0-1
January 2018
Sheet 22001

Panelboards Contents
Panelboards
Overview
22

23
Market and Segment Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-2
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-2 24
Available Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-2
Panelboard Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-2
Panelboard Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-5
25
General Construction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-5
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-6 26
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-9
Series Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.0-12 27
Pow-R-Line 1a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.1-1
Pow-R-Line 2a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.2-1 28
Pow-R-Line 3a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-1
Pow-R-Line 3E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-5
Pow-R-Line 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.4-1
29
Pow-R-Line Column Type
Pow-R-Line 1a-LX Column Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.5-1 30
Pow-R-Line 2a-LX Column Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.5-4
Retrofit Panelboards 31
Pow-R-Line 1R Retrofit Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-1
Pow-R-Line 2R Retrofit Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-3
32
Pow-R-Line 1aF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-5
Pow-R-Line 2aF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-7
Pow-R-Line 3FQS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-9
33
Elevator Control Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-11
Panelboard Modifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.6-12 34
Specifications
See Eatons Product Specification Guide, available on CD or on the Web. 35
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010
Section 16470 Section 26 24 16
36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-2 Panelboards
Overview January 2018
Sheet 22 002
General DescriptionPow-R-Line

22 Overview Available Ratings Special Use Pow-R-Line


Choices to quickly change feeder
The panelboards are rated at 240 Vac, Panelboards
480 Vac and 600 Vac. Fault current is Pow-R-Line 1a-LX and Pow-R-Line
breakers in electrical distribution
23 equipment have evolved over the years.
available up to 200 kAIC at 240 Vac,
100 kAIC at 480 Vac and 65 kAIC at
2a-LX column panelboards are
While using drawout switchgear with designed to fit within the structural
600 Vac. The short-circuit current I-beam of a facility and offer branch
power air circuit breakers remains a
24 highly reliable solution, requests for
rating of the panelboard is determined circuits up to 100 A
by the low short-circuit current rating
drawout molded-case circuit breakers Pow-R-Line 1aF and Pow-R-Line
of the lowest rated overcurrent device
(MCCBs) have increased. And, 2aF fusible lighting panelboards
25 customers need a wall-mounted
in the panelboard.
were developed for ultra high fault
panelboard solution with front Boxes and trims are UL 50 Listed and currents and for use in selective
accessibility and front-connected labeled. Both the box and the trim are coordination applications and
26 equipment to meet space require- painted ANSI-61 light gray. Deadfront test circuits
ments and application needs. covers are also painted ANSI-61 light Pow-R-Line 1R and Pow-R-Line 2R
gray to match box and trim. Retrofit Panelboards are the only
27 Eatons drawout MCCB Pow-R-Line
panelboards in the market listed for
4D (PRL4D) panelboard provides Drawout feeder MCCBs are available in
this solution. use in retrofit applications in other
two- and three-pole offerings from 20 A
28 manufacturers existing back boxes
to 600 A. Main breakers above 600 A
This is the first design to offer two- and Elevator control panelboards
are fixed-mounted using a traditional
three-pole MCCBs in a mechanical integrate electrical protection
bolt-on design. Main breakers 600 A
29 drawout design. Breaker ratings from and controls for elevators and
and below are available with either the
20 A to 600 A use unique drawout meet stringent code requirements
traditional fixed-mounted, bolt-on
cassettes. Breakers are inserted and in a single, cost-effective package
design or in a drawout cassette. For
30 removed via a mechanical removal
drawout mains or feeders above 600 A,
system similar to other drawout designs Pow-R-Line 4B and 4F
please use Eatons switchboard offering.
associated with switchgear; however,
Power Panels
31 these breakers are horizontally
mounted in a traditional panelboard
Panelboard Options Pow-R-Line 4B panelboard uses
group-mounted manner. Copper and silver-plated copper circuit breakers
32 Copper lugs Pow-R-Line 4F panelboard uses
Market and Segment Applications Density-rated bus fusible switches
While the drawout MCCB panelboard Ground bars A single chassis accommodates
33 design may be substituted for nearly Customer-owned meters both circuit breakers and
any traditional application with fusible switches
Service equipment construction
feeder MCCBs, it has been specifically Main and neutral are located at the
34 designed to meet the needs of several Surge protective devices
same ends to provide additional
industries, including: Seismically qualified panelboards space for branch devices
Three-piece trim facilitates
35 Electrical distribution systems where Pow-R-Line 1a, 2a and 3a, and 3E installation
a changeout of circuit breakers is
needed to upgrade equipment to Robust design using Eaton Will accommodate circuit breakers
36 a new process circuit breakers to provide higher ratings in a
Data centers Increased ratings (with Series standard chassis and increased
Rated main circuit breakers) series ratings
Industrial facilities to minimize
37 downtime
provide higher short-circuit ratings UL tested and approved. Meets
Pow-R-Line 3a can accommodate NEC and NEMA standards
Institutions
branch breakers dual-mounted
38 Laboratories through 150 A and single-mounted Pow-R-Line 4D Drawout Panelboard
Health care facilities through 225 A
Quick change-out or addition of
Critical load applications Pow-R-Line 3E panelboards breakers without changing hardware
39 accommodate branch-mounted
Front connected, front accessible
Standards and Certifications breakers up to 125 A
Drawout circuit breakers
UL 67 Listed for wall-mounted Lock and Door opening mechanism
40 applications from 600 A to 1200 A includes a positive slide catch and
20600 A ratings
right- or left-hand installation Fixed-mounted molded-case circuit
National Electrical Code
breakers 151200 A
41 Surface or flush trims
Mains 4001200 A
UL tested and listed. Meets NEC
and NEMA standards Main lugs only
42 Main molded-case circuit breaker
Single chassis supports both drawout
and fixed-mounted breakers
43 Mains and neutrals mounted on
same end of chassis/box

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-3
January 2018 Overview
Sheet 22 003
General DescriptionPow-R-Line

Product Selection 22
Table 22.0-1. Product Types

23

24

25

26

27
Type PRL1a Fusible Lighting Type PRL1a-LX Type PRL2a Fusible Lighting Type PRL2a-LX
Panelboard PRL1aF Column Type Panelboard PRL2aF Column Type 28
Bolt-on or plug-on 240 Vac maximum Bolt-on circuit breakers Bolt-on or plug-on 240 and 480Y/277 Vac Bolt-on or plug-on
circuit breakers 240 Vac maximum circuit breakers 240 maximum circuit breakers 240
240 Vac maximum or 480Y/277 Vac or 480Y/277 Vac 29
125/250 Vdc maximum 125/250 Vdc maximum
Main lugs only Main lugs only Main lugs only Main lugs only Main lugs only Main lugs only
600 A maximum 400 A maximum 225 A maximum 600 A maximum 400 A maximum 225 A maximum
30
Main circuit breaker Main circuit breaker Main circuit breaker Main circuit breaker
600 A maximum 225 A maximum 600 A maximum 225 A maximum
Branch circuit breakers Branch overcurrent Branch circuit Branch circuit breakers Branch overcurrent Branch circuit breakers
31
100 A maximum protective devices breakers 100 A maximum protective devices 100 A maximum
Single, two- and 30 A maximum, 100 A maximum Single-, two- and 30 A maximum, Single-, two-, and
three-pole Single-, two- and Single-, two- and three-pole Single-, two- and three-pole 32
three-pole utilizing three-pole three-pole utilizing
Class CC fuses Class CC fuses
33

34

35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-4 Panelboards
Overview January 2018
Sheet 22 004
General DescriptionPow-R-Line

Table 22.0-1. Product Types (Continued)


22

23

24

25

26

27 Retrofit Panelboard Type PRL3a Type PRL3E Type PRL4 Type PRL5P
PRL-1R and PRL-2R

Bolt-on or plug-on circuit Bolt-on circuit breakers Bolt-on circuit breakers Circuit breakers or fusible switches; Plug-on circuit breakers
28 breakers 240 or 480Y/277 Vac 240, 480 or 600 Vac; 240 Vac maximum 240, 480 or 600 Vac; 240, 480 or 600 Vac;
250 Vdc maximum 600 Vdc maximum 250 Vdc maximum
Main lugs only Main lugs only Main lugs only Main lugs only Main lugs only
29 225 A maximum 800 A maximum 600 A maximum 1200 A maximum 1200 A maximum
Main circuit breaker
1200 A maximum
30 Main circuit breaker Main circuit breaker Main circuit breaker Main fusible switch Main circuit breaker
225 A maximum 600 A maximum 600 A maximum 1200 A maximum 1200 A maximum
Branch circuit breakers
31 1200 A maximum,
Single-, two- and three-pole
Branch circuit breakers Branch circuit breakers Branch circuit breakers Branch fusible switches Branch circuit breakers
32 100 A maximum 225 A maximum 125 A maximum 1200 A maximum, 1200 A maximum,
Single-, two- and three-pole Single-, two- and Single-, two- and three-pole Single-, two- and three-pole Single-, two- and three-
three-pole pole
33 Table 22.0-1. Product Types (Continued)

34

35

36

37

38
Pow-R-Command Metering Service Section Elevator Control Panelboard
39 Bolt-on or plug-on circuit breakers Bolt-on circuit breakers Bolt-on fusible switches
240 or 480Y/277 Vac 240, 480 or 600 Vac 600 Vac maximum
Main lugs only Service entrance panels combining a main Controls for up to four elevators
40 400 A maximum disconnect with a power company metering in a single panelboard
Main circuit breaker compartment 4001200 A Main lugs only
400 A maximum 800 A maximum
41 Branch circuit breakers Branch overcurrent devices
225 A maximum 15200 A fusible switches with
Single-, two- and three-pole Class J fuse clips maximum
42 Single- and two-pole remote operated circuit breakers
Integral load switching and dimming controls Designed to meet specific sections various codes
impacting elevators
43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-5
January 2018 Overview
Sheet 22 005
General DescriptionPow-R-Line

Table 22.0-2. Panelboard Selection Guide


Panelboard Page Device Maximum Maximum Main Branch Circuits Short-Circuit Current Ratings
22
Type Reference Type Voltage Rating Rating, Amperes Ampere Range rms Symmetrical Amperes, AC
AC DC Main Lugs Only Main Device Fully Rated Series Rated
(kA) (kA) 23
Pow-R-Line 1a 1 22.1-1 Breaker 240 600 600 15100 1022 22200
Pow-R-Line 2a 1 22.2-1 Breaker 240
480Y/277
250 600
400 2
600
400 2
15100
15100
65
14
65200
22150
24
Pow-R-Line 3a 1 22.3-1 Breaker 240 250 800 600 15225 10200 22200
480 800 600 15225 14100 22150
600 800 600 15225 1435 25
Pow-R-Line 3E 1 22.3-5 Breaker 480 250 600 600 15125 3565 35100
Pow-R-Line 4B 1 22.4-1 Breaker 240 600 1200 1200 151200 10200 22200
480 1200 1200 151200 14200 22150 26
600 1200 1200 151200 14200
Pow-R-Line 4F 1 22.4-8 Fusible switch 240 250 1200 1200 301200 100200

Pow-R-Line 4D 22.4-11 Breaker


600
240
1200
1200
1200
1200
301200 100200
20600 Drawout 100


27
480 1200 1200 151200 Fixed 65
Pow-R-Line 1aF 22.6-5 Fusible switch 240 400 400 1530 200 200
Pow-R-Line 2aF 22.6-7 Fusible switch 480Y/277 400 400 1530 200 200 28
Pow-R-Line 1a-LX 22.5-1 Breaker 240 225 225 15-30 1022 18200
Pow-R-Line 2a-LX 22.5-4 Breaker 480Y/277 125/250 225 225 1530 14 25150
Pow-R-Line 1R 22.6-1 Breaker 240 225 225 15100 1022 22100 29
Pow-R-Line 2R 22.6-3 Breaker 480Y/277 225 225 15100 14 22150
Elevator control 22.6-11 Fusible 480 800 800 15200 10200 14100
panelboard 1 30
1 Available with surge protective device (SPD) and metering.
2 Amperage rating for dc voltage.
31
General Construction Features All enclosures are furnished in The trims for lighting and appliance
accordance with UL standards and branch circuit panelboards and small
Eatons assembled panelboards
are designed for sequence phase
include wiring gutters with proper wire power distribution panelboards 32
bending space. Special cabinets can include a door with rounded corners
connection of branch circuit devices. be provided at an additional charge. and concealed hinges. A flush-type
This allows complete flexibility of
circuit arrangement (single-, two- or The box dimensions shown are inside
latch and lock assembly is included. All 33
locks are keyed alike. These trims are
three-poles) to allow balance of the dimensions. For outside dimensions, available in both surface and flush
electrical load on each phase. add 0.25-inch (6.4 mm). mounted designs. 34
Sturdy, rigid chassis assembly ensures Standard panelboard boxes are supplied Fronts for power distribution panel-
accurate alignment of interior with without knockouts (blank endwalls). boards use a unique breaker front
panel front; prevents flexing and cover design in which each device has
35
minimizes possibility of loosening EZ Trim
a dedicated bolt-on steel cover. The
or damage to current carrying parts The EZ box and EZ trim are provided
individual covers form a single dead- 36
during and after installation. standard for Pow-R-Line 1a and
front for the panelboard that is used
Pow-R-Line 2a lighting panelboards, as
Four point in-and-out adjustment in conjunction with two wiring gutter
well as Pow-R-Line 3a and Pow-R-Line
of panel interior is provided to meet covers to complete the trim. A door 37
3E mid-range panelboards.
critical depth dimensions on flush is not finished as part of the standard
installations. This compensates offering on these panelboards but can
for possible misalignment of box be provided, for an additional charge, 38
at installation. using a deeper than standard box.

Main lugs are mechanical solderless Combination AFCI Circuit Breakers 39


type and approved for copper and
aluminum conductors. Eatons 125 Vac AFCI single- and two-
pole, 15 A and 20 A bolt-on breakers in
Enclosures panelboards meet Article 210.12 of the 40
Boxes are code-gauge galvanized steel NEC. See the NEC code for definitions
except for column type panelboards, and details.
which include a painted box finished in
41
ANSI-61 light gray to match the trim.
Standard panelboard cabinets are 42
designed for indoor use. Alternate
types are available for outdoor and
special purpose applications. 43
EZ Trim Provides Standard Door-in-Door
Construction With No Exposed Hardware
or Sharp Ridges. No Tools are Required
for Installation.

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-6 Panelboards
Overview January 2018
Sheet 22 006
General DescriptionPow-R-Line

Application Considerations Selective Coordination Interconnecting Multi-Section


22 Please refer to Molded-Case Circuit Panelboards
Standards Breakers, Tab 27, for detailed When a panelboard, for connection to
All Eatons panelboards are designed to information on overcurrent protective one feeder, must be furnished in more
23 meet the following applicable industry device combinations for use on than one section (box), each section
standards, except where noted: selectively coordinated systems. must be furnished with main bus and
terminals of the same rating, unless a
24 1. Underwriters Laboratories Service Entrance Equipment main overcurrent device is provided in
a. Panelboards: UL 67 NEC Articles 230.F and G, and UL, each section.
require that:
25 b. Cabinets, boxes and trims: Sub-feed or through-feed provisions
UL 50 a. Panels used as service entrance must also be added to provide connec-
equipment must be located tion capability to the second section.
Note: Only panelboards containing UL
26 listed devices can be UL labeled.
near the point where the supply
Note: Sub-feed or through-feed lugs
conductors enter the building.
2. National Electrical Code cannot be used on any panelboard that
b. A panelboard having main lugs is not protected by a single main over-
27 3. NEMA Standards: PB 1 only shall have a maximum current device either in the panelboard or
of six service disconnects to immediately upstream, i.e., service entrance
4. Federal Specification W-P-115c de-energize the entire panel- panelboards with main lugs only using the
28 Circuit breakerType I Class 1 board from the supply six disconnect rule.
Fusible switchType II Class 1 conductors. Where more Sub-Feed Lugs (Figure 22.0-1)
Panelboard Selection Factors than six disconnects are
29 required, a main service Sub-feed lugs are one means of
In selecting a panelboard, the follow- interconnecting multi-section panels.
disconnect must be provided.
ing factors must be considered: The sub-feed (second set of) lugs are
30 a. Service (voltage and frequency).
c. Must include connector mounted directly beside the main lugs.
for bonding and grounding These are required in each section
b. Interrupting capacity (fully or neutral conductor. except the last panel in the lineup.
31 series rated). d. A service-entrance-type UL The feeder cables are brought into
c. Ampere rating of main. label must be factory installed. the wiring gutter of the first section
e. Ground fault protection of and connected to the main lugs.
d. Ampere ratings of branches.
32 equipment shall be provided Another set of the same size cables
e. Installation environment. are connected to the sub-feed lugs
for solidly grounded wye
f. Codes and standards electrical services of more (Section 1) and are carried over to the
33 mandates. than 150 V to ground, but not main lugs of the adjacent panel. Cross
exceeding 600 V phase-to- connection cables are not furnished by
Panelboard Short-Circuit Rating Eaton. Sub-feed lugs are only available
phase for each service
34 The short-circuit rating of Eatons disconnecting means rated on main lug only panels.
assembled panelboards are 1000 A or more. Note: Sub-feed lugs may not be used on
test verified by, and listed with,
35 Underwriters Laboratories. Generally, Service entrance panels must be
main lug only (six disconnect rule) service
entrance panels.
these ratings are that of the lowest identified as such on the order entry
interrupting rated device in the panel. to the manufacturing location.
36 Box Box
Certain exceptions to this rule exist Column Type Panelboards
where branch devices have been The same general code restrictions
37 UL tested in combination with apply as for standard width panels
specific main devices having a except where trough extensions
higher interrupting rating. Where are used.
38 these defined main breaker and branch Neutral Neutral
breaker combinations are Multi-Section Panelboards
Panel

Panel

used, the series short-circuit rating When more than 42 overcurrent


39 of the assembled panelboard will be protective devices are required, two
the same as the series tested rating or more separate enclosures may be
of the approved rated main breaker. required. Separate fronts for each
40 Available main and branch breaker box are standard.
combinations are tabulated on
Page 22.0-12 through Page 22.0-22.
41 All combinations shown are UL
tested and listed.

42 These series ratings apply to panels Conduit


having main devices, or main lug
only panelboards fed remotely by the Section 1 Section 2

43 device listed in the series ratings chart


as the main, for which UL listed tests Figure 22.0-1. Sub-Feed Lugs
were conducted.

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-7
January 2018 Overview
Sheet 22 007
General DescriptionPow-R-Line

Application Considerations Multiple Section Panelboard Ground Fault Protection


(Continued) Flush Mounted Ground fault protection (GFP) may 22
Shown below is the standard method be added to most panelboards using
Through-Feed Lugs (Figure 22.0-2) for flush mounting multiple section Eatons integral molded-case circuit
lighting and distribution panelboards breaker GFP and included feeder 23
Through-feed lugs are another
method to interconnect multi-section using standard flush trims. devices on power panelboards and
mains on all panelboards.
panelboards. The incoming feeder 24
cables are connected to the main Conduit Nipple for Cross Wiring by Contractor Arcflash Reduction Maintenance System
lugs or main breaker at the bottom of
Eatons Arcflash Reduction
panel (Section 1). Another set of lugs
Maintenance System is available 25
(through-feed) are located at the
on many molded-case circuit
opposite end of the main bus. The .75 .75
(19.1) .75 .75 breakers from 70 A to air power
interconnecting cables are connected
Wall
(19.1)
1.5 (19.1) (19.1)
Wall circuit breakers at 5000 A. Recognized 26
to the through-feed lugs in Section 1 Trim (38.1) Trim
Top Section by the 2011 National Electrical Code
and are carried over to the main Contractor to Mount Boxes
View and the National Electrical Safety
lugs in Section 2. The connection 1-1/2-inch (38.1 mm) Apart to
Allow for 3/4-inch (19.1 mm) Code (NFPA 70E), the Arcflash 27
arrangement could be reversed, i.e., .75 Extension on Both Flush Trims
(19.1) Trim Reduction Maintenance System
main lugs at top; through-feed lugs Outside Edge of Box
allows breakers to trip quickly thus
at bottom end of panel. Cross cables
significantly reducing the available 28
are not furnished by Eaton.
arc flash potential.
Note: Through-feed lugs may not be used
on main lug only (six disconnect rule) Ambient Temperatures 29
service entrance panels. The primary function of an overcurrent
device is to protect the conductor and
its insulation against overheating. In 30
Box Box
.75
selecting the size of the devices and
(19.1) conductors, consideration should be
Cross Cables
given to the ambient temperature 31
Main
Lugs .75 .75 .75 surrounding the conductors within and
(19.1) (19.1) .75 (19.1)
(19.1) external to the panelboard. Cumulative
Neutral Two Section Flush Trim Extends 3/4-inch heating within the panelboard may 32
Panelboard
(Flush Mounting)
(19.1 mm) Beyond Outside
of Box on All Four Sides
cause premature operation of the over-
current protective devices.
33
Panel

Thru- Figure 22.0-3. Multiple Section Panelboard UL test procedures are based, in part,
Panel

Feed Flush MountedDimensions in Inches (mm)


Lugs on 80% loading of panelboard branch
Branch Circuit Loading for Lighting Panels circuit devices. Article 408 of the NEC 34
limits the loading of overcurrent devices
The size of mains and branches should
in panelboards to 80% of rating where
Neutral be selected based on the following: 35
in normal operation the load will
Main Lugs a. Lighting circuits: NEC Article continue for three hours or more.
210, 215, 220 and 240.
Conduit b. Distribution circuits, actual or
Further derating may be required, 36
depending on such factors as ambient
Incoming Feeder Cables continuous loads: NEC Article temperature, duty cycle, frequency
384.16. or altitude. 37
Section 1 Section 2
c. Motor circuits: NEC Article 430.
Exception: There is one exception
Figure 22.0-2. Through-Feed Lugs d. Diversity factor. to this rule in both UL and NEC. It
e. Provision for future loading. applies to assemblies and overcurrent 38
devices that have been approved
Overcurrent Protection for continuous duty at 100% of its
National Electrical Code Article 408 rating. This exception is covered in
39
states a panelboard shall be protected NEC 210.20 (a). Also see Tab 27 of
by an overcurrent protective device this application guide for additional
having a rating not greater than that information.
40
of the panelboard. The overcurrent
protective device shall be located
within or at any point on the supply
41
side of the panelboard.
Exceptions to Article 408 selectively 42
apply. Refer to the National Electrical
Code Article 408 for specifics.
43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-8 Panelboards
Overview January 2018
Sheet 22 008
General DescriptionPow-R-Line

Application Considerations Harmonic Currents Eaton can provide protective and


22 (Continued) Standard panelboard neutrals are diagnostic systems integral to panel-
rated for 100% of the panelboard boards. The SPD is integrated into
Special Conditions current. However, because harmonic the panelboards using a zero lead
23 currents can cause overheated length direct busbar connection.
Standard panelboards, assembled Integral disconnect is used on all
with standard components, are neutrals, an option is provided for
neutrals to be rated at 200% (1200 A Pow-R-Line 4 panels.
24 adequate for most applications.
maximum neutral for 600 A main bus)
However, special consideration
should be given to those required of the panelboard phase current.
Panelboards with the 200% rated
25 for application under special
neutral are UL listed as suitable for
conditions such as:
use with nonlinear loads.
a. Excessive vibration or shock.
26 Prior to specifying the 200% rated
b. Frequencies above 60 cycles. neutral, Eaton recommends a harmonic
c. Altitudes above 6600 ft (2012 m). survey be conducted of the distribution
27 d. Damp environment (possible system, be it new or existing.
fungus growth). Eaton SPDs May be Integrated
Surge Protective Devices (SPD) into Most Panelboards
28 e. Compliance with federal, state The quality of power feeding sensitive
The SPD protects sensitive electronic
and municipal electrical codes electronic loads is critical to the reliable
and standards. operation of any facility. In modern equipment from the damaging effects
29 offices, hospitals and manufacturing of high and low energy transients.
Seismic Qualification
facilities, the most frequent causes For complete product description and
of microprocessor-based equipment available ratings, refer to Tab 34.
30 downtime and damage are voltage
transients and electrical noise. Compact Panelboard Meter
Most Eaton panelboards can integrate
31 Electrical loads and microprocessor-
a compact meter for reading the
based equipment are highly susceptible
Refer to Tab 1 for information on panelboard power and energy usage.
to both high and low energy transients.
seismic qualification for this and Eatons IQ 35M has ANSI 12.20 0.5%
32 other Eaton products.
High energy transients include lightning
accuracy, a bright backlit LCD display,
induced surges and power company
real energy pulse output, phase
switching. These high energy transients
loss alarm and optional RS-485
33 can destroy components instantly.
communication capability.
More frequently the electrical system
experiences low energy transients and
34 high frequency noise.
The effects of continual low energy
35 transients and high frequency
noise can cause erratic equipment
performance or sudden failure of
36 electronic circuit board components.

