to the receiver sump. Those col­
lected on the inner second stage
collect on the bottom of the ele­
ment, and are drawn back to the
compressor inlet through a filter­
screen and orifice fitting installed
in the separator scavenge line.
The air stream, now essentially
free of lubricant, flows from the
separator to the aftercooler, then
to the condensate separator, and
on to the plant air system.


12

AIRCOOLED COOLING FAN MOTOR
COMPRESSORS In a standard compressor, the
cooling fan motor is wired at the
DESIGN TEMPERATURES factory. It is a three phase motor.
It is protected by a suitable
The standard compressor is designed circuit breaker and/or fuses and
for operation in an ambient range of overload relay. The fan motor is
35 °F. to 100 ° F. (1.7 ° C. to 38 ° C.). If energized at the same time the
the compressors are to operate in compressor drive motor is energized.
ambient temperatures above 100 ° F. The fan motor overload is wired in
for periods of more than one hour or series with the compressor drive
two per day, it is assumed that they motor overload. If an overload
will have been ordered with optional occurs in the fan motor circuit,
higher temperature rated coolers, and both the fan motor and compressor
possibly drive motors. When drive motor will stop.
conditions other than the design
levels described are encountered, we
recommend you contact your nearest
Ingersoll-Rand representative for
additional information.
The standard maximum temperature
(100 ° F.) is applicable up to an
elevation of 7500 ft. (2300 meters)
above sea level. Above this altitude,
significant reductions in ambient
temperature are required if a
standard drive motor is to be used.

LUBRICANT COOLERS


For integral cooled systems, the
lubricant cooler is an integral part
of the compressor package. Cool­
ing air flows into the package
through the right end and exits out
the top. For remote cooled
systems, the cooler, fan, and fan
motor are mounted separate from
the compressor package.

AFTERCOOLER
The discharge air aftercooling
system consists of a heat ex­
changer, a condensate separator,
and a drain trap.
By cooling the discharge air, much
of the water vapor naturally con­
tained in the air is condensed and
eliminated from the downstream
plant-piping and equipment.


13

WATERCOOLED LUBRICANT
THERMOSTATIC
COMPRESSORS CONTROL
OUT VALVE
IN
DESIGN TEMPERATURES
The standard compressor is designed
for operation in a temperature range
of 35 ° F. to 100 ° F. (1.1 ° c. to 38 ° C.).
The standard shell and tube coolers
are designed to use clean fresh COOLER
cooling water at temperatures up to
90 ° F. (32°C.).

AFTERCOOLING .--� AIR


To reduce or eliminate downstream
condensation of water vapor, an
aftercooler is furnished as standard AFTERCOOLER
equipment. It is of shell and tube
construction, with the water flowing
through the tubes. COOLING
WATER
In a standard compressor, the 90 °F. (32 °C.)
cooling water flows to the MAXIMUM
aftercooler, and then to the l_ubricant
cooler. This "series" flow keeps the 1 - STANDARD COOLING
total required cooling water flow to a WATER SYSTEM
minimum. By bringing the cooling
water to the aftercooler first, lower


temperature air is discharaed to the
plant system. See Figure 7-1.
When the cooling water available is
LUBRICANT
at temperatures above the standard
requirement of 90 ° F. (32 ° C.), the
cooling water flow is in a "parallel"
arrangement. Thermostatic IN
temperature control is furnished THERMOSTATIC
similar to that of the air cooled units, CONTROL
VALVE
and a throttling valve is installed in
the aftercooler circuit to balance the
water flows. See Figure 7-2.
The standard cooling water system
COOLER
and the high water temperature­
systems are shown in Figure 7.

AIR

AFTERCOOLER

COOLING
.__......,..___ IN WATER
115 °F. (46 °C.)
MAXIMUM
'--------1► OUT


2 - HIGH TEMPERATURE
COOLING WATER.SYSTEM

Figure 7
Cooling Water Flow
14

INSTALLATION When sound transmission is of
particular importance, it is often
For ease of inspection of the
automatic drain trap operation, the
DETAILS helpful to install a sheet of rubber­ drain piping should include an
fabric-matting, or cork under the open funnel.
GENERAL compressor to reduce the possibili­
ty of resonant sounds being It is essential in installing a new
The condition of the arriving com­ transmitted or amplified through compressor to review the total
pressor should be carefully in­ the floor. plant air system. This is to insure
spected. Any indication of a safe and effective total system.
careless handling by the carrier LOCATION IN PLANT One item which must be con­
should be noted on the delivery sidered is liquid carryover into the
receipt especially if the com­ The compressor should be install­ plant air line. Installation of after­
pressor will not be immediately un­ ed in a dry, well-ventilated area coolers, air dryers and line
crated. Obtaining the delivery where the air is as clean as separators is always good practice
man's signed agreement to any possible. and these added safety features
noted damages will facilitate any are recommended.
Air cooled units, in particular, re­
future insurance claims. quire a free flow of cooling air. Water condensation can affect the
Cooling air enters at the end of the operation of pneumatic devices.
UNPACKING AND HANDLING
enclosure (see Figure 8} and P.Xits at Aftercoolers and the addition of air
The compressor package has been the top side. The possibi lily of ex­ dryers can eliminate this hazard.
mounted on a skid type frame to cessive recycling of cooling air
facilitate handling during ship­ must be avoided. Similarly, there can be bad effects
ment. The shipping crate has been if compressor coolants or
Consideration must be given to the lubricants are allowed to enter
marked to show the safe and cor­ need for clearances around the
rect sides that forklifts can be plant air systems.
compressor for ease of main­
used. Care in positioning the tenance. The foundation plan Air line separators, properly
forklifts is important because the shows the minimum clearances re­ selected and installed, can reduce
location of the center of gravity is quired. The front of the unit, that any liquid carryover close to zero.
strongly affected by the inline


is, the instrument panel side,
assembly of the compressor airend should be left clear for a maximum CAUTION
and drive motor. distance, because this side pro­ The use of plastic bowls on line
Slings can be used to lift the vides access to the compressor filters without metal guards can be
crates but spreader bars must be and motor assembly. hazardous. Their safety can be
used to prevent the slings from ex­ affected by either synthetic
erting a force against the sides of CONDENSATE DRAIN PIPING lubricants, or the additives used in
the crates. After uncrating, the mineral oils. From a safety
Condensate (condensed water
above handling precautions should standpoint, metal bowls should be
vapor). is removed from the com­
still be observed. Forklift holes are used on any pressurized system.
pressor system through an
furnished in the steel base but lif­ Review of your plant air line
automatic drain trap, and piped to
ting should ONLY be on the com­ system is recommended.
the plant drains. The location of
pressor airend and drive motor the condensate drain in the base
side. If slings are used, spreader of the compressor is shown on the CAUTION
bars must be used. Placing protec­ foundation plans. -The drain piping Exhaust ductwork must be sized so
tive material between the slings and lower half of condensate that no excessive back pressure is
and the compressor enclosure separator must not be subject to exerted on the fan. (Maximum
should not be attempted. freezing. allowable is .25 inches of water
COOLING column.)
FOUNDATION REQUIREMENTS AIR OUT
Refer to the foundation plan for
the particular model compressor to
be installed. Foundation plans for
all models are furnished as part of
the service-literature-package sent
COOLING
with each compressor, in addition AIR IN
to other normal drawing-handling­
procedures.
Note that all piping and wiring con­ CAUTION
nections are made at the rear,


NEVER ELEVATE THE
which is the side opposite to the COMPRESSOR UNIT
instrument panel of the com­ ABOVE THE FLOOR
pressor. LEVEL WHICH MAY
The compressor can be installed ALLOW AIR TO ENTER
on any level floor that is capable of THE CABINET UNDER
supporting it. Compressor weights THE BASE.
are listed on the foundation plans. PERFORMANCE WILL
Figure 8 BE AFFECTED.
Cooling Air Flow

15

liil D'il

I◄ B .. , A

Figure 9
Standard Enclosure
Overall Unit Dimensions

• (SEE FOUNDATION PLANS FOR SPECIFIC


DETAILS ON CONNECTIONS, ETC.)

DIMENSIONS IN INCHES

UNIT DESIGNATIONS A B C

SSR-125/150/200 HP 113.2 69.0 57.8


SSR-250/300 HP 124.0 84.0 63.8
SSR-E300/350 HP 124.0 84.0 63.8
SSR-400/450 HP 124.0 84.0 63.8


16

[ii] Iii]
D

I� B A .I
Figure 10
Low Sound Enclosure


Overall Unit Dimensions

INTERNATIONAL AND DOMESTIC UNITS (50HZ and 60HZ)


(SEE FOUNDATION PLANS FOR SPECIFIC DETAILS ON CONNECTIONS, ETC.)

DIMENSIONS IN INCHES

UNIT DESIGNATIONS A B C

SSR-125/150/200 HP 113.2 69.0 75.3


SSR-250/300 HP 124.0 84.0 83.8


17

ELECTRICAL SYSTEM 1. The Compressor Motor Starter,
with auxiliary contacts and overload
relays.
GENERAL
2. The Cooling Fan Motor overload
The electrical system of each SSR relays and circuit breaker or fuses.
compressor is built with solid state
components and printed circuits as 3. The main printed circuit board,
its base. Plug-in modules and with Plug-in Power Control Module.
relays allow variations and
additions to the standard control 4. The Control Relay.
circuit. 5. The Control Transformer and
The standard electrical Fuse.
components, enclosed in a readily Modifications to the capacity
accessible, but lockable sheet control system are made by
metal b·ox are (Refer to Figure 1l): plugging in solid state modules
which contain the necessary
special circuitry.

