Вы находитесь на странице: 1из 37

INGENIERÍA DE DETALLE DOCUMENTO N

DISEÑO Y ESTUDIOS AMBIENTALES DE LA DLY-MC-C-TS-501-CO_GE


RED TRONCAL DEL GASODUCTO Y LA RED
SECUNDARIA DE LAS ZONAS URBANAS ELABORÓ: PLH/SRA
RESIDENCIALES, COMERCIALES E
INDUSTRIALES EN EL DEPARTAMENTO DE REV. 0
ICA – PERÚ

MEMORIA DE CÁLCULO CUARTO DE CONTROL HUMAY,


PISCO, MARCONA, CHINCHA

PLH/SRA RPA ARO


0 EMISIÓN FINAL 28-JUN-10 25202-73906CND/ 68205-19848
25202-42658CND
63202-94730 QND

PLH RPA HEE


B EMITIDO PARA COMENTARIOS Y/O APROBACIÒN 26-FEB-10
25202-73906CND 25202-42658CND 230 11366
PLH RPA HEE
A EMITIDO PARA COMENTARIOS INTERNOS 26-FEB-10 230 11366
25202-73906CND 25202-42658CND

REV. DESCRIPCIÓN FECHA ELABORÓ REVISÓ APROBÓ


DISTRIBUIDO POR
ÁREA DE DISTRIBUCIÓN Ing. Jorge González /Ing. Eduardo Narváez ARCHIVO
(GP)
MAGNÉTICO
C:\PDLY\01 ID_Transporte\CO_GE\05 Civil\DLY-
MC-C-TS-501-CO_GE-R0 CUARTO CONTROL HU
PI MA CHI.docx
INGENIERÍA DE DETALLE o
DOCUMENTO N
DISEÑO Y ESTUDIOS AMBIENTALES DE LA RED DLY-MC-C-TS-501-CO_GE
TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA
DE LAS ZONAS URBANAS RESIDENCIALES,
COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ o
HOJA N 2 DE 5

MEMORIA DE CÁLCULO CUARTO DE CONTROL


HUMAY, PISCO, MARCONA, CHINCHA
REV. 0, 28-JUN-10

TABLA DE CONTENIDO
1.  OBJETIVO 3 
2.  ALCANCE 3 
3.  DOCUMENTOS DE REFERENCIA 3 
4.  DISEÑO 3 
4.1.  CÁLCULO DE CARGAS 3 
4.2.  PARÁMETROS DE DISEÑO 4 
4.3.  MÉTODO DE DISEÑO 4 
4.4.  PROCEDIMIENTO 4 
5.  ANEXOS 5
INGENIERÍA DE DETALLE o
DOCUMENTO N
DISEÑO Y ESTUDIOS AMBIENTALES DE LA RED DLY-MC-C-TS-501-CO_GE
TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA
DE LAS ZONAS URBANAS RESIDENCIALES,
COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ o
HOJA N 3 DE 5

MEMORIA DE CÁLCULO CUARTO DE CONTROL


HUMAY, PISCO, MARCONA, CHINCHA
REV. 0, 28-JUN-10

1. OBJETIVO
El objetivo del presente documento es diseñar la estructura típica de concreto para el
cuarto de control y de facilidades de Humay, Pisco, Marcona, Chincha para el
proyecto: “INGENIERÍA DE DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ”.

2. ALCANCE
El alcance de este informe es el diseño de la estructura de 128.96m2 en planta,
proyectada en pórticos con muros de concreto reforzado, la cubierta maciza y su
fundación constituida por zapatas individuales y cimientos corridos. Los muros de
fachadas serán en ladrillo tolete prensado a la vista, la edificación se desarrolla en
un nivel y sus luces son de 4.00 a 6.00m entre ejes.

3. DOCUMENTOS DE REFERENCIA
 Estudio de suelos para el diseño de las cimentaciones de las estructuras,
JEOPROBE LTDA, Enero de 2010.
 Planos de Arquitectura para los cuartos.
 Reglamento Nacional de Edificaciones del Perú, Junio de 2006.