37

38

39

40
Closeup of IQM 35 With Deadfront

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-9
January 2018 Overview
Sheet 22 009
Technical Data and SpecificationsPow-R-Line

Technical Data and Specifications


Table 22.0-3. Electrical Characteristics of Circuit Breakers
22
Circuit Breaker Ratings UL Listed Interrupting Ratings (kA rms Symmetrical)
Type Ampere Number Volts AC Rating, Volts DC Rating, Volts 1 23
Rating of Poles AC 120/240 240 277 480 600 125 250
BAB, HQP 1570
15100
1
2
120
120/240
10
10












24
BAB-H, HQP-H 15100 2, 3 240 10
BABRP, BABRSP 1530 1 120 10
1530 2 120/240 10 25
QBGF, QPGF, QPGFEP 1550 1 120 10
QBGFEP 1550 2 120/240 10
QBAF, QBAG 1520 1 120 10 26
1520 2 120/240 10
QBHW, QPHW 1570 1 120 22
15100 2 120/240 22
QBHW-H, QPHW-H 15100 2, 3 240 22
27
QBHGF, QPHGF, QPHGFEP 1530 1 120 22
QBHGFEP 1530 2 120/240 22
QBHAF, QBHAG 1520 1 120 22 28
1520 2 120/240 22
GHB 15100 2 1 277 65 14 14

GHQ
15100
1520
2, 3
1
480Y/277
277

65
65


14
14 3





14

29
HGHB 1530 1 277 65 25
GHBGFEP
GHQRSP
1560
15100
1
1
277
277

65


14
14








30
15100 2 480Y/277 65 14 14 3
GHBS 1530 1 277 65 14
1530 2 480Y/277 65 14 14 3 31
EGB 15125 1 277 35 35 18 10
15125 2, 3 480 35 18 10
EGS 15125
15125
1
2, 3
277
480
100


100
35


35


35


35
32
EGH 15125 1 277 200 65 42
15125 2, 3 480 200 65 42
EHD 15100 1 277 14 10 33
15100 2, 3 480 18 14 10
FDB 15150 2, 3 600 18 14 14 10
FD, FDE 15150 1 277 35 10 34
15225 2, 3 600 65 35 18 10
EDB 100225 2, 3 240 22 10
EDS
ED
100225
100225
2, 3
2, 3
240
240


42
65






10
10


35
DK 250400 2, 3 240 65 10
JD 70250 2, 3 600 65 35 18 10
KD 4, CKD 5 100400 2, 3 600 65 35 25 10 36
LHH 6 150400 2, 3 480 100 65 35 42
NHH 150350 3 600 100 65 35
LGE 250600 3 600 65 35 18 22
4
LD , CLD 45 300600 2, 3 600 65 35 25 22 6 37
4
MDL , CMDL 45 300800 2, 3 600 65 50 25 22
4
ND , CND 45 4001200 2, 3 600 65 50 25
CNGC 800, 1200 200 100 65 38
CNGH 800, 1200 100 65 35
CNGS 800, 1200 85 50 25
NGC 800, 1200 200 100 65
NGH 800, 1200 100 65 35 39
NGS 800, 1200 85 50 25
1 dc ratings apply to substantially non-inductive circuits.
2 dc rated single-pole, 1570 A only. 40
3 Rating 480Y/277 Vac maximum.
4 Available with integral ground fault protection.
5 100% rated breaker.
6 dc rating not available with Digitrip 310.
41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-10 Panelboards
Overview January 2018
Sheet 22 010
Technical Data and SpecificationsPow-R-Line

Table 22.0-3. Electrical Characteristics of Circuit Breakers (Continued)


22 Circuit Breaker Ratings UL Listed Interrupting Ratings (kA rms Symmetrical)
Type Ampere Number Voltage AC Rating, Volts DC Rating, Volts 1
Rating of Poles
23 AC DC 120/240 240 277 480 600 125 250 600
High Interrupting Capacity Circuit Breakers
HFD, HFDE 15150 1 277 65 10
24 EDH
15225
100225
2, 3
2, 3
600
240




100
100


65

25


10
22



HJD 70250 2, 3 600 100 65 25 22
HKD 2, CHKD 3 100400 2, 3 600 100 65 35 22
25 LGH 250600 3 600 100 65 35 22
HLD 2, CHLD 23 300600 2, 3 600 100 65 35 25 4
HMDL 2, CHMDL 23 300800 2, 3 600 100 65 35 25
26 HND 2, CHND 23 4001200 2, 3 600 100 65 35
Current Limiting Circuit Breakers
FDC, FDCE 15225 2, 3 600 200 100 35 22
27 EDC
JDC
100225
70250
2, 3
2, 3
240
600




200
200



100

35
10


22


KDC 2 100400 2, 3 600 200 100 65 22
LGC 4 250600 2, 3 600 200 100 50 42
28 LGU 4 250600 2, 3 600 200 150 65 50
LDC 2, CLDC 23 300600 2, 3 600 200 100 50 25 4
NDC 2, CNDC 23 4001200 2, 3 600 200 100 65
29 Current Limit-R Circuit Breakers
FCL 15100 2, 3 480 200 150
LCL 2 125400 2, 3 480 200 200
30 TRI-PAC Current Limiting Circuit Breakers
FB-P 15100 2, 3 600 200 200 200 3
LA-P 70400 2, 3 600 200 200 200 3
31 NB-P 300800 2, 3 600 200 200 200 3
Direct Current (DC) Rated Breakers
HFDDC 56 15150 2, 3 600 42 42 35
32 HJDDC 57 70250 2, 3 600 42 42 35
HKDDC 57 100400 2, 3 600 42 42 35
HLDDC 57 300600 2, 3 600 42 42 35
33 HMDLDC 57
NBDC 57
300800
7001200
2, 3
2, 3


600
600










42
42
42
42
35
35
1 dc ratings apply to substantially non-inductive circuits.
34 2
3
Available with integral ground fault protection.
100k based on NEMA test procedure.
4 dc rating not available with Digitrip 310.
35 5
6
For use on dc systems only.
Non-interrupting trip type.
7 Interrupting trip type.
36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-11
January 2018 Overview
Sheet 22 011
Technical Data and SpecificationsPow-R-Line

Terminal Wire Ranges, Pressure-Type Al/Cu Terminals Except as Noted


Where copper-aluminum terminals are supplied on designated panelboard types, best results are obtained if a suitable joint
22
compound is applied when aluminum conductors are used.
Table 22.0-4. Standard Main Lug Terminals 23
Panel Wire Size Ranges for Ampere Capacity
Type 100 A 225 A 250 A 400 A 600 A 800 A 1200 A 24
Pow-R-Line 1a, 1aF, 1R #121/0 #6300 kcmil (2) #4500 kcmil (2) #4500 kcmil 1
Pow-R-Line 2a, 2aF, 2R #121/0 #6300 kcmil (2) #4500 kcmil (2) #4500 kcmil 1
Pow-R-Line 3a #121/0 #6350 kcmil (2) #4500 kcmil (2) #4500 kcmil (3) #4500 kcmil 25
Pow-R-Line 3E #121/0 #6350 kcmil (2) 4/0500 kcmil (2) 4/0500 kcmil
Pow-R-Line 4 #4500 kcmil (2) #4500 kcmil (2) #4500 kcmil (3) #4500 kcmil (4) #4500 kcmil
Pow-R-Command #121/0 #6300 kcmil (2) #4500 kcmil 26
PRL1a-LX #121/0 #6300 kcmil
PRL2a-LX #121/0 #6300 kcmil
PRCE #121/0 #6300 kcmil (2) #4500 kcmil 27
PRC100 #121/0 #6350 kcmil (2) #4500 kcmil
PRC25 #121/0 #6300 kcmil (2) #4500 kcmil
PRL5P (1) #1/0500 kcmil or (2) #4500 kcmil (1) #2500 kcmil or (2) #4750 kcmil 28
(2) #1/0250 kcmil (2) #2400 kcmil
Elevator control #4500 kcmil (2) #4/0-500 kcmil (2) #4/0-500 kcmil (3) #4/0-500 kcmil
1 Not applicable PRL 1aF, 1R, PRL 2aF, 2R.
29
Note: Optional 750 kcmil mechanical screw-type terminals are available upon request. Panelboard dimensions may be affected. Refer to Eaton.

Table 22.0-5. Standard Main Breaker and Branch Breaker Terminals Table 22.0-6. Fusible Switch Terminals 30
Breaker Type Ampere Rating Wire Size Ranges Ampere Rating Wire Size Ranges

BAB, QBHW, BABRSP 1570 #14#4 30 #141/0 31


HQP, QPHW 90100 #81/0 60 #141/0
EDB, EDS, ED 100225 #44/0 or 100 #141/0
EDH, EDC 2 #6300 kcmil 200 #4300 kcmil 32
EGB, EGE, EGS, EGH 1550 #143/0 AL/CU 400 250750 kcmil or
60125 #63/0 AL/CU (2) 3/0250 kcmil
EHD, FDB, FD 15100 #141/0 600 (2) #4600 kcmil or (4) 3/0250 kcmil
33
HFD, FDC 2, HFDDC 3 125225 #44/0 800 (3) 250750 kcmil or (6) 3/0250 kcmil
FCL 15100 #141/0
GHB, HGHB, GHQ, 1550 #141/0
1200 (4) 250750 kcmil or (8) 3/0250 kcmil 34
GHQRSP 25100 #101/0
JD, HJD, JDC 2, HJDDC 3 70250 #4350 kcmil
35
DK 250350 250500 kcmil
400 (2) 3/0250 kcmil or
(1) 3/0500 kcmil
KD 225 (1) #3350 kcmil
36
HKD, KDC, HKDDC 3 350 (2) 3/0250 kcmil or
CKD 2, CHKD 2 400 (2) 3/0250 kcmil or
(1) 3/0500 kcmil 37
LHH 150400 #2500 kcmil
(2) #2500 kcmil or
(1) 500750 kcmil 38
LGE, LGH, LGC 250400 (1) #2500 kcmil
500600 (2) #2500 kcmil
LD, HLD, LDC, CLD 2 300500 (2) 250350 kcmil 39
HLDDC 3, CHLD 2 600 (2) 400500 kcmil
MDL, HMDL, HMDLDC 2 400600 (2) #1500 kcmil
CMDL, CHMDL 700800 (3) 3/0400 kcmil 40
ND, HND, CND, CHND, NDC 8001000 (3) 3/0400 kcmil
CLD, 2 CNDC 2 1200 (4) 4/0500 kcmil
NGS, NGH, NGC, CNGS 4001200 (4) 4/0500 kcmil or 41
CNGH, CNGC (3) 500750 kcmil
2 Suitable for dc applications only.
3 LHH is 400 A maximum. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-12 Panelboards
Overview January 2018
Sheet 22 012
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations Industry standards and the NEC to interpret series connected
22 UL permits panelboards to be labeled
require protection of the entire ratings in assembled equipment.
electrical distribution system from The assembled equipment must also
with a short-circuit rating of up to damage due to short-circuit faults. be UL tested for series ratings.
23 200,000 A symmetrical where UL
listed combinations of main and branch
Article 230.205 of the NEC states that
service equipment shall be suitable Code Issues
circuits are used. for the short-circuit current available The fault current contribution of
24 These combinations consist of main at its supply terminals. The entire motors connected between series
breakers or fusible devices connected distribution system is required to meet rated breakers must be considered.
ahead of, and in series with approved this standard. Series rated systems Article 240.86 in the NEC states that for
25 conventional devices. have become an effective method series ratings, the sum of the motor
of meeting these requirements. full-load currents cannot exceed 1%
Two arrangements are acceptable and of the interrupting rating of the lower
26 comply with UL standards for panel- There are three protection systems rated circuit breaker. The actual fault
boards. The main circuit breaker may used to protect low voltage power current contribution from induction
be installed in the panel as a main distribution equipment. They are: motors is about four times their full-
27 device (Figure 22.0-4), or it may be Fully rated protection load current (impedance value of 25%).
mounted remote (Figure 22.0-5) from For example, if the downstream branch
Fully rated, selectively
the panel. In either case, the approved circuit breakers used in a series rated
28 main and branch combinations must coordinated protection combination have an interrupting
be followed. These arrangements are Series rated protection rating of 14,000 A rms symmetrical
acceptable and are UL listed having for a 480 V system, the maximum
Fully Rated ProtectionWhere all
29 been tested in accordance with
overcurrent devices are rated for the allowable motor contribution to that
UL standards. panel from the branch circuit breakers
full prospective short-circuit current
at their line side terminals throughout is 140 A (1%). For typical induction
30 From the tables on Page 22.0-14
the system. motors, this is equivalent to a total
through Page 22.0-22, specific horsepower at 480 V of approximately
combinations of main devices 115 horsepower.
Selectively Coordinated Protection
31 (upstream) and branch devices
A fully rated system where the
(downstream), series connected and Requirements of the NEC (NFPA-70)
overcurrent device closest to the
electrically adjacent in the system, for series ratings may be met by
fault will open first, thus isolating
32 may be selected to qualify the
the faulty circuit. equipment marked with ratings
assembled panelboard for the adequate for the available fault
short-circuit ratings shown. Series Series Rated ProtectionA short- current at the point of application
33 ratings apply only to those Eaton circuit interrupting rating assigned to in the electrical system. Eaton
breakers listed and published. a combination of two or more over- panelboards and switchboards
Do not use Classified breakers. current protective devices that are are marked consistent with NEC
34 connected in series and in which the Article 240.83.
rating of the downstream device(s)
UL Labeled in the combination is less than the Additionally, Article 110.22 requires
field marking on equipment where
35 Upstream
Overcurrent
series rating.
series ratings are used. This label
Device Series ratings are also known in is supplied standard with all Eaton
36 the industry as integrated ratings, panelboards and switchboards.
UL Labeled series combination ratings and
Conventional
Branch
series connected ratings.
37 Breakers
UL Issues
Neutral In a series rated system, all of the
38 overcurrent devices in series in the
protective scheme must have been
Figure 22.0-4. Main Device tested and listed by Underwriters
39 Laboratories for series combination
use in the system.
UL Labeled
All Eatons series ratings are in
40 Remote Upstream
Overcurrent full compliance with all applicable
Device requirements of the latest editions
of UL 489, 891 and 67.
41 Main
Lugs
The UL Recognized Component NEC Required Caution Label
Directory (the Yellow Book) contains
UL Labeled
42 Conventional breaker manufacturers series Note: The NEC requires the installer to
properly apply and complete this label.
Branch connected listings. These are
intended ONLY as a guideline for Label(s) must be placed on all equipment
Breakers
where series ratings are used.
43 use by others who are responsible
Neutral for their own testing, labeling and
listing. Therefore, the UL Recognized
Component Directory cannot be used
Figure 22.0-5. Mounted Remote

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-13
January 2018 Overview
Sheet 22 013
Technical Data and SpecificationsSeries Ratings

Fuse Application Considerations Example 1:


22

Prospective Peak Let-through Current in Amperes


Fuses can be used instead of circuit 240 V, three-phase, three-wire, AC
breakers in fully rated, selectively system with available fault current of
coordinated and series connected 37,438 A. Main (upstream) device is 23
460,000
protection systems. See the tables Asymmetrical a three-pole, 150 A, FD breaker. The
Prospective
on Page 22.0-19 through Page 22.0-20 Peak Curve
branch (downstream) breakers are
for fuse breaker data applied to series at 15% two- and three-pole, 20, 30 and 60 A, 24
connected designs. Power Factor 240 V, BAB breakers.
B A
Dont apply fuses using the up- 150,000 2000 Ampere 1. Go to the 240V table (Table 22.0-8).
over-down method, which has Current-limiter 25
been recommended by some fuse
Fuse Curve 2. Look down under the 42 kA
manufacturers for sizing a current- column. This rating is not shown.
limiting fuse that protects a down- 26
3. Look to the columns to the right.
stream molded-case circuit breaker This rating is shown under the 65 kA
with a specified rms symmetrical
interrupting rating. The method 65,000 200,000
column, and therefore is valid. 27
can lead to erroneous and unsafe Prospective Short-circuit rms Amperes Example 2:
conclusions, and should not be used. Do Not Use This Method
480Y/277 V, three-phase, four-wire, AC 28
Example: Assume a specific type of Figure 22.0-6. Old Up-Over-Down Chart system with available fault current of
current-limiting fuse rated 2000 A. Then 62,097 A. Main (upstream) device is a
using the figure below: Applying Series Ratings three-pole, 250 A, HJD breaker. The 29
branch (downstream) breakers are
1. Draw a vertical line from the The following is provided to use two- and three-pole, 60, 70 and 100 A
prospective short-circuit current of the series rating tables on the FDB breakers. 30
200 kA to intersect the typical peak following pages.
let-through curve at A. 1. Go to the 480Y/277 V table
Step 1. Determine the available system
2. Draw a horizontal line left from voltage and fault current.
(Table 22.0-11). 31
Point A to intersect the 2. Look down under the 65 kA
prospective peak curve at B. Step 2. Select the appropriate table column. This rating is not shown.
using the system voltage. 32
3. Drop a vertical line from B 3. Look to the columns to the right.
to intersect the horizontal axis Step 3. Use the appropriate Series This rating is still not shown.
and read the recommended rating, Equipment Rating column
4. Look at the table with the next
33
65 kA rms, concluding that a equal to, or greater than,
circuit breaker with a 65 kA the available fault current, higher system voltage (480 V,
interrupting capacity will be to determine the allowable Table 22.0-12). 34
protected by a specified 2000 A combinations of main
5. This rating is shown under the 65 kA
current-limiting fuse. (upstream) and branch (down-
column, and therefore is valid.
stream) overcurrent devices. 35
This conclusion is wrong when the Main devices are shown in Example 3:
downstream service has a blow-open bold/shaded areas. Respective
contact assembly, as does a molded- branch breakers are shown 208Y/120 V, three-phase, four-wire, AC 36
case circuit breaker or similar device. directly below their associated system with available fault current of
main device. If a rating is 56,438 A. Main (upstream) device is
The reason: The up-over-down method a three-pole, 225 A, ED breaker. The
ignores dynamic impedance (the
not initially found in a column,
branch (downstream) breakers are
37
first look to the columns to
inherent current-limiting of the down- single-pole, 20 A BAB (120/240 V), and
the right for higher Series
stream molded-case circuit breaker).
Such impedance is developed directly
Equipment Ratings within two- and three-pole, 70 A BAB (240 V). 38
the same table. If still not 1. Go to the 240 V table (Table 22.0-8).
by the forces of the let-through current
found, use ratings from table
created when the contacts are
blown open.
of a higher system voltage 2. Look under the 65 kA column. 39
(higher numbered tables). This rating is shown under the
For proper application of current- 65 kA column, and therefore is
limiting fuses, always refer to valid for the two- and three-pole 40
recommendations by the manufacturer (240 V) breakers.
of the circuit breaker, which are based
3. Look at the 120/240 V table 41
on actual test data.
(Table 22.0-7) for the single-pole
(120/240 V) rating.
4. Look under the 65 kA column. 42
This rating is shown under the
65 kA column, and therefore
is valid for the single-pole 43
(120/240 V) breakers.

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-14 Panelboards
Overview January 2018
Sheet 22 014
Technical Data and SpecificationsSeries Ratings

Other Applications of Series Ratings Main and branch series ratings may breakers B and C series rate at the
22 Series ratings can also be applied
be combined if: same interrupting rating level (or
higher), it is NOT allowable to use A,
under the following guidelines: Breakers A, B and C are in series B and C together at the A-B or B-C
23 Any FULLY RATED breaker can be
respectively from main to branch. series rating. However, combining
Breakers A and B series rate together, multiple overcurrent devices as in
applied upstream, downstream, or in breakers A and C series rate at the
the middle of, any of the series ratings this example, can be accomplished if
24 stated in the tables.
same interrupting rating level (or all devices in the series combination
higher), it is allowable to use A, B and have been tested together and listed
Any series rating stated in the tables C together at the A-B series rating. in triple rating Table 22.0-20.
25 may have additional branch breakers It is improper to combine series
of the EXACT SAME TYPE further Main devices shown centered at top
ratings under the following condition: in shaded area, respective branch
downstream in that rating.
26 COMBINING SERIES RATINGS is
Breakers A, B and C are in series devices shown directly below.
respectively from main to branch.
allowed under certain conditions. Breakers A and B series rate together,
27
Table 22.0-7. 120/240 VacBreaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
28 Main Series Equipment RatingkA Symmetrical
Breaker 18 22 42 65 100 200
Maximum
29 Amperes

100 EHD QBHW GB, GHB FB-P FCL


30 BAB
HQP
QPHW BAB
HQP
BAB
HQP
BA
HQP
BAB
QBGF HQP QBGF QBGF QBGF
QBGFT QPGF QPGF QPGF
31 QBCAF
QBGF
QPGF QBAG QBAG QBAG
QBAG QBHW QBHW QBHW
QBGFT QPHW QPHW QPHW
32 QPGFT QBHW
QPHW
EHD
FD
GB, GHB
GHQ
QBGFT QBGFT EHD
QPGFT QPGFT FD
33 QBCAF HFD
QBGFT
QPGFT
34 QBCAF
125 BRX EGH
BAB (1570 A) GHQ, GHB
35 BAB (90100 A)
HQP (1570 A)
HQP (90100 A)
36 150 FDB FDE HFDE
BAB BAB BAB
HQP HQP HQP
37 QBGF
QBAG
QBHW
QPHW
GHB
EHD
QBGFT FD (15150 A)
QBCAF QBHW
38 QPHW
200 LA-P
BAB
39 HQP
QBHW
QPHW
40 EHD
FD

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-15
January 2018 Overview
Sheet 22 015
Technical Data and SpecificationsSeries Ratings

Table 22.0-7. 120/240 VacBreaker/Breaker Series Ratings (Continued)


Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. 22
Main Series Equipment RatingkA Symmetrical
Breaker 18 22 42 65 100 200
Maximum 23
Amperes

225 EDB EDS ED, FD FDE HFDE EDH, EDC HFD FDC FDC
BAB BAB BAB QBGF BAB BAB 1 BAB BAB GB, GHB
24
HQP HQP HQP QPGF HQP HQP 1 HQP HQP GHQ
QBGF QBGF QBGF QBAG QBHW QBGF QBGF QBHW EHD
QPGF QPGF QPGF QBHGF QPHW QPGF QBAG QPHW FD 25
QBHGF QBHGF QBAG QBGFT QBAG QBHW HFDE HFD
QPHGF QPHGF QBHW QPGFT QBGFT QPHW EGS
BAB
QBHW
QPHW
QBHW
QPHW
QBHGF
QBGFT
QBHGFT
QBCAF
QPGFT
QBCAF
QBHGF
GB, GHB HQP
EGH 26
QBAG QBAG QPGFT QPHGF GHQ, GHQRSP QBGF
QBGFT QBGFT QBHGFT QPHGFT EHD, EGS QBAG
QPGFT QPGFT QBCAF FD QBHW 27
QBHGFT QBHGFT QBGFT QPHW
QPHGFT QPHGFT QPGFT QBHGF
GHB, EHD
QBCAF QBCAF
FD (15150 A) 28
QBGFT
EGS
FDE (15150 A)
QBCAF
29
QBHGFT
QPGF
QPGFT 30
QPHGF
QPHGFT
250 JD, JDB HJD JDC HJD JDC JDC 31
BAB (1570 A) BAB QBGF GB, GHB BAB GB, GHB
HQP (1570 A) HQP QPGF EHD HQP EHD
QBHW QBHW QBAG FD QBHW FD 32
QPHW QPHW QBGFT EGS QPHW HFD
EHD QPGFT EGS
QBCAF EGH
400 DK, KD DK, KD HKD, CHKD DK, KD KDC HKD KDC KDC LCL
33
KDB KDB, CKD BAB (1570 A) KDB BAB (1570 A) CHKD QBHW GB, GHB BAB
BAB BAB (1570 A) HQP (1570 A)
QBHW
CKD HQP (1570 A) GB, GHB QPHW EHD
FD
HQP
QBGF
34
HQP HQP (1570 A) EHD EHD
QBGF QBHW QPHW FD HFD QPGF
EGS 2 EGS QBAF
QPGF
QBAG
QPHW
EGH QBAG 35
QBGFT QBHW
QPGFT QPHW
GB, GHB
EHD
36
FD
HFD
QBGFT 37
QPGFT
QBCAF
600 CHLD, HLD 38
EHD
800 HMDL
EHD
39
1200 HND
CHND
NGH 40
NGH-C
EHD
EDB 41
EDS
ED
1 Single-pole version is restricted to 1570 A. 42
2 Not valid with CHKD.

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-16 Panelboards
Overview January 2018
Sheet 22 016
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations


22 Table 22.0-8. 240 VacBreaker/BreakerSeries Ratings
For single- and two-pole 120/240V rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 22.0-7.
23 Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
Main Series Equipment RatingkA Symmetrical
Breaker 18 22 42 65 100 200
24 Maximum
Amperes

100 EHD QBHW_H GB, GHB FB-P FCL


25 BAB_H QPHW_H BAB_H BAB_H BAB_H
HQP_H BAB_H HQP_H HQP_H HQP_H
HQP_H QBHW_H EHD QBHW_H
26 QPHW_H FDB QPHW_H
FD GB, GHB
EHD
FD, FDE
27 FDB
HFD, HFDE
125 EGH
28 GHB
150 FDB
29 BAB_H
HQP_H
200 LA-P
30 BAB_H
HQP_H
QBHW_H
31 QPHW_H
EHD
FDB
FD
32 JD, JDB
225 EDB EDS ED FD, FDE EDH, EDC HFD, HFDE FDC FDC
HQP_H HQP_H BAB_H BAB_H BAB_H BAB_H BAB_H GB, GHB
33 BAB_H BAB_H HQP_H HQP_H HQP_H HQP_H HQP_H EHD
QBHW QBHW QBHW_H QBHW_H QBHW_H QBHW_H FDB
QPHW QPHW QPHW_H QPHW_H QPHW_H FD, FDE
34 CHH EHD 1
FDB
GB, GHB
EHD
HFD, HFDE

BAB_H FDB
FD, FDE
35 250 JD, JDB HJD HJD JDC JDC
BAB_H (1570A) BAB_H (1570 A) GB, GHB BAB_H GB, GHB
HQP_H (1570 A) HQP_H (1570 A) EHD HQP_H EHD
36 QBHW_H QBHW_H FD QBHW_H FD, FDE
QPHW_H QPHW_H FDB QPHW_H FDB
EHD ED HFD, EDB, EDS
37 FDB JD, JDB ED, HFDE
EGS EDH
JD, JDB
HJD, EGS, EGH
38 1 Valid on two- and three-pole breaker only. Not valid for single-pole.

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-17
January 2018 Overview
Sheet 22 017
Technical Data and SpecificationsSeries Ratings

Table 22.0-9. 240 VacBreaker/BreakerSeries Ratings


For single- and two-pole 120/240 V rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 22.0-7. 22
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
Main Series Equipment RatingkA Symmetrical
Breaker 65 100 200
23
Maximum
Amperes

400 DK, KD, KDB HKD, CHKD KDC KDC LCL


24
CKD QBHW_H 1 QBHW_H GB, GHB BAB_H
BAB_H
HQP_H
QPHW_H 1
GB, GHB
QPHW_H EHD
FDB
HQP_H
QBHW_H
25
QBHW_H EHD FD, FDE QPHW_H
QPHW_H FDB, FDE HFD, EDB, EDS, HFDE GB, GHB
EHD FD, EDB, EDS ED EHD 26
FDB ED EDH FDB
JD, JDB JD, JDB FD, HFD, EDB, EDS
DK, KD, KDB
EGS 2
HJD
DK, KD, KDB
ED, FDE, HFDE
EDH
27
HKD JD, JDB
HJD
DK, KD, KDB 28
HKD
500 NB-P
JD, JDB 29
KD, KDB, DK
CKD
600 HLD, HLDB, CHLD LDC 30
GB 1, GHB 1 EDB, EDS, ED
FD, EDB, EDS EDH
ED, EHD 31
JD, JDB
KD, KDB, DK, CKD
LD, LDB
800 NB-P HMDL
32
KD, KDB, DK EHD
FD 33
1200 HND, CHND NDC
EDB, EDS, ED EDB, EDS, ED
EHD EDH 34
2500 RD RDC
EDB, EDS, ED EDB, EDS, ED
EDH 35
1 Valid on two- and three-pole breakers only. Not valid for single-pole.
2 Not valid with CHKD.
36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-18 Panelboards
Overview January 2018
Sheet 22 018
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations (Continued)


22 Main devices shown in shaded area, respective branch devices shown directly below.
Table 22.0-10. 277 VacBreaker/Breaker Series Ratings
23 Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
All ratings in this table apply to single-pole branch breakers only. For two- and three-pole branch breakers, see other tables.
24 Main
Breaker
Series Equipment RatingkA Symmetrical
22 25 35 65 100 150
Maximum
Amperes
25
100 FCL
GHB
26 GHQ, GHQRSP
EHD
FD
HFD
27 125 EGS EGH
GHQ, GHB GHQ, GHB
28 225 FD, FDE HFD, HFDE FDC
GHB GHB GHB
GHQ GHQRSP 2 EHD
29 GHQRSP 1
GHBGFEP 1
GHBGFEP 2
GHQ
FD
HFD
EHD
FD
30 250 JD, JDB JD, JDB HJD LCL JDC
GHB GHB (1550 A) GHB (1550 A) FDC GHB
GHBGFEP 3
31 EHD
FD
EHD
FD
GHBGFEP HFD
400 KD, KDB HKD KD, KDB HKD, CHKD KDC LCL
32 CKD CHKD CKD GHB GHB GHB
GHB GHB GHB EHD EHD EHD
FD FD FD
33 EHD
FD GHQ 5 HFD HFD
GHQ 4
1
34 2
Not valid with FDE.
Not valid with HFDE.
3 Not valid with JDB.
4 Not valid with KDB or CKD.
35 5 Not valid with CHKD.

