Вы находитесь на странице: 1из 6

www.comfortstarusa.

com

Air Conditioning and Heating

ADH2
14 SEER • High Efficiency • R410a

SPECIFICATION sheet
SPECIFICATION sheet

ADH2
14 SEER • High Efficiency • R410a

Split System Heat Pump


Standard features: Cabinet features:
• R410a system • Heavy gauge galvanized steel with gray
• Copeland Scroll compressor powder paint finish
• Compact design for easy installation and transportation • Fully louvered removable coil guard to protect
• Ultra quiet condenser surface
• Factory installed liquid line filter drier • Easy access to service valves and
• Pre-charged R410a good for 25' of lineset electrical connections
• Brass liquid and suction service valves • Easy access to fan motor without
with sweat connections disconnecting wires
• Contactor with lug connections
• Ground lug connection
• Terminal block provided for low voltage connections
• High and low pressure switch included
• Crankcase heater is included General Terms of Limited Warranty
• Copper Tube-Aluminum Fin Coil used on all models ComfortStar USA warrants that our products
• ARI certified conform to the manufacturer specifications and
• ETL listed will be free of defects in material and workmanship
under normal use and maintenance.

For complete details of the limited warranty, including applicable


terms and conditions, see your local distributor or contact the
manufacturer for a copy.

Model Number Identification

Before proceeding with installation, refer to


ADH2 18 410
14 SEER capacity R410a
installation instructions packaged with each series air 18,000 (Btu/h)
model, as well as complying with all federal, conditioner
state, provincial, and local codes, regulations second
and practices. generation

 ComfortStar Air Conditioning & Heating


Condensing Unit Refrigerant Line Set Information
Suction line Sizing

Unit Size 1 1/2 Ton 2 Ton 2 1/2 Ton 3 Ton 3 1/2 Ton 4 Ton 5 Ton

Suction Line Connection Size standard 3/4" I.D.* 3/4" I.D.* 3/4" I.D.* 3/4" I.D.* 3/4" I.D.* 7/8" I.D.* 7/8" I.D.*
Suction Line Run - Feet optional 5/8" 5/8" 5/8" 5/8" 5/8" 3/4" 1 1/8"

Capacity Factor
standard 1.00 1.00 1.00 1.00 1.00 1.00 0.99
25'
optional 1.00 1.00 1.00 1.00 1.00 1.00 1.00

standard 0.98 0.98 0.98 0.99 0.98 0.98 0.98


50'
optional 0.97 0.97 0.97 0.97 0.98 0.98 0.99

standard 0.95 0.95 0.96 0.97 0.97 0.97 0.94


100'
optional 0.94 0.94 0.94 0.94 0.95 0.95 0.98

standard 0.92 0.92 0.93 0.96 0.96 0.96 0.90


150'
optional 0.90 0.90 0.90 0.90 0.91 0.92 0.97
Notes: * Standard size. Using suction line larger than shown in chart will result in poor oil return and is not recommended.

Liquid line Sizing


Liquid Line Size
Line Size Outdoor Unit above or below indoor coil
Liquid Line
System Compressor Connection and Total Equivalent Length - Feet
Connection Size
Capacity Type Line Size
(inch I.D.) 25 50 75 100 125 150
(inch I.D.)
Maximum Vertical Separation - Feet
1 1/2 Ton 3/8" Scroll 1/4 25 40 25 9 N/A N/A
5/16 25 50 62 58 53 49
3/8* 25 50 75 72 70 68
2 Ton 3/8" Scroll 1/4 23 N/A N/A N/A N/A N/A
5/16 25 36 29 23 16 9
3/8* 25 50 72 70 68 65
2 1/2 Ton 3/8" Scroll 1/4 25 N/A N/A N/A N/A N/A
5/16 25 49 38 27 17 6
3/8* 25 50 68 65 62 58
5/16 25 50 37 22 7 N/a
3 Ton 3/8" Scroll
3/8* 25 50 68 63 58 53
5/16 25 23 4 N/A N/A N/A
3 1/2 Ton 3/8" Scroll
3/8* 25 50 43 36 30 24
3/8* 25 46 38 30 22 15
4 Ton 3/8" Scroll
1/2 25 50 56 55 53 52

