Академический Документы
Профессиональный Документы
Культура Документы
n°155
MV public distribution
networks throughout
the world
Christian Puret
Producing electrical current in power corresponding voltage levels can be the transmission and
stations is not enough in itself, it must different from country to country.
also be brought to the end-user. However, in general the number of
interconnection network
In order to link production and voltage levels is limited to three; indeed The geographical distance between
consumption, which in turn can be in 1983 the IEC publication 38 production sites and consumer centres,
translated into financial benefit, a formulated recommendations for the irregularity of consumption and the
country’s electrical structure is voltage levels for 50 and 60 Hz impossibility of storing electrical energy
generally broken down into several networks. create the need for an electrical
levels that correspond to different types However, in order to gain better network that is capable of directing and
of electrical networks. (see fig. 1). understanding of this split, the following transmitting it across large distances.
It should be noted that there is no paragraphs present each grid with: These lines can stretch across
standard structure that exists ■ its object, thousands of kilometers , for
worldwide, and that the split into ■ its voltage level, example in the French network there
several networks with their ■ its structure. exists 20 000 km.
fig. 1: illustrated layout of an electrical network showing that electricity is produced, carried and distributed at various voltage levels.
reason of existance: The role of the MV distributor is not transmission and distribution; it
clear-cut: it often covers LV - Low manages around 80% of the electricity
to supply electricity Voltage - distribution and in some distributed in Italy.
The electrical energy distributors exist cases he is also in charge of ■ in France the situation is similar with
to supply electrical energy to transmission, for example: the E.D.F.
consumers taking into account several
■ in Japan, nine regional private
objectives such as:
companies are each responsible for the
■ continuity and quality of service,
production, transmission and
■ safety of people and goods, transformers
distribution for their area, = 5% MV switchgear
■ flexibility and ease of operation,
■ in Germany around a thousand = 5%
■ commercial competitiveness.
companies are involved in the
distribution of electricity. Around 1/3
his role have their own production facilities.
If electricity supply is satisfactory in ■ in Great Britain production is the
industrialized countries, the degree of responsibility of two companies (NP -
electrification still remains variable in National Power - and PG - Power Gen).
certain other countries. The NGC (National Grid Company) are
Varying objectives depending on the in charge of transmission, and the
degree of electrification... regional distribution is looked after by
For countries that are not 100% around twelve Regional Electricity
electrified, the priority objective remains Companies. This structure is a result of lines
a privatisation bill for British distributors + poles
the improvement of this degree of + total installation
electrification. To this end, investment voted in 1990.
= 90%
is mostly in construction of networks ■ in Italy a law founded the E.N.E.L. in
and installations (see fig. 3). 1962. This is a public service fig. 3: break-down of costs of MV overhead
However, the investment capabilities, responsible for the production, lines.
sometimes reduced, can lead to
solutions based on simplification of the
networks’ structure to the detriment of
the system performance. In the same Net consumption / country Net consumption / inhabitant
way, sometimes a lack of availability TWh KWh
and competence of the operators can 3000 30000
lead to over-simplified operation.
2355
Varying situations in industrialized
countries 11760
In countries that are 100% electrified, 1000 10000
there are considerable differences in 595
uses of electrical energy: 5320
5200 4900
■ national electrical energy 3190
300 294 3000
consumptions show great differences 2790
(see fig. 4). These differences are due 1860 183
to the size of country, to its economic 108
growth (GNP) and to the weight of the 100 1000
industrial sector (example 40% of the
French consumption).
■ per capita consumption can vary by a 27
30 300
factor of 10 between certain countries 19
(see fig. 4). These differences are
mostly due to the pricing policy of
distributors, but also to climatic
Portugal Denmark Spain Italy France Japan United states
conditions.
fig. 4: net consumption per country and per inhabitant.
powerful to help with the decision. the current changes in work practices in logging).
To measure the reliability of energy
supply to a residential LV customer,
distributors prefer to use the criteria of %
"degree of unavailability": this is the number of
LV customers 1986 1995
total annual time during which an
average customer has his supply 60
interrupted due to a fault on the
electrical network (HV, MV or LV).
50
Lastly, it is important to note that for a
LV customer, numerous incidents are
due to the MV network (60% according 40
to an EDF study) (see fig. 7).