4. DISEÑO
4.1. CÁLCULO DE CARGAS

Las cargas muertas en la estructura están conformadas básicamente por la cubierta


en placa maciza, el afinado de dicha placa, los muros y antepechos y las cargas al
interior del edificio. La carga viva al interior de la edificación se toma de 300 kg/m2,
el cálculo detallado de cargas se incluye en el Anexo 1.

Las cargas horizontales de sismo y de viento se calcularán de acuerdo con los


parámetros establecidos en el Reglamento Nacional de Edificaciones del Perú. Para
la modelación en computador se realiza un análisis estático, según los
procedimientos exigidos por el Reglamento Nacional de Edificaciones del Perú y
calculando una masa de la edificación a partir de las cargas muertas.
INGENIERÍA DE DETALLE o
DOCUMENTO N
DISEÑO Y ESTUDIOS AMBIENTALES DE LA RED DLY-MC-C-TS-501-CO_GE
TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA
DE LAS ZONAS URBANAS RESIDENCIALES,
COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ o
HOJA N 4 DE 5

MEMORIA DE CÁLCULO CUARTO DE CONTROL


HUMAY, PISCO, MARCONA, CHINCHA
REV. 0, 28-JUN-10

4.2. PARÁMETROS DE DISEÑO

Se usaron características de los materiales de acuerdo con los requisitos mínimos


prescritos en el Reglamento Nacional de Edificaciones del Perú, de tal manera que
se garantiza su satisfactorio comportamiento en cuanto a resistencia y su
durabilidad. Dichas características son:

 f’c = 210 kg/cm2 (3000 psi). Resistencia del concreto a


los 28 días.

 fy = 4200 kg/cm2 (60000 psi). Esfuerzo de fluencia del


acero de refuerzo.

Los parámetros de suelos para las verificaciones de capacidad portante de la


cimentación, fueron tomados del estudio de suelos realizado por JEOPROBE LTDA,
estos son:

 Capacidad portante del suelo: 4.00 ton/m2, para un


asentamiento total de 2.00cm.

Los parámetros tomados del Reglamento Nacional de Edificaciones del Perú fueron:

 Categoría de la edificación: Esencial, factor U= 1.50.

 Velocidad del viento de diseño, V=65 km/h.

 Zona sísmica: 3, factor de zona Z=0.40.

 Sistema estructural dual, R=7.00.

 Procedimiento de análisis: F.H.E.

4.3. MÉTODO DE DISEÑO

El método de diseño es el de los factores de carga y resistencia para el concreto


reforzado y esfuerzos de trabajo para las verificaciones de cimentación. Todo el
procedimiento de diseño se ajusta al Reglamento Nacional de Edificaciones del Perú
y se detalla en el Anexo 1.

4.4. PROCEDIMIENTO

Para el diseño se utilizó el programa de cálculo estructural SAP2000. La geometría


necesaria se toma del plano arquitectónico, el cual a su vez se dimensionó en
función de los espacios y usos requeridos. Luego se le aplicaron las cargas
INGENIERÍA DE DETALLE o
DOCUMENTO N
DISEÑO Y ESTUDIOS AMBIENTALES DE LA RED DLY-MC-C-TS-501-CO_GE
TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA
DE LAS ZONAS URBANAS RESIDENCIALES,
COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ o
HOJA N 5 DE 5

MEMORIA DE CÁLCULO CUARTO DE CONTROL


HUMAY, PISCO, MARCONA, CHINCHA
REV. 0, 28-JUN-10

estáticas y dinámicas calculadas en el anexo 1 y se procedió a analizar el modelo.


Posterior al análisis se procede a tomar las solicitaciones críticas de la estructura y
diseñar las secciones con el método de la resistencia última.

5. ANEXOS
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

1. Materiales:

Concreto:

f'c= 21MPa Para vigas, columnas y zapatas


f'c= 14MPa Para limpieza

Acero:

fy= 420MPa Acero de refuerzo

2. Evaluación de cargas:

Cargas según Norma E-020

2.1 Carga muerta:

Para las vigas de cubierta:

2
Placa cubierta en concreto e=100mm 0.24 ton/m
2
Afinado placa cubierta e=10mm 0.02 ton/m
2
Total 0.26 ton/m

Vigueta 150x250mm 0.09 ton/m


2
Antepecho 0.27 ton/m con h=1.20m: 0.32 ton/m

Equipos 1.00 ton


Tanque de almacenamiento 3.00 ton

Para las vigas de cimentación:

2
Muro en mampostería 0.27 ton/m con h=4.40m: 1.13 ton/m
2
Total 0.27 ton/m

Nota: el peso propio de los elementos estructurales es calculado por el programa.