7 6 9

13


14

Figure 11
Components Located in Starter Box

1. Start-run contactor (1M) • • 8. Power control module 15.Terminal strip (3TB)


2. Start contactor (1S)*• 9. Fuse (1 FU)*•


16.Auto stop-start module (3TR)*
3. Run-contactor (2M)*• 10. Fan motor circuit breaker (1 CB)** 17.Auto stop-start relay (3TR)* (Not shown)
4. Star-Delta timer module (HR) 11.Overload relay (20L)*• 18. Shutdown annunciator module (1SA)
5. Overload relay (10L)* • 12.Main board assembly 19.A.C.S. System module (4TR)*
6. Control transformer (T)*• 13.Terminal strip (1TB) 20.Vacuum Switch
7. Control relay (1 CR) 14.Terminal strip (2TB) 21.Cold Start Relay (4CR)

*Optional
**Machines with remote starters will have these components located in a separate box outside the compressor package.

18

AUTOMATIC UNLOADED START When the start button (2PB) is 2. The action of auxiliary contacts
CONTROL closed, the following sequence (1Sa) and (1Sb) will put control
To provide a manual and/or auto­ takes place: voltage across the start-run con­
matic unloaded compressor start, tactor coil (1M), and wi11 prevent
the following components have Control voltage is placed across the run contactor coil (2M) from be­
the starter coil (1M). The com­ ing energized. Auxiliary contacts
been coordinated into the starting
system. pressor motor will start and the (1 MA) will then close to provide an
Normal Unload Selector Switch interlock to hold the coil (1M) in an
a. A Normal-Unload Selector should then be moved from the energized state. The time delay
Switch. Unload position to the Normal relay (HR) will be energized and
An unloaded start is achieved by position and the compressor will begin to time out. Contactors (1S)
load. and (1M) are now energized and
preventing the inlet valve positioner the compressor motor will start
from opening the inlet valve before STAR-DELTA TYPE STARTERS and run in the "star connected"
the compressor has come up to full mode.
speed. By use of the Star-Delta type
The Normal-Unload Selector Switch starter, the compressor motor can 3. When the time delay relay (HR)
mounted on the compressor panel be started and accelerated using a runs out its time, which is ad­
performs this function. For manual greatly reduced "inrush" electric justable and usually set to about
starting, placing the switch in the current. The starter is completely 12-15 seconds, its contact (HR)
Unload position de-energizes the automatic and controlled by a opens. This breaks the circuit to
load solenoid valve circuit and push button station mounted in the the start contactor (1S), and
stops pressure from being compressor panel. The sequence energizes the run contactor coil
transmitted to the inlet valve of operation of the starter is ex­ (2M) through the auxiliary contact
positioner thus preventing the plained in the following section. (1Sb). Contactors (1M) and (2M)
compressor from loading. are now energized and the com­
Refer to the electrical schematic pressor is running in the "delta"
After approximately 2 minutes wiring drawing, Figure 16 or 18, mode and the auxiliary contacts
operation, place selector switch and note that the starter coils (2Ma), (used as the unloaded start
in the Normal position and allow and time delay relay are controlled automatic control) are closed per­
the compressor to load. by the normally open contacts


mitting the compressor to be
b. Star Delta Time Delay Unloading. of the control relay (1CR). Note, loaded.
(Star Delta Starter only) too, that if all protective temper­
ature switches and motor overload 4. A mechanical interlock exists
The use of the interlocking switch relays are closed, the control between contactors (1S) and (2M),
(2Ma) in the Star Delta Starter pro­ relay (1CR) will be energized when which prevents both these contac­
vides for an automatic unloaded the start button (2PB) is closed. tors "pulling in" at the same time.
start. The switch is connected to An additional interlock, electrical,
insure that during the starting cycle When start button (2PB) is closed, exists; auxiliary contact, (2Mb),
of the Star Delta Starter, the load the following sequence takes place when contactor (2M) is energized.
solenoid valve is shut down. When automatically in the Star-Delta This auxiliary contact opens,
the starter transfers to the run Type Starter: preventing any possible energiza­
position, the switch contacts close, tion of the start contactors (1S).
1. Control voltage is available
arming the load solenoid valve across the starter contactor coil 5. The time delay relay (HR) is a
circuit. The compressor will now (1S) because the timer contact solid state module plugged into
load. provided the Normal-Unload (HR) and auxiliary contact (2Mb) the main printed circuit board. A
Selector Switch is in the Normal are both closed. The start contac­ light, (?LT) mounted on the module
position on the compressor panel. tor coil (1S) will be energized and face, is lit when the time delay
FULL VOLTAGE TYPE STARTER
auxiliary contacts (1Sa) will close relay is timing and can be used to
(ACROSS LINE, MAGNETIC) and (1Sb) will open. check the timer adjustment.

Refer to the electrical schematic


wiring drawing, Figure 15 or 17.
The starter coil is controlled by
the normally open contacts of the
control relay (1CR). Note that if
all protective temperature switches
and motor overload relays are
closed, the control relay (1CR)
will be energized when the start
button (2PB) is closed.


19
* *

CAUTION
1Sb 2Mb
-II- 1Sa -II- 2Ma -II- 1Ma
Care should be exercised during
any such checks because of the
electrical hazards that will be pre­
sent when the electrical box is
* Normally
Closed
open.
1S 1M

SHUTDOWN ANNUNCIATOR -II- Normally


(OPTIONAL) Open
Start Run Start-Run
The SSR Compressor can be fur­
nished with a plug in module solid
state annunciator which indicates Figure 12
reasons for a compressor shut­
down. These are, Star Delta Contactors
1. High discharge air temperature
2. Compressor motor overcurrent
3. Cooling fan motor overcurrent
4. High bearing scavenge
temperature.
5. High motor windings
temperature (50 HZ only).
The indication of shutdown cause
is shown on the compressor con­
trol panel by lights and identifica­
tion. Only the reason for the shut­ LINE HZ LINE JUMPERS SEC SEC
down is indicated if a shutdown VOLTS VOLTS


occurs - no other lights are lit. 220 50 H6-H7 NONE 95 X2-X3
230 60 H5-H7 NONE 120 X1-X3
STAR-DELTA STARTER AUXILIARY 380 50 H4-H7 NONE 95 X2-X3
CONTACTS 415 50 H3-H7 NONE 95 X2-X3
460 60 H2-H7 NONE 120 X1-X3
The auxiliary contacts which con­ 575 60 H1-H7 NONE 120 X1-X3
trol the starter sequencing are 380 60 H4-H7 NONE 120 X1-X3
located on the upper rear section 415 60 H3-H7 NONE 120 X1-X3
of the contactor which bears its
number. The auxiliary contacts on
a standard star-delta starter are
shown in Figure 12. Figure 13
CONTROL TRANSFORMER Control Transformer Connections
The control transformer, mounted
in the electrical control box, is a
universal type. It is suitable for
use with various primary voltages
and frequencies and is connected
according to the rated voltage of
the compressor: up to 575 volts.
The transformer primary-secondary H2 H3 H4 H5 H6 H7
connections should be confirmed
prior to initial start-up on the com­
pressor. The primary-secondary
connections for various primary
voltages are shown in Figure 13.
The electrical terminals at the trans­
former are as shown in Figure 14. H1 X3
rrn7
X2 X1

• Figure 14
Transformer Terminals

20

2TI
2T2
"APPROVED FUSED DISCONNECT OR 21"3
CIRCUIT BREAKER PER NE.C. REOUIREMOffS
ri- MUST BE PROVIDED BY INSTAU.ER." IM ITI
LI •-i) 0-------- - -- ----- ---
.......
..
.. IT2
L2 u.1 I tr-- ------ --- --
,
_ , IT3
L3·-C ,-;..----------
0

IFU
ITB-1
9
ITB-5
PC XI· X2
.:TB-I ne-,
0

Z.TB-1 2TB·5
ZTB-10 5TS
4 PC
2J
PC
1TH
2TB-S
3TB- 2TB 7
p,; ·11 2TB-5

IC!I
PC
1TB
1CR
HB·I -12 24
IM 2T&-9

IJ PC
5SV
z 3TB-5 2TB·I I 7
2T8·5
C

3TB-t2 ' ,, ZTB·5


3TB·I 30P
3LT
,, '
PC Ill
2TB-l
91
lTB-6
2TB·6
4
' ,, zre-,
:nB-6 1LT 2T�
97
2TB-6
ITB·1
'!� 6J 2TB-Hl
ZTB-l
�c 96
2.TB·l2. ua-,
r , ,z 96 5J
ITB·IO 1CR

i
1ps
97
ITB-7 C

ITB-11
1CR
II
2.TB-13 zre-,

B-1 _4_ _2__0-4T...sO---IJ..._.___.LL.._--f.-4C


ITll-7 .,...________s_1___3_r,.... 1
2TB-5

Figure 15
Full Voltage Wiring Schematic
LEGEND
J Jumper Wire lPS Line Pressure Switch COOLER CIRCUIT
PC Printed Circuit tSV Load Solenoid Valve
1MTR Compressor Motor 2MTR Fan Motor
3SV Slowdown Solenoid Valve
1M 1MTR Slarl-Run ContacI0, 20L 2MTR Overcurrent Relay
5SV Oil Slop Solenoid Valve
10L 1MTR Overcurrent Relay 2FU Fuse
asv Cold Star! Blowdown Sol. Valve
1CR Control Relay lAS Normal-Unload Selector
T Control Transformer 1VAC Fouled Air Filter Switch
OPTIONAL EQUIPMENT
1FU Fuse 3DP Fouled Coolant Filler Swilch lSA Shutdown Annunciator Moaule - With Lignts
GAO Ground 4CR Cold SIar1 Control Relay BLT High Air Temperature - Red
1HM Hourmeter 9LT
1PB
High Bearing Scavenge Temperature
Stop Button INDICATING LIGHTS 10LT lMTR Overcurrent Relay - Red
2PB Start Button