Table 22.0-11. 480Y/277 VacBreaker/Breaker Series Ratings


36 Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
All ratings in this table apply to two- and three-pole branch breakers only. For single-pole branch breakers, see Table 22.0-10.
Main Series Equipment RatingkA Symmetrical
37 Breaker 22 25 35 65 100 150
Maximum
Amperes
38 100 FCL
GHB, GHQRSP
39 125 EGS EGH
GHB GHB
225 FD, FDE HFD, HFDE FDC
40 GHB, GHQRSP 6 GHB, GHQRSP 7 GHB
250 JD, JDB JD, JDB HJD JDC
41 GHB GHB (1550 A) GHB (1550 A) GHB
400 KD, KDB HKD, CHKD KD, KDB HKD, CHKD KDC LCL
CKD GHB CKD GHB (1550 A) GHB (1550 A) GHB
42 GHB GHB (1550 A)
6 Not valid with FDE.
7 Not valid with HFDE.
43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-19
January 2018 Overview
Sheet 22 019
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations (Continued)


Main devices shown in shaded area, respective branch devices shown directly below.
22
Table 22.0-12. 480 VacBreaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
23
All ratings in this table apply to two- and three-pole branch breakers only. Not valid for single-pole branch breakers.
Main
Breaker
Series Equipment RatingkA Symmetrical 24
25 35 65 100 150
Maximum
Amperes
25
100 FB-P FCL
EHD EHD
FDB FDB 26
FD FD, FDE
HFD HFD, HFDE
200 LA-P 27
EHD
FDB
FD
HFD
28
JD, JDB
HJD
225 FD, FDE HFD, HFDE FDC 29
EHD EHD EHD, EGS, EGH
FDB FDB FDB
FD, FDE FD, FDE 30
EGS 1 HFD, HFDE
250 JD, JDB HJD JDC LCL
EHD EHD EHD, EGS, EGH FDE, HFDE
31
FDB FDB FDB
FD FD, FDE
FDE HFD, HFDE 32
JD, JDB JD, JDB
EGS HJD
400 KD, KDB HKD KDC LA-P LCL 33
EHD EHD EHD, EGS, EGH JD, JDB EHD
FDB FDB FDB HJD FDB
FD, FDE
JD, JDB
FD, FDE
HFD, HFDE
KD, KDB
HKD
FD, FDE
HFD, HFDE
34
KD, KDB JD, JDB FDC
EGS HJD JD, JDB
KD, KDB HJD 35
HKD KD, KDB
HKD
500 NB-P 36
JD, JDB
HJD
KD, KDB
HKD
37
600 LD, LDB HLD, HLDB
CLD CHLD 38
JD, JDB FD, FDE
JD, JDB
KD, KDB 39
LD, LDB
1 Not valid with HFDE.
40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-20 Panelboards
Overview January 2018
Sheet 22 020
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations (Continued)


22 Table 22.0-13. 600 VacBreaker/Breaker Series Ratings
Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
23 All ratings in this table apply to two- and three-pole branch breakers only. Not valid for single-pole branch breakers.
Main Series Equipment RatingkA Symmetrical
Breaker 18 25 35 42 50 100
24 Maximum
Amperes

225 FD HFD FDC


25 FDB FDB FDB
FD FD, FDE
HFD, HFDE
26 250 JD, JDB HJD JDC LCL
FDB FDB FDB FDE, HFDE
FD FD
27 JD, JDB HFD
JD, JDB
HJD
28 400 KD, KDB HKD, CHKD KDC KDC LCL
CKD FDB FDB JD, JDB FDB
FDB FD, FDE FD, FDE HJD FD, FDE
29 FD HFD, HFDE HFD, HFDE KD, KDB HFD, HFDE
JD, JDB JD, JDB HKD FDC
HJD JD, JDB
HJD
30 JDC
KD, KDB
HKD
31 KDC
600 LD, LDB HLD, HLDB
CLD CHLD
32 FD KD, KDB
JD, JDB LD, LDB

33 Table 22.0-14. 120/240 VacFuse/Breaker Series Ratings


Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
34 Main
Fuse
Series Equipment RatingkA Symmetrical
100 200
Maximum
Amperes
35
100 R
BAB
36 HQP
QBHW
QPHW
GB
37 GHB
200 R J T
GB BAB BAB
38 GHB HQP HQP
QBHW QBHW
QPHW QPHW
39 400 J T J T
BAB BAB GB GB
HQP HQP GHB GHB
40 QBHW QBHW
QPHW QPHW

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.0-21
January 2018 Overview
Sheet 22 021
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations (Continued)


Main devices shown in shaded area, respective branch devices shown directly below.
22
Table 22.0-15. 240 VacFuse/Breaker Series Ratings
For single- and two-pole 120/240 V rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 22.0-14.
23
Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
Main
Fuse
Series Equipment RatingkA Symmetrical 24
100 200
Maximum
Amperes
25
100 R
BAB_H
HQP_H 26
QBHW_H
QPHW_H
GB
GHB 27
200 R J T R
GB
GHB
BAB_H
HQP_H
BAB_H
HQP_H
GB 1
GHB 1
28
QBHW_H QBHW_H
QPHW_H QPHW_H
400 J T J T 29
BAB_H BAB_H GB GB
HQP_H HQP_H GHB GHB
QBHW_H QBHW_H 30
QPHW_H QPHW_H
600 L
EHD
31
FDB
FD, FDE
ED 32
JD, JDB
DK, KD, KDB
1 Valid on two- and three-pole breakers only. See Table 22.0-14 for single-pole. 33
Table 22.0-16. 277 Vac Fuse/Breaker Series Ratings
Main fuse class are shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings 34
in this table apply to single-pole branch breakers only. For two- and three-pole branch breakers, consult other tables.
Main Series Equipment RatingkA Symmetrical
Fuse 65 100 200
35
Maximum
Amperes

100 J T R
36
GHQ GHQ GHB
GHQRSP GHQRSP
200 J T J T R
37
GHQ GHQ EHD EHD GHB
GHQRSP GHQRSP FD
HFD
FD
HFD
38
400 J T
GHB GHB 39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.0-22 Panelboards
Overview January 2018
Sheet 22 022
Technical Data and SpecificationsSeries Ratings

Series Rated Combinations (Continued)


22 Table 22.0-17. 480Y/277 VacFuse/Breaker Series Ratings Table 22.0-19. 600 VacFuse/Breaker Series Ratings
Main fuse class shown centered at top, in shaded area. Main fuse class shown centered at top, in shaded area.
23 Respective branch devices shown directly below. All ratings Respective branch devices shown directly below. All ratings
in this table apply to two- and three-pole branch breakers in this table apply to two- and three-pole branch breakers
only. For single-pole branch breakers, see Table 22.0-16. only. Not valid for single-pole branch breakers.
24 Main Series Equipment RatingkA Symmetrical Main Series Equipment RatingkA Symmetrical
Fuse 65 100 200 Fuse 100 200
Maximum Maximum
25 Amperes Amperes

100 R 100 R
GHB FD, FDE
26 200 R HFD, HFDE
FDC
GHB
200 J T R
27 400 J T
FD, FDE FD, FDE JD
GHB GHB HFD, HFDE HFD, HFDE HJD
600 J T FDC FDC JDC
28 EHD GHB 400 J T R
FD, FDE EHD JD JD KD
HFD FD, FDE HJD HJD HKD
29 FDC HFD, HFDE JDC JDC KDC
HFDE FDC
JD 600 J T
HJD KD KD
30 JDC HKD HKD
KDC KDC
Table 22.0-18. 480 VacFuse/Breaker Series Ratings
31 Main fuse class shown centered at top, in shaded area. Table 22.0-20. Triple Series Ratings
Respective branch devices shown directly below. All ratings Main Fuse Tenant Main Branch System Short-
in this table apply to two- and three-pole branch breakers Class and Type Type Voltage Circuit
32 only. Not valid for single-pole branch breakers. Maximum Series
Amperes Rating
Main Series Equipment RatingkA Symmetrical (kA, Sym.)
33 Fuse
Maximum
100 200
L-6000 DK, KD, KDB GB, GHB, EHD 1 240 100
Amperes L-6000 DK, KD, KDB GB, GHB 120/240 100
34 100 R L-6000 DK, KD, KDB FD 1, FDB 240 100
EHD L-6000 DK, KD, KDB JD, JDB 240 100
200 J T L-6000 JD, JDB GB, GHB 240 100
35 EHD EHD L-6000 JD, JDB GB, GHB 120/240 100
FD FD L-6000 FD GB, GHB 240 100
HFD HFD
36 FDC FDC L-6000 FD GB, GHB 120/240 100
L-6000 FD, FDB BAB_H, HQP_H 240 100
QBHW_H, QPHW_H
37 L-6000 FD, FDB BA, BAB 120/240 100
HQP (1570 A)
L-6000 EHD BAB_H, HQP_H 240 100
38 L-6000 EHD BA, BAB, HQP 120/240 100
1 Valid on two- and three-pole breakers only. Not valid for single-pole.

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.1-1
January 2018 Pow-R-Line 1a
Sheet 22 023
General DescriptionPow-R-Line 1a

Pow-R-Line 1a Main Lugs Only Table 22.1-1. Main Circuit Breakers


22
The short-circuit rating of the MLO Breaker Breaker Interrupting Rating
assembled panelboard will be fully Frame Type (kA Symmetrical)
rated based upon the lowest rated Amperes at 240 Vac
branch device or may be series rated 100 BAB 10
23
with an approved upstream device. 100 QBHW 22
100 EHD 18
Main lugs only ampere ratings:
150 FDB 18
24
100, 225, 400 and 600.
225 FD, FDE 65
Main Circuit Breakers 225 HFD, HFDE 100
225 FDC, FDCE 200 25
The short-circuit rating shown is that 225 EDB 22
of the main breaker only. The short- 225 EDS 42
circuit rating of the assembled 225 ED 65 26
panelboard is the rating of the lowest 225 EDH 100
fully rated main or branch device 225 EDC 200

Pow-R-Line 1a or the rating of an approved series 250


250
JD
HJD
65
100
27
rated combination.
250 JDC 200
General Description 400
400
DK
KD
65
65
28
Panelboard Ratings 400 HKD 100
400 KDC 200
Voltage 400 LHH 100 29
240 Vac maximum 600 LGE 65
600 LGS 85
Main Lugs 600 LGH 100 30
100600 A 600 LGC 200
600 LGU 200
Main Breakers
Table 22.1-2. Branch Circuit Breakers
31
100600 A
Breaker Ampere Number Interrupting Rating (kA Symmetrical)
Branch Breakers Type Rating of Poles 120 Vac 120/240 Vac 240 Vac 32
15100 A
BAB, HQP 1570 1 10
(Bolt-on or plug-on chassis) BAB, HQP 15100 2 10
Short-Circuit Current Ratings (Symmetrical) BAB, HQP 15100 2, 3 10 33
BAB-D 1, HQP-D 1 1560 1, 2 10 10
240 Vac: 10 kA and 22 kA fully rated BAB-C 2, HQP-B 2 1530 1, 2 10 10
240 Vac: 22200 kA series rated BABRP 3 1530 1, 2 10 10 34
BABRSP 3 1530 1, 2 10 10
Service QBGF, QBGFEP, 1550 4 1, 2 10 10
Three-phase, four-wire 208Y/120 V QPGF, QPGFEP 1550 4 1, 2 10 10 35
and 240/120 V delta QBCAF 5 1520 1 10 10
Single-phase, three-wire 120/240 V QBHW 1570 1 22
Single-phase, two-wire 120 V
QBHW 15100 2 22 36
QBHW 15100 2, 3 22
Three-phase, three-wire QBHGF, QBGFEP 1530 1, 2 22 22
208 V and 240 V QPHGF, QPHGFEP
QBHCAF 5
1530
1520
1, 2
1
22
22
22
22


37
Suitable for service entrance 1 HID (High Intensity Discharge) rated breaker.
applications when specified. 2 Switching neutral breaker. Single-pole device requires two-pole space, two-pole device requires
three-pole space.
38
Mains 3 Solenoid operated breaker.
For available mains, refer 4 50 A is two-pole only.
to Table 22.1-1. 5 Arc fault breaker.
39
Main breakers, 100 A, Types BAB and Series Rated Combinations
QBH are horizontally mounted, same Refer to series rating tables beginning 40
as branch breakers. All other main on Page 22.0-14 for the approved
breakers are vertically mounted. series rated combinations available
Branch Circuits for the branch circuit breakers listed 41
in Table 22.1-2.
For available branch devices, refer
to Table 22.1-2. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.1-2 Panelboards
Pow-R-Line 1a January 2018
Sheet 22 024
Technical Data and SpecificationsPow-R-Line 1a

Technical Data and Specifications Table 22.1-5. Sub-Feed Breakers Box Sizing and Selection
22 (One Per Panel)
Box size for all Type 1 panelboards
Bussing Ampere Breaker Interrupting Rating
Rating Type (kA Symmetrical)
are available from Table 22.1-6.
100400 A: Tin-plated aluminum
23 is standard, copper is available
at 240 V
Instructions
as an option. 150 FDB 18 1. Select the rating and type of mains
225 FD 65 required.
24 600 A: Only copper density is available 225 HFD 100
for these applications. 225 FDC 200 2. Count total number of branch
225 EDB 22
circuit poles (including spaces)
25 Boxes 225 EDS 42
225 ED 65 required in the panelboard. Do
Boxes are made from code-gauge 225 EDH 100 not count main breaker poles.
galvanized steel. 225 EDC 200 Convert two- or three-pole branch
26 Blank ends are supplied as standard, 250 JD 65 breakers to single-poles, i.e.,
250 HJD 100 three-pole breaker, count as
knockouts are available upon request. 250 JDC 200
three poles.
27 EZ Trim 400 DK 65
400 KD 65 Note: For horizontal mounted mains
Trims are made from code-gauge steel 400 HKD 100 (BAB Type), use main lug table, include
and painted ANSI 61 gray. 400 KDC 200
28 600 LGE 65
space in branch section for mains.
All panelboards have door-in-door 600 LGS 85 3. Using correct table, type of mains
as standard with multi-point 600 LGH 100
and ampere rating per Step 1, find
29 catch and lock, and concealed 600 LGC 100
total number of poles.
mounting hardware.
Shunt Trips Note: Where total number of poles (Step 2)
30 Modifications Shunt trips are available on breakers. fall between number in table, use the next
Table 22.1-3. Sub-Feed Lugs (Main Lugs Only) BAB, HQP, QBHW and QPHW require higher number.
Ampere Panel Height one additional pole space for shunt
31 Rating Addition trip, i.e., single-pole is two-pole size, 4. Read box size across columns to
two-pole is three-pole size and three- the right.
100 0 Inches (0 mm)
225 0 Inches (0 mm) pole is four-pole size. Top and Bottom Gutters (Minimum)
32
Ground Bar 5.50 inches (139.7 mm).
Table 22.1-4. Through-Feed Lugs
Ampere Information Standard bolted in box. Aluminum Side Gutters
33 Rating is standard, copper is available as
20.00-inch (508.0 mm) wide box:
an option.
100 See Table 22.1-6 6.50 inches (165.1 mm).
34 225
400
See Table 22.1-6
See Table 22.1-6
Enclosures
600 See Table 22.1-6 Types 1, 12, 3R, 4 and 4X.

35 Surge Protective Device (SPD)


Integrated onto panelboard chassis.
For complete product description and
36 available ratings, refer to Tab 34.

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.1-3
January 2018 Pow-R-Line 1a
Sheet 22 025
Technical Data and SpecificationsPow-R-Line 1a

Table 22.1-6. Type 1 PanelboardsDimensions in Inches (mm)


Panelboard Types and Mounting Position Maximum Box Dimensions 123 Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Sub-Feed Circuits 23
Breaker Including
Provisions
100A 24
Main BAB, 15 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker QBHW 27 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
(H)



39
42
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
25
Main 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
lugs





30
42
36.00 (914.4)
48.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2048
LT2036S or F
LT2048S or F
EZB2036R
EZB2048R
EZT2036S or F
EZT2048S or F
26
48 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F






54
60
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
27
72 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EHD, FDB, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
28
breaker FD, FDE, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
HFD, FDC, 42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
HFDE, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 29
FDCE
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
(V)
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 30
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main lugs EHD, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 100 A FDB, FD, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 31
through- FDE 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
feed lugs HFD, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or sub-feed FDC,
breaker HFDE,


54
60
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
32
FDCE
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
(V)
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EHD, FDB, EHD, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
33
breaker FD, FDE, FDB, FD, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 100 A HFD, FDC, FDE 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- HFDE, HFD, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 34
feed lugs FDCE FDC,
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or sub-feed (V) HFDE,
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker FDCE
(V)
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 35
225A
Main 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F 36
lugs 4 30 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
48 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
37
54 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F






72
84
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
38
Main EDB, EDS, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker 4 ED, EDH, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
EDC, FD, 42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 39
HFD, FDC, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
FDE,
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
HFDE,
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 40
FDCE
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
(V)
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information. 41
2 Add 8.00 inches (203.2 mm) for SPD.
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
4 JD, HJD, JDC is same space requirement as 400 A DK, HKD, KDC. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.1-4 Panelboards
Pow-R-Line 1a January 2018
Sheet 22 026
Technical Data and SpecificationsPow-R-Line 1a

Table 22.1-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


22 Panelboard Types and Mounting Position Maximum Box Dimensions 123 Catalog Number
Types (H) = Horizontal / (V) = Vertical Number
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
23 Breaker Breaker Sub-Feed Circuits
Breaker Including
Provisions
24 225 A (Continued)
Main lugs EDB, EDS, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
with 225 A ED, EDH, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
25 through-
feed
EDC, FD,
HFD, FDC,


42
48
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
lugs or FDE, 54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
sub-feed HFDE,
26 breaker 4 FDCE


60
72
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
(V) 84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EDB, EDS, EDB, EDS, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
27 breaker ED, EDH, ED, EDH, 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 225 A EDC, FD, EDC, FD, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- HFD, FDC, HFD, FDC, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
28 feed lugs
or sub-feed
FDE,
HFDE,
FDE,
HFDE,
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 4 FDCE FDCE
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
(V) (V)
29 Main lugs EDB, EDS, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 225 A ED, EDH, 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
dual EDC, FD, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 sub-feed HFD, FDC, 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 4 FDE,
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
HFDE,
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
31 FDCE
(V)
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main EDB, EDS, EDB, EDS, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
32 breaker ED, EDH, ED, EDH, 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 A EDC, FD, EDC, FD, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
dual HFD, FDC, HFD, FDC, 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
33 sub-feed
breakers 4
FDE,
HFDE,
FDE,
HFDE,
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F

FDCE FDCE
(V) (V)
34 400 A
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
35 lugs





30
42
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
36 60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
37 Main DK, KD, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
breaker HKD, KDC, 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
LHH 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
38 (V) 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
39



72
84
90.00 (2286.0)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2090
YS2090
LT2090S or F
LT2090S or F
EZB2090R
EZB2090R
EZT2090S or F
EZT2090S or F
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
40 lugs with
through-






30
42
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
feed lugs 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F

41





54
60
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
42 1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2 Add 8.00 inches (203.2 mm) for SPD.
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
43 4 JD, HJD, JDC is same space requirement as 400 A DK, HKD, KDC.

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.1-5
January 2018 Pow-R-Line 1a
Sheet 22 027
Technical Data and SpecificationsPow-R-Line 1a

Table 22.1-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


Panelboard Types and Mounting Position Maximum Box Dimensions 123 Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Sub-Feed Circuits 23
Breaker Including
Provisions
400 A (Continued) 24
Main DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker HKD, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with
through-
KDC,
LHH




42
48
72.00 (1828.8)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2090
LT2072S or F
LT2090S or F
EZB2072R
EZB2090R
EZT2072S or F
EZT2090S or F
25
feed lugs (V) 54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 26
Main lugs EDB, EDS, EDB, EDS, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 A ED, EDH, ED, EDH, 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or 100 A EDC, FD, EDC, FD, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 27
sub-feed HFD, FDC, HFD, FDC, 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker FDE, FDE,
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or dual
sub-feed
HFDE,
FDCE
HFDE,
FDCE
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 28
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker (V) (V)
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main DK, KD, EDB, EDS, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 29
breaker HKD, ED, EDH, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 225 A KDC, LHH EDC, FD, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or 100 A
sub-feed
(V) HFD, FDC,
FDE,
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 30
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker HFDE,
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
FDCE
(V)
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 31
Main DK, KD, EDB, EDS, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker HKD, ED 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 225 A KDC, LHH EDH, EDC 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 32
or 100 A (V) FD, HFD, 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
dual FDC, FDE,
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed
breaker
HFDE,
FDCE
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 33
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
(V)
Main lugs DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 400 A HKD, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
34
sub-feed KDC, LHH 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 35
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main DK, KD, DK, KD, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 36
breaker HKD, KDC, HKD, 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
with 400 A LHH KDC, LHH 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed
breaker
(V) (V)

48
54
90.00 (2286.0)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2090
YS2090
LT2090S or F
LT2090S or F
EZB2090R
EZB2090R
EZT2090S or F
EZT2090S or F
37
600 A
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 38
lugs 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 39
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F






72
84
72.00 (1828.8)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2090
LT2072S or F
LT2090S or F
EZB2072R
EZB2090R
EZT2072S or F
EZT2090S or F
40
Main LGE, LGH, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker LGC, LGU
(V)


30
42
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
41
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F




54
60
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
42
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
43
2 Add 8.00 inches (203.2 mm) for SPD.
3 28.00 inch (711.2 mm) optional width is available for panelboards with high circuit counts.

CA08104001E For more information, visit: www.eaton.com/consultants


22.1-6 Panelboards
Pow-R-Line 1a January 2018
Sheet 22 028
Technical Data and SpecificationsPow-R-Line 1a

Table 22.1-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


22 Panelboar Types and Mounting Position Maximum Box Dimensions 123 Catalog Number
d (H) = Horizontal / (V) = Vertical Number
Types Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
23 Breaker Breaker Sub-Feed Circuits
Breaker Including
Provisions
24 600 A (Continued)
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
lugs with 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
25 through-
feed lugs






42
48
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
26 72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main LGE, LGH, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
27 breaker LGC, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with LGU 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
through- (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
28 feed lugs
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
29 Main lugs EDB, EDS, EDB, EDS, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 A ED ED, EDH, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or 100 A EDH, EDC EDC, FD, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
30 sub-feed
breaker
FD, HFD,
FDC, FDE,
HFD, FDC,
FDE,
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
or dual HFDE, HFDE,
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed FDCE FDCE
31 breaker (V) (V)
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F

Main LGE, LGH, EDB, EDS, EDB, EDS, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker LGC, LGU ED, EDH, ED, EDH, 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
32 with 225 A (V) EDC, FD, EDC, FD, 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
or 100 A HFD, FDC, HFD, FDC,
sub-feed FDE, FDE,
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
33 breaker
or dual
HFDE,
FDCE
HFDE,
FDCE
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed (V) (V)
breaker
34 Main lugs DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 400 A HKD, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed KDC, LHH 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
35 breaker (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
36 72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main LGE, LGH, DK, KD, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker LGC, LGU HKD, 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
37 with 400 A (V)
sub-feed
KDC, LHH
(V)
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
38 Main lugs LGE, LGH, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 600 A LGC, LGU 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed (V) 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
39 breaker 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
40 72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main LGE, LGH, LGE, LGH, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker LGC, LGU LGC, LGU 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
with 600 A (V) (V) 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
41 sub-feed
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
42 1
2
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
Add 8.00 inches (203.2 mm) for SPD.
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.2-1
January 2018 Pow-R-Line 2a
Sheet 22 029
General DescriptionPow-R-Line 2a

Pow-R-Line 2a Mains Main Lugs Only


22
For available mains, refer to Table 22.2-1. The short-circuit rating of the MLO
assembled panelboard will be fully
The GHB main breaker is horizontally rated based upon the lowest rated
mounted, same as branch breakers. branch device or may be series rated 23
All other main breakers are vertically with an approved upstream device.
mounted.
Branch Circuits
Main lugs only ampere ratings: 24
100, 225 and 400.
For available branch devices, refer to
Table 22.2-2. Main Circuit Breakers 25
The short-circuit rating shown is that
of the main breaker only. The short
circuit rating of the assembled panel- 26
board is the rating of the lowest fully
rated main or branch device or the
Pow-R-Line 2a rating of an approved series rated 27
combination.
General Description
Table 22.2-1. Main Circuit Breakers 28
Panelboard Ratings Breaker Frame Breaker Interrupting Rating (kA Symmetrical)
(Amperes) Type
Voltage 240 Vac 480Y/277 Vac 125/250 Vdc 29
240 Vac maximum 100 GHB 1 65 14 14
480Y/277 Vac maximum 100 EHD 18 14 10
Note: PRL2a panelboards are suitable for 150 FDB 18 14 10 30
use on three-phase, three-wire applications 225 FD, FDE 65 35 10
when derived from a three-phase, four-wire 225 HFD, HFDE 100 65 22
480Y/277 Vac service where the neutral is 225 FDC, FDCE 200 100 22 31
not brought to the panelboard. For three- 225 ED 65
phase, three-wire 480 Vac Delta services use 250 EDH 100
a PRL3a panelboard. 250 EDC 200 32
250 JD 65 35 10
250 Vdc maximum 250 HJD 100 65 22

Main Lugs
250 JDC 200 100 22
33
400 DK 65 10
100600 A 400 KD 65 35 10
400 HKD 100 65 22
Main Breakers 400 LHH 100 65 34
400 KDC 200 100 22
100600 A
600 LGE 65 35 22
Branch Breakers 600 LGS 65 50 22 35
600 LGH 100 65 42
15100 A (bolt-on) 600 LGC, LGU 200 100 42
Short-Circuit Current Ratings (Symmetrical) 1 For use on 480Y/277 Vac systems only. 36
240 Vac: 65 kA fully rated
Table 22.2-2. Branch Circuit Breakers
240 Vac: 100200 kA series rated
Breaker Ampere Number Interrupting Rating (kA Symmetrical) 37
480Y/277 Vac: 14 kA fully rated Type Rating of Poles 120 Vac 240 Vac 277 Vac 480Y/277 Vac 125/250 Vdc
480Y/277 Vac: 22150 kA series rated
250 Vdc: 10 kA and 14 kA fully rated GHB 2 15100 1 65 14 14 38
GHB 2 15100 2, 3 65 14 14
Service GHQ 1520 1 65 14

Three-phase, four-wire 208Y/120 V HGHB 1530 1 65 25 39


GHQRSP 23 1520 1, 2 65 65 14 14
and 240/120 V Delta and 480Y/277 V GHBGFEP 1560 1 14
Single-phase, three-wire 120/240 V 2 For use on 480Y/277 Vac systems only. 40
Single-phase, two-wire 120 V 3 Solenoid operated breaker.
Three-phase, three-wire 208
and 240 V Series Rated Combinations 41
Two-wire 125 Vdc Refer to series rating tables beginning
Two-wire 250 Vdc on Page 22.0-14 for the approved
series rated combinations available for 42
Suitable for service entrance the branch circuit breakers listed in
applications when specified. Table 22.2-2.
43

CA08104001E For more information, visit: www.eaton.com/consultants


22.2-2 Panelboards
Pow-R-Line 2a January 2018
Sheet 22 030
Technical DataPow-R-Line 2a

Technical Data Shunt Trips Box Sizing and Selection


22 Shunt trips are available on breakers. Box size for all Type 1 panelboards are
Bussing GHB breakers with shunt trips require available from Table 22.2-6.
100400 A: Tin-plated aluminum is three-pole frame.
23 standard, copper is available Instructions
as an option. Ground Bar
Standard bolted in box. Aluminum 1. Using description on the required
24 Boxes is standard. Copper is available as panelboard, select the rating and
Boxes are made from code-gauge an option. type of mains required.
galvanized steel.
25 Enclosures 2. Count total number of branch
Blank ends are supplied as standard, Types 1, 12, 3R, 4/4X. circuit poles (including spaces)
knockouts are available upon request. required in the panelboard. Do
26 Surge Protective Device (SPD) not count main breaker poles.
EZ Trim
Integrated onto panelboard chassis. Convert two- or three-pole branch
Trims are made from code-gauge steel breakers to single-poles. i.e.,
For complete product description and
and painted ANSI 61 gray. three-pole breaker, count as
27 available ratings, refer to Tab 34.
three poles.
All panelboards have door-in-door as
standard with multi-point catch and Note: For horizontal mounted mains
28 lock, and concealed mounting (GHB Type), use main lug table, include
hardware. space in branch section for mains.