Networks, equipment and operators, 30
are all evolving
It should not be forgotten that a
20
network’s performance depends above
all on its topology. However, throughout
the world, present networks are simply 10
the result of years of laying of
structures one on top of the other as
needs have increased. In addition a 0
0 1 2 3 4 5 >5 hours
network ages and is constantly in need
duration of interruption
of maintenance and renovation work to
retain its performance level and to fig. 7: degree of unavailability of electrical energy on one LV network (EDF - France).
avoid incidents, the sources of
"undistributed energy".
To answer these needs, the
manufacturers thus propose
"maintenance-free" or reduced
maintenance equipment; equipment for
which maintenance, modification and
addition type operations do not
adversely effect the continuity of
service.
In addition, energy distributors are not
willing to undertake preventive
maintenance, particularly device
monitoring by recording and analysing
incidents that occur on the network
(use of "disturbance recorders" and
time-stampers).
The topology of an electrical network is items that depend on the ■ the choice of an overhead or
defined here as all of the principles underground distribution system has a
involved in carrying electrical energy in
chosen topology big influence on the installation costs
public distribution (layout, protection, The choice of a topology fixes the main and the quality of service (e.g.: costs of
operation). design elements of a distribution a trench / vulnerability to momentary
system, such as: faults...). For MV, in industrialized
In practice for a distributor, defining a
■ the rated power and the maximum countries, this choice can be broken
topology means fixing a certain number
value of earthing currents, e.g. for MV, down into three cases:
of physical factors, whilst taking
the EDF limits the value of these ■ highly populated urban area with an
account of criteria dependant on
currents to 300 A at 20 kV overhead underground distribution system,
objectives aimed for and technical
and to 1000 A underground; ■ highly populated suburban area with
constraints. Since these factors are
■ the rated voltages, e.g.:for MV Japan underground or part-underground part-
closely interrelated, choice of a certain
supplies at 6.6 kV, Great Britain at 11 overhead distribution system;
topology is always the result of
and 33 kV and France mostly at 20 kV; ■ scarcely populated rural area with
technico-economic compromises.
■ voltage surge ratings and
Here, the graphical representation of a overhead distribution.
coordination of isolation as well as
topology will be by simplified single-line protection systems against atmospheric However it should be noted that
layouts. voltages surges; historically, due to high initial costs,
■ the earthing connection layouts, as numerous urban areas have overhead
well as the number of distributed wires, distribution systems, as in Japan and
criteria in choosing a ■ the maximum feeder lengths (tens of the United States.
topology kilometers at MV);
The choice of a topology depends on ■ the type of distribution: overhead or
meeting objectives: underground (see fig. 8);
various MV network layouts
■ to ensure the safety of people and ■ the type of operation: manual, The choice of layout is important to a
goods, automatic, remote controlled. country: particularly for MV networks
■ to attain a pre-defined level of quality since they are of great length. Thus, for
It is important to note that:
of service, example, the total MV structure in
■ the choice of short circuit current has
■ to produce the desired profitability. France is around 570 000 km long, that
repercussions on the rating of the
of Italy being 300 000 km long and that
However, it must also meet certain equipment used in the network;
of Belgium being 55 000 km long.
requirements: ■ the choice of voltage rating(s) is
■ to correspond to the housing density always a compromise between the Several topologies exist:
and/or to consumption, known as the installation and operating costs of the ■ lattice type, closed loop topology,
load density, it plays an ever increasing network; ■ simplified lattice type, open loop
role. Calculated in units of MVA/km2, ■ the choice of insulation rating of topology,
this density enables the expression of equipment is generally in line with ■ open loop topology,
various geographical zones in terms of international and/ or national standards; ■ radial topology.
load concentration. Certain distributors
distinguish two types of consumption
zones by defining:
0 25 50 75 100%
■ low load density zone:
Germany
< 1 MVA/km2,
■ high load density zone: Canada
> 5 MVA/km2.
United States
■ to account for the geographical
spread, terrain and construction Denmark
problems,
Great Britain
■ to satisfy environmental constraints,
particularly climatic (maximum and Netherlands
minimum temperatures, frequency of
storms, snow, wind, etc.) and respect underground overhead
for surroundings.
fig. 8: proportion of lengths of overhead (lines) and underground (cables) on MV networks, for
several countries.
It is of arborescent type (cf. fig. 9). open loop ■ simplicity ■ operation with more
HV/ MV
substations
HV/ MV transformers
MV/ LV
transformer
supply path for
substation n°1
fig. 9: the two basic layouts of a MV distribution network, radial (or antenna) and open loop (or artery break).