1 lLT 2MTR Overcurrent Relay - Red
HAS High Air Temperature Swilch (Airend Disch.) 1LT Power On - While 3PB ReseI-TesI Bullon
5TS High Bearing Scavenge Temp. Switch 2L T' Power On - Red 2RS Control Mode Selector
4TS Cold Start Temperature Switch 3LT Fouled Coolant Filler - Amber 2SV Control Mode Solenoid Valve
4LT Fouled Air Filler - Amber
3TR AuIomaIic Starl-Slop Timer Module
13LT" Aulomalic Stan-Slop Timer - Red
14LT Slopped-Auto ResIar1 - Amber
4TR Aulo Control Selector (A.C.S.) Timer Module
15LT" A.C.S.-Modulale Mode - Red
'Localed in Starter Box 4SV Waler Shuloll Solenoid Valve
7SV Remote Cooler Solenoid Valve

21

ICB

"APPROVED FUSED DISCONNECT OR


CIRCUIT BREAKER PER NEC REQUIREMENTS
UST BE PROVIDED BY INSTALL£R:'
.-T•�
LI-� J t.�--- ------- --- - --- - -0------�1--+--+---<Y

L2 -4j
L3-�.l
..I-:..�--
_ ,
---------- - - -<>---+----<11---H F'-+--+---<>-'
t.'- ------------<;:-�:---=--+--..--t-+1 J!!!!---.---<>J
0. 0

ITB-5
XI X2 PC
ZTB-5
2TB-I ZTB-5
ZTB-10
4 'I-
ITB-14

PC
ZTB-5
PC 2TB-5
3TB-3
ICR ZTU 1
-II ZTB-5
2TB
II

PC
31"8·1

IJ


3TB�5

3TB-I ZTB-5
30P 91 3 TB:-12 91
PC ZTB-1
97
2TB-6

9
2TB-5
2TB-6
ZTB-5
ZTB-5
pc
ITB-7

II
2TB·5

Figure 16
Star Delta Wiring Schematic
LEGEND
J Jumper Wire 1PS Line Pressure Switch COOLER CIRCUIT
PC Printed Circuit ,sv Load Solenoid Valve
2MTR Fan Motor
1MTR Compressor Motor 3SV Slowdown Solenoid Valve
20L 2MTR Overcurrent Relay
1M 1MTR Start-Run Contactor 5SV Oil Stop Solenoid Valve
1CB Circuit Breaker
2M 1MTR Run Contactor 8SV Cold Start Blowdown Sol. Valve
1S 1MTR Start Contactor 1RS Normal-Unload Selector
OPTIONAL EQUIPMENT
1Ma Auxiliary Contacts 1TR Starter Time Delay Relay
2Ma,b Auxiliary Contacts 1VAC Fouled Air Filter Switch 1SA Shutdown Annunciator Module - With Lights


1Sa,b Auxiliary Contacts 3DP Fouled Coolant Filter Switch BLT High Air Temperature - Red
·10L 1MTR Overcurrent Relay 4CR Cold Start Control Relay 9LT High Bearing Scavenge Temperature
1CR Control Relay 10LT 1MTR Overcurrent Relay - Red
T Control Transformer INDICATING LIGHTS 11LT 2MTR Overcurrent Relay - Red
1FU Fuse 3PB Reset-Test Button
GAD Ground 1LT Power On - While �H::i Conl(cil MciclE!' sere_ctor
1HM Hourmeter 2Lr Power On - Red 2SV Con.trol Mode Solenoid Valve
1PB Stop Button 3LT Fouled Coolant Filler - Amber
2PB Start Button 4LT Fouled Air Filter - Amber 3TR Automatic Start-Stop Timer Module
HAS High Air Temperature Switch ?LT Starter Timer Energized - Red 13LT" Automatic Start-Stop Timer - Red
5TS High Bearing �cavenge Temp Sw;tch 14LT Stopped-Auto Restart - Amber
4TS Cold Start Temperature Switch 4TR Auto Control Selector (A.C.S.) Timer Module
15Lr A.C.S.-Modulale Mode - Red
• Located in Starter Box 4SV Water Shutoff Solenoid Valve

22

INSTRUMENTATION Hour Meter - reads the total time
of operation of the compressor. It
Air Filter Maintenance Indicator -
Mounted in the starter box, a
runs only when the motor starter vacuum switch senses the
CONTROL PANEL coils are energized. It should be pressure drop across the air filter
Discharge Temperature Gauge - in­ used to schedule maintenance element. As the filter element
dicates temperature of air leaving functions such as coolant, and traps dust, the pressure drop in­
the compressor. The temperature coolant-tilter changes. creases causing the vacuum
sensing bulb is located in the Normal • Unload Selector - con­ switch to switch on the panel
receiver tank in line with the trols the ability of the compressor mounted Air Filter Light indicating
discharge air flow. to "load up". When the selector is that the filter element should be
in the Normal mode, the Load replaced.
Dual Air Pressure Gauge - reads
receiver (sump) pressure and line Solenoid Valve can be energized, In addition to the pressure and
pressure simultaneously on the and the Inlet Valve Positioner can temperature indicators and other
same ga':lge using two separate open the Inlet Valve. When the instruments on the control panel,
selector is in the Unload mode, each compressor is equipped with
pointers. Line Pressure is in­ the Load Solenoid Valve cannot be
dicated by a Blue pointer while a high pressure relief valve -
energized. This selector position mounted on the receiver-separator.
Sump Pressure is indicated by a is used when the compressor is
White pointer. By reading the It is set to open at the maximum
started manually. working pressure stamped on the
pressure on either side of the
lubricant separator, the differential On Line-Off Line/Modulate A.C.S. tank.
shows the condition of the Selector (Optional) - chooses the
separator element. Differential type of compressor capacity con­
pressure readings shou Id be taken trol. Refer to the capacity control
when the compressor is operating section for an explanation of the
at rated capacity and pressure. different modes of control. Each is
The differential pressure should be designed for varying plant needs.
recorded when the unit is first
started or after a replacement ele­ Lubricant Filter Maintenance In­
ment is installed. This base dicator Light - Mounted on the


reading can then be used to deter­ lubricant filter. a differential
mine the proper change period. pressure switch senses the
(See maintenance section.) pressure drop across the filter, and
switches on the panel mounted
Power On Light - indicates that Lubricant Filter light indicating
control voltage is available to the that the filter element should be
control circuit and that the line replaced. However, the indicator
voltage is available at the motor­ coming on when the compressor
starter main-contacts. starts cold is a normal condition.
After operating for a short period
Start-Stop Push Buttons - energize of time, the indicator must ex­
or de-energize the control relay tinguish. Refer to the lubrication
(1 CR) to start or stop the com­ section for specific details.
pressor.

-


Figure 17 Figure 18
STD Instrument Panel NEMA 4/12 Instrument Panel

23

DUAL SLOWDOWN These controls are: The operating mode of the
compressor is controlled by the
VALVE SYSTEM A. On line-Off line (Standard,
Figure 19).
pressure switch (1 PS) responding to
changes in plant air pressure. This
The SSA Compressor package B. On line-Off line with Upper switch energizes the Load Solenoid
includes a dual blowdown valve Range Modulation (Optional, Fig­ Valve (1 SV) and Slowdown Solenoid
ure 20) . . . and either is avail­ Valves (3SV & 8SV) whenever the:
system, designed to maintain the
proper lubricant flow to the able by operation of the selector plant air pressure drops below the
switch on the compressor panel. lower set point of (1 PS) and keeps
compressor during all phases of
machine operation. these solenoid valves energized un­
ON LINE-OFF LINE CONTROL til the upper set point is reached.
The system includes the main blow­ For those plants which have a widely
down valve, the cold start blowdown varying air demand, the On Line- When these solenoid valves are
valve, the cold start temperature Off Line control will deliver air at energized. pressurized coolant is fed
switch, and control relay. full capacity, (the compressor max­ to the inlet valve positioner through
imum efficiency condition) or will the Load Solenoid Valve (1SV) forcing
The main blowdown valve (3SV), is an the inlet valve to open fully. The
electrically operated, normally open operate at zero capacity with low
receiver pressure (the compressor Slowdown Solenoid Valve closes off
solenoid valve, controlled by the the atmostpheric vent.
normal/unload switch (1RS), or the minimum power condition.)
pressure switch (1 PS).
COOLANT PRESSURE
The cold start blowdown valve (8SV)
is an electrically operated, normally
open solenoid valve, controlled by
the normal/unload switch (1RS), the
pressure switch (1 PS), or the cold
start temperature switch (4TS).
During initial cold, unloaded starting


of the machine, the cold start blow­
down valve (8SV) remains closed as
long as the lubricant injection
temperature is less than 120 ° F.
(49 ° C.) and the main blowdown valve
(3SV) is open. This results in an
INLET
elevated receiver (sump) pressure, VALVE
approximately 50 psig (3.4 BAR), to
provide adequate lubricant flow until Figure 19
the compressor has reached the On Line-Off Line Control
120 ° F. minimum warm-up
temperature.
As the injected lubricant temperature COOLANT PRESSURE INLET AIR
rises to 120 ° F. (49 ° C.), the normally VENT FLOW
closed, cold start temperature switch
(4TS) opens, de-energizing and
opening the cold start blowdown
valve (8SV), allowing the receiver
pressure to decrease to the normal
unloaded level, approximately 25 psig
(1.7 BAR).
The main and cold start blowdown
valves operate simultaneously once

"'
the injection temperature reaches the
120 ° F. (49 ° C.) minimum warm-up
temperature. INLET
VALVE

CAPACITY CONTROL
MODULATOR


The SSA compressor is equipped
with two types of capacity control -
each designed to suit the individual LINE PRESSURE
plant requirements. ( t"\OOU L A 1 El
Figure 20
On Line-Off Line with Upper Range Modulation
Control
(Optional)

