NOTES:
6
7 1 Required only for optional Var/PF control. Var/PF is active with
8
10
52b open. Var/PF is inactive with 52b closed.
10
2 Parallel control and droop active with S2 open, inactive with S2
closed.
3 S1 (SPDT, spring-return to center-off position) adjusts DECS-
PMG
10 52 100 setpoint.
4 Normally-open output contact closes for customer alarm or trip.
DECS-100 Installation
+
A
10 CTB
GEN B 5 Analog input voltage between +/- 3 Vdc provides adjustment of
11 voltage sepoint (optional feature).
C
D2881-09 6 External fuses should be Bussman type KTK-10 or equivalent.
05-10-02
Generator Utility
Side Side 7 Sensing potential transformer is required if line voltage exceeds
660 Vac.
8 3-phase PMG is shown. For 1-phase PMG, omit B-phase
connection.
9 Optional voltage matching control input. Voltage matching is
active with S3 closed, inactive with S3 open.
10 Item not supplied by Basler Electric.
Figure 4-6. Typical Connections for PMG Application with ABC Rotation and Three-Phase Sensing
CTB should be reversed.
9287500991 Rev H