2.2 Carga viva:

Vigas de cubierta:

2
Placa cubierta 0.30 ton/m

1 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

2.3 Carga de viento:

Clasificacion de la edificación

Se toma la edificación como tipo 1.

De acuerdo al mapa eolico del Perú, la estructura esta localizada en una zona con una velocidad de
diseño de 65 km/h. La velocidad de diseño del viento en cada altura de la edificación se define así:

2 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

V(km/h)= 65

h(m) Vh(km/h) Según 12.3


0.01 14.2
1.00 39.2
2.00 45.6
3.00 49.9
4.20 53.7
5.40 56.8

Carga exterior de viento

La fuerza de presion o succion en kg/m2, se calculará mediante la siguiente formula

Ph = 0.05 Vh 2 Según 12.4

3 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Barlovento Sotavento
Para los muros se toma: 08
0.8 -0 6
-0.6
Para la cubierta se toma: -0.7 -0.7

Barlovento Sotavento
h(m) Ph (kg/m2) Ph (kg/m2)
0.01 8.09 -6.07 128.87 kg/m2 -96.65
1.00 61.36 -46.02 kg/m2
2.00 83.24 -62.43 estructura
3 00
3.00 99 50
99.50 74 62
-74.62
4.20 115.38 -86.53 8.09 kg/m2 -6.07
5.40 128.87 -96.65 kg/m2

-112.76 kg/m2 -112.76


Barlovento Sotavento kg/m2
h(m) Ph (kg/m2) Ph (kg/m2)
0.01 -7.08 -7.08
1 00
1.00 -53.69
53 69 -53.69
53 69 estructura
2.00 -72.84 -72.84
3.00 -87.06 -87.06
4.20 -100.95 -100.95
5.40 -112.76 -112.76 + Compresión - Succión

2.4 Diseño sismo resistente

2.4.1 Zonificación

Zona 3

Z= 0.4

4 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Perfil de suelo según el estudio de suelos:

Para la determinación de los parámetros de suelo se toman los valores del área 35. En este caso el estudio de
suelos indica para la zona, suelos muy sueltos y con una rigidez muy baja. Estos suelos son originados por la
depositacion de arenas por el viento, lo que produce dunas que se caracterizan por tener arenas sueltas hasta 3m
de profundidad. Debido a que el informe no incluye la caracterización del suelos se acoge la recomendación del
reglamento nacional que indica tomar los parametros de un suelo S3 cuando las propiedades del suelo sean poco
conocidas.

Tipo de suelo Parámetros del suelo Tp S


s3 Suelos flexibles o con estratos de gran espesor 0.90 1.4

Factor de amplificación sísmica:

C= 2.50 (Tp/T) <= 2.50


C= 2.50

Categoria de la edificación

5 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

La estructura se clasifica como categoria: A


Factor U: 1.5

Configuración Estructural

Se considera que la estructura es regular en planta y elevación.

Categoria y estructura de las edificaciones

Sistema estructural

Se escoje el sistema estructural Dual, según la anterior tabla.


R
Sistema dual 7.0

Procedimiento de analisis

Debido
D bid a que lla estructura
t t cumple
l con llos requisitos
i it d dell numerall 14
14.2
2dde llas N
Normas L
Legales,
l se utilizara
tili ell
metodo de la fuerza horizontal equivalente.