24
-n-

The compressor will then operate to
Line pressure increases deliver full capacity air to the plant
110 when compressor output system. If the plant air system
is greater than plant pressure rises to that of the pressure
105 air demand. - Pr essure switch ( 1 PS)
switch upper set point, all

--
'- solenoids will be de-energized.
� ,1 upper set point
100 -i:. H � ..... rll The Load Solenoid Valve will shut off
� ,:. the flow of pressured coolant to the
I inlet valve positioner, allowing the
95
-
I
I inlet valve to close.
Compressor rated
>, tI L--._
discharge pressure

1
� The Slowdown Solenoid Valves
·c:; 90 (3SV & 8SV) will open the receiver
ro Compressor I,,
vent line, and allow the receiver
a. 85 .... capacity increases �

t
pressure to drop.
when line pressure
The compressor will continue to run,
"O
80 .... drops to reset ,_

-
but since most pressure has been
ro point of 1 PS I
Compressor
I., ,..� relieved, ii will do so with a minimum

r
75 I � capacity drops power draw.
t._.....v to zero when
0
:::,g
0
I line pressure The Pressure Switch (1 PS) has a 12
70 I
I l reaches upper psi (0.83 BAR) range between its

65 V
Reset pressure.
I I set point of 1 PS upper and lower set-point pressures.
The upper set-point pressure is
tI t factory set at slightly above the
compressor rated discharge
60 I
pressure. The correct upper-set-point
I Line pressure decreases ; pressures are listed in Regulation
I\ as air consumption Adjustment Section of this manual


'".Jl li"u_ lliJ
o and, also, on decals affixed to the

i I�
compressor.
A graph indicating the relationships
0 90 95 100 105 between the compressor output, the
% of rated line pressure line pressure, and the pressure
switch 11PS) setting is shown in
Figure 21 Figure 21.
Operating Sequence
Using On Line-Off Line Control


25

ON LINE-OFF LINE WITH UPPER AUTOMATIC START-STOP CONTROL If the timer continues to operate for
RANGE MODULATION CONTROL (OPTION) as long as its adjusted time setting,
(OPTIONAL) a relay contact in the timer module
For those plants which have a widely opens to de-energize the compressor
For those plants which have varying plant air demand, large air motor and fan motor coils. At the
relatively high and constant air storage capacity and/or want same time. an amber light (14LT) on
demand, relative to the compressor automatically available standby air the instrument panel is lit to indicate
capacity, the recommended control capacity, Automatic Start-Stop that the compressor has shut down
mode is Upper Range Modulation Control by solid state module automatically and will restart
(URM). addition is available. autornatically.
The URM control system retains the During periods of low demand, if the The automatic restart will take place
features of the On line-Off line line pressure rises to the upper set when the line pressure drops to the
control, but provides for throttling of point of pressure switch (1 PS), a time lower set point of pressure switch
the inlet air flow as the line pressure delay relay (3TR) is energized and (1 PS).
rises to the upper set point of the begins to time out. The timer,
pressure switch (1 PS). mounted on the main board in the An indicating light. red (13LT), is lit
starter box, is adjustable in a 0-15 when the timer is running. This light
By applying line pressure to a spring minute range. The timer will can be used to confirm the timer
loaded diaphragm valve, that is, the continue to operate as long as the setting and can be of assistance if
Modulator, the throttling position of plant line-pressure remains above the electrical checks are being
the inlet valve is controlled. The inlet considered. It is mounted on the
lower set-point of the pressure
valve positioner is part of the linkage, face of the Automatic Start-Stop
switch.
but does not act to do other than
module.
move the inlet valve to the open
position, allowing the modulator to
"trim·· the inlet valve position as
dictated by the line pressure.
Factory Optional Pressure
The modulating pressure range is
setting field settings switch ( 1 PS)
f od u lator
about 7 psi (0.5 BAR) and the

�,
of modulator upper set


om
moculator is factory set to straddle
the compressor rated pressure. 105 '\ ,-..... � point
Moculation begins when the line \ � \

..... ,_ 1--C >- � ...
pressure reaches about 96 percent of

100 -!►

\ \
the compressor rated pressure and
I �
-
con:inues as/if the line pressure
rises. Modulation becomes stable 95 ... Modulate to
I
\
\ )-

-
whe1 the compressor output equals 94% capacity
I \ �
the ::,lant air demand. When the
:::,:. 90
moculation is at the factory setting
the maximum capacity reduction will ·uro I \
\
\
I� Modulate to
a. 85
I \
be c::wm to approximately 60 percent I � 1--
85% capacity

of tr:e compressor rated capacity. ro
I
-... ''
(.)
80 I\
If the air demand has decreased to a
levei below the 60 percent modulated
'O
Q) I 1
out::,ut. the line pressure will increase ro
75 I \
sli�htly to actuate the pressure
switch (1 PS). The compressor will II \ �
>- - 1-- Modulate to
72'½, capacity
then shift to the off line control ?ft. 70 I \
position. and operate at unload with
the receiver vented. 65
I l
I I\
It is sometimes desirable to begin
moculation at a higher pressure than 60 I \
.,__ 60%
Modulate to
the standard factory setting thereby I capacity

.-
increasing the modulated capacity at
the time the pressure switch (1 PS) is
,r 1�, I I
actuated. Reference to Figure 22 will
indicate the typical modulated
I
capacities available v1hen this is
done.
90 95 100 105


% of rated line pressure

Figure 22
Modulation Capacity

26

AUTOMATIC CONTROL SELECTOR REGULATION
(ACS) (OPTIONAL)
ADJUSTMENT
The automatic control selector
(ACS) is designed to continuously
INSTRUCTIONS
monitor the plant air demand and IF PROPER ADJUSTMENT IS LOST,
select either the on line-off line, or PROCEED AS FOLLOWS TO RE­
the modulate control mode - ESTABLISH CORRECT SETTING:
whichever is most desirable at any ON LINE-OFF LINE CONTROL
time during an operating day.
A. Setting the inlet control valve
It allows the compressor to
operate in its most efficient mode 1. Remove bolt (A). Loosen clamp
without attendance, thereby reduc­ screw (B). Slide the travel stop (d)
ing power costs to a minimum. in the direction of the arrow in
Figure 23 until it stops.
When the compressor operates in
the on line-off line control mode, 2. Rotate the inlet air control valve
the length of time the compressor shaft counterclockwise until the
remains in the "off line" condition valve plate (E) is in the closed
is an indication of the plant air de­ position. While assuring the valve
mand. The compressor switch plate (E) is closed, position the
(1 PS) is sensing and awaiting a lever arm (F) against the travel
sufficient line pressure decrease stop (D) as shown in Figure 23
before signaling a shift to the on­ Tighten the clamp screw (B).
line mode. If the "off-line" time B. Setting the inlet valve positioner
period is relatively short, thereby linkage
indicating a high demand for air, it
is preferable to shift the control 1. Adjust the length of the inlet
system to upper range modulation. valve positioner linkage (G) until


the lever end bolt (A) threads
The ACS control does this. and easily into lever (F) while the lever
does it automatically. is held against the travel stop (D).
Tighten bolt (A).
If later. the plant demand de­
creases, and even under modu- C. Setting the pressure switch
late control the line pressure
reaches the setting of the pressure
switch (1 PS). and the control shifts TABLE I
to the "Off-line" mode. the time in
this mode will still be monitored.
A long "off-line" time-period in­ MAXIMUM
dicates a low plant air demand. in­ MODEL DISCHARGE PRESSURE
dicating the desirability of opera­
ting in the on line-off line mode. XF 103 PSIG
EP 128 PSIG
The ACS control then does this, HP 150 PSIG
and does it automatically.
The ACS control is a solid state
module addition to the standard
compressor control system. It can
operate independently of any other
optional equipment. It can add
additional usefullness to an auto­
matic start-stop control system.

D B
Figure 23
E

Inlet Control Valve


INLET
VALVE


27

4. Slowly close the isolation
CAUTION valve, allowing the line
When adjusting differential, adjust pressure to rise to the max-
switch so that maximum discharge imum discharge pressure or
pressure does not exceed value "trip" setting of the pressure
listed in Table 1. switch as shown in Table 1,
P. 27.

5. Remove cover from pressure


Setting Pressure Switch switch. Adjust as required by
turning range adjustment
screw clockwise to increase
and counterclockwise to
decrease trip setting. When
1 PS trips the compressor
should unload and vent the
receiver/separator tank. When
the Iine pressure fal Is to the
reset point of 1 PS (about 12
psig), the unit should reload.
The pressure switch differen­
tial is adjustable and factory
set at about 12 psig to meet
the requirements of the
average application.

Limited receiver and line


storage may require a wider
differential. Sufficient receiver
DIFFERENTIAL
and line storage can accept a


ADJUSTMENT
narrower differential. If adjust­
SCREW ment is required turn differen­
tial adjustment screw
clockwise to decrease the dif­
ferential and counter-clockwise
to increase the differential.
See Figure 25.

6. Vent air from customer system


Figure 25
to confirm switch operation is
Pressure Switch (1PS) satisfactory.

1. Open isolation valve. allowing 7. Replace switch cover and


control system to sense "line·· place unit in service.
pressure.

2. Place the Normal/Unload


rocker switch in the "Unload··
position an the optional con­
trol selector in the ··On/Off
Line·· Position.