3/8* 25 50 56 44 32 20
5 Ton 3/8" Scroll
1/2 25 50 75 81 79 76

Notes: * Standard size. N/A Application not recommended

ComfortStar Air Conditioning & Heating 


Electrical And Physical Data
Dimensions

NOTE: LOUVER APPEARANCE


MAY VARY

ACCESS VALVE
FOR LOW PRESSURE

ONLY ON FOR
HEAT PUMP FUNCTION

SUCTION LINE
CONNECTION

Dimensional Data
Refrigerant Connection
Dimensions (inches)
Unit Model (Btu/h) Service Valve Size
“H” in (mm) “W” in (mm) “L” in (mm) Liquid Suction

1 1/2 Ton (Cooling Unit) 24-15/16 (633) 21-7/8 (554) 21-7/8 (554) 3/8 3/4

1 1/2 Ton (Heat Pump Unit) 24-15/16 (633) 23-5/8 (600) 23-5/8 (600) 3/8 3/4

2 Ton 24-15/16 (633) 23-5/8 (600) 23-5/8 (600) 3/8 3/4

2 1/2 Ton 24-15/16 (633) 28 (710) 28 (710) 3/8 3/4

3 Ton 24-15/16 (633) 29-1/8 (740) 29-1/8 (740) 3/8 3/4

3 1/2 Ton 29-7/8 (759) 28 (710) 28 (710) 3/8 3/4

4 Ton 33-3/16 (843) 28 (710) 28 (710) 3/8 7/8

5 Ton 33-3/16 (843) 29-1/8 (740) 29-1/8 (740) 3/8 7/8

 ComfortStar Air Conditioning & Heating


Specifications

Model ADH2-18-410 ADH2-24-410 ADH2-30-410 MHH-36-410 MHH-42-410 MHH-48-410 ADH2-60-410

208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V


Power supply V-Ph-Hz
1Ph 60Hz 1Ph 60Hz 1Ph 60Hz 1Ph 60Hz 1Ph 60Hz 1Ph 60Hz 1Ph 60Hz
Capacity Btu/h 18000 23200 29000 36000 42000 48000 57000
Cooling
SEER Btu/h.W 14.00 14.00 14.00 14.00 14.00 14.00 14.00
Capacity Btu/h 18000 22000 29800 34600 40000 48000 56000
Heating
HSPF Btu/h.W 7.8 7.8 8.3 8.3 8.3 8.3 8.3
ZP16K5E-PFV- ZP20K5E-PFV- ZP25K5E-PFV- ZP31K5E-PFV- ZP36K5E-PFV- ZP42K5E-PFV- ZP51K5E-PFV-
Model
130 130 130 130 130 130 130
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Brand Copeland Copeland Copeland Copeland Copeland Copeland Copeland
Compressor Rated current (RLA) A 7.3 9.1 11.1 13.5 17.5 18.6 21.8
Locked rotor
A 48 58.3 73 79 112 117 134
Amp (LRA)
Capacitor uF 30 35 40 45 45 70 70
Crankcase W 30 30 30 30 30 30 30
Type PSC Motor PSC Motor PSC Motor PSC Motor PSC Motor PSC Motor PSC Motor
Horse Power HP 1/12 1/12 1/6 1/6 1/3 1/3 1/3
Outdoor
Rated current A 0.61 0.61 0.96 0.96 1.7 1.7 1.7
Fan Motor
Capacitor uF 6 6 6 6 15 15 15
Speed RPM 1075 1075 825 825 1075 1075 1075
Outdoor Type Axial flow fan Axial flow fan Axial flow fan Axial flow fan Axial flow fan Axial flow fan Axial flow fan
Fan blade Diameter inch 18-7/8 18-7/8 23 23-5/8 23 23 23-5/8
Outdoor air flow CFM 1600 1600 3100 3300 4300 4300 4500
Outdoor sound level dB(A) 57 57 62 63 67 67 66
23-5/8"× 23-5/8"× 28"× 29-1/8"× 28"× 28"× 29-1/8"×
Body (WxHxD) inch 24-15/16"× 24-15/16"× 24-15/16"× 24-15/16"× 29-7/8"× 33-3/16"× 33-3/16"×
23-5/8" 23-5/8" 28" 29-1/8" 28 28" 29-1/8"
Dimensions 24-3/4"× 24-3/4"× 29"× 30-1/4"× 29"× 29"× 30-1/2"×
Packing (WxHxD) inch 26-1/4"× 26-1/4"× 26-1/4"× 26-1/4"× 31-1/4"× 34-1/2"× 34-1/2"×
24-3/4" 24-3/4" 29" 30-1/4" 29" 29" 30-1/2"
Net/Gross weight lbs 130/141 134/145 165/176 172/185 200/216 213/223 240/255
Charged refrigerant type Ozs R410a/112 R410a/123 R410a/137 R410a/129 R410a/150 R410a/167 R410a/172
Refrigerant
Liquid/Suction inch 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4 3/8 / 3/4 3/8 / 7/8 3/8 / 7/8
piping
MCA A 9.7 12 14.9 18 23.6 24.7 29.1
MOP A 15 20 30 30 40 40 50
Min/Max V V 197/253 197/253 197/253 197/253 197/253 197/253 197/253
Electrical Conduit Size Inch 1/2"/3/4"/1" 1/2"/3/4"/1" 1/2"/3/4"/1" 1/2"/3/4"/1" 1/2"/3/4"/1" 1/2"/3/4"/1" 1/2"/3/4"/1"

