Вы находитесь на странице: 1из 1

Power Consumtion for Control Equipment TPSS Ciracas 1

No. Equipment Voltage(VDC) (KVA)


1 20 kV switchgear
- Contactor Relay 110.00 0.035
- Protection Relay 110.00 0.09
- Energy Meter 110.00 0.03
- Motor Charging Safe V & CB 110.00 0.17
- Motor Charging Safe F 110.00 0.14
- VCB Closing Coil Safe CB, F & V 110.00 0.2
- VCB Tripping Coil Safe CB, F & V 110.00 0.2
2 Auxiliary Transformer
- Digital Thermometer c/w contact alarm & trip 110.00 0.012
3 LVMDP 380 V
- Opening Release 110.00 0.01
- Closing REL 110.00 0.01
- Motor charging 110.00 0.5
- Pilot Lamp (Green & Red) 110.00 0.024
- Pilot Lamp (Yellow) 110.00 0.02
- Control Relay 110VDC 110.00 0.0117
- Timer Delay 110.00 0.00188
- Relay Interposing 110.00 0.00102
- IFE 110.00 0.00864
4 Traction transformer
-Total Control Relay 110VDC 110.00 0.03
5 750V DC Rectifier
- Power Supply 110.00 0.1536
- Indicating Current 110.00 0.008
- Switch Clossing 110.00 0.104
- Switch Opening 110.00 0.104
6 750V DC Switchgear
DC Switchgear (Rectifier HSCB)
- Power Supply 110.00 0.0768
- HSCB during closing 110.00 1.04
- HSCB during open 110.00 0.02
- HSCB closed 110.00 0.00368
DC Switchgear (Feeder HSCB)
- Power Supply 110.00 0.384
- HSCB during closing 110.00 1.04
- HSCB during open 110.00 0.02
- HSCB closed 110.00 0.00736
- Switch Clossing 110.00 0.104
- Switch Opening 110.00 0.104
7 750V TBS (Track Bypass Switch)
- Power Supply 110.00 0.1536
- Indicating Current 110.00 0.016
- LBS during closing 110.00 0.08
- LBS during opening 110.00 0.08
Total Power Consumption 4.99328