29 Modifications 3. Using correct table, type of mains


Table 22.2-3. Sub-Feed Lugs (Main Lugs Only) and ampere rating per Step 1, find
Amperes Panel Height total number of poles.
30 Addition
Note: Where total number of poles (Step 2)
100 0 Inches (0 mm) fall between number in table, use the next
225 0 Inches (0 mm) higher number.
31
4. Read box size across columns to
Table 22.2-4. Through-Feed Lugs
the right.
32 Amperes Information
Top and Bottom Gutters (minimum)
100 See Table 22.2-6 5.50 inches (139.7 mm).
33 225 See Table 22.2-6
400 See Table 22.2-6 Side Gutters
600 See Table 22.2-6
20.00-inch (508.0 mm) wide box:
34 Table 22.2-5. Sub-Feed Breakers 5.50 inches (139.7 mm).
(One Per Panel)
35 Ampere
Rating
Breaker
Type
Interrupting Rating
(kA Symmetrical)
240 V 480Y/277 V
36 150 FDB 18 14
225 FD 65 35
225 HFD 100 65
37 225 FDC 200 100
225 ED 65
225 EDH 100
38 225 EDC 200
250 JD 65 35
250 HJD 100 65
39 250 JDC 200 100
400 KD 65 35
400 HKD 100 65
40 400 KDC 200 100

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.2-3
January 2018 Pow-R-Line 2a
Sheet 22 031
Technical DataPow-R-Line 2a

Table 22.2-6. Type 1 PanelboardsDimensions in Inches (mm)


Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Sub-Feed Circuits 23
Breaker Including
Provisions
100 A 24
Main GHB 15 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker (H) 27 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F




39
42
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
25
Main 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
lugs





30
42
36.00 (914.4)
42.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2042
LT2036S or F
LT2042S or F
EZB2036R
EZB2042R
EZT2036S or F
EZT2042S or F
26
48 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F






54
60
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
27
72 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EHD, FDB, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
28
breaker FD, FDE 30 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
HFD, FDC, 42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
HFDE, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 29
FDCE
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
(V)
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 30
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main lugs EHD, FDB, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 100 A FD, FDE 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 31
through- HFD, FDC, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
feed lugs HFDE, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or sub-feed FDCE
breaker (V)


54
60
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
32
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EHD, FDB, EHD, FDB, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
33
breaker FD, FDE FD, FDE 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 100 A HFD, FDC, HFD, FDC, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- HFDE, HFDE, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 34
feed lugs FDCE FDCE
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or sub-feed (V) (V)
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 35
225 A
Main
lugs 4






18
30
36.00 (914.4)
36.00 (914.4)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2036
LT2036S or F
LT2036S or F
EZB2036R
EZB2036R
EZT2036S or F
EZT2036S or F
36
42 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
48 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
54 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
37
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
72 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 38
Main EHD, FDB, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker 4 FD, FDE 30 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
HFD, FDC,
HFDE,




42
48
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
LT2048S or F
LT2060S or F
EZB2048R
EZB2060R
EZT2048S or F
EZT2060S or F
39
FDCE
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
(V)




60
72
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
40
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
1
2
Smaller panelboard box sizes are available if required. Contact Eaton for application information. 41
Add 8.00 inches (203.2 mm) for SPD and metering.
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
4 JD, HJD, JDC is same space requirement as 400 A DK, HKD, KDC. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.2-4 Panelboards
Pow-R-Line 2a January 2018
Sheet 22 032
Technical DataPow-R-Line 2a

Table 22.2-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


22 Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
23 Breaker Breaker Sub-Feed Circuits
Breaker Including
Provisions
24 225 A
Main lugs EHD, FDB, 18 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
with 225 A FD, FDE 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
25 through-
feed lugs
HFD, FDC,
HFDE,


42
48
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
or sub-feed FDCE
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker 4 (V)
26

60
72
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
84 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F

27 Main
breaker
EHD, FDB,
FD, FDE
EHD, FDB,
FD, FDE


18
30
42.00 (1219.2)
48.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2042
YS2048
LT2042S or F
LT2048S or F
EZB2042R
EZB2048R
EZT2042S or F
EZT2048S or F
with 225 A HFD, FDC, HFD, FDC, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- HFDE, HFDE, 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
28 feed lugs FDCE FDCE
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or sub-feed (V) (V)
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 4
72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
29 Main lugs EHD, FDB, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 225 A FD, FDE 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
dual HFD, FDC, 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 sub-feed HFDE, 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 4 FDCE
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
(V)
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
31 72
84
90.00 (2286.0)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2090
YS2090
LT2090S or F
LT2090S or F
EZB2090R
EZB2090R
EZT2090S or F
EZT2090S or F
Main EHD, FDB, EHD, FDB, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
32 breaker
with 225 A
FD, FDE
HFD, FDC,
FD, FDE
HFD, FDC,
30
42
60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
dual HFDE, HFDE,
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed FDCE FDCE
33 breakers 4 (V) (V)
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F

400 A
34 Main 18 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
lugs 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
35 48 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
60 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
36 72 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2 Add 8.00 inches (203.2 mm) for SPD and metering.
37 3 28.00 inches (711.2 m) optional width is available for panelboards with high circuit counts.
4 JD, HJD, JDC is same space requirement as 400 A DK, HKD, KDC.

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.2-5
January 2018 Pow-R-Line 2a
Sheet 22 033
Technical DataPow-R-Line 2a

Table 22.2-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Sub-Feed Circuits 23
Breaker Including
Provisions
400 A (Continued) 24
Main DK, KD, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
breaker HKD, 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
KDC, LHH
(V)




42
48
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
25
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 26
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 27
lugs with 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
feed lugs 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
28
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 29
Main DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker HKD, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with KDC, LHH 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 30
through- (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
feed lugs
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 31
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main lugs EHD, FDB, EHD, FDB, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 A FD, FDE FD, FDE 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 32
or 100 A HFD, FDC, HFD, FDC, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed HFDE, HFDE, 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker
or dual
FDCE
(V)
FDCE
(V)
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 33
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 34
Main DK, KD, EHD, FDB, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker HKD, FD, FDE 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 225 A
or 100 A
KDC, LHH
(V)
HFD, FDC,
HFDE,


42
48
72.00 (1828.8)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2090
LT2072S or F
LT2090S or F
EZB2072R
EZB2090R
EZT2072S or F
EZT2090S or F
35
sub-feed FDCE
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker (V)


60
72
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
36
Main DK, KD, EHD, FDB, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker HKD, FD, FDE 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 225 A KDC, LHH HFD, FDC, 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 37
or 100 A (V) HFDE, 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
dual FDCE
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed (V)
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 38
breaker
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main lugs DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 400 A HKD, 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 39
sub-feed KDC, LHH 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 40
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main DK, KD, DK, KD, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 41
breaker HKD, HKD, 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
with 400 A KDC, LHH KDC, LHH 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed
breaker
(V) (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 42
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2 Add 8.00 inches (203.2 mm) for SPD and metering. 43
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.

CA08104001E For more information, visit: www.eaton.com/consultants


22.2-6 Panelboards
Pow-R-Line 2a January 2018
Sheet 22 034
Technical DataPow-R-Line 2a

Table 22.2-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


22 Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
23 Breaker Breaker Sub-Feed Circuits
Breaker Including
Provisions
24 600 A
Main 18 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
lugs 30 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
25





42
48
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
54 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
26





60
72
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F

27 Main
breaker
LGE, LGH,
LGC, LGU


18
30
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
(V) 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
28 54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
29 84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
lugs with 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 through- 42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
feed lugs 48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
31 60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
84 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
32 Main
breaker
LGE, LGH,
LGC, LGU


18
30
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
with (V) 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
through- 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
33 feed lugs
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
34 Main lugs EHD, FDB, EHD, FDB, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 A FD, FDE FD, FDE 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or 100 A HFD, FDC, HFD, FDC, 42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
35 sub-feed HFDE, HFDE, 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker FDCE FDCE
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
or dual (V) (V)
60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
36 sub-feed
breaker
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F

Main lugs DK, KD, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
37 with 400 A
sub-feed
HKD,
KDC, LHH


30
42
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
breaker (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
38 60 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
72 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main LGE, LGH, DK, KD, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
39 breaker LGC, LGU HKD, 30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
with 400 A (V) KDC, LHH 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed (V) 48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
40 breaker 54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2 Add 8.00 inches (203.2 mm) for SPD and metering.
41 3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.2-7
January 2018 Pow-R-Line 2a
Sheet 22 035
Technical DataPow-R-Line 2a

Table 22.2-6. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed Dual of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Sub-Feed Circuits 23
Breaker Including
Provisions
600 A (Continued) 24
Main lugs LGE, LGH, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 600 A LGC, LGU 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed
breaker
(V)

42
48
72.00 (1828.8)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2090
LT2072S or F
LT2090S or F
EZB2072R
EZB2090R
EZT2072S or F
EZT2090S or F
25
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F


60
72
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
26
Main LGE, LGH, LGE, LGH, 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker
with 600 A
LGC, LGU LGC, LGU
(V) (V)


30
42
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
27
sub-feed
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker
1
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
28
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2 Add 8.00 inches (203.2 mm) for SPD and metering.
3 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts. 29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.2-8 Panelboards
January 2018
Sheet 22 036

This page intentionally left blank.


22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.3-1
January 2018 Pow-R-Line 3a
Sheet 22 037
General DescriptionPow-R-Line 3a

Pow-R-Line 3a Mains Main Lugs Only


22
For available mains, refer to Table 22.3-1. The short-circuit rating of the MLO
assembled panelboard will be fully
Main breakers, 100, 150 and 225 A, rated based upon the lowest rated
Types EHD, FD, FDE, FDB, HFD, HFDE branch device or may be series rated 23
and FDC may be horizontally mounted, with an approved upstream device.
same as branch breakers. All other
main breakers are vertically mounted. Main lugs only ampere ratings: 24
100, 250, 400, 600 and 800.
Branch Circuits
For available branch devices, refer Main Circuit Breakers 25
to Table 22.3-2. The short-circuit rating shown is that
of the main breaker only. The short-
circuit rating of the assembled panel- 26
board is the rating of the lowest fully
rated main or branch device, or the
rating of an approved series rated 27
combination.
Pow-R-Line 3a Table 22.3-1. Main Circuit Breakers 28
General Description Breaker Frame Breaker Interrupting Rating (kA Symmetrical)
(Amperes) Type 240 Vac 480 Vac 600 Vac 250 Vdc
Panelboard Ratings
100 EHD 18 14 10
29
Voltage 100 FCL 200 150
100 FB-P 200 200 200 1
240 Vac maximum
150 FDB 18 14 14 10
30
480 Vac maximum
225 FD, FDE 65 35 18 10
600 Vac maximum 225
225
HFD, HFDE
FDC, FDCE
100
200
65
100
25
35
22
22
31
250 Vdc maximum
225 EDB 22
Main Lugs 225 EDS 42

100800 A
225 ED 65 32
225 EDH 100
225 EDC 200
Main Breakers
100600 A
250
250
JD
HJD
65
100
35
65
18
25
10
22
33
250 JDC 200 100 35 22
Branches
240 Vac 15225 A
400
400
DK
KD
65
65

35

25
10
10
34
480 Vac 15225 A 400 HKD 100 65 35 22
400 LHH 100 65
600 Vac 15225 A (bolt-on) 400 KDC 200 100 65 22 35
400 LCL 200 200
Interrupting Capacity (Symmetrical) 400 LA-P 200 200 200 1

240 Vac: 10200 kA fully rated 600 LGE 65 35 18 22 36


240 Vac: 22200 kA series rated 600 LGH 100 65 35 22
400 LGC 200 100 50 42
480 Vac: 14100 kA fully rated 400 LGU 200 150 65 50
480 Vac: 22150 kA series rated 600 LD 65 35 25 22 37
600 HLD 100 65 35 25
250 Vdc: 1022 kA fully rated 600 LDC 200 100 50 25
Service
600 CLD 2 65 35 25 22 38
600 CHLD 2 100 65 35 25
Three-phase, four-wire 208Y/120 V, 600 CLDC 2 200 100 50 25
240/120 V delta and 480Y/277 V 1 100,000 AIC based on NEMA test procedure. 39
2
Single-phase, three-wire 120/240 V 100% rated breaker. Requires copper bus. Not available in Type 12, 4 or 4X enclosure.
Single-phase, two-wire 120 V
Three-phase, three-wire 240, 480 40
and 600 V
Two-wire 125 Vdc 41
Two-wire 250 Vdc
Suitable for service entrance
applications when specified. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.3-2 Panelboards
Pow-R-Line 3a January 2018
Sheet 22 038
General DescriptionPow-R-Line 3a

Series Rated Combinations Table 22.3-2. Branch Circuit Breakers


22 Refer to series rating tables beginning Breaker Ampere Number Interrupting Rating (kA Symmetrical) Volts
Type Rating of Poles 120 120/240 240 480 600 125 250
on Page 22.0-14 for the approved
Vac Vac Vac Vac Vac Vdc Vdc
23 series rated combinations available
for the branch circuit breakers listed BAB 1570 1 10
in Table 22.3-2. BAB 15100 2 10
24 BAB 15100 2, 3 10
BAB-D 1 1560 1, 2 10 10
BAB-C 2 1530 1, 2 10 10
BABRP 3 1530 1, 2 10 10
25 BABRSP 3 1530 1, 2 10 10
QBGF, QBGFEP 1550 4 1, 2 10 10
QBCAF 5 1520 1 10 10
26 QBHW 1570 1 22
QBHW 15100 2 22
QBHW 15100 2, 3 22
27 QBHGF, QBHGFEP 1550 4 1, 2 22 22
QBHCAF 5 1520 1 22 22
GHB 67 15100 1 65 14 14
28 GHB 6 15100 2, 3 65 14 14
GHQ 67 1520 1 65 14
HGHB 67 1530 1 65 25
29 GHBGFEP 1560 1 65 14 14
GHQRSP 367 1520 1, 2 65 65 65 14
EHD 7 15100 1 14 14 10
30 EHD 15100 2, 3 18 14 10
FDB 15150 2, 3 18 14 14 10

31 FD 7
FD, FDE
15100
15225
1
2, 3




65
65
35
35

18
10


10
HFD 7 15100 1 65 65 10
HFD, HFDE 15225 2, 3 100 65 25 22
32 FDC, FDCE 15225 2, 3 200 100 35 22
EDB 100225 2, 3 22 10
33 EDS
ED
100225
100225
2, 3
2, 3




42
65




10
10


EDH 100225 2, 3 100 10
EDC 100225 2, 3 200 10
34 1 HID (High Intensity Discharge) rated breaker.
2 Switching neutral breaker. Single-pole device requires two-pole space, two-pole device requires
three-pole space.
35 3 Solenoid operated breaker.
4 50A is two-pole only.
5 Arc fault breaker.
36 6 For use on 480Y/277 Vac systems only.
7 Single-pole breaker rated 277 Vac.

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.3-3
January 2018 Pow-R-Line 3a
Sheet 22 039
Technical Data and SpecificationsPow-R-Line 3a

Technical Data and Specifications Shunt Trips Ground Bar


Shunt trips are available on breakers. Standard bolted in box. Aluminum 22
Bussing BAB and QBHW require one additional is standard. Copper is available as
Tin-plated aluminum is standard, pole space for shunt trip, i.e., single- an option.
copper is available as an option. pole is two-pole size, two-pole is 23
Density rated bus is also available three-pole size and three-pole is Enclosures
as an option. four-pole size. GHB breakers with Types 12, 3R, 4/4X.
shunt trip require three-pole frame. 24
Boxes Note: Type 12, 3R, 4/4X enclosures are
Remote Control Switches not available for 800 A applications.
Boxes are made from code-gauge
galvanized steel. ASCO 920 can be bus connected 25
Top and Bottom Gutters (Minimum)
and mounted in panel for main or
Blank ends are supplied as standard, sub-main (split-bus) applications. All mains: 5.50 inches (139.7 mm).
knockouts are available upon request.
Side Gutters (Minimum)
26
Time Clocks
EZ Trim 4.00 inches (101.6 mm).
Time clocks are mounted at the top or
Trims are made from code-gauge steel bottom of the panel, either in extended 27
and painted ANSI 61 gray. end gutters or in a separate enclosure
All panelboards have door-in-door under a separate door.
as standard with multi-point
28
Table 22.3-6. Type 1 Box SizesDimensions in Inches (mm)
catch and lock, and concealed
Maximum Box Dimensions
mounting hardware.
Panel Height Height Width Depth 29
Modifications X Units

Table 22.3-3. Sub-Feed Lugs (Main Lugs Only) 100400 A


14X 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) 30
Ampere Rating Added Panel Height
23X 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1)
31X 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1)
100 0X
250 1X 40X
53X
72.00 (1828.8)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
31
Table 22.3-4. Through-Feed Lugs 600800 A

Ampere Rating Added Panel Height


23X 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1) 32
31X 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
100 2X 40X 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
250
400
5X
8X
53X 90.00 (2286.0) 28.00 (711.2) 5.75 (146.1)
33
600 8X

Note: Sub-feed breakers and through-feed 34


lugs cannot be supplied in the same panel.

Table 22.3-5. Sub-Feed Breakers (One Per Panel) 35


Ampere Breaker Interrupting Added
Rating Type Rating Panel
(kA Symmetrical) Height 36
240 V 480 V

225/250 JD 65 35 14X
225/250 HJD 100 65 37
225/250 JDC 200 100
400 KD 65 35 15X
400 HKD 100 65 38
400 KDC 200 100
600 LD 65 35 17X
600
600
HLD
LDC
100
200
65
100
39
Note: Sub-feed breakers and through-feed
lugs cannot be supplied in the same panel. 40
Note: Twin mounted J-Frame sub-feed
breakers are available. Requires 20X panel
height addition. 41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.3-4 Panelboards
Pow-R-Line 3a January 2018
Sheet 22 040
Technical Data and SpecificationsPow-R-Line 3a

Panel Layout Instructions Table 22.3-7. Layout Example


22 1. Select: Poles
3X-6 BAB
a. Required mains (lugs or 5X-12 QBGF
23 breaker). 8X-18 QBHW
10X-24 QBHGF
b. Neutral where required. 13X-30 QBGFEP
c. Branch circuits as required. QBCAF
24 GHB
2. Layout panel as shown in 15X-36 GHQ
Table 22.3-7, using appropriate 18X-42 HGHB
25 X dimensions.
QBHGF
QBHCAF
GHBGFEP
3. Using total X units (panel height) GHQRSP
26 find box height in inches from
Multiple selections 1
Table 22.3-6. (When total X units may be used on panel.
come out to an uneven number,
27 use next highest number, i.e., if Single-pole Single-pole 1X
2X
EHD
FDB
total X comes out 25X, use 31X.) Two-pole Two-pole
3X FD,FDE (150 A
Single-pole Three-pole HFD, HFDE maximum)
28 Surge Protective Device (SPD) Two-pole FDC
Integrated onto panelboard chassis.
Neutral selection 2 5X 100, 250 A
For complete product description and
8X 400, 600, 800 A
29 available ratings, refer to Tab 34. 11X 800 A with through-feed lug
Two- and three-pole 2X, EHD, FDB, FD, HFD, FDC, FDE, HFDE
3X, EDB, EDS, ED, EDH, FDE, EDC 3, FD, HFD, FDC, HFDE
30 (225 A maximum)
Main lug section 2X 100 A
5X 250 A
31 8X 400, 600 A
14X800 A
Surge protective device 4

32 Horizontal 2X two-pole
mounting EHD, FDB, FD, HFD, FDC 5, EDB, EDS, ED, EDH, EDC
3X three-pole
33 Main breaker
EHD, FDB, FD, HFD, FDE, FDC 5, HFDE, EDB, EDS, ED, EDH, EDC

section
7X EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC, FDE, HFDE
34 Vertically 9X FCL, FB-P 6
mounted 14X JD, HJD, JDC
15X DK, KD, HKD, KDC, LHH
35 17X LD, HLD, LDC, CLD, CHLD, CLDC
18X LGE, LGH, LGC, LGU
21X LCL 7, LA-P 67
1 GHB, GHQ and HGHB breakers cannot be mixed on same connector as BAB, QBHW.
36 2 Sizing shown is for 100% rated neutral with
mechanical lugs. For 200% rated neutral with mechanical lugs, add 3X. For special lug
arrangements, contact Eaton.
37 3 Maximum of six breakers per panel.
4 Add 5X for 200 kA maximum SPD.
5 Horizontally mounted 15225 A main
38 breakers EHD, FDB, FD, HFD, FDC, may be furnished as branch breaker construction. Branch
breakers single-, two- or three-pole as required, may be located opposite these main breakers
(150 A maximum).
6 FB-P and LA-P top mounting only.
39 7 LCL, LA-P main breaker requires 6.50 inch (165.1 mm) deep box.

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.3-5
January 2018 Pow-R-Line 3E
Sheet 22 041
General DescriptionPow-R-Line 3E

Pow-R-Line 3E Mains Main Lugs Only


22
For available mains, refer to Table 22.3-8. The short-circuit rating of the MLO
assembled panelboard will be fully
Main breakers, 100, 150 and 225 A, rated based upon the lowest rated
Types EG, EHD, FD, FDE, FDB, HFD, branch device or may be series rated 23
HFDE and FDC may be horizontally with an approved upstream device.
mounted, same as branch breakers.
All other main breakers are vertically Main lugs only ampere ratings: 24
mounted. 100, 250, 400 and 600.
Branch Circuits Main Circuit Breakers 25
For available branch devices, refer The short-circuit rating shown is that
to Table 22.3-9. of the main breaker only. The short-
circuit rating of the assembled 26
panelboard is the rating of the
lowest fully rated main or branch
device, or the rating of an approved 27
series rated combination.
Pow-R-Line 3E Table 22.3-8. Main Circuit Breakers 28
General Description Breaker Frame Breaker Interrupting Rating (kA Symmetrical)
(Amperes) Type 240 Vac 480 Vac 250 Vdc
Panelboard Ratings
125 EGB 1 35 18 10
29
Voltage 125 EGS 1 100 35 35
125 EGH 1 200 65 42
240 Vac maximum
225 EDB 22
30
480 Vac maximum 225 EDS 42
250 Vdc maximum 225 ED 65
225 EDH 100 31
Main Lugs 225 EDC 200
225 FD, FDE 65 35 10
100600 A 225
225
HFD, HFDE
FDC
100
200
65
100
22
22
32
Main Breakers
400 DK 65
100600 A 400 KD 65 35 10
400 HKD 100 65 22 33
Branches 400 LHH 100 65
240 Vac 15125 A 400 KDC 200 100 22
480 Vac 15125 A 600 LGE 65 35 22 34
600 LGH 100 65 22
Interrupting Capacity (Symmetrical) 1 Horizontally/branch mounted.
240 Vac: 25100 kA fully rated 35
240 Vac: 65100 kA series rated
Table 22.3-9. Branch Circuit Breakers
Breaker Ampere Number Interrupting Rating (kA Symmetrical)
480 Vac: 1865 kA fully rated
Type Rating of Poles 120 Vac 2 240 Vac 277 Vac 2 480 Vac 250 Vdc
36
480 Vac: 65100 kA series rated
EGB 15125 1, 2, 3 25 25 18 18 10
Service EGS 15125 1, 2, 3 85 85 35 35 35 37
Three-phase, four-wire 208Y/120 V, EGH 15125 1, 2, 3 100 100 65 65 42
240/120 V delta and 480Y/277 V 2 Applicable to single-pole devices only.
Single-phase, three-wire 120/240 V 38
Series Rated Combinations
Single-phase, two-wire 120 V
Refer to series rating tables beginning
Three-phase, three-wire 39
on Page 22.0-14 for the approved
240 and 480 V series rated combinations available
Two-wire 125 Vdc for the branch circuit breakers listed
Two-wire 250 Vdc in Table 22.3-9. 40
Suitable for service entrance
applications when specified. 41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.3-6 Panelboards
Pow-R-Line 3E January 2018
Sheet 22 042
Technical Data and SpecificationsPow-R-Line 3E

Technical Data and Specifications Modifications Box Sizing and Selection


22 Table 22.3-10. Through-Feed Lugs, Box size for all Type 1 panelboards are
Bussing Sub-Feed Lugs (Main Lug Panels Only) available from Table 22.3-4.
100600 A: Tin-plated aluminum and Sub-Feed Breakers (One Per Panel)
23 is standard, copper is available Ampere Information Instructions
as an option. Rating 1. Using description on the required
24 panelboard, select the rating and
Boxes All Table 22.3-11
type of mains required.
Boxes are made from code-gauge
galvanized steel. Shunt Trips 2. Count total number of branch
25 Shunt trips are available on two- and circuit poles (including spaces)
Blank ends are supplied as standard, three-pole breakers. required in the panelboard. Do
knockouts are available upon request. not count main breaker poles.
26 EZ Trim
Ground Bar Convert two- or three-pole branch
Standard bolted in box. Aluminum breakers to single-poles, i.e.,
Trims are made from code-gauge steel is standard, copper is available as three-pole breaker, count as
27 and painted ANSI 61 gray. an option. three poles.
All panelboards have door-in-door Enclosures Note: For horizontal mounted mains
as standard with multi-point (GHB Type), use main lug table, include
28 catch and lock, and concealed
Types 1, 12, 3R, 4/4X. space in branch section for mains.
mounting hardware. Surge Protective Device (SPD)
3. Using correct table, type of mains
29 Integrated onto panelboard chassis. and ampere rating per Step 1, find
For complete product description total number of poles.
and available ratings, refer to Tab 34.
30 Note: Where total number of poles (Step 2)
fall between number in table, use the next
higher number.
31 4. Read box size across columns to
the right.
32 Top and Bottom Gutters (Minimum)
5.50 inches (139.7 mm).
33 Side Gutters
20.00-inch (508.0 mm) wide box:
5.50 inches (139.7 mm).
34

35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.3-7
January 2018 Pow-R-Line 3E
Sheet 22 043
Technical Data and SpecificationsPow-R-Line 3E

Table 22.3-11. Type 1 PanelboardsDimensions in Inches (mm)


Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Circuits 23
Including
Provisions
125 A 24
Main lugs 12 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F




24
30
42.00 (1219.2)
42.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2042
YS2042
LT2042S or F
LT2042S or F
EZB2042R
EZB2042R
EZT2042S or F
EZT2042S or F
25
36 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F




42
48
48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048
72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072
LT2048S or F EZB2048R EZT2048S or F
LT2072S or F EZB2072R EZT2072S or F
26
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
27
Main EHD, FDB, FD, 12 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker FDE, HFD, 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
FDC, HFDE, 24 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
FDCE 30 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F 28
(V)
36 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 29
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main lugs EHD, FDB, FD, 12 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
30
with 100 A FDE, HFD, FDC, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
through- HFDE, FDCE 24 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
feed lugs (V) 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 31
or sub-feed
36 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker
42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 32
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main EHD, FDB, FD, EHD, FDB, FD, 12 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F 33
breaker FDE, HFD, FDE, HFD, FDC, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 100 A FDC, HFDE, HFDE, FDCE 24 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
through- FDCE (V) 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F 34
feed lugs (V)
36 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or sub-feed
42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
breaker
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 35
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
60 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
225 A 36
Main lugs EHD, FDB, FD, 12 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
or main FDE 18 36.00 (914.4) 20.00 (508.0) 5.75 (146.1) YS2036 LT2036S or F EZB2036R EZT2036S or F
breaker 4 HFD, FDC, 24 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F 37
HFDE, FDCE 30 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F
(V)
36 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
42 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F 38
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main lugs EHD, FDB, FD, EHD, FDB, FD, 12 42.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2042 LT2042S or F EZB2042R EZT2042S or F 39
or main FDE, HFD, FDE, HFD, FDC, 18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
breaker FDC, HFDE, HFDE, FDCE 24 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
with 225 A FDCE (V) 30 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
through- (V) 40
36 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
feed lugs
42 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or sub-feed
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 4
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 41
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2
3
Add 8.00 inches (203.2 mm) for SPD and metering.
28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
42
4 JD, HJD, JDC is same space requirement as 400 A DK, HKD, KDC.