3. Start the compressor. Place


the normal/unload rocker
switch in the "Normal"· posi­
tion. The compressor should
load if the line pressure is
lower than the switch reset
(lower pressure) setting. It
may be necessary to vent air
from customer system to load


unit

28

D. Setting Receiver Pressure B. Setting the inlet valve positioner 60 HZ
linkage UNITS
1. Turn the Normal/Unload switch
to "Unload." Start the com­ 1. While being sure that the lever Model "XF" compressors 103 PSIG
pressor. Allow the unit to arm (G) of the modulator (H) is Model "EP" compressors 128 PSIG
reach operating temperature against its full open stop (I), Model "HP" compressors 150 PSIG
with both blowdown valves ex­ adjust the length of the inlet valve
ahusting. positioner linkage (J) until the
lever end bolt (A) threads easily 5. After confirming the upper trip
2. Close the isolation valve. into lever (F) while the lever is held setting of the pressure switch
3. Rotate the lever arm (F) until against the travel stop (D). (1PS), open the isolation valve and
25-30 PSIG or (1.7-2.0 BARS for Tighten bolt (A). set the discharge pressure 4 psi
50 Hz Units) Sump pressure is (0.3 BAR) below the rated opera-
C. Setting the modulator ting pressure listed on the com-
read on the air pressure gauge.
(See Figure 23). 1. Remove the acorn nut (K) from the pressor data plate.
modulator (H), loosen locknut (L),
6. After adjusting the discharge
4. Loosen travel stop bolts (C). and run adjusting screw (M) in a
pressure with the isolation valve,
Slide the travel stop (D) until ii few turns.
confirm that the inlet air valve is
touches the lever arm (F). fully open.
2. Start the compressor with the
Tighten the travel stop bolts (C).
Normal/Unload selector switch in
7 Turn the compressor control
5. Adjustment is now complete. the ··unload" position and the
selector to the "Modulate"
On/Off Line/Modulate selector in
the "On/Off Line" position. Allow position.
ON LINE-OFF LINE WITH UPPER the unit to reach operating
RANGE MODULATION CONTROL 8. Airflow should be sensed coming
temperature. from the orifice located in the
3. Turn the Normal/Unload selector bottom of the modulator body (H).
A. Setting the Inlet Control Valve
switch to the "Normal" position.
9 Turn the modulator adjusting
1. Remove bolt (A). Loosen clamp This allows the positioner (N) to screw (M) until lever (G) begins to
screw (B). Loosen travel stop be actuated, opening the inlet con­
move off stop (I).


bolts (C). Slide the travel stop trol valve (E) loading the com­
(D) in the direction of the arrow pressor.
NOTE: Confirm !ine pressure has
in Figure 26 until it stops. held steady and the inlet valve is
4. Insure that the pressure switch
(1PS) is operating properly by still fully open.
2. Rotate the inlet air control valve
shaft counterclockwise until closing the isolation valve located 10. While holding adjusting screw
valve plate (E) is in the closed on the discharqe line of the.com­ (M) firm, tighten locknut (L).
position. While assuring the pressor. Watch the pressure Replace acorn nut (K).
valve plate (E) is closed, position gauge to insure that the pressure
switch (1 PS) opens at the correct 11. Raise the line pressure by the
the lever arm (F) against the travel
maximum discharge pressure for use of the isolation valve to just
stop (D) as shown in Figure 26. below the upper trip setting of
the model being adjusted. These
Tighten clamp screw (8). the Iine pressure switch (1 PS).
maximum discharge pressures or
upper trip settings of the line Set adjustment lock bolt (0) so
pressure switch (1PS) are as that it just contacts lever (G).
follows: Tighten locknut on bolt.

J
N C

H D L M K B
Figure 26. Inlet Control Valve With Modulator

29

D. Setting receiver pressure 7. Look through the compressor­ 12. Because some lubricant will
motor cooling-air-access and, remain in the piping and acces­
1. Turn the Normal/Unload switch to
with a flashlight, observe a blade sories, it may be necessary to
"Unload," and compressor control add lubricant to bring the level
of the compressor motor cooling
selector to "On/Off Line." Allow fan. Have an assistant jog the back to the mid-point of the sight
unit to blowdown fully with both compressor motor and note the glass. Tighten the fill plug
blowdown valves exhausting. direction of rotation of the securely.
2. Close the isolation valve. motor. The rotation must be in 13. Start the compressor and let it
accordance with the directional­ warm up for approximately 2
3. Rotate the lever arm (F) until 25-30 arrow-decal affixed to the motor.
psig or (1.7-2.0 BARS for 50 Hz minutes while operating in the
Units) is read on the air pressure Note: The correct motor rotation "Unload" and "On/Off Line"
gauge. is clockwise when the motor is control modes.
viewed from the end opposite the 14. When operating the compressor
4. Loosen travel stop bolts (C). Slide drive end.
travel stop (D) until it touches the in the "Unload" mode, observe
lever arm (F). Tighten the travel the Sump Pressure Reading on
stop bolts (C). the Air Pressure Gauge. The
CAUTION sump pressure should not fall
5. Adjustment is now complete. For the motor rotation check, the below 25 psig (1.7 BAR). If so,
motor jogging must be for as short please refer to section D of
OPERATION a time as possible. After depressing Regulation Adjustment instruc­
tion elsewhere in this manual.
the start switch, immediately
INITIAL PREPARATIONS AND depress the stop switch.
START-UP 15. After approximately 2 minutes,
switch the load control to
1. Inspect and confirm that all pip­ WARNING "Normal".
ing and electrical work is tight
and that the main disconnect If main motor rotation is not 16. SLOWLY open the discharge
switch is in the OFF position. correct, disconnect the main isolation valve to put the
power, and interchange any two line compressor on the line.


2. Confirm ihat line voltage and connections (L 1, L2, or L3) at the
compressor nameplate voltage 17. If the compressor is discharging
starter. into a non-pressurized system, it
are the same. Confirm that the
control transformer is connected is good practice to use the
correctly. Refer to the electrical isolation valve to develop a back
8. For air cooled units, or cabinet pressure of about 5 psig (0.4
section of this manual for trans­ vented units, when the compres­
former hook-up. BAR) below the compressor
sor rotation is correct, the cool­ rated pressure. When the
3. The unit will normally be prefilled ing or venting fan motors will system is pressurized, open the
with Ingersoll-Rand lubricant also be correct. In each case, isolation valve completely, and
and it is only necessary to check cooling air should be exiting allow the unit to operate
the level gauge before and imme­ from the enclosure. If, for some normally.
diately after start-up. Add two reason, this is not so, the fan
quarts of lubricant through the motor rotation should be re­ 18 For air cooled units, the
compressor inlet. versed. Put the main disconnect discharge temperature should
in the "OFF" position, and inter­ rise to near 190 ° F. (88 ° C.) and
4. Remove the panel section in the change any two fan motor leads may rise to as high as 210 ° F.
enclosed unit to expose the com­ (2T1, 2T2, or 2T3) at the fan (99 ° C.) at full load if the ambient
pressor motor. Inspect the motor overload relay (2OL). cooling air is as high as 100 ° F.
motor and control wiring for (38 ° C.).
tightness and safety. 9. Check to determine that the
lubricant level is at the mid-point
5. Place the main disconnect of the sight glass provided.
switch in the ON position. Note
whether the white "power on" 10. If the compressor is watercooled,
light on the panel is lit, indica­ turn on the cooling water. Close
ting control voltage is available the discharge isolation valve.
to the control circuit. Start the compressor.
6. Place the Normal/Unload selec­ 11. Check for tightness of all fit­
tor switch in the Unload position, tings, particularly in the
the control selector in the "On/ lubricant system. After a few
Off Line" position. minutes operation, shut the
unit down and check the lubri­


cant level in the receiver.

30

LUBRICANT FILTRATION
LUBRICATION Due to the large volume of lubricant
circulated and its direct contact with Each compressor has a hydraulic­
the air being compressed, foaming at type full flow filter with a single
LUBRICANT blowdown or other pressure change replaceable element.
SSR ULTRA Coolant conditions is often a problem with
rotary compressors. The SSR ULTRA The filter is mounted downstream of
Rotary screw compressor fluids have Coolant has quick air release the cooler and the thermostatic
a triple function to perform. They characteristics and minimal air­ control valve.
lubricate the bearings and contacting entrainment, such that foaming has It is rated at 10 microns.
surfaces of the rotors; they seal been largely eliminated as an
internal clearances within the rotor operating concern. It has a differential-pressure-bypass­
chamber; and they provide for the valve set to open in the event that
cooling of the compression process. In addition, the SSR ULTRA Coolant the pressure drop across the filter
The bulk of the fluid is actually used has little affinity for water as well as element rises to as high as 15 psi,
for cooling with only small amounts quick, effective water release at which indicates an excessively
used for lubrication and sealing. shutdown. These characteristics fouled element. as well as poor
provide for maximum bearing maintenance practice.
The lubricant used in the SSR com­ lubrication integrity, as even small
pressor has been specially blended amounts of water in the lubricant can To eliminate this latter possibility, a
and formulated to perform the be highly detrimental. These factors maintenance indicator consisting of
above three functions exceptional­ also provide for easy draining of a filter mounted differential pressure
ly well. Its lubricating qualities ex­ condensation from the vertical switch and a panel mounted indi­
ceed those of standard petroleum separator receiver tank. cating light, is provided. This
oils as well as those of previously indicator will signal that a differential
available synthetic lubricants. Its pressure of 15 psi has been reached
Each SSR compressor will normally
•1iscos1ty characteristics are such as and the filter element should be
to pro·;ide excellent sealing of be filled, tested, and shipped with a
replaced.
complete charge of Ingersoll-Rand
intern2.I clearances over broad
SSR ULTRA Coolant. This fluid is During some start-ups. if the coolant
ranges of operating temperatures. In
changed each 8000 hours of oper­ is cold. the indicator may light up.
fact. 1�e viscosity change with
ation or once a year, whichever This is normal. If the filter element


tempe·ature is small enough to
comes first. While operation far is serviceable. the indicator will
permit the lubricant to be used extinguish as the compressor
beyond this time frame is possible
over the entire range of ambients temperature rises.
under favorable conditions, change­
from 20 ° F. (-7 ° C.) to 115 ° F. (46 ° C.)
out at the recommended times will
without significant loss of its LUBRICANT FILTER INDICATOR
assure maximum unit protection and
qualities. When conditions other
operating life for all installations.
than the design levels described However. regardless of the main­
are encountered. we recommend Filter change-periods should be tenance indicator reading. the filter
you contact your nearest Ingersoll­ strictly adhered to for proper fluid
element should be changed after the
Rand representative for additional maintenance. See the Filtration
first 150 hours of operation and
information. Section for specific filter change
again after each 2000 hours of
recommendations.
operation. If the compessor operates
Most important is the performance of less than 2000 hours per year. the
the fluid as a coolant. In this function Readily available but normally element should be replaced when the
the SSR ULTRA Coolant demon­ ordered and shipped with the unit is annual lubricant chanqe is made.
strates its outstanding abilities. It has a service kit which includes air and
exceptional oxidation stability at lubricant filter elements and make­ The procedure for renewing the filter
system operating temperatures so as up lubricant for approximately one element is outlined in the
to provide long life. Advanced rust year's operation. maintenance section of this manual.
inhibitors assure clean piping, clean Spare elements and gaskets should
cooler tubes, and clean separator If a situation arises where. for some be kept in stock at the installation to
tanks. reason. this fluid cannot be used. facilitate regular replacement.
consult Ingersoll-Rand for specifica­
The procedure for change out of the
tions and recommendations on
lubricant is outlined in the
possible substitutes.
maintenance section. Make-up
lubricant for use between annual
changes should also be kept in
plant stock.