Wire size should be determined in accordance with National Electrical Code


Must use time-delay fuses or HACR type circuit breaker

ComfortStar Air Conditioning & Heating 


Outdoor Condenser Units
Outdoor Indoor Air Handler Cooling Capacity SEER Rating EER Rating Heating @47F Heating @17F HSPF
ADH2-18-410 HD2-18 + TXV 18000 14 11.35 18000 10100 7.8
HD2-24 +TXV 22400 13.5 11.35 22000 13100 7.8
ADH2-24-410
HD2-25 23200 14 11.65 22000 13100 7.8
ADH2-30-410 HD2-31 29000 14 11.65 29800 17500 8.3
MHH-36-410 HD2-36 +TXV 36000 14 10.95 34600 21200 8.3
HD2-42 +TXV 42000 13.5 11.25 40000 23800 8.3
MHH-42-410
HD2-43 42000 14 11.5 40000 23800 8.3
MHH-48-410 HD2-48 +TXV 48000 14 11.2 48000 29200 8.3
HD2-60 +TXV 57000 13.5 11.1 56000 32400 8.3
ADH2-60-410
HD2-61 + TXV 57000 14 11.2 56000 32400 8.3

Part Number of TXV


installation kit
Air handler Model Number TXV Installation Kit
HD2-18 TR6-3TONB
HD2-24 TR6-3TONB
HD2-36 TR6-4TON
HD2-42 TR6-4TON
HD2-48 TR6-5TON
HD2-60 TR6-6TON
HD2-61 TR6-6TON

Field Installed Optional Accessories


Thermostats:
CP series:
Horizontal non-programmable
or programmable thermostat

iSTAT series: CVT series:


Wireless Remote Control Vertical
Thermostat non-programmable CDT series: Touch Screen
thermostat programmable thermostat

ComfortStar
®

12201 N.W. 107th Avenue


Medley, FL 33178
toll free: 1-866-524-9898 • fax: 305-500-9896
e-mail: info@comfortstarusa.com • www.comfortstarusa.com

 ComfortStar Air Conditioning & Heating Part no. ADH2/SPEC-1009