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.3-8 Panelboards
Pow-R-Line 3E January 2018
Sheet 22 044
Technical Data and SpecificationsPow-R-Line 3E

Table 22.3-11. Type 1 PanelboardsDimensions in Inches (mm) (Continued)


22 Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
23 Breaker Breaker Circuits
Including
Provisions
24 400 A
Main lugs 12 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
25



24
30
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
36 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
26



42
48
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F

27 Main
breaker
DK, KD, HKD,
KDC, LHH


12
18
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
(V) 24 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
28 36 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
29 54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main lugs EHD, FDB, FD, 12 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 FDE, HFD, FDC, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 or 100 A HFDE, FDCE 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
through- (V) 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
feed lugs
36 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or sub-feed
31 breaker
42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
32 Main
breaker
DK, KD, HKD,
KDC, LHH
EHD, FDB, FD,
FDE, HFD, FDC,
12
18
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
with 225 (V) HFDE, FDCE 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or 100 A (V) 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
33 through-
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
feed lugs
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
or sub-feed
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
34 breaker
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main Lugs DK, KD, HKD, 12 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 400 A KDC, LHH 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
35 sub-feed (V) 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
36 42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
37 Main DK, KD, HKD, DK, KD, HKD, 12 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
breaker KDC, LHH KDC, LHH 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 400 A (V) (V) 24 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
38 sub-feed
breaker
30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
39 48
54
90.00 (2286.0)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2090
YS2090
LT2090S or F
LT2090S or F
EZB2090R
EZB2090R
EZT2090S or F
EZT2090S or F
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
40 2
3
Add 8.00 inches (203.2 mm) for SPD and metering.
28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.3-9
January 2018 Pow-R-Line 3E
Sheet 22 045
Technical Data and SpecificationsPow-R-Line 3E

Table 22.3-12. Type 1 PanelboardsDimensions in Inches (mm)


Panelboard Types and Mounting Position Maximum Box Dimensions Catalog Number 22
Types (H) = Horizontal / (V) = Vertical Number in Inches (mm) 123
Main Sub-Feed of Branch Height Width Depth YS Box LT Trim EZ Box EZ Trim
Breaker Breaker Circuits 23
Including
Provisions
600 A 24
Main lugs 12 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F
18 48.00 (1219.2) 20.00 (508.0) 5.75 (146.1) YS2048 LT2048S or F EZB2048R EZT2048S or F




24
30
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
25
36 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F




42
48
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2072
LT2060S or F
LT2072S or F
EZB2060R
EZB2072R
EZT2060S or F
EZT2072S or F
26
54 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
Main
breaker
LGE, LGH,
LGC, LGU


12
18
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
LT2060S or F
LT2060S or F
EZB2060R
EZB2060R
EZT2060S or F
EZT2060S or F
27
(V) 24 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
36 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
28
42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
48 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 29
Main lugs EHD, FDB, FD, 12 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
with 225 FDE, HFD, FDC, 18 60.00 (1524.0) 20.00 (508.0) 5.75 (146.1) YS2060 LT2060S or F EZB2060R EZT2060S or F
or 100 A HFDE, FDCE 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 30
through- (V) 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
feed lugs
36 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or sub-feed
breaker
42 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 31
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main
breaker
EHD, FDB, FD,
FDE, HFD,
EHD, FDB, FD,
FDE, HFD, FDC,
12
18
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
32
with 225 FDC, HFDE, HFDE, FDCE 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
or 100 A FDCE (V) 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
through- (V)
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
33
feed lugs
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
or sub-feed
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
breaker
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 34
Main lugs DK, KD, HKD, 12 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 400 A KDC, LHH 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
sub-feed (V) 24 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 35
breaker 30 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F 36
48 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
54 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
Main DK, KD, HKD, DK, KD, HKD, 12 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F 37
breaker KDC, LHH KDC, LHH 18 72.00 (1828.8) 20.00 (508.0) 5.75 (146.1) YS2072 LT2072S or F EZB2072R EZT2072S or F
with 400 A (V) (V) 24 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
sub-feed
breaker
30 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
38
36 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
42 90.00 (2286.0) 20.00 (508.0) 5.75 (146.1) YS2090 LT2090S or F EZB2090R EZT2090S or F
48
54
90.00 (2286.0)
90.00 (2286.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
YS2090
YS2090
LT2090S or F
LT2090S or F
EZB2090R
EZB2090R
EZT2090S or F
EZT2090S or F
39
1 Smaller panelboard box sizes are available if required. Contact Eaton for application information.
2
3
Add 8.00 inches (203.2 mm) for SPD and metering.
28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts.
40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.3-10 Panelboards
January 2018
Sheet 22 046

This page intentionally left blank.


22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-1
January 2018 Pow-R-Line 4
Sheet 22 047
General DescriptionPow-R-Line 4

Pow-R-Line 4 Branches Bussing


22
Breakers 151200 A, bolt-on 2501200 A tin-plated aluminum is
Breakers 20600 A drawout standard; copper is available as an
option. Density rated bus is also
Fusible switches 301200 A, bolt-on
available as an option. 23
Short-Circuit Current Ratings (Symmetrical)
Main Lugs Only
240 Vac: 10200 kA fully rated 24
The short-circuit rating of the MLO
240 Vac: 22200 kA series rated assembled panelboard will be fully
480 Vac: 14200 kA fully rated rated based upon the lowest rated
480 Vac: 22150 kA series rated branch device or may be series rated 25
250 Vdc: 1022 kA fully rated with an approved upstream device.

Service Main lugs only ampere ratings: 26


250, 400, 600, 800 and 1200.
PRL4B PRL4F Three-phase, four-wire 208Y/120 V,
240/120 V delta and 480Y/277 V Main Circuit Breakers
Circuit Breaker Fusible 27
Panelboard Panelboard Single-phase, three-wire 120/240 V The short-circuit rating shown is that
Single-phase, two-wire 120 V of the main breaker only. The short-
General Description Three-phase, three-wire 120, 240, circuit rating of the assembled 28
480 and 600 V panelboard is the rating of the lowest
Panelboard Ratings fully rated main or branch device, or
Two-wire 125 Vdc
Voltage Two-wire 250 Vdc
the rating of an approved series rated 29
combination.
240 V, 480 V or 600 Vac maximum Two-wire 600 Vdc
600 Vdc maximum
Suitable for service entrance
30
Main Lugs applications when specified.
2501200 A 31
Main Breakers
2501200 A 32
Main Switches
2001200 A
33

34

35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-2 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 048
Technical Data and SpecificationsPow-R-Line 4

Table 22.4-1. Main Circuit BreakersType PRL4B and PRL4D Main Fusible Switches
22 Breaker Frame Breaker Interrupting Rating (kA Symmetrical) The short-circuit rating shown is that
Amperes Type 240 Vac 480 Vac 600 Vac 250 Vdc 600 Vdc of the main switch only. The short-
circuit rating of the assembled panel-
23 250 JD 65 35 18 10 boards is the rating of the lowest fully
250 HJD 100 65 25 22
250 JDC 200 100 35 22
rated main or branch device or the
rating of an approved series rated
24 250
250 1
LCL
HJDDC
200

200




42

35 combination. (Fuses are not included.)
350 NHH 100 65 35
400 and 600 A switches with shunt trip
400 DK 65 10
25 400 KD 2 65 35 25 10 will be rated 100 kA.
400 CKD 23 65 35 25 10
Note: Circuit breaker panelboards
400 LHH 100 65 35 42
are designated PRL4B. Fusible Switch
26 400 HKD 2 100 65 35 22
panelboards are designated PRL4F.
400 CHKD 23 100 65 35 22
400 KDC 2 200 100 65 22
400 LCL 2 200 200 Table 22.4-2. Main Fusible Switches
27 400 LA-P 200 200 200 2 Switch Fuse Interrupting Rating
400 1 HKDDC 42 65 Rating Class (kA Symmetrical)
600 LGE 4 65 35 18 22 Amperes
28 600 LGH 4 100 65 35 22
240 Vac 600 Vac 250 Vdc
600 LGC 4 200 100 50 42 Switches Rated 240 Vac, 250 Vdc
600 LGU 200 150 65 50 200 R, T 200 10
29 600
600
LD 2
CLD 23
65
65
35
35
25
25
22
22


400
600
R, T
R, T
200
200
10

600 HLD 2 100 65 35 25 800 L 200
600 CHLD 23 100 65 35 25 1200 L 200
30 600 LDC 2 200 100 50 25
Switches Rated 600 Vac
600 CLDC 3 200 100 50 25
600 1 HLDDC 42 35 200 R, J, T 200 200
31 800 MDL 2 65 50 25 22 400
600
R, J, T
R, J, T
200
200
200
200


800 CMDL 23 65 50 25 22
800 HMDL 2 100 65 35 25 800 L 200 200
800 CHMDL 23 100 65 35 25 1200 L 200 200
32 800 NB-P 200 200 200 5
800 1 HMDLDC 42 35
800 NGS 85 50 25
33 800 CNGS 85 50 25
800 NGH 100 65 35
800 CNGH 100 65 35
800 NGC 200 100 65
34 800 CNGC 200 100 65
1200 NGS 85 50 25
1200 CNGS 85 50 25
35 1200 NGH 100 65 35
1200 CNGH 100 65 35
1200 NGC 200 100 65
36 1200 CNGC 200 100 65
1 For use on DC systems only.
2 Available with integral ground fault protection.
37 3
4
100% rated circuit breaker.
Available in drawout configuration for PRL4D.
5 100,000 AIC based on NEMA test procedure.
38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-3
January 2018 Pow-R-Line 4
Sheet 22 049
Technical Data and SpecificationsPow-R-Line 4

Table 22.4-3. Branch Circuit Breakers


Breaker Ampere Number Interrupting Rating (kA Symmetrical) 22
Type Rating of Poles 120 Vac 120/240 Vac 240 Vac 480 Vac 600 Vac 125 Vdc 250 Vdc 600 Vdc

BAB 1570 1 10 23
BAB 15100 2 10
BAB 15100 2, 3 10
QBGF, QBGFEP 1550 1 1, 2 10 10 24
QBHW 1570 1 22
QBHW 15100 2 22
QBHW 15100 2, 3 22
QBHGF, QBHGFEP 1530 1, 2 22 22 25
GHB 23 15100 1 65 14 14
GHB 3 15100 2, 3 65 14 14
GHQ 23 1520 1 65 14
26
HGHB 23 1530 1 65 25
GHBGFEP 1560 1 65 27
EHD 15100 1 14 14 10
EHD 15100 2, 3 18 14 10
FDB 15150 2, 3 18 14 14 10 28
FD 2 15100 1 65 35 10
FD, FDE 4 15225 2, 3 65 35 18 10
HFD 2 15100 1 65 65 10 29
HFD, HFDE 4 15225 2, 3 100 65 25 22
HFDDC 5 15150 2,3 42 42 35
FDC, FDCE 15225 2, 3 200 100 35 22 30
FB-P 15100 2, 3 200 200 200 6
EDB 100225 2, 3 22 10
EDS 100225 2, 3 42 10 31
ED 100225 2, 3 65 10
EDH 100225 2, 3 100 10
EDC 100225 2, 3 200 10 32
JD 70250 2, 3 65 35 18 10
HJD 70250 2, 3 100 65 25 22
JDC
HJDDC 5
70250
70250
2, 3
2, 3




200

100

35
42
22
42

35
33
LCL 125250 2, 3 200 200
NHH
DK
150350
250400
3
2, 3


100


65
65

35


10


34
KD 100400 2, 3 65 35 25 10
CKD 7 100400 3 100 65 35 22
HKD 100400 2, 3 100 65 35 22 35
LHH 6 125400 2, 3 100 65 35 42
CHKD 7 100400 3 100 65 35 22
KDC 100400 2, 3 200 100 65 22
36
HKDDC 5 100400 2, 3 42 42 35
LCL 200400 2, 3 200 200
LA-P 125400 2, 3 200 200 200 6
LGE 250600 3 65 35 18 22
37
LGH 250600 3 100 65 35 22
LGC 250600 2, 3 200 100 50 42
LGU 250600 2, 3 200 150 65 50 38
LD 300600 2, 3 65 35 25 22
CLD 6 300600 3 65 35 25 22
HLD 300600 2, 3 100 65 35 25 39
CHLD 6 300600 3 100 65 35 25
LDC 300600 2, 3 200 100 50 25
CLDC 6 300600 3 200 100 50 25
HLDDC 5 300600 2, 3 42 42 35
40
1 50 A is two-pole only.
2 Single-pole breaker rated 277 Vac.
3 At 480 V, use on 480Y/277 Vac system only.
41
4 Three-pole only.
5 For use on DC systems only.
6 100,000 AIC based on NEMA test procedure. 42
7 100% rated breaker. Requires copper bus. K- and N-Frame breakers
require density rated copper bus. Not available in Type 12, 4 and
4X enclosures. 43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-4 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 050
Technical Data and SpecificationsPow-R-Line 4

Table 22.4-3. Branch Circuit Breakers (Continued)


22 Breaker Ampere Number Interrupting Rating (kA Symmetrical)
Type Rating of Poles 120 Vac 120/240 Vac 240 Vac 480 Vac 600 Vac 125 Vdc 250 Vdc 600 Vdc

23 MDL 300800 2, 3 65 50 25 22
CMDL 1 300800 3 65 50 25 22
HMDL 300800 2, 3 100 65 35 25
24 CHMDL
HMDLDC 2
300800
300800
3
2, 3




100

65

35
42
25
42

35
NGS 320800 2, 3 85 50 25
CNGS 2 320800 2, 3 85 50 25
25 NGH 320800 2, 3 100 65 35
CNGH 2 320800 2, 3 100 65 35
NGC 320800 2, 3 200 100 65
26 CNGC 2 320800 2, 3 200 100 65
NB-P 400800 2, 3 200 200 200
NBDC 2 7001200 2, 3 42 42 50
27 NGS 5001200 2, 3 85 50 25
CNGS 2 5001200 2, 3 85 50 25
NGH 5001200 2, 3 100 65 35
28 CNGH 2
NGC
5001200
5001200
2, 3
2, 3




100
200
65
100
35
65






CNGC 2 5001200 2, 3 200 100 65
1 100,000 AIC based on NEMA test procedure.
29 2 For use on dc systems only.

Table 22.4-4. Branch Fusible Switches (Fuses are not included) Circuit Breaker Trip Units
30 Switch Mounting Fuse Interrupting Rating (kA Symmetrical) Circuit breakers will have thermal-magnetic trip units with
Rating Class 240 V 600 V 250 Vdc the following exceptions:
Amperes
31 Switches Rated 240 Vac, 250 Vdc 100% rated breakers and all N-Frame breakers have
30/30 Twin R 200 10
Digitrip RMS 310 solid-state trip units as standard
K-, L- and M-Frame three-pole circuit breakers are option-
32 60/60
100/100
Twin
Twin
R
R
200
200


10
10 ally available with the Digitrip RMS 310 solid-state trip unit
200/200 Twin R, T 200 10
The trip function options for the Digitrip RMS 310 include
100 Single R 200 10
33 200 Single R, T 200 10 LS and LSI. Main circuit breakers can also include the LSG
400 Single R, T 200 10 and LSIG integral ground fault trip functions
600 Single R, T 200 Digitrip OPTIM trip units are not available in panelboard
800 Single L 200
34 1200 Single L 200
construction
Switches Rated 600 Vac Series Rated Combinations
35 30/30
60/60
Twin
Twin
R, J
R, J
200
200
200
200


Refer to the series rating tables beginning on Page 22.0-14
for the approved series rated combinations available for
100/100 Twin R, J 200 200
200/200 Twin J, T 200 200
the branch circuit breakers listed in Table 22.4-3.
36 100 Single R, J 200 200
Modifications
200 Single R, J, T 200 200
400 Single R, J, T 200 200
Enclosures
37 600
800
Single
Single
R, J, T
L
200
200
200
200

Types 12, 3R, 4/4X.
1200 Single L 200 200
Ground Bar
38 Note: Twin branch switches of different ampere ratings are available, Standard bolted in box with (3) #6300 kcmil terminals.
i.e., 30/60, 30/100, 60/100. Aluminum is standard, copper is available as an option.
39 Trims
Trim with door is available as an option for Type 1 enclosures.
40 Surge Protective Device (SPD)
Integrated onto panelboard chassis. For complete product
description and available ratings, refer to Tab 34.
41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-5
January 2018 Pow-R-Line 4
Sheet 22 051
Panelboard Layout and DimensionsPow-R-Line 4B

Main Lug (MLO), Main Breaker, Neutral, Through-Feed (TFL) and Sub-Feed Lug (SFL) X Space Requirements
(For compression lugs, or other configurations not shown, refer to Eaton.)
22
= Blank means no bus under cover to meet NEC cable bending space.
23
Standard Main Lug, Through-Feed and Main Breaker with Neutral (when required)
Sub-Feed Lugs (500 kcmil Maximum) (500 kcmil Maximum) 24
MLO, SFL MLO, TFL
Main
10X 10X 7X Breaker 19X
88 A Vertically Mtd. 25
MSD Main Breaker
only, in 24.00-inch
Main (609.6 mm) wide
250 A , 400 A , Branch Branch 250 A, 400 A Breaker Branch Branch box. Available with 26
600 A and 800 A Devices Devices 600 A and 800 A Devices Devices 38X and 50X Panel
Branch
Devices Height only.
7X Through-
Feed Lugs 27
3Ph 4W, 3Ph 3W 3Ph 4W 3Ph 3W 3Ph 4W
3Ph 3W
28
MLO MLO, TFL
2X Blank
12X 12X 7X Main 29
1200 A 1200 A Breaker

36.00-inch Branch Branch 36.00-inch


Main
Breaker Branch
30
(914.4 mm) Devices Devices (914.4 mm) Devices
Minimum Minimum Branch
Devices
Width
2X Blank 7X Through-
Feed Lugs
Width
2X Blank 2X Blank 31
3Ph 4W, 3Ph 3W 3Ph 4W 3Ph 3W 32
Figure 22.4-1. X Space RequirementsDimensions in Inches (mm)
1 Sub-feed lugs are available 250600 A. For 600 A, use 1200 A X space. 33
Optional Main Lugs, Through-Feed and
Sub-Feed Lugs (750 kcmil Maximum)
34
MLO, SFL MLO, TFL
35
20X 20X 13X 13X

36
250 A , 400 A , Branch Branch Branch Branch
600 A and 800 A Devices Devices Devices Devices

9X Through- 9X Through-
37
3X Blank Feed Lugs 3X Blank Feed Lugs

3Ph 4W 3Ph 3W
38
MLO MLO, TFL
39
20X 20X 15X 15X
1200 A 1200 A
40
Branch Branch Branch Branch
Devices Devices Devices Devices
36.00-inch 36.00-inch
(914.4 mm)
11X Through- (914.4 mm)
11X Through-
41
Minimum 5X Blank Feed Lugs Minimum 5X Blank Feed Lugs
Width Width

3Ph 4W 3Ph 3W
42
Figure 22.4-2. X Space RequirementsDimensions in Inches (mm)
2
43
Sub-feed lugs are available 250600 A. For 600 A, use 1200 A X space.

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-6 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 052
Panelboard Layout and DimensionsPow-R-Line 4B

Breaker (PRL4B) Type Distribution Layout Example


22 Panelboards 600 Vac, 250 Vdc 1 PRL4B panelboard, 480Y/277V,
three-phase, four-wire, 65 kA,
Panelboard Layout and Dimensions 800A, main lug, consisting of:
23
To determine the dimensions of a 12 20 A/single-pole HFD
given panelboard enclosure, make
24 a layout sketch by fitting together 2 250 A/three-pole HJD
the main branch and lug modules
1 400 A/three-pole HKD
according to the appropriate tables in
25 the layout guide. Assign X units to 20 A/1P 20 A/1P 1X 1. From layout guide, total X
each module as shown and obtain a 20 A/1P 20 A/1P 1X height of panel = 26X, (which is a
total X number. design standard and no rounding
20 A/1P 20 A/1P 1X
26 The height of the enclosure is related 20 A/1P 20 A/1P 1X
off is necessary).
to the total X units in the layout as 20 A/1P 20 A/1P 1X 2. From Table 22.4-5, enclosure
shown in Figure 22.4-3. Three standard height for 26X panel = 57.00 inches
27 box heights are available to accommo-
20 A/1P 20 A/1P 1X
(1447.8 mm).
250 A/3P 3X
date any and all layout arrangements.
X unit totals that do not exactly 3. Width = 24.00 inches (609.6 mm)
28 match those in Table 22.4-5 must be directly from layout guide.
250 A/3P 3X
rounded off to the next higher standard 4. Total enclosure depth = 11.30
(26X, 38X, 50X).
29 inches (287.0 mm)standard
When a calculated X total for a panel 400 A/3P 4X for all PRL4 panelboards.
exceeds 50X, the panel must be split
30 into two or more separate sections
with X space for through-feed lugs Main Lugs 800 A 10X
figured in for all but one section. If a
31 neutral is required, a separate neutral
bar and appropriate X space must
be included in each section.
32

33 Neutral

TOTAL = 26X

34 Note: For SPD unit, add 7X up to 200 kA and


10X for SPD above 200 kA.

35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-7
January 2018 Pow-R-Line 4
Sheet 22 053
Panelboard Layout and DimensionsPow-R-Line 4B

Table 22.4-5. Standard Panelboard and Box


Dimensions in Inches (mm) 22
Panel Box Box Box 1 Filler 1X Breaker To Fusible Transition, All Widths
Height Height Width Depth

26X 57.00 (1447.8) 24.00 (609.6) 2 10.40 (264.2)


Sub Panel
18
12X Poles
23
38X 73.50 (1866.9) 24.00 (609.6) 2 10.40 (264.2) 100 A
50X 90.00 (2286.0) 24.00 (609.6) 2 10.40 (264.2) 42 Max.
38X 73.50 (1866.9) 36.00 (914.4) 10.40 (264.2) 400 AMaximum Bus Rating
20X Poles 24
50X 90.00 (2286.0) 36.00 (914.4) 10.40 (264.2)
1P 1P 1X
38X 73.50 (1866.9) 44.00 (1117.6) 10.40 (264.2)
50X 90.00 (2286.0) 44.00 (1117.6) 10.40 (264.2) 2P 2P 2X
25
EHD,
1 Box depth is 10.40 inches (264.2 mm), 225 A FDB, FD, FDE, HFDE
cover adds 0.90 inches (22.9 mm) for overall Max. HFD, FDC, FDCE
enclosure depth of 11.30 inches (287.0 mm). 3P 3P 3X 26

24.00-Inch (609.6 mm) Wide Box


2 800 A maximum bus size in
24.00 inches (609.6 mm) wide box.
2P 2P
Note: Flush trims available on PRL4B panels 2X
225 A
27
with Door-in-Door enclosure only. EDB, EDS, ED, EDH, EDC
Max.
3P 3P 3X
Top and Bottom Gutters (Minimum) 28
10.62 inches (269.9 mm)
2 or 3P 3X 250 A JD, HJD, JDC, HJDDC
Max.
Side Gutters (Minimum) 29
400 A DK, KD, HKD, KDC, LHH,
24.00-inch (609.6 mm) wide box: 2 or 3P 4X
Max. CKD, CHKD, HKDDC
5.00 inches (127.0 mm)
30
Load
4X
36.00-inch (914.4 mm) wide box: 3P
600 A LGE, LGH, LGC, LGU
Max.
6.00 inches (152.4 mm)
44.00-inch (1117.6 mm) wide box:
8.00 inches (203.2 mm) 2 or 3P
Load
6X
600 A LD, HLD, CLD, CHLD, LDC, HLDDC
31
Max.

32
36.00-Inch (914.4 mm) Wide Box

Surge Protective Device (SPD) 7X


SPD (7X through 200 kA)
10X (10X through 400 kA)

2 or 3P 2 or 3P 3X 100 A
FCL, FB-P, HFDDC
33
Max.