31

SAFETY SHUTDOWN (2TB-5) for an open temperature
switch, an open overload relay, an
manifold block. The proper injec­
tion temperature, for test purposes,
CHECKS open "stop" push button or a is in the 130 ° F. to 150 ° F. range
defective control relay (1CR). (55 °C. to 65 ° C.).
HIGH AIR TEMPERATURE 3. Fouled coolers. Check external
If the trouble is in the motor starter
A high air temperature shutdown control circuit, check across ter­ cooler surface of aircooled units
switch is located at the discharge minals (2TB-11) and (HB-13) to and internal cooler tubes of water
port of the compressor. confirm that the time delay relay cooled units.
contacts (HR) are closed. If they 4. Operating air cooled units in ex­
This switch should be checked at cessively high ambients.
regular intervals; about once a month are open. the time delay relay solid
state module should be replaced. 5. Insufficient ventilation.
is recommended. 6. Defective thermostatic valve.
This switch can be checked for COMPRESSOR WILL NOT BUILD 7. Operating above rated
proper operation by either: UP RATED PRESSURE discharge pressure. This also
shortens motor insulation life
1. Shutting down the cooling fan on The air demand may be too high. because of the overload the motor
an aircooled unit by opening the Check for plant air leaks or open must carry.
disconnect switch on the fan motor service valves.
circuit breaker, or, EXCESSIVE LUBRICANT
The pressure switch (1 PS) may be CONSUMPTION
2. Shutting off the cooling water on set too low. Check the pressure
a watercooled unit. A ruptured or fouled separator ele­
setting when the unit is operating
ment or a blocked scavenge
In either case, the discharge in "Normal". and the line-off line orifice-screen-assembly will in­
temperature will rise at a fairly rapid control mode. If the pressure set­ crease coolant-lubricant consump­
rate. Shutdown should occur at ting is increased. it must not be tion. The orifice-screen-assembly
about 230 ° F. (110 ° C.). set higher than the upper set point should be checked regularly.
pressure listed on the Compressor
The temperature at which the shut­
Data Plate. An increase in pressure differential
down occurs should be recorded for
comparison with similar future test across the separator is the indica­
COMPRESSOR FAILS TO DELIVER tion of a fouled separator.


results.
RATED .CAPACITY
A decrease of pressure differential
HIGH BEARING SCAVENGE A fouled inlet air-filter will reduce from the previous reading would in­
TEMPERATURE the actual weight flow of air which dicate a ruptured separator.
A high bearing scavenge lubricant will show up as reduced capacity
Differential pressure should be
temperature switch is located in of the compressor. The filter ele­
noted and recorded. It should be
the compressor rear bearing ment should be changed when the
taken when the compressor is
scavenge manifold piping panel-mounted indicator light
operating at rated capacity and
comes on.
pressure.
This switch will open and shut the A faulty adjustment of the capacity
unit down at a bearing scavenge regulation system could cause
temperature of about 230 ° F. modulation of capacity at incorrect CAUTION
(110 °C). pressures. Check the inlet valve Hoses should be checked every
positioner and the modulator.
TROUBLE A defective modulator needle and
three months for signs of
deterioration. Hairline cracks and
INVESTIGATION seat could cause modulation at hardening are two signs to look
lower than intended line pressures. for; replace hoses as required. A
COMPRESSOR FAILS TO START Inspection of the inlet valve posi­ service life of two to four years is
tion during modulation will in­ normal.
1. If the main disconnect switch is dicate this condition. The inlet­
closed and the "power on·· light valve should be in a throttle posi­
bulb is good but does not light up. tion consistent with the curves
the control voltage is probably not shown in the "Upper Range
available. Check the transformer Modulation Control" section of this
secondary for control voltage and manual.
check the fuse (1 FU) for continuity.
If the fuse is blown. check for the COMPRESSOR
fault. OVERTEMPERATURE SHUTDOWN
2. If "power on" light (1 LT) is lit
and starter button is depressed. Compressor overtemperature shut­


check the voltage across the hour down may be caused by:
meter terminals (2TB-11) and 1. Insufficient lubricant being cir­
culated. Check the lubricant level
(2TB-5). If full control voltage ex­
ists across the hour meter, the in receiver sump.
trouble is in the motor starter. If 2. Insufficient cooling of lubricant.
full voltage does not exist across Check injection temperature by in­
the hour meter, check the protec­ serting a dial type thermometer in
tive control circuit from (1TB-1) to the specially provided port in the

32

EXCESSIVE LINE CURRENT By connecting the test wire clip to Procedure -
(1TB-1) carefully touch the probe to
If shutdown occurs because of (3TB-12). This applies power to the Place a suitable container under the
electrical overload, a trip indicator Coolant Filter Lamp (3LT). If the filter housing drain valve which is
projects from an opening in the lower lamp is good it will light up. located near the bottom of the
portion of the relay. housing.
Leaving the clip connnected to
Overload relays can trip if line (HB-1), move the probe to (3TB-13). Remove the bolt at the bottom of the
voltage is excessively low. This This applies power to the Air Filter housing. This will free the housing
condition causes the motor to draw Warning Lamp (4LT). If the lamp is and element from the filter head.
higher current. Unbalanced electrical good it will light up. Remove the "O" ring gasket.
phase can contribute to this problem.
Still leaving the clip connected to Inspect the element and housing for
Operating at pressures above the (HB-1), move the probe to (3TB-8). foreign particles which have been
rated pressure will cause higher This applies power to the Automatic trapped in the element and also for
motor currents. Restart Lamp (14L T). If the lamp is general overall condition - then
good it will light up. discard the element and clean the
All starter contacts must be in good housing.
condition. The contacts can be
inspected by removing the arc box LUBRICANT LEVEL CHECK Reassemble the filter using a new
from the front of the starter. With the unit not running, lubricant element and "O" ring. Each
should appear in the sight glass. replacement element is furnished
WATER CARRYOVER TO with replacement gaskets -including
DISCHARGE LINES With the unit runnina unloaded and one which fits under the bolt head.
the lubricant at operating
A fouled or defective condensate trap temperature, the lubricant level Torque the bolt to 20 Lb.-Ft.
that does not drain condensate will should be at mid-range in the sight
allow the condensate to be carried to glass. AIR FILTER ELEMENT
the plant system. The trap operation
must be checked regularly. Time of change - when the panel

Condensate should flow whenever


MAINTENANCE mounted indicator lights up. or
annually, when the coolant is


the aftercooler lowers the discharge GENERAL changed. Indicator should be
air temperature below the dew point. observed at full load.
Under atmospheric conditions of very The SSA Compressor requires a
low humidity, it is possible that no minimum of maintenance. The major Procedure -
water vapor is condensed and concerns are the air cleanliness, the
therefore there will be no flow from quality of the lubricant and the Shut down the compressor.
the condensate trap. lubrication of the electric motors. Loosen wing nut on top of inlet filter
Over relatively long periods of time, housing. Lift cover up and away to
The use of an open funnel in the other system accessories will require
drain line has been recommended to expose element.
replacement; items such as the air
make a visual inspection easier. separator element. Carefully remove the old element to
prevent dirt from entering the inlet
LAMP TEST PROCEDURE The procedures to follow when valve. Discard old element.
servicing the compressor or
Periodic maintenance of the com­ replacing major accessories are Thoroughly clean the element
pressor should include checks of the described in the following housing and wipe all surfaces.
safety shutdown devices, and paragraphs.
problem warning lights. Each of the Install new element and inspect to
four lamps on the instrument panel LUBRICANT FILTER ELEMENT insure that it has seated properly.
may be tested by using a short test Install top of inlet filter housing.
jumper wire with a clip on one end Time of Change - after first 150
and a test probe on the other. hours and every 2000 hours Inspect the rubber seal on the
thereafter. or when the filter indicator retainer wing nut and replace seal if
shows the need for element change, required.
or when the lubricant is being
CAUTION
changed. Tighten wing nut.
Care should be exercised during
Place unit in service.
these lamp checks because of the
electrical hazards that will be WARNING
present when the electrical box
is open. Confirm all pressure is relieved
from the compressor system and
that the main electric disconnect


By applying main power to the switch is open and tagged to
compressor the control transformer remain open.
will be energized to supply proper
voltage for testing the lamps.
Provided the 1FU is not open, the
Power On (1LT) lamp will light as
soon as power is applied to the
transformer.