This chapter is a reminder of the main The MV/LV substation in a public performs the transfer from MV
substations installed on MV networks, distribution system (≈ 10 kV) to LV (≈ 100 V).
and the main technologies used in MV Positioned between the MV network The typical layout of this substation is
equipment. It is concluded by two and the LV network, this installation of course a lot more simple than the
layouts showing their applications in
real terms.
HV/MV
substation HV incomers
substations on MV
networks
A substation or installation is a physical
entity defined by its position and its HV/MV transformers
function within electrical networks.
The role of a substation is essentially to
perform the transition between two MV bus section
voltage levels and/ or to supply the end circuit breaker
user.
The HV/MV substation in a public
distribution system
This installation is present in any of a
country’s electrical structures; it is overhead and/or underground MV feeders
positioned between the
subtransmission network and the MV MV/MV
network. substation MV incomers
Its function is to ensure transition from
HV (≈ 100 kV) to MV (≈ 10 kV).
Its typical layout (see fig. 15) involves
two HV inputs, two transformers HV/
MV, and 10 to 20 MV feeders. These
feeders supply overhead lines and/ or
underground cables. overhead and/or underground MV feeders
fig. 16: various functions of MV devices that are used in public distribution(contactors are essentially used in industry).
switchgear bloc CB or S S CB CB or S
circuit
breaker compartmented CB or S S CB CB or S
incomer
feeder metal clad CB CB CB
busbars GIS CB CB
RMU S S
fig. 17: various compartments of a MV
cubicle, surrounded with a metal enclosure,
S = with switch CB = with circuit breaker
and their main elements.
fig. 18: main MV switchgear applications.
following principles:
■ maximum MV distribution, by MV/LV
reducing the length of LV feeders in
order to reduce losses; MV/LV
■ MV neutral distribution with regular MV/LV
earthing (e.g. every 300 meters); transformer
■ three-phase MV lines on main
RCOS
structure, with three-phase, two-phase
or one-phase shunting for the MV/LV
connections.
fig. 20: overhead MV distribution layout (EDF - France).
HV/MV
substation
HV/MV transformer
circuit breaker
(3 independant single phases
or 1 three-phase)
MV/LV transformer
(see inset below)
MV/LV Nb
sectionaliser
MV/LV
North-American MV/LV
transformer substation
Nb MV/LV MV
grid
in
ma
Nb MV/LV
LV LV
fig. 23: example of remote control of a MV network, with the various links required for
information exchange.
=
off, this being done by remote
consultation of fault position indicators
(see glossary) that are installed at
different points on the MV network,
followed by remote control of MV
switches. This results in a considerable
reduction in the amount of undistributed
remote supervision remote controlling energy, but also in network optimization
(information transmission) (command transmission) with possibilities of optimum
management of the load distribution.
The network loading can also be
+
analysed.
In particular, by logging the load curve
verification and optimization of energy
consumptions can be performed.
Finally, to increase efficiency, the
operator can have rapid access to the
■ remote data transmission ■ remote control of most relevant information via an
■ telemetering network's MV devices automatic pre-processing method such
■ remote adjustment
as a sorting operation, graphical
of settings.
representation operation, calculation
operation,....
fig. 24: several functions, here grouped according to the direction of transmissions between
operator and network, are required for remote control.
trol of
e-con
remot al network
ic
electr
ation
install
local
l
contro
ntrol
nd co
tion a
protec cubicle
of MV
sors
s and sen
evice
MV d
The diversity of equipment mentioned ■ with respect to Ring Main Unit ■ with respect to electromagnetic
in this "Cahier Technique" makes it IEC 129,265,298, and 420, compatibility:
impossible to give all of their respective UTE C 64-130, C 64-131, ■ in terms of susceptibility to
standards. and C 64-400, disturbances,
As an example here are a few VDE 0670, IEC 801 - chapters 1 to 4,
standards: BS 5227, NF C 46-020 to 023,
■ with respect to protection devices ■ in terms of disturbance emission
■ with respect to MV switchgear
IEC 68, EN55 022,
IEC 56 and 694, NF C 91-022.
IEC 470 for contactors IEC 225,
UTE C 64-100 and C 64-101, IEC 655,
VDE 0670, NF C 20-455,
BS 5311, NF C 63-850.
ANSI C37-06 for circuit breakers.
,
,
,
, control interfaces :
internal internal external
,
2
,
,
TCL11MS
,
substation
computer
Isis 2000 :
mimic
diagram
,
status logger
Vigi PA
1 protection and
,
control-command unit
,
,
,
M2S :
remote-controlled
overhead switch