3X
250 A
2 or 3P 2 or 3P Max. JD, HJD, JDC
34
400 A
Max. LCL, LA-P, NHH
2 or 3P 6X
800 A MDL, HMDL, HMDLDC 35
Max. CMDL, CHMDL
44-Inch (1117.6 mm) Wide Box

800 A
2 or 3P 6X
Max. 36
1200 A
NGC, NGH, NGS
Max.

400 A DK, KD, HKD,


37
2 or 3P 2 or 3P 4X
Max. KDC
800 A
Max. NB-P 38
2 or 3P 6X
1200 A
CNGS, CNGH, CNGC
Max.
39
Breaker may be used as main.

Figure 22.4-3. Layout for Branch and Horizontally Mounted Main Devices 40
3 BAB and QBHW breakers with shunt trips require one additional pole space, i.e., single-pole
is two-pole size, two-pole is three-pole size, and three-pole is four-pole size.
4 If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. 41
5 GHB, HGHB or GHQ breakers cannot be mixed on same subchassis as BAB, QBHW.
6 If panel contains only GHB, HGHB or GHQ branch breakers, use a PRL2a panelboard.
7 When only one single-pole breaker of the group is required on either side of chassis, 42
the single-pole breaker space required changes from 1X to 2X.
8 Minimum 36.00-inch (914.4 mm) wide box is required if optional #6300 kcmil lug is required.
9
j
MDL main breaker in 24.00-inch (609.6 mm) wide box, refer to Figure 22.4-1. 43
Optional 750 kcmil terminal requires 44.00-inch (1117.6 mm) wide box.
Note: See Page 22.4-5 for MLO or Neutral and Vertically Mounted Mains space requirements.

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-8 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 054
Panelboard Layout and DimensionsPow-R-Line 4F

Main Lug (MLO), Main Switch, Neutral Through-Feed Lug (TFL) and Sub-Feed Lug (SFL) X Space Requirements
22 (For other configurations refer to Eaton.)
= Blank means no bus under cover to meet NEC cable bending space.
23
Standard Main Lugs, Through-Feed Lugs Main Switch with Neutral (when required)
24 and Sub-Feed Lugs (500 kcmil Maximum) (500 kcmil Maximum)

MLO, SFL MLO, TFL


Main
25 10X 10X 7X Switch 22X
400 A and 600 A
Vertically Mounted
Main Switch.
26 250 A , 400 A , Branch Branch 200 A, 400 A
Main
Switch Branch
36.00-inch (914.4 mm)
Branch or 44.00-inch
600 A and 800 A Devices Devices 600 A Devices Devices (1117.6 mm)
Branch
Devices wide box.
27 7X Through-
Feed Lugs
7X

28 3Ph 4W, 3Ph 3W 3Ph 4W 3Ph 3W 3Ph 4W


3Ph 3W
MLO MLO, TFL

29 12X 12X
800 A 25X
1200 26X 800 A and 1200 A
1200 A Vertically Mounted
Main Switch .
30 Branch Branch
800 A,
1200 A Branch 36.00-inch (914.4 mm) or
Devices Devices Devices 44.00-inch (1117.6 mm)
wide box.
31 2X Blank 7X Through-
Feed Lugs
7X

32 3Ph 4W, 3Ph 3W 3Ph 4W

Figure 22.4-4. X Space RequirementsDimensions in Inches (mm)


33 1 Sub-feed lugs are available 250600 A. For 600 A, use 1200 A X space.
2 800 and 1200 A mains available only in vertical mounting.

34
Optional Main Lugs, Through-Feed and
Sub-Feed Lugs (750 kcmil Maximum)
35 MLO, SFL MLO, TFL

20X 20X 13X 13X


36
250 A , 400 A , Branch Branch 250 A, 400 A, Branch Branch
37 600 A and 800 A Devices Devices 600 A and 800 A Devices Devices

9X Through- 9X Through-
3X Blank Feed Lugs 3X Blank Feed Lugs
38
3Ph 4W 3Ph 3W
39 MLO MLO, TFL

20X 20X 15X 15X


40 1200 A 1200 A

Branch Branch Branch Branch


41 36.00-inch Devices Devices Devices Devices

(914.4 mm) Through- Through-


5X Blank 11X 5X Blank 11X
Minimum Feed Lugs Feed Lugs
42 Width

3Ph 4W 3Ph 3W
43
Figure 22.4-5. X Space RequirementsDimensions in Inches (mm)
3 Sub-feed lugs are available 250600 A. For 600 A, use 1200 A X space.

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-9
January 2018 Pow-R-Line 4
Sheet 22 055
Panelboard Layout and DimensionsPow-R-Line 4F

Fusible (PRL4F) Type Distribution Layout Example


Panelboards 600 Vac, 250 Vdc 1 PRL4F, three-phase, four-wire, 22
208Y/120 V complete with
Panel Layout and Dimensions 400 A main switch and the
following branches: 23
To determine the dimensions of a
given panelboard enclosure, make 1 200 A/three-pole
a layout sketch by fitting together
2 100 A/three-pole
24
the main branch and lug modules
according to the appropriate tables
2 30 A/three-pole
in the layout guide. Assign X units 25
to each module as shown and obtain Panel to have short-circuit rating of
a total X number. 100,000A symmetrical.
The height of the enclosure is related 400 A Neutral 7X 1. From layout guide,
26
to the total X units in the layout as X height of panel = 43X.
shown in Figure 22.4-6. Three standard
box heights are available to accommo- 2. Rounded off to next higher 27
date any and all layout arrangements. standard = 50X.
X unit totals that do not exactly
match those in Table 22.4-6 must
3. From Table 22.4-6, enclosure 28
30 A/three-pole 30A/three-pole 4X height for 50X panel =
be rounded off to the next higher 90.00 inches (2286.0 mm).
standard (38X, 50X).
4. Width = 36.00 inches (914.4 mm)
29
When a calculated X total for a panel because no switch in the assembly
100 A/three-pole 100A/three-pole 4X
exceeds 50X, the panel must be split requires a 44.00-inch (1117.6 mm)
into two or more separate sections wide enclosure.
30
with X space for through-feed lugs
figured in for all but one section. If a 200 A/three-pole 6X 5. Total enclosure depth =
neutral is required, a separate neutral 11.30 inches (287.0 mm) 31
bar and appropriate X space must standard for all PRL4 panelboards.
be included in each section.
Cabinet Specifications 32
Boxes: Code-gauge commercial
400A three-pole 22X galvanized sheet steel (no knockouts).
main switch (vertically mounted) 33
Total = 43X
34
Note: In the above example, if a horizontally
mounted 400 A main switch was used, the
enclosure size would be: 73.50 inches H x 35
44.00 inches W x 11.30 inches D (1866.9 mm
H x 1117.6 mm W x 287.0 mm D).
36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-10 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 056
Panelboard Layout and DimensionsPow-R-Line 4F

Table 22.4-6. Standard Panel and Box


22 Dimensions in Inches (mm)
Fusible to Breaker 1X
Panel Box Box Box 1 Transition, All Widths
Height Height Width Depth
23 30 A 30 A 4X
38X 73.50 36.00 10.40
(1866.9) (914.4) (264.2)
24 50X 90.00 36.00 10.40 60 A 60 A

36.00-inch (914.4 mm) Wide Box


4X
(2286.0) (914.4) (264.2)
38X 73.50 44 10.40
25 (1866.9) (1117.6) (264.2) 100 A
250 V Max.
100 A
250 V Max. 4X
50X 90.00 44.00 10.40
(2286.0) (1117.6) (264.2)
26 1 Box depth is 10.40 inches (264.2 mm), cover 100 A 5X
adds 0.90 inches (22.9 mm) for overall
enclosure depth of 11.30 inches (287.0 mm).

27 Note: Flush trims are available on PRL4F
panels with door-in-door enclosure only. 200 A
Main or Branch 6X

28 Top and Bottom Gutters (minimum)


10.63 inches (269.9 mm)
Surge Protective 7X (7X for SPD 200 kA and below)
Side Gutters (minimum)
29 Device (SPD) 10X (10X for SPD above 250 kA)
36.00-inch (914.4) wide box:
200 A maximum
30 8.00 inches (203.2 mm) 100 A 100 A 5X

4001200 A maximum

6.00 inches (152.4 mm)
31 44.00-inch (1117.6 mm) wide box:
400 A Branch 9X (11X with Shunt Trip)


200 A maximum
600 A Branch 11X
32 10.00 inches (254.0 mm)
4001200 A maximum
8.00 inches (203.2 mm) 200 A 200 A 6X
44.00-inch (1117.6 mm) Wide Box

33

400 A 9X
Main or Branch (11X with Shunt Trip)
34

600 A
Main or Branch 11X
35
800 A
Branch 11X (16X with Shunt Trip)

36
1200 A
Branch 15X (16X with Shunt Trip)

37
Fusible switch may be used as horizontal main.
400 and 600 A horizontally mounted feeder switches in 36.00-inch (914.4 mm) or
38 44.00-inch (1117.6 mm) wide box. 400 and 600 A horizontally mounted main switches
only in 44.00-inch (1117.6 mm) wide box.
For vertically mounted main switch see Page 22.4-5 for sizing.

39
Figure 22.4-6. Branch and Horizontally Mounted Main Fusible Switch Layout
Dimensions in Inches (mm)
40 Note: See Page 22.4-8 for MLO or neutral and vertically mounted main space requirements.

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-11
January 2018 Pow-R-Line 4
Sheet 22 057
General Description and Technical DataPow-R-Line 4D

Pow-R-Line 4D Application Description Benefits


22
Interrupting ratings up to Ease of maintenance
200 kAIC symmetrical Faster to remove and install
Feeder power panelboard Less downtime 23
Rated as Service Entrance
Equipment when appropriately Standards and Certifications
equipped UL 67 Listed chassis
24
Ideal for:
UL 50 Listed box and trim
Data centers
25
Industrial facilities Technical Data
Process equipment manufacturing
Instructions 26
Anywhere that requires quick
Determine box size by locating all
change of feeder devices main and feeder devices in your panel.
is needed The width of box is determined by the 27
maximum box size shown for each
device. For main lugs, through-feed
lugs and sub-feed lugs. 28
Type PRL4D Drawout Molded-Case
Circuit Breaker Power Panelboard 29
General Description
Drawout molded-case circuit 30
breaker power panelboard
Front accessible
31
Front connected
Through-the-door design
drawout mechanism 32
Visual indication of breaker status
and position
Large grab handles for easy removal 33
600 Vac maximum
1200 A maximum mains 34
600 A maximum drawout
molded-case feeder breakers
35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-12 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 058
Panelboard Layout and DimensionsPow-R-Line 4D

Table 22.4-7. Standard Panel and Box


22 Dimensions in Inches (mm)
Panel Box Box Box 1 2 or 3P
Height Height Width Depth Feeder Only 7X
250 A JGS, JGH, JGC
23 Single Drawout Max.
38X 73.50 36.00 11.31
(1866.9) (914.4) (287.0)
24 50X 90.00
(2286.0)
36.00
(914.4)
11.31
(287.0) 2 or 3P
Main or Feeder 600 A
38X 73.50 44.00 11.31 9X
Max.
LGS, LGH, LGC
Single Drawout
25 (1866.9) (1117.6) (287.0)
50X 90.00 44.00 11.31
(2286.0) (1117.6) (287.0)
2 or 3P
26 1 Box depth is 10.40 inches (264.2 mm); cover Main Only 4X 600 A
LGS, LGH, LGC
adds 0.90 inches (22.9 mm), for overall Fixed Mount Max.
enclosure depth of 11.30 inches (287.0 mm).
27 Note: Flush trims not available on PRL4D
panels. Door-to-door option not available on
2 or 3P
Main Only
600 A
6X CLD , CHLD , CLDC
Max.
PRL4D panels. Fixed Mount

28

36-Inch (914.4 mm) Wide Box


Top and Bottom Gutters (minimum)
2 or 3P
10.63 inches (269.9 mm) Main Only 6X
800 A MDL, HMDL, CMDL ,
Max. CHMDL
29 Side Gutters (minimum)
Fixed Mount

36.00-inch (914.4) wide box:


2 or 3P
30 6.00 inches (152.4 mm) Main Only 6X
1200 A
Max. NGS , NGH , NGC
Fixed Mount
44.00-inch (1117.6 mm) wide box:
8.00 inches (203.2 mm)
31
2 or 3P 2 or 3P
44-Inch (1117.6 mm) Wide Box
Feeder Only Feeder Only 7X 250 A JGS, JGH, JGC
Max.
32 Dual Drawout Dual Drawout

2 or 3P
33 Main Only 6X 1200 A
NGSC , NGHC , NGCC
Fixed Mount Max.

34
Figure 22.4-7. Layout for Branch and Horizontally Mounted Main DevicesPRL4D
1 100% rated breaker.
35 2 Optional 750 kcmil terminal requires 44.00-inch (1117.6 mm) wide box.
3 Contact Eaton for availability.

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-13
January 2018 Pow-R-Line 4
Sheet 22 059
General DescriptionPow-R-Line Multipoint Meter

Power Xpert When you need accurate information Benefits 22


of consumed energy for monthly
Multipoint Meter invoicing statements, use Eatons Factory-wired system
integrated multipoint metering solution. Integrated display
Using Power Xpert Multipoint
Saves floor space
23
Metering for utility allocation
maximizes revenue by effectively Lower installed cost
measuring, allocating and recovering Network compatible 24
utility expenditures. The Power Xpert Tenant sub-billing
Multipoint Metering solution can UL Listed
interface with a third-party utility 25
Integral Web-based and third-party
allocation service. The Power Xpert
Multipoint Metering solution offers to: software solutions available
26
Purchase energy at bulk rates
while charging consumer rates
Capitalize on naturally variable 27
tenant loads by purchasing
energy at lower coinciding load
Capture and allocate common 28
area maintenance cost
Promote tenant retention with
accurate and defensible billing
29
Eliminate subsidization of
other tenants 30
Power Xpert Multipoint Meter
Switchboards and Panelboards 31

General Description 32
Allocation of energy consumption
in a residential or commercial 33
application is a tremendous task
for a property owner, management
firm or electrical energy manager.
To assist in allocation or direct billing
34
Factory Assembled and Wired Meters
of consumed energy, use Eatons
Power Xpert Multipoint Meter low 35
cost solutions. The Power Xpert
Multipoint Meter provides a cost-
effective energy tabulation system 36
for residential or commercial metering
installations. These installations
can include: 37
High-rise buildings
Universities and campuses 38
Office buildings
Apartment and condominium Power Xpert Multipoint MeterCTs are
complexes Factory-Mounted and Wired to Meter 39
Shopping malls The Power Xpert Multipoint Metering Panelboard Uses the Pow-R-Line 4 Panelboard
Airports with Eaton's Power Xpert Multipoint Meter and Current Sensors
40
System commissioning is required
Local display and network capable
and priced separately devices are available as optional
components. 41
See Tab 3, Section 3.1 Metering for
more information. 42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-14 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 060
Panelboard Layout and DimensionsPow-R-Line Multipoint Meter

22 Layout Guide

23 Pow-R-Line MPM
See Page 22.4-8 for MLO or
Neutral and Vertically Mounted
24 Main Space Requirements

25 Bucket for Meter(s)


Maximum (1) PXMPM Meter
11X PXMPM Multipoint Meter

EHD
26 FDB 2X 2-Pole 2-Pole
FD, HFD, FDC, FDE, HFDE, FDCE
3X 3-Pole 3-Pole
Trip Range (15125A)
27 ED, EDH, EDC, 3X 2-Pole 2-Pole
EDB, EDS
5X 3-Pole 3-Pole
Trip Range (150225A)
28

Load
Lugs
Line
DK, KDB, KD, HKD, KDC 4X 2P 2- or 3-Pole
Trip Range (70400A) 6X 3P

29
Figure 22.4-8. Power Xpert MPM Layout Guide for Current Sensor and Current Transformer SizingStandard Pow-R-Line 4 Panelboard
Construction Applies
30 Note: For all other breaker frames and Note: Consult Section 22.4 for Pow-R-Line 4
amperages, consult factory for X structure configuration.
space sizing.
31 Table 22.4-8. Power Xpert MPM Breaker Frames
Breaker Maximum Trip Number Current Sensor X Minimum Enclosure
32 Type Amperes of Poles (100 mA) I.D. in Inches Space Width in Inches (mm)

EHD 100 2 0.53 2X 36.00 (914.4)


EHD 100 3 3X
33 FDB, FD, HFD, FDC 125 2 0.53 2X 36.00 (914.4)
FDB, FD, HFD, FDC, FDE, HFDE, FDCE 125 3 3X
EDB, EDS, ED, EDH, EDC, FD, HFD, FDC 225 2 1.12 3X 36.00 (914.4)
34 EDB, EDS, ED, EDH, EDC, FD, HFD, FDC, FDE, HFDE, FDCE 225 3 5X
DK, KD, HKD, KDC (Single Mounting Only) 400 2 1.74 4X 36.00 (914.4)
DK, KD, HKD, KDC (Single Mounting Only) 400 3 6X
35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-15
January 2018 Pow-R-Line 4
Sheet 22 061
Pow-R-Line PXBCM Panelboard

Pow-R-Line PXBCM Application Description Product Specifications 22


Panelboard The Pow-R-Line PXBCM can be used in NEMA Enclosure Options and
various industries and LEED certified
buildings. There is a rapidly changing Dimensions in Inches (mm) 23
emphasis on LEED designs and the A variety of NEMA enclosures
Pow-R-Line PXBCM panelboard helps are available as options: NEMA Type 1,
you meet the measurement and verifi- 2, 3R, 4, 4X, and 12. Pow-R-Line 1a, 24
cation points required by LEED and the 2a, with 400 A main bus, all PRL3e
U.S. Green Building Council. Some and Pow-R-Command panel applica-
applications the Pow-R-Line PXBCM tions require a 28-inch wide box to 25
panelboard include: provide additional gutter space for
cable bending.
Energy management 26
Industrial monitoring Heights
Cost allocation 36.00 (914.4) 27
Data center management 42.00 (1066.8)
Light commercial 48.00 (1219.2)
Industrial 60.00 (1524.0) 28
Institutions 72.00 (1828.8)
90.00 (2286.0) 29
Features and Benefits Widths 1
The Pow-R-Line PXBCM panelboard 30
20.00 (508.0)
offers Modbus RS-485 and TCP out-
put standard while allowing flexibility 28.00 (711.2)
for onboard configuration. Also, Depth 1 31
communication and analysis can be
communicated through an integrated 5.75 (146.1)
Pow-R-Line PXBCM Panelboard Web server or a number of building
automation sources, including Eatons
1 Dimensions for NEMA Type 1 enclosure. 32
For dimensions of optional NEMA
General Description Power Xpert and Foreseer products. enclosure, contact your Eaton distributor

The Pow-R-Line PXBCM panelboard


or sales engineer. 33
Eatons Pow-R-Line Branch Circuit
allows you to:
Monitoring (PXBCM) panelboards
is an integrated, affordable metering Make informed load shifting and 34
device that combines exceptional load shedding decisions
performance and easy installation to Fairly and accurately allocate energy
deliver a cost-effective solution for costs to users 35
branch circuit level energy and power
Identify wasteful practices
monitoring. The Pow-R-Line PXBCM
can monitor up to 84 branch circuits Decrease unnecessary usage 36
and 16 main and auxiliary panel Produce an energy profile
connections.
Pow-R-Line PXBCM key
The Pow-R-Line PXBCM panelboard features include:
37
provides a means to monitor main
Power and energy readings at the
power coming into the panelboard 38
and up to four additional three-phase branch circuit level
meters. The Pow-R-Line PXBCM Integrated Web server for remote
panelboard can be used in lighting monitoring and configuration
appliance, small power distribution Optional remote color touchscreen
39
panelboards, and Pow-R-Command display for local readings
lighting control panelboards with a Compatibility with the Power Xpert 40
maximum 400 A main breaker and gateway for remote monitoring
125 A branch breakers.
The Pow-R-Line PXBCM panelboard is 41
available in PRL1a, PRL2a, and PRL3e
panelboard classifications.
42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-16 Panelboards
Pow-R-Line 4 January 2018
Sheet 22 062
Pow-R-Line PXBCM Panelboard

22 Technical Data and Specifications


Table 22.4-9. Pow-R-Line 1a, 2a and 3e Specifications Table 22.4-10. Meter Measurement Parameters
Description Rating Measured Parameter Main Branch Virtual 3
23 Pow-R-Line 1a Ratings Current per phase
Voltage 240 Vac maximum
Maximum and minimum current per phase
24 Main breaker 100600 A
Current demand per phase
Main lug 100600 A
Peak current demand per phase
Maximum kAIC 1022 kA fully rated
25 22200 kA series rated
Forward and reverse energy (kWh) per
phase

Branch circuit breaker 15100 A Maximum and minimum real power (W)
26 Branch breaker connector 140 A per phase
Branch circuit breaker types BA (BAB, BAB-H), QBH (QBHW, Apparent power (VA)
QBHW-H), QBGFT, QBGFEP, QBH- Power factor total 4
27 GFT, QBHGFEP, HQP, QPHW, QHPX,
QPGF, QPHGF QPGEP, QPHGFEP
Power factor per phase
BABR, QBAF, QBAG, QBHAF, QBCAF Maximum and minimum voltage
and QBHCAF (line-to-line)
28 Pow-R-Line 2a Ratings Maximum and minimum voltage
(line-to-neutral)
Voltage 240 Vac, 480Y/277 Vac and
125/250 Vdc maximum Maximum and minimum voltage (phase A)
29 Main breaker 100600 A Current
Main lug 100600 A Maximum current

30 Maximum kAIC 240 Vac: Current demand


65 kA fully rated Real power (W)
65200 kA series rated
Forward and reverse real power (W)
31 480Y/277 Vac: demand
14 kA fully rated
Forward and reverse energy (kWh)
22150 kA series rated
per circuit
32 125/250 Vdc:
1014 kA fully rated
Maximum apparent power (kVA)
Power factor
Branch circuit breaker 15100 A
Virtual meters
33 Branch breaker connector 140 A
Average current
Branch circuit breaker types GB, GHB, GHBGFEP, HGHB, GQ,
GHQ, GHQRD 1 and GHQRSP 1 Forward and reverse energy (kWh)
34 Pow-R-Line 3e Ratings Forward and reverse power (W) demand
Voltage 240 Vac, 480Y/277 Vac or 480 Vac Forward and reverse power (W)
and 250 Vdc maximum peak demand
35 Main breaker 125400 A 2 Maximum real power (W)
Main lug 100400 A 2 Maximum apparent power (VA)
3
36 Maximum kAIC 240 Vac:
20100 kA fully rated 4
Virtual means Web server.
Based on a three-phase breaker rotation.
100200 kA series rated

37 480Y/277 Vac or 480 Vac:


1865 kA fully rated
65100 kA series rated
250 Vdc:
38 1042 kA fully rated
Branch circuit breaker 15125 A

39 Branch breaker connector 140 A


Branch circuit breaker types EGB, EGS and EGH
1 Remote operated circuit breaker.
40 2 600A is available without main metering.

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.4-17
January 2018 Pow-R-Line 4
Sheet 22 063
Pow-R-Line PXBCM Panelboard

Modifications and 22
Accessories
Because each Pow-R-Line 1a, 2a, 23
and 3e panelboard is assembled by
an experienced technician, we can
easily and efficiently incorporate any 24
combination of modifications and
accessories, including:
Breaker lock-off devices 25
Compression type lugs
(main lugs only) 26
Arc fault breakers
Increased dimensions
Trim to fix existing boxes 27
Main breakers with solid-state
trip units
28
Permanent circuit numbering
Service entrance
Special doors and locks 29
Surge protection devices
Pow-R-Command lighting control 30
Note: Contact your local Eaton distributor
or sales engineer for additional information
on these and other modifications and 31
accessories.

32

33

34

35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.4-18 Panelboards
January 2018
Sheet 22 064

This page intentionally left blank.


22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.5-1
January 2018 Column Type
Sheet 22 065
General DescriptionPow-R-Line 1a-LX Column Type

Pow-R-Line 1a-LX Main Lugs Only Main Circuit Breakers


22
The short-circuit rating of the MLO The short-circuit rating shown is that
assembled panelboard will be fully of the main breaker only. The short-
rated based upon the lowest rated circuit rating of the assembled
branch device or may be series rated panelboard is the rating of the lowest 23
with an approved upstream device. fully rated main or branch device
or the rating of an approved series
Main lugs only ampere ratings: rated combination. 24
100 and 225.
Table 22.5-1. Main Circuit Breakers 25
Breaker Frame Breaker Interrupting Rating
Amperes Type (kA Symmetrical) at 240 Vac

100 BAB 10 26
100 QBHW 22
100 EHD 18
150 FDB 18 27
150 FD, FDE 65
150 HFD, HFDE 100
150 FDC 200 28
225 EDB 22
225 EDS 42
225
225
ED, FD
EDH, HFD
65
100
29
Pow-R-Line 1a-LX Column Type 225 EDC, FDC 200

General Description Table 22.5-2. Branch Circuit Breakers 30


Breaker Ampere Number Interrupting Rating (kA Symmetrical)
Panelboard Ratings Type Rating of Poles 120 Vac 120/240 Vac 240 Vac 31
Voltage BAB 1570 1 10
240 Vac maximum BAB 15100 2 10
BAB 15100 2, 3 10 32
Main Lugs BAB-D 1 1560 1, 2 10 10
100 and 225 A BAB-C 2 1530 1, 2 10 10
BABRP 3 1530 1, 2 10 10 33
Main Breakers BABRSP 3 1530 1, 2 10 10
100 and 225 A QBGF 1550 4 1, 2 10 10
QBGFEP
QBCAF 5
1550 4
1520
1, 2
1
10
10
10
10


34
Branch Breakers
15100 A (bolt-on) QBHW 1570 1 22
QBHW
QBHW
15100
15100
2
2, 3


22


22
35
Short-Circuit Current Ratings (Symmetrical)
QBHGF 1530 4 1, 2 22 22
240 Vac: 10 kA and 22 kA fully rated
QBGFEP 1530 4 1, 2 22 22
240 Vac: 22200 kA series rated QBHCAF 5 1520 1 22 22
36
1 HID (High Intensity Discharge) rated breaker.
Service 2
Three-phase, four-wire 208Y/120 V
Switching neutral breaker. Single-pole device requires two-pole space, two-pole device requires
three-pole space.
37
and 240/120 V delta 3 Solenoid operated breaker.
4
Single-phase, three-wire 120/240 V 50 A is two-pole only.
Single-phase, two-wire 120 V
5 Arc fault breaker. 38
Three-phase, three-wire Series Rated Combinations
208 and 240 V Refer to series rating tables beginning 39
Mains on Page 22.0-14 for the approved
series rated combinations available
For available mains, refer for the branch circuit breakers listed 40
to Table 22.5-1. in Table 22.5-2.
Main breakers, 100 A, Types BAB and
QBHW are horizontally mounted, same
41
as branch breakers. All other main
breakers are vertically mounted.
42
Branch Circuits
For available branch devices, refer
to Table 22.5-2. 43

CA08104001E For more information, visit: www.eaton.com/consultants


22.5-2 Panelboards
Column Type January 2018
Sheet 22 066
Technical Data and SpecificationsPow-R-Line 1a-LX Column Type

Technical Data and Specifications Top and Bottom Gutters Assembled Circuit Breaker Panelboards
22 4.50 inches (114.3 mm) minimum. Box size, box and trim catalog numbers
Bussing for standard column type panelboards
100225 A: copper is standard. Left Side Gutter listed are available from Table 22.5-4.
23 4.50 inches (114.3 mm) minimum.
Boxes Instructions
Boxes are made from code-gauge steel. Pull Box 1. Using description of the required
24 Pull box is furnished without knockouts. panelboard, select the rating and
Blank ends are supplied as standard. type of main required.
Modifications
25 Trims a. 100 A panelboards
Table 22.5-3. Sub-Feed Breakers (One Per Panel)
Trims are made from code-gauge steel Table 22.5-4.
Ampere Breaker Interrupting Rating
and painted ANSI 61 gray. Rating Type (kA Symmetrical) b. 225 A panelboards
26 Doors have three-point catch and lock. Space at 240 V Table 22.5-4.
150 FDB 18 2. Count total number of branch
Neutral Bars 150 FD, FDE 65 circuit poles, including provisions,
27 When column type panels are 150 HFD, HFDE 100 required in the panelboard.
furnished with trough extensions 150 FDC 200
Do not count main breaker poles.
and pull box, the neutral bar will 225 EDB 22 Convert two- or three-pole branch
28 be placed in the pull box unless 225 EDS 42
breakers to single poles, i.e.,
otherwise specified. 225 ED, FD, FDE 65
225 EDH, HFD, HFDE 100 three-pole breaker, count as
29 When troughs and pull box are not 225 EDC, FDC 200 three poles.
furnished, the neutral bar will be Determine sub-feed breaker or
located on the panel at the same Shunt Trips
through-feed lug requirements.
30 end as the main. Shunt trips are available on BAB,
QBHW and FDB breakers. BAB and 3. Select the panelboard main
Cabinets QBHW require one additional pole ampere rating from Table 22.5-4.
31 Boxes and trims are code-gauge steel. space for shunt trip, i.e., single-pole
4. Panelboard Type from first
ANSI-61 light gray painted finish. is two-pole size, two-pole is three-pole
size and three-pole is four-pole size. column, main breaker Frame and
32 Boxes are furnished without knockouts. Designation, if applicable from
Ground Bar second column, and sub-feed
Standard depth is 6.00 inches breaker Frame and Designation, if
(152.4 mm). Standard width is Standard bolted in box. Aluminum
33 is standard, copper is available as applicable, from the third column.
8.63 inches (219.1 mm).
an option. 5. From Step 2, determine the number
of branch circuits in Column 4.
34
6. Read box size numbers across
columns to the right. All panels
35 are surface mounted.