33

LUBRICANT CHANGE TIME LUBRICANT SEPARATOR Clean the gasket surface on both the
ELEMENT tank and its cover. Exercise care to
AFTER EVERY 8000 HOURS OR prevent pieces of the old gasket from
Time of Change - when the falling down into the tank.
ANNUALLY (SSA ULTRA)
differential pressure across the
Procedure and Comments - element reaches three times the Check the tank to be absolutely
initial pressure drop or a maximum certain that no foreign objects such
There are two points of lubricant of 15 psi at full load. as rags or tools have been allowed to
drainage on each compressor; 1) a fall into the tank. Install replacement
NOTE: A drop to zero differential element down into the tank after
valved drain in the base, and 2) a
draincock or valve in the oil filter also indicates a failing or by passing checking the new element gaskets
housing. Both of these drainage element that must be replaced. for possible damage. Center the
points should be used to obtain element up within the tank.
the maximum drainage of used Procedure -
_!_yg_r icant. Place the tank cover in its correct
CAUTION position and install bolts. Tighten
the bolts in a cross-pattern to
WARNING Shut down the compressor, close prevent over-tightening one side of
the service air line isolation valve the cover. An improperly tightened
No drainage points should be and open the main electrical dis­ cover will likely result in a leak.
opened until the compressor has connect switch. Confirm all air
been isolated electrically and all air pressure is relieved from receiver. Install scavenge tube down into the
pressure has been removed from tank until the tube just touches the
the system. separator element. Tighten fittings_
Disconnect the scavenge tube at the
airend. Install the regulation lines in their
original position.
The lubricant should be drained soon Loosen the fitting that holds the
after the compressor has been shut scavenge tube into the tank and Start unit, check for leaks, place in
down_ When the lubricant is hot, the withdraw the tube assembly. service.
drainage will be more complete and
Disconnect the piping from the


any particles in suspension in the DRIVE MOTOR LUBRICATION
lubricant will be carried out with the receiver cover. Tag the lines if
lubricant. required. The induction-type squirrel cage
Use a suitable wrench and remove motor have anti-friction ball or roller
the bolts that hold the tank cover in bearings front and rear.
WARNING position. Remove cover by lifting up The periods between re-greasings of
Extreme care should be exercised and away. the motor bearings can vary, primarily
when draining the hot lubricant so with the severity of the service
Carefully lift the separator element
that no possibility of injury to up and out of the tank. Discard the conditions under which the motor
personnel elCists. faulty element. operates. As a general rule the
following would apply:

After the unit is drained and a new


filter element is installed, refill the
system with fresh lubricant. Frequency of Lubrication

Service Condition
RECOMMENDED
MODEL LUBRICANT Dirty Environment Clean Environment
CAPACITY Enclosure Frame or Non-Continuous and Continuous Lubrication
Type Size Operation Operation Amount
SSR-125 thru 200 HP 22 Gal.
SSR-250 thru 300 HP 35 Gal. Open OP 404T to 449T 1 to 3 Months 6 Months 2.5 cu. in.

SSR-E300 thru 350 HP 32 Gal.


Enclosed-Fe 405T to 449T 1 to 3 Months 6 Months 2.5 cu. in.
SSR-400 thru 450 HP 28 Gal.

Bring the receiver level of lubric,ant


up to the mid-point of the gauge
:;ilass. Replace the fill cap.


Start the compressor and run it for a
short '.',hile. Shut it do•:;n and check
the lubricant le•iel 1n the receiver.
Add enough lu:::ir1cant so that it
appears in the sight glass

34

A major cause of bearing failure is 1. Prior to placing a unit in storage, REFER TO THE OPERATION
over-greasing.Follow the procedure rotate the drive motor several revo­ SECTION of this Manual for initial
below to prevent over-greasing: lutions by hand in the proper direc­ preparation and start up instruc­
• Run the compressor for 1 5 to 30 tion of rotation. This can be accom­ tions. However, before putting the
minutes, then shut the com­ plished by carefully turning the rotor unit into operation, the Vapor
pressor down and open, lock and with the fan blades located at each Space Inhibitors must be drained
tag the main electrical end of the rotor. and replaced with new lubricant as
disconnect. follows:
• Remove the lower grease outlet 2. Thereafter, rotate the motor as
plugs. described in Step 1 at three month Procedure and Comments -
• Clean the grease fittings. intervals until such time as the unit
is placed in service. 1. There are two points of lubri­
• With a hand-operated grease gun cant drainage on each compressor.
add 2.5 cubic inches of grease. 3. If the storage time should exceed 1) A valved drain in the base, 2)
Determine in advance the number a total of six (6) months duration, re­ drain cock in the lubricant filter
of strokes required to deliver 2.5 grease the motor using the amount housing.
cubic inches of grease.If grease of type of grease described in the
appears at the outlet while you Both of these drainage points should
maintenance section of this manual
are adding grease, stop pumping. be used to obtain maximum drain­
covering the specific unit.
• Start the unit and let it run un­ age of the used lubricant.
loaded for about 10 minutes. After re-greasing, continue to rotate
• Shut the compressor down, open, the motor at three (3) month
lock and tag the main electrical intervals as previously described. WARNING
disconnect. No drainage points should be
• Replace the lower grease outlet MOTOR FRAMES LARGER opened until the compressor has
plugs. THAN 449T been isolated electricaly and all
air pressure has been relieved
Recommended Motor Greases 1. Prior to placing a unit in storage, from the system.
(or equals) grease the motor bearings using the
amount and type of grease de­
Chevron SRl-2 .......Standard Oil scribed in the Maintenance Section 2. A hand operated transfer pump.


of California of the Operator's Manual. connected to the base drain cou­
Premium RB ............. Texaco pling will be a convenient way to
Unirex #2 ................. Exxon 2. Rotate the motor by hand several
times in the proper direction of remove the used lubricant.
Dolium .................... Shell
Polyrex .................. Exxon rotation. This can be accomplished 3. The lubricant should be drained
by carefully turning the motor with soon after the compressor has
the fan blades located at either end been shut down. When the lubri­
of the rotor. cant is hot, the drainage will be
WARNING 3. Thereafter, rotate the motor as more complete and any particles in
described in Step 2 at three (3) suspension in the lubricant will be
Grease should only be added carried out with the lubricant.
when the motor is stopped and month intervals until such time as
power disconnected. the unit is placed in service.
4. When the unit has been removed WARNING
from storage, re-grease the motor at
start-up using the complete proce­ Extreme care should be excercised
dure as outlined in the Maintenance when draining the hot coolant so
DRIVE MOTOR section of this manual. that no possibility of injury to per•
BEARING sonnet exists.
MAINTENANCE­ LONG TERM
STORED UNITS STORAGE 4. After the unit is drained. close all
drain valves and refill the system
GENERAL with fresh lubricant. Add two
GENERAL
gallons of lubricant to the com­
The factory upon special request
To ensure that complete contact is pressor through the air inlet piping
prepares compressor units for long
maintained between the motor while holding the inlet valve open.
term storage. In such cases. the Bring the receiver level of lubricant
bearings and the bearing grease on following guidelines and recommen­
units to be placed in storage for up to the midpoint of the gauge
dations apply. glass.
extended intervals, the following
motor maintenance procedures 5. Start the compressor and run it
CAUTION


should be adhered to: for a short while. Shut it down and
404T THROUGH 449T VAPOR SPACE INHIBITORS check the lubricant level in the
FRAME DRIVE MOTORS receiver. Add enough lubricant to
Before actual start up of the
compressor. the unit must be bring the level back to the gauge
midpoint.
drained of lubricant containing
vapor space inhibitors.

35

COMPRESSOR ITEMS REQUIRED NOTE: 1. Module area must be dry
and completely free of dirt prior to
CHANGE/LUBRICANT In addition to the tools normally applying a decal.
PROCEDURE found in any reasonably equipped
NOTE: 2. Decals in sufficient
serviceman's toolbox, the following
items should be available at the quantities must be ordered from
GENERAL work site: Piscataway Parts Center, contact
To drain coolant/lubricant from your Ingersoll-Rand distributor.
A suitable drain pan and container
compressor as completely as to hold coolant drained from unit. NOTE: 3. Units running on Food
possible when changing types of Grade Coolant SSA H-1 F must have
coolant/lubricant to avoid A quantity of proper coolant the coolant changed at least every
contamination or dilution of sufficient to refill the compressor. 3000 hours or more frequently under
new fluid. dirty environmental conditions.
A minimum of one replacement
coolant filter element.

CAUTION PROCEDURE
ULTRA coolant is not compatible
with certain "Compressor Condi­
tioner" fluids often utilized to WARNING
CAUTION
remove varnish deposits from
No drainage points should be
machines running on pertroleum THIS COMPRESSOR UNIT CONTAINS
opened until the compressor has
oil products. Addition of these INGERSOLL-RAND SSR-ULTAA
been isolated electrically and all COOLANT. SSR-UL TRA IS FREE OF
products to ULTRA Coolant can
air pressure has been removed HYDROCARBONS AND IS SUITABLE FOR
lead to plugged filters and
from the system. USE IN INSTRUMENT AIR SYSTEMS.
bearing lines, potentially leading
to severe mechanical problems.
Therefore, do not flush the com­
pressor system with a "Com­ Operate the unit to bring the
pressor Conditioner" prior to complete system up to operating


filling with ULTRA Coolant. temperature. Shut compressor
down.
Initiate remainder of change
AVOID THE USE OF ANY OTHER
NOTE: If changing to food grade procedure while system is still warm. FLUID IN THIS UNIT. REFER TO
coolant/lubricant SSA H-1 F, the SPECIAL INSTRUCTION SHEET
following procedure is mandatory. APDD HM! FOR DETAILS.
The initial fill of SSA H-1 F should be
run a few hours (2-10 hours) at NO WARNING FAILURE TO HEED THIS WARNING
LOAD and then drained. A fresh '
MAY RESULT IN SYSTEM CONTAMI-
change of SSA H-1 F is then added Extreme care should be exercised ■ NATION. •1N2c

and the unit is placed in normal when draining the hot lubricant
service. so that no possibility of injury to
personnel exists.

