Вы находитесь на странице: 1из 2

Pressure Gauge

Models 131-10, 131-11, 131-17 & 131-18

Model 131-10 Model 131-11

General Description Model Numbers Connection


131-10 & 131-17: f or water. ¼" NPT, lower.
The Inbal Pressure Gauge models 131- 131-11 & 131-18: f or air.
10 and 131-11 are used for water and air Pressure Rating
systems in Deluge, Dry Pipe, Preaction, Dial Size 131-10 : Retard to 450 psi (31 bar).
Pressure Reducing, Pressure Relief, and 3½" (89 mm). 131-11 : Retard to 250 psi (17 bar).
Remote Control Inbal Valves. The core
of the Pressure Gauge is the spring
suspended movement, which has been 1 9/64"
4"
proven to be of reasonable resistant to 29 mm Æ
100 mm
shock, vibration, and pulsation - thus
assuring an accurate, dependable, and
long-lasting gauge. 3
The Gauge models 131-10 and 131-11 2 4
have an ABS case, model 131-17 and 40 50
131-18 - Stainless Steel case. Both types 30 60
of cases provide impact resistance,
20 70
toughness, rigidity, and excellent 1 5
corrosion resistance. The Gauges utilize 10
80
an impact / heat resistant polycarbonate 5.5
0
or double strength glass window. All the psi
Pressure Gauges models are FM 0
70 mm

approved and UL listed. bar


2 ¾"

AIR

Technical Data

Manufactured by
Ashcroft, Brecco.
15
Approvals /32" ¼" NPT
Factory Mutual (FM). 12 mm
Underwriters Laboratory (UL). Model 131-10/1

F40-04-01
Pressure Gauge
Models 131-10, 131-11, 131-17 & 131-18

Scale
Dual psi and bar
131-10 & 131-17 : 0 to 300 psi (0-21 bar).
131-11& 131-18 : 0 to 80 psi (0-5.5 bar).

Case
Black ABS (Acrylonitrite Butadiene
Styrene) or Stainless Steel.

Window
Polycarbonate or glass, double strength.

Dial
Black figures on white background,
Steel or Brass.

Pointer
Black, aluminum.

Bourdon Tube
C-shaped, bronze.

Movement
Spring suspended with polyester
segment. Model 131-17

Socket
Brass.
1 5/16"
Accuracy 33 mm
ASME B40.1, Grade B, 3-2-3%. 4"
Æ
101 mm
Temperature Range 3
-400F to +1500F (-400C to +650C).
2 4
40 50
30 60
Installation
20 70
1 5
Pressure Gauge must be installed so that 10
80
misuse or misapplication is minimized. 0 5.5
Personnel responsible for installation psi
should be conversant with ASME B40.1. 0
bar
3 1/16"
78 mm

The range of the gauge should be AIR


approximately twice the actual operation
pressure. Avoid applying pressure
beyond the top of the scale. Excessive
vibration should cause movement wear
resulting in loss of accuracy. Excessive
pressure pulsation usually evidenced by
continuous rapid pointer oscillation ½" ¼" NPT
could result in fatigue failure of the 12.5 mm
pressure element or rapid movement Model 131-17/ 8
wear. Excessive temperature could result
in long term creep of soldered joints, and
possibly eventual failure.

Copersa. Eduard Calvet i Pintó 20, 08339 - Vilassar de Dalt, (Barcelona). Tel: +34 937 59 25 00, Fax: +34 937 59 50 08, E-mail: industrial@copersa.com
March 2000 / F40-04-01-002

Вам также может понравиться