36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.5-3
January 2018 Column Type
Sheet 22 067
Technical Data and SpecificationsPow-R-Line 1a-LX Column Type

Table 22.5-4. PanelboardsDimensions in Inches (mm)


Panelboard Main Breaker Types Sub-Feed Maximum Number Box Dimensions 22
Types Mounting: Breaker Types of Branch Circuits Height Width Depth
(H) = Horizontal Vertical Mounting Including Provisions
(V) = Vertical 23
100 A
Main breaker BAB, QBHW (H) 27 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
39 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4) 24
Main lugs or EHD, FDB, FD, FDE, 30 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
main breaker HFD (V), HFDE 42 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4)
Main lugs or main breaker EDB, EDS, ED, EDH, EHD, 30 78.00 (1981.2) 8.63 (219.1) 6.00 (152.4) 25
with 100 A through-feed FD, FDE, HFD, HFDE 42 90.00 (2286.0) 8.63 (219.1) 6.00 (152.4)
lugs or sub-feed breaker
225 A 26
Main lugs or EHD, FDB, FD, FDE 30 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
main breaker HFD, HFDE, ED, EDH (V) 42 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4)
Main lugs or main breaker EDB, EDS, ED, EDH, EHD, 30 78.00 (1981.2) 8.63 (219.1) 6.00 (152.4)
27
with 225 A through-feed FD, FDE, HFD, HFDE 42 90.00 (2286.0) 8.63 (219.1) 6.00 (152.4)
lugs or sub-feed breaker
1 For horizontal mounted mains (BAB Type), use main lug table, include space in branch section for mains. 28
Trough Extension 29
6.00 16.00
(152.4) (406.4) When extension troughs are used,
the NEC requires that the number
12.00
(304.8) of conductors in wireways shall not 30
contain more than 30 conductors
at any cross section, unless the
Additional
Extensions
(If Required)
conductors are for signal circuits 31
or are control conductors between
a motor and its starter and used
only for starting duty. The sum of the 32
cross-sectional areas of all contained
conductors at any cross section of
H
Box
Height
a wireway shall not exceed 20% of 33
the interior cross-sectional area
6.00 8.63
of the wireway.
(152.4) (219.1)
The derating factors specified in the
34
NEC shall not be applicable to the 30
Figure 22.5-1. Trough Extension current-carrying conductors at 20% fill
Dimensions in Inches (mm) specified above.
35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.5-4 Panelboards
Column Type January 2018
Sheet 22 068
General DescriptionPow-R-Line 2a-LX Column Type

22 Pow-R-Line 2a-LX Mains Main Lugs Only


For available mains, refer to Table 22.5-5. The short-circuit rating of the MLO
assembled panelboard will be fully
Type GHB main breakers are hori- rated based upon the lowest rated
23 zontally mounted, same as branch branch device or may be series rated
breakers. All other main breakers with an approved upstream device.
are vertically mounted.
24 Branch Circuits
Main lugs only ampere ratings:
100 and 225.
For available branch devices, refer
25 to Table 22.5-6. Main Circuit Breakers
The short-circuit rating shown is that
of the main breaker only. The short-
26 circuit rating of the assembled
panelboard is the rating of the lowest
fully rated main or branch device
27 or the rating of an approved series
rated combination.

28 Table 22.5-5. Main Circuit Breakers


Breaker Breaker Interrupting Rating (kA Symmetrical)
Pow-R-Line 2a-LX Column Type Frame Type 240 Vac 480Y/277 Vac 125/250 Vdc
29 Amperes
General Description 100 GHB 65 14 14
100 EHD 18 14 10
30 Panelboard Ratings
150 FDB 18 14 10
Voltage 150 FD, FDE 65 35 10
150 HFD, HFDE 100 65 22
240 Vac
31 150 FDC, FDCE 200 100 22
480Y/277 Vac maximum 225 ED 65
Note: PRL2a panelboards are suitable 225 FD, FDE 65 35 10
32 for use on three-phase, three-wire appli-
cations when derived from a three-phase,
225
225
EDH
HFD, HFDE
100
100

65

10
four-wire 480Y/277 Vac service where the 225 EDC 200
neutral is not brought to the panelboard. 225 FDC 200 100 10
33 For three-phase, three-wire 480 Vac delta
services, use a PRL3a panelboard. Table 22.5-6. Branch Circuit Breakers
250 Vdc maximum Breaker Ampere Number of Interrupting Rating (kA Symmetrical)
34 Type Rating Poles 120 Vac 240 Vac 277 Vac 480Y/277 Vac 125/250 Vdc
Main Lugs
100 and 225 A GHB 15100 1 65 14 14
35 GHB 15100 2, 3 65 14 14
Main Breakers GHQ 1520 1 65 14
100 and 225 A HGHB 1530 1 65 25
36 GHQRSP 1 1520 1, 2 65 65 14 14
Branch Breakers GHBS 1 1530 1, 2 65 65 14 14
1 Solenoid operated breaker.
15100 A
37 Series Rated Combinations
Short-Circuit Current Ratings (Symmetrical)
240 Vac: 65 kA fully rated Refer to series rating tables beginning
38 240 Vac: 100200 kA series rated
on Page 22.0-14 for the approved
series rated combinations available
480Y/277 Vac: 14 kA fully rated for the branch circuit breakers listed
39 480Y/277 Vac: 22150 kA series rated in Table 22.5-6.
250 Vdc: 10 kA and 14 kA fully rated

40 Service
Three-phase, four-wire 208Y/120 V
and 240/120 V delta and 480Y/277 V
41 Single-phase, three-wire 120/240 V
Single-phase, two-wire 120 V
42 Three-phase, three-wire
208 and 240 V
Two-wire 125 Vdc
43 Two-wire 250 Vdc

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.5-5
January 2018 Column Type
Sheet 22 069
Technical Data and SpecificationsPow-R-Line 2a-LX Column Type

Technical Data and Specifications Top and Bottom Gutters Assembled Circuit Breaker Panelboards
4.50 inches (114.3 mm) minimum. Box size, box and trim catalog 22
Bussing numbers for standard column type
100225 A: copper is standard. Left Side Gutter panelboards listed are available
3.31 inches (84.2 mm) minimum. from Table 22.5-8. 23
Boxes
Boxes are made from code-gauge steel. Pull Box Instructions
Pull box is furnished without knockouts. 1. Using description of the required 24
Blank ends are supplied as standard. panelboard, select the rating and
Modifications type of main required.
Trims 25
Table 22.5-7. Sub-Feed Breakers (One Per Panel)
Trims are made from code-gauge steel a. 100 A panelboards
Ampere Breaker Interrupting Rating
and painted ANSI 61 gray. Rating Type (kA Symmetrical) Table 22.5-8.
Doors have three-point catch and lock. Space 240 V 480 V b. 225 A panelboards 26
Table 22.5-8.
Neutral Bars 150 FDB 18 14
150 FD, FDE 65 35 2. Count total number of branch 27
When column type panels are furnished 150 HFD, HFDE 100 65 circuit poles, including provisions,
with trough extensions and pull box, 150 FDC 200 100 required in the panelboard. Do not
the neutral bar will be placed in the count main breaker poles. Convert
pull box unless otherwise specified.
225
225
ED
FD, FDE
65
65

35 two- or three-pole branch breakers
28
225 EDH 100 to single poles, i.e., three-pole
When troughs and pull box are not 225 HFD, HFDE 100 65
furnished, the neutral bar will be located 225 EDC 200
breaker, count as three poles. 29
on the panel at the same end as the main. 225 FDC 200 100 Determine sub-feed breaker or
through-feed lug requirements.
Cabinets Shunt Trips 3. Select the panelboard main 30
Boxes and trims are code-gauge steel. Shunt trips are available on GHB, FDB ampere rating from Table 22.5-8.
ANSI-61 light gray painted finish. and FD breakers. GHB breakers with
Boxes are furnished without knockouts.
shunt trips require three-pole frame. 4. Panelboard type from first 31
column, main breaker frame and
Standard depth is 6.00 inches Ground Bar designation, if applicable from
(152.4 mm). Standard width is Standard bolted in box. Aluminum second column, and sub-feed 32
8.63 inches (219.1 mm). is standard, copper is available as breaker frame and designation, if
an option. applicable, from the third column.
5. From Step 2, determine the number
33
of branch circuits in Column 4.
6. Read box size numbers across 34
columns to the right. All panels
are surface mounted.
35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.5-6 Panelboards
Column Type January 2018
Sheet 22 070
Technical Data and SpecificationsPow-R-Line 2a-LX Column Type

Table 22.5-8. PanelboardsDimensions in Inches (mm)


22 Panelboard Main Breaker Types Sub-Feed Maximum Number Box Dimensions 1
Types Mounting: Breaker Types of Branch Circuits Height Width Depth
(H) = Horizontal Vertical Mounting Including Provisions
23 (V) = Vertical
100 A
Main breaker GHB 27 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
24 (H) 39 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4)
Main lugs or EHD, FDB, FD, FDE 30 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
main breaker HFD, HFDE, FDCE 42 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4)
25 (V)
Main lugs or main breaker FD, FDE, HFD, HFDE, 30 78.00 (1981.2) 8.63 (219.1) 6.00 (152.4)
with 100 A through-feed lugs FDC, FDCE 42 90.00 (2286.0) 8.63 (219.1) 6.00 (152.4)
26 or sub-feed breaker
225 A
Main lugs or EHD, FDB, FD, FDE, 30 69.00 (1752.6) 8.63 (219.1) 6.00 (152.4)
27 main breaker HFD, HFDE 42 81.00 (2057.4) 8.63 (219.1) 6.00 (152.4)
(V)
Main lugs or main breaker FD, FDE 30 78.00 (1981.2) 8.63 (219.1) 6.00 (152.4)
28 with 225 A through-feed lugs FDE, HFD, HFDE, FDC 42 90.00 (2286.0) 8.63 (219.1) 6.00 (152.4)
or sub-feed breaker
1 For horizontal mounted mains (BAB Type), use main lug table, include space in branch section for mains.
29
Trough Extension
6.00 16.00
When extension troughs are used,
30 (152.4) (406.4)
the NEC requires that the number
12.00
(304.8) of conductors in wireways shall not
contain more than 30 conductors
31 at any cross section, unless the
Additional
Extensions conductors are for signal circuits
(If Required) or are control conductors between
32 a motor and its starter and used only
for starting duty. The sum of the
33 cross-sectional areas of all contained
conductors at any cross section of
H
Box a wireway shall not exceed 20% of
Height the interior cross-sectional area of
34 the wireway.
6.00 8.63
(152.4) (219.1)
The derating factors specified in
35 the NEC shall not be applicable to the
Figure 22.5-2. Trough Extension 30 current-carrying conductors at 20%
Dimensions in Inches (mm) fill specified above.
36

37

38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-1
January 2018 Pow-R-Line 1R
Sheet 22 071
General DescriptionPow-R-Line 1R

Pow-R-Line 1R Retrofit Eaton offers a factory-assembled Main Lugs Only


22
panelboard interior and trim designed The short-circuit rating of the MLO
Panelboard to bolt directly into an existing enclosure. assembled panelboard will be fully
rated based upon the lowest rated
Custom-built panelboard interiors
branch device, or may be series rated 23
and trims can be provided to retrofit
most any manufacturers existing with an approved upstream device.
panelboard enclosure. Main lugs only ampere ratings: 24
The panelboards are listed and are 100 and 225.
marked with both the Underwriters Main Circuit Breakers
Laboratories (UL) and Canadian 25
The short-circuit rating shown is that
Standards Association (CSA) labels.
of the main breaker only. The short-
Why Retrofit? circuit rating of the assembled 26
Upgrade protective device panelboard is the rating of the lowest
interrupting ratings fully rated main or branch device,
Replacing old, obsolete circuit
or the rating of an approved series 27
rated combination.
breakers with new
Providing additional circuits for Table 22.6-1. Main Circuit Breakers 28
load growth Breaker Breaker Interrupting Rating
Accommodating system change Frame Type (kA Symmetrical)
Pow-R-Line 1R and additions Amperes at 240 V
29
Adding ground fault circuit 100 BAB 10
General Description interrupters 100 QBHW 22

Panelboard Ratings
100 EHD 18 30
Immediate Benefits 150 FDB 18
Voltage Installation time is dramatically 225 FD, FDE 65
240 Vac maximum reduced 225 HFD, HFDE 100 31
225 FDC 200
Disruption of existing power
225 EDB 22
Main Lugs service is minimal
100400 A Less cleanup and wall repair because
225
225
EDS
ED
42
65
32
there is no need to cut and break 225 EDH 100
Main Breakers concrete or finished wall surface
225 EDC 200
100225 A
33
Branch Breakers Table 22.6-2. Branch Circuit Breakers
15100 A (bolt-on chassis) Breaker Ampere Number Interrupting Rating (kA Symmetrical) 34
Type Rating of Poles 120 V 120/240 V 240 V
Short-Circuit Current Ratings (Symmetrical)
240 Vac: 10 kA and 22 kA fully rated BAB 1570 1 10 35
BAB 15100 2 10
240 Vac: 22200 kA series rated BAB 15100 2, 3 10

Service BAB-D 1
BAB-C 2
1560
1530
1, 2
1, 2
10
10
10
10


36
Three-phase, four-wire 208Y/120 V BABRP 3 1530 1, 2 10 10
and 240/120 V delta BABRSP 3 1530 1, 2 10 10
Single-phase, three-wire 120/240 V QBGF, QBGFEP 1550 4 1, 2 10 10
37
QBCAF 5 1520 1 10 10
Single-phase, two-wire 120 V
QBHW 1570 1 22
Three-phase, three-wire QBHW 15100 2 22 38
208 and 240 V QBHW 15100 2, 3 22
QBHGF, QBGFEP 1530 1, 2 22 22
Suitable for service entrance QBHCAF 5 1520 1 22 22 39
applications when specified. 1 HID (High Intensity Discharge) rated breaker.
2
Mains Switching neutral breaker. Single-pole device requires two-pole space, two-pole device requires
three-pole space. 40
For available mains, refer 3 Solenoid operated breaker.
to Table 22.6-1. 4 50 A is two-pole only.
Main breakers, 100 A, Types BAB and
5 Arc fault breaker. 41
QBH are horizontally mounted, same Series Rated Combinations The panelboards are listed and are
as branch breakers. All other main
breakers are vertically mounted. Refer to series rating tables beginning marked with both the Underwriters 42
on Page 22.0-14 for the approved Laboratories (UL) and Canadian
Branch Circuits series rated combinations available Standards Association (CSA) labels.
For available branch devices, refer for the branch circuit breakers listed 43
to Table 22.6-2. in Table 22.6-2.

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-2 Panelboards
Pow-R-Line 1R January 2018
Sheet 22 072
Technical Data and SpecificationsPow-R-Line 1R

Technical Data and Specifications Application Guidelines


22 The following dimensions and data Stud
Bussing Locations Front View
are necessary for production of a
100400 A: Tin-plated aluminum
23 is standard, copper is available
panelboard to fit an existing box:
as an option. Existing Flush-Mounted Box A C
Height dimension H
24 Boxes
Width dimension W
Fits existing box depths from B
4.50 (114.3 mm) to 6.00 inches Depth dimension D
H
25 (152.4 mm) deep. Flange width dimension F
If box is not flush with plaster line,
Optional mounting brackets are
dimension E
26 available if existing enclosure
exceeds 6.00 inches (152.4 mm) deep. Existing Surface-Mounted Box
Boxes shallower than standard may Height dimension H
27 require special collar adapters. Width dimension W
Depth dimension D W
Trims
28 Flange width dimension may be
F or FF as appropriate: Figure 22.6-1. Existing Interior Mounting Studs
Flange width dimension F
29 Flange width dimension FF Plaster Line
F E
Stud Locations
30 In most applications, the existing D
mounting hardware in the enclosure
may be removed, but in some areas,
31 the backpan may need to be attached
Top View (Flush Mounted)

FF
using a minimum of one existing
32 mounting stud to meet local code
D
requirements for grounding.
Confirm with your local electrical
Top View (Surface Mounted)
33 code authority having jurisdiction.
Stud location dimensions: Figure 22.6-2. Existing Box Top View
A _______, B _______ and C _______.
34
Pow-R-Line 1R
Table 22.6-3. Minimum Enclosure Sizing
The trim and door is designed to attach
35 directly to the panelboard Ampere Number of Main Device Minimum Enclosure Dimensions Inches (mm)
Rating Circuits Type Height Width Depth
deadfront assembly so that there
is no external trim-fastening Main Lug Only
36 hardware required. 100 18 MLO 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
The interior backpan or optional 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
37 mounting plates are fastened directly 225 18 MLO 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
to the back of the existing enclosure 30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
using the hardware provided. 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
38 400 18 MLO 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
Neutral and Ground Bus 30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
Integrally mounted Neutral 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
39 assembly Main Breaker
Ground bar and bonding 100 18 BAB, QBHW 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
conductor included 30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
40 Neutral and Ground convertible 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
from left-right 18 EHD, ED, EDH, 30.00 (762.0) 14.00 (355.6) 4.50 (114.3)
30 FDB, FD, HFD 36.00 (914.4) 14.00 (355.6) 4.50 (114.3)
41 Insulated/Isolated ground bus is 42 EDB, EDC, EDS 42.00 (1066.8) 14.00 (355.6) 4.50 (114.3)
available as an option
225 18 ED, EDH, EDB, EDS, 30.00 (762.0) 14.00 (355.6) 4.50 (114.3)
Aluminum is standard, copper is 30 EDC, FD, HFD, FDC 36.00 (914.4) 14.00 (355.6) 4.50 (114.3)
42 available as an option 42 42.00 (1066.8) 14.00 (355.6) 4.50 (114.3)

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-3
January 2018 Pow-R-Line 2R
Sheet 22 073
General DescriptionPow-R-Line 2R

Pow-R-Line 2R Retrofit Eaton offers a factory-assembled Main Lugs Only


22
panelboard interior and trim designed The short-circuit rating of the MLO
Panelboard to bolt directly into an existing enclosure. assembled panelboard will be fully
rated based upon the lowest rated
Custom-built panelboard interiors
branch device, or may be series rated 23
and trims can be provided to retrofit
most any manufacturers existing with an approved upstream device.
panelboard enclosure. Main lugs only ampere ratings: 24
The panelboards are listed and are 100 and 225.
marked with both the Underwriters Main Circuit Breakers
Laboratories (UL) and Canadian 25
The short-circuit rating shown is that
Standards Association (CSA) labels.
of the main breaker only. The short-
Why Retrofit? circuit rating of the assembled 26
Upgrade protective device panelboard is the rating of the lowest
interrupting ratings fully rated main or branch device,
Replacing old, obsolete circuit
or the rating of an approved series 27
rated combination.
breakers with new
Providing additional circuits for Table 22.6-4. Main Circuit Breakers 28
load growth Breaker Breaker Interrupting Rating
Accommodating system change Frame Type (kA Symmetrical)
Pow-R-Line 2R and additions Amperes 240 Vac 480Y/277 Vac 29
Adding ground fault circuit 100 GHB 65 14
General Description interrupters 150 FDB 18 14
225 FDB 65 35 30
Panelboard Ratings Immediate Benefits 225 HFD 100 65
Installation time is dramatically 225 FDC 200 100
Voltage 31
reduced
240 Vac
Disruption of existing power
480Y/277 Vac maximum service is minimal
Less cleanup and wall repair because
32
Main Lugs
100225 A there is no need to cut and break
concrete or finished wall surface 33
Main Breakers
100225 A Table 22.6-5. Branch Circuit Breakers
Branch Breakers Breaker Ampere Number Interrupting Rating (kA Symmetrical)
34
Type Rating of Poles 120 Vac 240 Vac 277 Vac 480Y/277 Vac
15100 A (bolt-on chassis)
Short-Circuit Current Ratings (Symmetrical) GHQ 1520 1 65 14 35
GHB 15100 1 65 14
240 Vac: 10 kA and 22 kA fully rated GHB 15100 2, 3 65 14
240 Vac: 22200 kA series rated GHB-HID 1 1520 1 65 14 36
GHBGFEP 2 1560 1 65 14
Service HGHB 1530 1 65 25
Three-phase, four-wire 480Y/277 Vac 1
2
HID (High Intensity Discharge) rated breaker. 37
Three-phase, four-wire 208Y/120 Vac GHB breaker with 30 ma equipment ground fault protection.
and 240/120 Vac delta Series Rated Combinations The panelboards are listed and are
Single-phase, three-wire 120/240 Vac marked with both the Underwriters
38
Refer to series rating tables beginning
Single-phase, two-wire 120 Vac on Page 22.0-14 for the approved Laboratories (UL) and Canadian
Standards Association (CSA) labels.
Three-phase, three-wire 208 and 240 Vac series rated combinations available 39
for the branch circuit breakers listed
Suitable for service entrance in Table 22.6-5.
applications when specified.
40
Mains
For available mains, refer
to Table 22.6-4. 41
Main breakers, 100 A, Type GHB is
horizontally mounted, same as branch 42
breakers. All other main breakers are
vertically mounted.
43
Branch Circuits
For available branch devices, refer
to Table 22.6-5.