CAUTION
(SYSTEM CONTAMINATION) Drain the module, lubricant cooler.
CAUTION
and any low points in the lubricant
The factory does not recommend piping system. THIS COMPRESSOR UNIT CONTAINS
field changes from SSR Coolant INGERSOLL-RAND SSA H·1F FOOD
to SSR H-1F based on tests and Change the coolant filter element. GRADE COMPRESSOR COOLANT.

experience as of January 1986. INGERSOLL-RANO RECOMMENDS THIS

We believe that in a majority of Refill the unit with proper type COOLANT BE CHANGED EVERY J.000

applications it may be impractical


coolant. Exercise care to prevent HOURS.

and undesirable to follow this


entry of any contamination.
course of action. Start unit and check coolant level.
With unit running unloaded the
The residual dye from SSR
Coolant will tint the replacement
coolant will be visible between the
bottom of the sight glass to midpoint
coolant after the double flush pro­
cedure has been completed. The
of the sight glass. DO NOT
factory recommends that the
OVER Fl LL. Add additional coolant if AVOID THE USE OF ANY OTHER


required. Check for any leaks. FLUID IN THIS UNIT. REFER TO
customer take this fact into con­
SPECIAL INSTRUCTION SHEET
sideration before decision is Thoroughly clean a suitable area of APDO 106 FOR DETAILS.
made to make a chargeout uti­ the module near the coolant fill
lizing SSR H-1F Food Grade connection. Install the correct decal, FAILURE TO HEED THIS WARNING
coolant. as shown below, for the fluid now '
MAY RESULT IN SYSTEM CONTAMI-

installed in compressor. ■ NATION. ll51U06

36

PRELUBE CAUTION
2. Install new oil filter element and
slowly fill canister with clean
PROCEDURE: The coolant-lubricant used lubricant. Pour oil slowly to allow
304MM AIREND during the Prelube procedure, any air to rise to top of canister as
lubricant is poured over the
{ONLY) must be the same type that is
contained in the unit. (i.e. SSR element. Replace filter cover
ULTRA Coolant, SSR Blue, SSR using new "O" ring provided with
REQUIRED BEFORE STARTING: Food Grade). element. Tighten cover.
Under the following circumstances: Steps One and Two do not apply to
new long term storage units. 1 & 2
1. It is preferred that this start-up do apply to airend replacements,
prelube procedure be done on all Items required, in addition to tools,
etc.
new units being started even if normally found in any reasonably
they are within 6 months from the equipped serviceman's toolbox are 3. Locate blowdown valves 3SV and
date of shipment from our as follows: 8SV and remove from tank cover
factory. by loosening the tubing manifold
A. Small pump of type found at most
at end connected to 1" tube x 1"
2. It is absolutely required when unit local hardware or tool supply
NPT 90 elbow screwed into
has been in long term storage. (6 stores capable of being driven by
separator-tank cover. Remove 90
months or more) a drill motor.
elbow from the cover and plug
3. Unit is to be re-started after any B. 1/4" or 3/8" drill motor and hole by installing 1" NPT plug
major component of the coolant extension cord. described in the "items required"
system has been changed or list.
C. Clean container to hold the
drained for any reason.
coolant which will be pumped 4. Loosen and remove 1/4" O.D.
4. When changing the coolant filter into the thrust bearings. tube from separator scavenge
element, install replacement orifice-screen. Remove orifice­
element in housing and slowly D. Various hoses or tubing to screen and adapter-tube
pour coolant into housing to fill. connect pump suction to the assemblies from separator
clean coolant container and to cover.
Install, cover, and tighten.


also connect pump discharge to
the 3/8" NPT female connections Install 1/4" NPT plug described
at airend thrust bearing housing. in "items required" list into tank
CAUTION cover.
E. A source of 110 AC volts to
This procedure should only be energize coolant stop solenoid Do not damage any
carried out by a qualified valve (5SV), and to operate your components as they are to be
Ingersoll-Rand Service drill motor. Extension cord of reinstalled after completing
Representative. Contact your suitable lengths. prelube.
nearest Ingersoll-Rand
Distributor or Air Center. F. A source of clean and dry 5. Locate 1/4" NPT x 1/4" O.D.
auxiliary air capable of 15-25 psig tube 90 fitting on side of the
FAILURE TO FOLLOW THIS to pressurize the receiver­ receiver-separator tank that
PROCEDURE MAY RESULT IN separator tank and a hose with provides a signal for "SUMP"
EQUIPMENT DAMAGE. fittings to connect with 1/4" NPT gauge. (See Figure C).
female port on side of receiver­
separator tank.
Objectives of the prelube procedure: G. One each 1" NPT pipe plug, one
Utilizing an auxiliary source of clean each 1/4" NPT pipe plug, one
pressurized air and a small pump, each 1/4" NPT pipe tee and a
fresh coolant-lubricant under short 1/4" NPT nipple.
pressure will be injected into the oil
piping, coolers and airend. The PROCEDURE ORIGINAL ¼P x '/,T
resulting air pressure will push the TANK 90 ° FITTING
coolant-lubricant through the piping 1. If the airend is a replacement,
and coolers to purge the system of connect all components and
air pockets. piping on installed replacement 1) REMOVE TUBE FROM FITTING
2) REMOVE FITTING FROM TANK
airend. Refill receiver-separator
In addition, the small pump will be sump with clean IA lubricant of
used to inject 1/2 gallon (2 liters) of proper type (SSA ULTRA, Blue or
fresh coolant directly into each of Food Grade).


the two thrust bearing assemblies.
Figure C.

37

Remove tubing and fitting from 8. Loosen vent valve on coolant NOTE: This may take a few
tank and install short 1/4" NPT filter cover and disconnect oil moments as the volume of air in
nipple and tee as shown in hose that feeds oil to female the coolant cooler and its
sketch "D". Install previously side of the rear bearing housing. associated piping must be
removed 90 fitting into the tee (See Figure "A" or "8''). purged.
and connect "SUMP" signal
line. (See Figure D). When coolant flows from hose,
THRUST BEARING immediately reconnect hose to
FEED LINE its proper fitting.
FROM OIL
FILTER
TUBE TO PANEL
Allow the receiver-separator to
GAUGE "SUMP' remain pressurized at 15-20 psig
for approximately two additional
minutes to allow coolant to
enter airend feed lines.
After two minutes, vent all air
TANK pressure from receiver­
separator tank and remove
auxiliary air line, pipe tee and
nipple. Re-install original 90
fitting and "SUMP" signal line in
side of tank. (See Figure C).
CLEAN.DRY Figure A. NEW PIPING 12. Remove 1" plug and 1/4" plug
AUXILIARY AIR
AT 15-25 PSIG in tank cover and re-install
THRUST BEARING scavenge lines and blowdown
FEED LINE FROM
OIL FILTER "NPT PLUGS valves as originally found.
Figure D. 12 PLACES1
Remove extension cord from
5SV and reconnect the red wires
Connect auxiliary air pressure as originally found. Replace
source in remaining hole (1/4"


cover, and tighten.
NPT tee). Do not apply air
pressure. Locate and remove the two 3/8"
NPT plugs in top of rear bearing
6. Locate coolant stop solenoid housing. (See Figure A).
valve 5SV near oil filter. Remove
cover from coil and disconnect Connect auxiliary pump suction
the two red wires attached to to clean container of coolant
coil terminals. and place pump discharge line
in waste container. Pump ap­
Connect extension cord to coil proximately 1/2 liter (1 quart) of
terminals on 5SV and place coil oil into waste container to flush
back in proper position on Figure B. OLD PIPING any dirt from pump or the
coolant stop valve assembly. connecting lines.
Install cover and tighten nut. 9. Slowly apply 15-25 psig of air
pressure to the sump and Connect pump discharge line to
7. After 5SV coil is back in its monitor pressure on "SUMP" either of the two 3/8" NPT
correct location with cover in indicator of panel mounted fittings at top of rear bearing
place, connect extension cord pressure gauge. housing and pump approxi­
to 11 O VAC power source to mately 2 liters (1/2 gallon) of
energize coil. This in turn. 10. Observe the loosened vent valve new clean coolant-lubricant into
opens the valve and will allow on coolant filter cover until housing. Install the other of the
coolant to flow through when coolant begins to flow from two 3/8" plugs to prevent
air pressure is applied to sump. vent. Close valve when coolant spillage during pumping
appears. process.

CAUTION 11. Maintain 15-25 psig of pressure


in the tank until coolant-lubri­
Do not apply power to coil unless cant flows from oil feedhose
coil is on valve or damage to coil previously disconnected from
will result! rear bearing housing.


CAUTION
Use care to prevent any electrical
shock hazard .

38
14. After pumping coolant into the
first side, change fittings and
repeat pumping with 2 liters (1/2
gallon) into other side.
Remove pumping connections
and install 3/8" NPT plugs back

in rear bearing housing and
tighten.
15. Observe drive motor coolant
fans and slowly rotate drive
motor BY HAND in direction of
proper rotation to remove any
excess coolant accumulated in
the rotor housing during
prelube procedure.
NOTE: If airend has excessive
oil in the rotor housing, it will
seem to "lock-up". However,
this is due to coolant trapped
between the rotors and is easily
removed from the airend by
maintaining a gentle but firm
pull on the motor. Turn motor
slowly in the normal direction of
rotation. When excess coolant
has been cleared, the rotors will


turn smooth and free.
16. Refill receiver-separator sump
to correct level and check all
piping and electrical connec-
tions for proper location and
tightness.
17. Follow normal start up proce-
dure. Shut unit down after two
minutes: Check for system
leaks.


39




Вам также может понравиться