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-4 Panelboards
Pow-R-Line 2R January 2018
Sheet 22 074
Technical Data and SpecificationsPow-R-Line 2R

Technical Data and Specifications Application Guidelines


22 The following dimensions and data Stud
Bussing Locations Front View
are necessary for production of a
100225 A: Tin-plated aluminum
23 is standard, copper is available
panelboard to fit an existing box:
as an option. Existing Flush-Mounted Box A C
Height dimension H
24 Boxes
Width dimension W
Fits existing box depths from B
4.50 (114.3 mm) to 6.00 inches Depth dimension D
H
25 (152.4 mm) deep. Flange width dimension F
If box is not flush with plaster line,
Optional mounting brackets are
dimension E
26 available if existing enclosure
exceeds 6.00 inches (152.4 mm) deep. Existing Surface-Mounted Box
Boxes shallower than standard may Height dimension H
27 require special collar adapters. Width dimension W
Depth dimension D W
Trims
28 Flange width dimension may be
F or FF as appropriate: Figure 22.6-3. Existing Interior Mounting Studs
Flange width dimension F
29 Flange width dimension FF Plaster Line
F E
Stud Locations
30 In most applications, the existing D
mounting hardware in the enclosure
may be removed, but in some areas,
31 the backpan may need to be attached
Top View (Flush Mounted)

FF
using a minimum of one existing
32 mounting stud to meet local code
D
requirements for grounding.
Confirm with your local electrical
Top View (Surface Mounted)
33 code authority having jurisdiction.
Stud location dimensions: Figure 22.6-4. Existing Box Top View
A _______, B _______ and C _______.
34
Pow-R-Line 2R
Table 22.6-6. Minimum Enclosure Sizing
The trim and door is designed to attach
35 directly to the panelboard Ampere Number of Main Device Minimum Enclosure Dimensions Inches (mm)
Rating Circuits Type Height Width Depth
deadfront assembly so that there
is no external trim-fastening Main Lug Only
36 hardware required. 100 18 MLO 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
The interior backpan or optional 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
37 mounting plates are fastened directly 225 18 MLO 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
to the back of the existing enclosure 30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
using the hardware provided. 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
38 Main Breaker
Neutral and Ground Bus
100 18 GHB 21.00 (533.4) 14.00 (355.6) 4.50 (114.3)
Integrally mounted Neutral 30 27.00 (685.8) 14.00 (355.6) 4.50 (114.3)
39 assembly 42 34.00 (863.6) 14.00 (355.6) 4.50 (114.3)
Ground bar and bonding 18 FDB, FD, 30.00 (762.0) 14.00 (355.6) 4.50 (114.3)
conductor included 30 HFD, FDC 36.00 (914.4) 14.00 (355.6) 4.50 (114.3)
40 Neutral and Ground convertible 42 42.00 (1066.8) 14.00 (355.6) 4.50 (114.3)
from left-right 225 18 FD, HFD, FDC 30.00 (762.0) 14.00 (355.6) 4.50 (114.3)
30 36.00 (914.4) 14.00 (355.6) 4.50 (114.3)
41 Insulated/Isolated ground bus is 42 42.00 (1066.8) 14.00 (355.6) 4.50 (114.3)
available as an option
Aluminum is standard, copper is
42 available as an option

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-5
January 2018 Pow-R-Line 1aF
Sheet 22 075
General DescriptionPow-R-Line 1aF

Pow-R-Line 1aF Mains Table 22.6-7. Main Circuit Breakers


22
For available mains, refer Breaker Breaker Interrupting Rating
to Table 22.6-7. Frame Type (kA Symmetrical)
Amperes at 240 Vac
Main breakers are vertically mounted.
100 EDB 22
23
Branch Circuits 100 EDS 42
100 ED 65
For available branch devices, refer
100 FD 65
24
to Table 22.6-8. 100 FDE 65
100 EDH 100
Application Description 100 HFD 100 25
For use on high fault current systems 100 HFDE 100
requiring lighting panels, selectively 225 EDB 22
coordinated systems and laboratories 225 EDS 42 26
and testing stations where overcur- 225 ED 65
rent protection below 15A is required. 225 FD 65
Pow-R-Line 1aF 225 FDE 65 27
Main Lugs Only 225 EDH 100
General Description The short-circuit rating of the MLO 225 HFD 100
assembled panelboard will be fully 225 HFDE 100 28
Panelboard Ratings rated based upon the upstream device. 400 DK 42
400 KD 65
Voltage Main lugs only ampere ratings: 400 HKD 100 29
240 Vac maximum 100, 225 and 400. 400 KDC 200
400 LHH 200
Main Lugs Main Circuit Breakers 30
100400 A The short-circuit rating shown is that Table 22.6-8. Branch Overcurrent Devices
of the main breaker only. The short Hybrid breaker/fuse (Class CC) branch
Main Breakers circuit rating of the assembled panel- device 1 31
100400 A board is the rating of the lowest fully Ampere Interrupting Breaker
rated main or branch device or the Rating Rating Type
Branch Devices rating of an approved series rated 32
30 A 30 200 Hybrid
combination
1 Class CC fuses are required, 30A maxi-
Hybrid breaker and fuse
Class CC fuses, 30 A maximum
mum. Fuses are not supplied by Eaton.
33
Short-Circuit Current Ratings (Symmetrical)
240 Vac: 200 kA fully rated 34
Service
Three-phase, four-wire 208Y/120 V 35
and 240/120 V delta
Single-phase, three-wire 120/240 V
Single-phase, two-wire 120 V
36
Three-phase, three-wire
208 and 240 V 37
Suitable for service entrance
applications when specified.
38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-6 Panelboards
Pow-R-Line 1aF January 2018
Sheet 22 076
Technical Data and SpecificationsPow-R-Line 1aF

Technical Data and Specifications Box Sizing and Selection 3. Using correct table, type of mains
22 Box size for all Type 1 panelboards
and ampere rating per Step 1, find
Bussing total number of poles.
are available from Table 22.6-10.
100400 A: Tin-plated aluminum
23 is standard, copper is available Instructions
Note: Where total number of poles (Step 2)
fall between number in table, use the next
as an option. 1. Select the rating and type of higher number.
24 mains required.
Boxes 4. Read box size across columns to
Boxes are made from code-gauge 2. Count total number of branch the right.
galvanized steel. circuit poles (including spaces)
25 required in the panelboard. Do Top and Bottom Gutters (minimum)
Blank ends are supplied as standard, not count main breaker poles. 5.50 inches (139.7 mm).
knockouts are available upon request.
26 Trim
Side Gutters
28.00-inch (508.0 mm) wide box:
Trims are made from code-gauge steel 6.50 inches (165.1 mm).
27 and painted ANSI 61 gray Type YS.
Modifications Table 22.6-10. Type 1 PanelboardsDimensions in Inches (mm)
28 Table 22.6-9. Through-Feed Lugs Ampere Main Breaker Maximum Box Dimensions
Ampere Rating Information Rating Type Number Height Width Depth
of Mains Mounting of Branch
100 See Table 22.6-14
29 225 See Table 22.6-14
Position Circuits
Including
400 See Table 22.6-14 Provisions

30 Ground Bar 100 A


100 A EHD, FDB, FD, 18 36.00 (914.4) 28.00 (711.2) 5.75 (146.1)
Standard bolted in box. Aluminum Main lugs or FDE, HFD, FDC, 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
is standard, copper is available as main breaker HFDE 42 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
31 an option. Vertical 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
100 A EHD, FDB, FD, 18 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
Enclosures Main lugs or main FDE, HFD, FDC, 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
32 Type 1. breaker with 100A HFDE 42 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
through-feed lugs Vertical 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
225 A
33 225 A EDB, EDS, ED, 18 36.00 (914.4) 28.00 (711.2) 5.75 (146.1)
Main lugs or EDH, EDC, 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
main breaker FD, HFD, FDC, 42 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
34 FDE, HFDE 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
Vertical
225 A EHD, FDB, FD, 18 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
35 Main lugs or HFD, FDE 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
main breaker FDC, EDB, EDS, 42 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
with 225 or 100 A HFDE 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
through-feed lugs ED, EDH, EDC
36 Vertical
400 A
37 400 A
Main lugs or
DK, KD,
HKD, KDC, LHH
18
30
60.00 (1524.0)
60.00 (1524.0)
28.00 (711.2)
28.00 (711.2)
5.75 (146.1)
5.75 (146.1)
main breaker Vertical 42 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
48 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
38

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-7
January 2018 Pow-R-Line 2aF
Sheet 22 077
General DescriptionPow-R-Line 2aF

Pow-R-Line 2aF Application Description Table 22.6-11. Main Circuit Breakers


22
For use on high fault current systems Breaker Breaker Interrupting Rating
Frame Type (kA Symmetrical)
requiring lighting panels, selectively Amperes at 480Y/277 Vac
coordinated systems and laboratories 23
and testing stations where overcurrent 100 FD, FDE 35
protection below 15 A is required. 100 HFD, HFDE 65
100 FDC 100
Mains 225 FD, FDE 35
24
For available mains, refer 225 HFD, HFDE 65
225 FDC, HFDE 100
to Table 22.6-11. 25
400 KD 35
Branch Circuits 400 HKD 65
400 KDC 100
For available branch devices, refer
to Table 22.6-12.
400 LHH 100 26
Main Lugs Only Table 22.6-12. Branch Overcurrent Devices
Pow-R-Line 2aF The short-circuit rating of the MLO
Hybrid breaker/fuse (Class CC) branch 27
device 1
assembled panelboard will be fully
Ampere Interrupting Breaker
General Description rated based upon the lowest rated
Rating Rating Type 28
branch device or may be series rated
Panelboard Ratings with an approved upstream device. 30 200 Hybrid

Voltage Main lugs only ampere ratings:


1 Class CC fuses are required, 30A maximum.
Fuses are not supplied by Eaton.
29
240 Vac 100, 225 and 400.
480Y/277 Vac maximum Main Circuit Breakers 30
Main Lugs The short-circuit rating shown is that
100400 A of the main breaker only. The short-
circuit rating of the assembled 31
Main Breakers panelboard is the rating of the lowest
100400 A fully rated main or branch device
or the rating of an approved series 32
Branch Devices rated combination.
30 A (bolt-on)
Hybrid breaker and fuse
33
Class CC fuses, 30 A maximum

Short-Circuit Current Ratings (Symmetrical) 34


480Y/277 Vac: 200 kA fully rated
Service 35
Three-phase, four-wire 480Y/277 V
Suitable for service entrance 36
applications when specified.
37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-8 Panelboards
Pow-R-Line 2aF January 2018
Sheet 22 078
Technical Data and SpecificationsPow-R-Line 2aF

Technical Data and Specifications Box Sizing and Selection 3. Using correct table, type of mains
22 Box size for all Type 1 panelboards are
and ampere rating per Step 1, find
Bussing total number of poles.
available from Table 22.6-14.
100400 A: Tin-plated aluminum is
23 standard, copper is available Instructions
Note: Where total number of poles (Step 2)
fall between number in table, use the next
as an option. 1. Using description on the required higher number.
24 panelboard, select the rating and
Boxes 4. Read box size across columns to
type of mains required.
Boxes are made from code-gauge the right.
galvanized steel. 2. Count total number of branch
25 circuit poles (including spaces)
Top and Bottom Gutters (Minimum)
Blank ends are supplied as standard, required in the panelboard. Do 5.50 inches (139.7 mm).
knockouts are available upon request. not count main breaker poles.
26 Side Gutters
Trim 20.00-inch (508.0 mm) wide box:
Trims are made from code-gauge steel 5.50 inches (139.7 mm).
27 and painted ANSI 61 gray, Type YS.
Modifications
Table 22.6-14. Type 1 PanelboardsDimensions in Inches (mm)
28 Table 22.6-13. Through-Feed Lugs
Ampere Rating Information Ampere Main Breaker Type Maximum Box Dimensions
Rating Mounting Number Height Width Depth
of Mains Position of Branch
29 100
225
See Table 22.6-14
See Table 22.6-14 Circuits
400 See Table 22.6-14 Including
Provisions
30 Ground Bar 100 A Panelboards
Standard bolted in box. Aluminum 100 A FDB, FD, FDE 18 36.00 (914.4) 28.00 (711.2) 5.75 (146.1)
is standard. Copper is available as Main lugs or HFD, FDC, HFDE 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
31 an option.
main breaker Vertical 42 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
Enclosures 100 A FDB, FD, FDE 18 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
32 Type 1.
Main lugs or main HFD, FDC, HFDE 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
breaker with 100 A Vertical 42 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
through-feed lugs 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
33 225 A Panelboards
225 A FD, HFD, FDC, FDE, 18 36.00 (914.4) 28.00 (711.2) 5.75 (146.1)
Main lugs or HFDE 30 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
34 main breaker Vertical 42
48
48.00 (1219.2)
60.00 (1524.0)
28.00 (711.2)
28.00 (711.2)
5.75 (146.1)
5.75 (146.1)
225 A FDB, FD, FDE 18 48.00 (1219.2) 28.00 (711.2) 5.75 (146.1)
35 Main lugs or main
breaker with 100 A
HFD, FDC, HFDE
Vertical
30
42
48.00 (1219.2)
60.00 (1524.0)
28.00 (711.2)
28.00 (711.2)
5.75 (146.1)
5.75 (146.1)
through-feed lugs 48 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
400 A Panelboards
36
400 A DK, KD, 18 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
Main lugs or HKD, KDC, LHH 30 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
main breaker Vertical 42 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
37 48 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
400 A DK, KD, Main 18 60.00 (1524.0) 28.00 (711.2) 5.75 (146.1)
Main lugs or main LHH 30 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
38 breaker with 100 A HKD, KDC 42 72.00 (1828.8) 28.00 (711.2) 5.75 (146.1)
through-feed lugs Vertical 48 90.00 (2286.0) 28.00 (711.2) 5.75 (146.1)

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-9
January 2018 Pow-R-Line 3FQS
Sheet 22 079
General DescriptionPow-R-Line 3FQS

Pow-R-Line 3FQS 240 V, three-phase, three-wire Communication systems


480 V, three-phase, three-wire Ventilation and smoke 22
600 V, three-phase, three-wire removal systems
Critical industrial processes
208/120 V, three-phase, four-wire 23
480/277 V, three-phase, four-wire Data centers
600/347 V, three-phase, four-wire Other critical or sensitive loads
240/120 V, three-phase, four-wire 24
Technical Data and Specifications
480/240 V, three-phase, four-wire
Table 22.6-15. Main Lugs Only
120/240 Vac, single-phase, three-wire
Ampere Standard Mechanical
25
208Y/120 Vac, three-phase, four-wire
Rating Lug Wire Range
240 delta/120 Vac, three-phase,
four-wire 100 (1) #1300 kcmil 26
200 (1) #1300 kcmil
480Y/277 Vac, three-phase, four-wire 400 (1) #4600 kcmil
600Y/347 Vac, three-phase, four-wire 27
240 delta Vac, three-phase, three-wire Table 22.6-16. Main Fused Switch
480 delta Vac, three-phase, three-wire (Class J Fuses Only)
600 delta Vac, three-phase, three-wire Ampere Standard Mechanical 28
Rating Lug Wire Range
Pow-R-Line 3FQS 25 Vdc
100 (1) #1300 kcmil
General Description Branch Overcurrent Devices 200 (1) #1300 kcmil 29
400 (1) #4600 kcmil
The Pow-R-Line 3FQS is a fusible Eaton Bussmann Type CCPB
(compact circuit protector base)
lighting panel designed for high fault Table 22.6-17. Main Non-Fused Switch 30
current applications where circuit 15100 A
Ampere Standard Mechanical
breakers may not meet the application. Single-, two- and three-pole Rating Lug Wire Range
This panel is ideal when the selective Branch fuses: Bussmann TCF or 31
coordination mandates apply. Designed FCF CUBEFuse 100 (1) #1300 kcmil
for use with Eatons Bussmann 200 (1) #1300 kcmil
400 (1) #4600 kcmil
CUBEFuse, the panel will selectively Short-Circuit Current Ratings 32
coordinate with the maximum available 50 kAIC symmetrical standard
fault current. The PRL 3FQS is ideal
Up to 200 kAIC symmetrical when
for control circuits below 15 A.
appropriate upstream overcurrent 33
Panelboard Ratings device is applied

Listings Main Bus and Branch Connectors 34


UL 67 panelboard chassis Tin plated, copper bus and
UL 50 listed box and trim
branch connectors
35
UL 98 listed fusible switches Enclosures Branch Disconnects
NEMA Type 1
Voltage 36
600 Vac maximum NEMA Type 3R Options
125 Vdc maximum Branch Circuit Spaces Loadside Chassis
(80A maximum branch) 18, 30 and 42 circuit chassis Feed-thru lugs
37
Mains Incoming Line Sub-feed lugs
Main lugs: 30400 A Top or bottom Sub-feed fused switch 38
Main fusible switch: 30400 A Surge protective device
Main non-fused switch: 30400 A
Spare Fuse Compartment
Provisions for six spare Service Equipment 39
Voltage Systems CUBEFuses, standard Labeled suitable for use as service
120 V, single-phase, two-wire equipment (bonded neutral)
240 V, single-phase, two-wire
Seismic Qualifications 40
Qualified for International Building Neutrals
240 V, single-phase, two-wire Code (IBC) categories and site class A, Isolated neutral
no neutral B, C and D. Bonded neutral 41
277 V, single-phase, two-wire
200% rated neutrals
120/240 V, single-phase, three-wire Application Description
208/120 V, single-phase, three-wire Hospitals Ground Bars 42
480/240 V, single-phase, three-wire Bonded neutral
Surgery centers
Isolated neutral
277/480 V, single-phase, three-wire Emergency systems 43
480 V, single-phase, two-wire Fire stations Special Trims
no neutral Police stations Door-in-door
Laboratories No trim

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-10 Panelboards
Pow-R-Line 3FQS January 2018
Sheet 22 080
Technical Data and SpecificationsPow-R-Line 3FQS

Table 22.6-18. Branch Circuit Disconnects Compact Circuit Protector Base (CCPB)
22 CCPB 1 Part Number Fuse Ampere Maximum CCPB Non-Indicating Indicating Fuses
Number of Poles Range Ampacity Fuses (Standard) (Optional) 2

23 CCPB-1-15CF
CCPB-2-15CF
1
2
115
115
15
15
TCF1RN, TCF3RN,
TCF6RN, TCF10RN,
TCF6, TCF10,
TCF15
CCPB-3-15CF 3 115 15 TCF15RN

24 CCPB-1-20CF
CCPB-2-20CF
1
2
17.520
17.520
20
20
TCF17-1/2RN,
TCF20RN
TCF17-1/2,
TCF20
CCPB-3-20CF 3 17.520 20
CCPB-1-30CF 1 2530 30 TCF25RN, TCF25,
25 CCPB-2-30CF 2 2530 30 TCF30RN TCF30
CCPB-3-30CF 3 2530 30
CCPB-1-40CF 1 3540 40 TCF35RN, TCF35,
26 CCPB-2-40CF 2 3540 40 TCF40RN TCF40
CCPB-3-40CF 3 3540 40
CCPB-1-50CF 1 4550 50 TCF45RN, TCF45,
27 CCPB-2-50CF 2 4550 50 TCF50RN TCF50
CCPB-3-50CF 3 4550 50
CCPB-1-60CF 1 60 60 TCF60RN TCF60
28 CCPB-2-60CF 2 60 60
CCPB-3-60CF 3 60 60
CCPB-1-70CF 1 1 70 70 TCF70RN TCF70
29 CCPB-2-70CF 2
CCPB-3-70CF 3
2
3
70
70
70
70
CCPB-1-90CF 1 8090 90 TCF80RN, TCF80,
30 CCPB-2-90CF
CCPB-3-90CF
2
3
8090
8090
90
90
TCF90RN TCF90

CCPB-1-100CF 1 100 100 TCF100RN TCF100


31 CCPB-2-100CF
CCPB-3-100CF
2
3
100
100
100
100
1 CCPB disconnect can accept CUBEFuses with ampere ratings less than or equal to the ampere rating of the CCPB disconnect.
2
32 Correct fit with CCPB disconnect requires indicating CUBEFuses with date code R38 or later.
Note: Spare or replacement CCPB available only from authorized Eaton Bussmann distributors.

NEMA Type 1 Box Options Chassis mounts directly onto Table 22.6-21. CCPB Horsepower Ratings
33 enclosure studs in the enclosure
No knockouts (standard) CCPB Ampere Horsepower
Knockouts, both top and bottom Trim finished with gray powder Disconnect Rating Rating at Vac
34 (optional) coat paint over phosphatized steel 120 240 480 600
(ANSI 61) with door
Knockouts, top or bottom (optional) CCPB 15 0.5 3 5 7.5
Circuit directory card is located (Poles)-15CF
35 Replacement Fuses on the inside of the door CCPB 20 0.75 3 7.5 10
Replace only with Bussmann Concealed trim screws (Poles)-20CF
fuses of the same type and size CCPB 30 1.5 5 15 10
36 Contact your authorized
NEMA Type 3R Outdoor (Optional) (Poles)-30CF
Eaton Bussmann distributor Surface mount only CCPB 40 2 7.5 20 10
for replacement fuses Finished with gray powder coat (Poles)-40CF
37 Nameplates paint over phosphatized steel CCPB 50 3 7.5 20 10
(ANSI 61) (Poles)-50CF
Permanent circuit numbering
Bottom feed only, no knockouts CCPB 60 3 7.5 20 10
38 (Poles)-60CF
Box Sizing and Selection Table 22.6-20. NEMA Type 3R Outdoor CCPB 70 3 15 30 40
Box SizesDimensions in Inches (mm) (Poles)-70CF
39 Enclosures
Width Depth Height CCPB 80 5 20 40 50
NEMA Type 1 Indoor (Poles)-90CF
20.00 (508.0) 7.75 (196.9) 34.50 (876.3)
40 Flush mount or surface mount CCPB 100 5 20 50 50
20.00 (508.0) 7.75 (196.9) 51.50 (1308.1) (Poles)-100CF
Galvanized steel with removable
20.00 (508.0) 7.75 (196.9) 60.50 (1536.7)
end wallsblank or with knockouts
41 (specify on order) 20.00 (508.0) 7.75 (196.9) 70.50 (1790.7)

Table 22.6-19. NEMA Type 1 Box Sizes Chassis mounts directly onto studs
Dimensions in Inches (mm) in the enclosure
42
Width Depth Height Gasketed door has vault handle
with lock
20.00 (508.0) 5.75 (146.1) 33.00 (838.2)
43 20.00 (508.0) 5.75 (146.1) 50.00 (1270.0)
Circuit directory card is located
on the inside of the door
20.00 (508.0) 5.75 (146.1) 59.00 (1498.6)
Contact Eaton for other
20.00 (508.0) 5.75 (146.1) 69.00 (1752.6) enclosure types

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-11
January 2018 Elevator Control Panelboard
Sheet 22 081
General DescriptionElevator Control Panelboard

Elevator Control Panelboard Standards Codes


22
The Elevator Control Panelboard The Elevator Control Panelboard is
meets and is listed to the following designed to meet the following codes:
standards:
UL 67 listed panelboard
NFPA 70 (National Electrical Code) 23
NFPA 72 (National Fire Alarm Code)
UL 50 listed enclosure
ANSI/ASME A17.1 (Safety Code
UL 98 listed fusible elevator for Elevators and Escalators) 24
control fusible switches NFPA 13 (Installation of
Options Sprinkler Systems) 25
Integrated Surge Protective Device Selective Coordination
(SPD) 100400 kA Eatons Elevator Control Panelboard
Specialized control to meet has superior selective coordination
26
local codes properties. When paired with the
appropriate upstream fusing, the 27
Elevator Control Panelboard
Application Description elevator control panelboard can
The Elevator Control Panelboard selectively coordinate with higher
General Description is designed to replace multiple fault current levels. All fuses must 28
components provided in elevator be of the same manufacturer. Consult
Ratings control rooms, thus consolidating the specific fuse manufacturers data
240 Vac and 600 Vac and standardizing this area. With the for selective coordination values. 29
Three-phase, three-wire and ability to control up to four elevators
Surge Protective Device (SPD)
three-phase, four-wire in a common shaft, the Elevator
Control Panelboard offers the needed Surge Protective Devices (SPD) may 30
200 kA short-circuit current ratings be integrated into all Elevator Control
controls in a space-saving design
while allowing access by the various Panelboards. Because most installa-
Main Lugs Only
trades involved with the installation. tion calls for SPDs, integrating an 31
800 A maximum Eaton SPD ensures proper installation
Not only does the Elevator Control and significantly limits destructive
Branch Devices
Panelboard provide electrical feeds, it let-through beyond all size-mounted 32
30200 A, 240 Vac and 600 Vac fused also contains necessary components solutions. Please see Section 36 for
switch to feed the elevator for the control of the elevator and the more information.
Elevator Controls Standard Features fire alarm system. 33
Factory wired from switch Table 22.6-22. Elevator Feeder Devices
to controls
200 kA rms short-circuit
Ampere Fuse Class Short-Circuit Current Rating (kAIC Symmetrical) 34
Rating 240 Vac 600 Vac
current rating
120 Vac shunt trip 30 Class J 200 200
35
60 Class J 200 200
Ground termination
100 Class J 200 200
Branch fusible switch 200 Class J 200 200
Class J fuse clips on switch 36
(fuses not included) Table 22.6-23. Box Sizing and SelectionDimensions in Inches (mm)
100 VA Control Power Transformer
(CPT) with 120 Vac secondary
Ampere
Rating
Number of Dimensions
Elevators Without SPD
37
With SPD
CPT primary and secondary fusing Width Height Width Height
Selection of primary CPT voltages
400 2 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
38
Fire safety interface relay with 400 3 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
user-selected coil voltage 400 4 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
Fire alarm voltage monitoring relay 600 2 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
39
Keyed test switch 600 3 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
600 4 40.00 (1016.0) 57.00 (1447.8) 40.00 (1016.0) 73.00 (1854.2)
ON pilot light; user selects color
800 3 40.00 (1016.0) 73.00 (1854.2) 40.00 (1016.0) 73.00 (1854.2) 40
800 4 40.00 (1016.0) 73.00 (1854.2) 40.00 (1016.0) 73.00 (1854.2)

Note: Dimensions reflect NEMA Type 1 enclosures. 41


All boxes are 11.31 inches (287.3 mm) deep.

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-12 Panelboards
Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications January 2018
Sheet 22 082
General DescriptionTypes PRL1a, 2a, 3a, 3E, 4 and Column Modifications

22 Types PRL1a, 2a, 3a, 3E, 4 and


Column Modifications
23

24

25

26
Types PRL1a, 2a, 3a, 3E, 4 and Column

27 Modifications Selection Guide


Table 22.6-24. ModificationsAlphabetical Index
28 Modification Available on Panelboard Types
PRL1a PRL2a PRL3a PRL3E PRL4B PRL4F Column Type
29 Ambient compensating breakers No No Yes No Yes No
Bus density Yes Yes Yes Yes Yes Yes Yes

30 Cabinetsspecial: Types 2, 3R, 4, 4X, 12 Yes Yes Yes Yes Yes Yes No
Complete assembly Yes Yes Yes Yes Yes Yes Yes
Compression type lugs, mains only Yes Yes Yes Yes Yes Yes Yes
31 Concealed trim clamps (LT trim) Yes Yes Yes Yes No No No
Conduit covers Yes Yes Yes Yes Yes Yes No
Copper lugs Yes Yes Yes Yes Yes Yes Yes
32 Copper main bus Yes Yes Yes Yes Yes Yes Standard
Directory framemetal Yes Yes Yes Yes Yes Yes No
33 Doors, special Yes Yes Yes Yes Yes Yes Yes
Electronic trip units No No No Yes Yes No
Fungus-proof Yes Yes Yes Yes Yes Yes Yes
34 Ground bar Yes Yes Yes Yes Yes Yes Yes
Ground fault protection (zero sequence) No No No No Yes Yes No
35 Handle lockoff device Yes Yes Yes Yes Yes Std. Yes
Hinges, special (LT trim) Yes Yes Yes Yes Yes Yes No
Increased dimensions Yes Yes Yes Yes No No No
36 Increased panel bus rating Yes Yes Yes Yes No No No
Interiors to fit existing boxes Yes Yes Yes Yes Yes Yes No

37 Locks, special (LT trim) Yes Yes Yes Yes Yes Yes No
Metering devices No No No Yes Yes Yes No
Molded-case switches Yes Yes Yes Yes Yes No Yes
38 Nameplates engraved Yes Yes Yes Yes Yes Yes Yes

39

40

41

42

43

For more information, visit: www.eaton.com/consultants CA08104001E


Panelboards 22.6-13
January 2018 Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications
Sheet 22 083
General DescriptionTypes PRL1a, 2a, 3a, 3E, 4 and Column Modifications

Table 22.6-24. ModificationsAlphabetical Index (Continued)


Modification Available on Panelboard Types 22
PRL1a PRL2a PRL3a PRL3E PRL4B PRL4F Column Type

Neutral rated 200% Yes Yes Yes Yes Yes Yes Yes 23
Painting and special coating Yes Yes Yes Yes Yes Yes Yes
Permanent circuit numbers Yes Yes Yes Yes Yes Yes Yes
Remote control switches (ASCO 920) No No Yes Yes No No No
24
Service entrance Yes Yes Yes Yes Yes Yes No
Shunt trips Yes Yes Yes Yes Yes Yes Yes 25
Split bus or meter loop No No Yes No No No No
Sub-feed breakers Yes Yes Yes Yes No No Yes
Sub-feed lugs Yes Yes Yes Yes Yes Yes No
26
Sub-metering, IQ Energy Sentinel No No No No Yes No No
Surge protective device (SPD) Yes Yes Yes Yes Yes Yes No 27
Tamperproof screws (LT trim) Yes Yes Yes Yes Yes Yes Yes
Terminals, copper only for breakers Yes Yes Yes Yes Yes Yes
Through-feed lugs Yes Yes Yes Yes Yes Yes Yes 28
Time clock space only Yes Yes Yes Yes No
Touchup paint Yes Yes Yes Yes Yes Yes Yes
29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

CA08104001E For more information, visit: www.eaton.com/consultants


22.6-14 Panelboards
January 2018
Sheet 22 084