Desplazamientos Laterales

6 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Análisis Estático

Periodo fundamental

hn= 4.20 m
Ct= 60.00 -
T= 0 07 seg
0.07

Fuerza cortante en la base

Componente Horizontal

Z= 0.40
U= 1.50
C= 2.50
S= 1.40
C/R= 0.357
P= Peso de la estructura

Columnas 8.6 ton


Vigas aereas 16.4 ton
Placa cubierta 31.0 ton
Afinado placa 3.1 ton
Vi
Viguetas
t 13 1
13.1 t
ton
Antepecho 14.8 ton
Equipos 1.0 ton
Tanques 3.0 ton
Muros 21.6 ton
50% de carga viva 19.3 ton, según 16.3
Total 131.8 ton

V
V= 0.30 P
V= 39.6 ton

Si algún elemento toma más del 30% de V, deberá


diseñarse para el 125% de dicha fuerza.
Las fuerza sísmicas horizontales actuarán independien
temente en cada una de las direcciones en el caso de
estructuras regulares. Para estructuras irregulares la
fuerza sísmica debe aplicarse en la dirección mas
desfavorable de la estructura.

7 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Componente vertical

Zona= 3
Fv= 26.4 ton

La fuerza sísmica vertical actuará simultaneamente con


la horizontal.

3.4 Torsión accidental

3.4.1 Centro de gravedad :

Dimensiones en metros.

Xg

A1 10.40

Yg

12.40

Centro de gravedad
Centro de rigidez (coincide en este caso con el geometrico)
Centro de gravedad desplazado

Sección X(m) Y(m) A(m2) XA(m3) YA(m3)


A1 6.20 5.20 128.96 799.55 670.59
 128.96 799.55 670.59

Xg= XA/A= 6.20 m


Yg= YA/A= 5.20 m

8 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

3 4 2 Desplazamiento del centro de gravedad:


3.4.2

xg= 0.62 m
yg= 0.52 m
Xg desp.= 5.58 m
Yg desp.= 5.72 m

Desplazamientos laterales permisibles

El máximo desplazamiento relativo de entrepiso, calculado según el articulo 16 (16.4) no deberá exceder la fracción
de altura de entrepiso que se indica en la tabla Nº 8.

Se deberá considerar el efecto de la excentricidad de la carga vertical producida por los desplazamientos laterales
de la edificación. Los desplazamientos laterales se calularán multiplicando por 0.75R los resultados obtenidos del
análisis lineal y elástico con las solicitaciones sísmicas reducidas. Para el cálculo de los desplazamientos
p
laterales no se consideran los valores mínimos de C/R indicados en el articulo 17 (17.3), ni el cortante mínimo
en la base indicado en el articulo 18 (18.2d).

Piso Nudo  (m) hi(m) (m) perm.(m)


0 0 0.00 -
1 0.0063 5.40 0.03308 Cumple max sismo x
0 0 0.00 -
1 0.00655 5.40 0.03439 Cumple max sismo y

4. Requisitos y predimensionamiento de elementos estructurales

4.1. Muros de cortante

Los muros de cortante deberan ser diseñados para la acción combinada de carga axial momentos y corte, de
acuerdo a las siguientes disposiciones:

Espesor mínimo: 0.10 m Según 15.4.1.2

Diseño por flexión:

Muros esbeltos: H/L>=1, para estos muros son aplicables los lineamientos generales establecidos de
flexocompresion. El refuerzo vertical sera distribuido a lo largo del muro, concentrando mayor refuerso en sus
extremos.
Muros de poca esbeltez:H/L<1 y con cargas axiales poco significativas, no deberan aplicarse los lineamientos
generales de flexocompresion y se debera calcular el area de refuerzo del esteemo en traccion para el caso de

9 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

secciones rectangulares como sigue:

Debera colocarse acero uniformemente repartido a lo largo de la longitud del muro, cumpliendo con el minimo
refuerzo vertical de muros indicado en 15.4.3

El acero de refuerzo concentrado en los extremos de los muros deberá confinarse con estribos como en el caso
de columnas y los empalmes de este refuerzo deberán diseñarse a tracción.
El refuerzo vertical distribuido no necesitara ser confinado por estribos a menos que su cuantia exceda a 0.01 o
que sea necesario por compresión.

Si el esfuerzo en la fibra extrema en traccion calculado suponiendo un comportamiento lineal elastico:

excediera de 2√f`c
2√f c, deberá verificarse que el refuerzo en tracción de los extremos provea un momento resistente
por lo menos igual a 1.5 veces el momento de agrietamiento Mcr de la sección:

Diseño por cortante:

p
Los muros con esfuerzos de corte debidos a la accion de fuerzas coplanares se diseñarán considerando:

Requisitos para Columnas

Denominación B(mm) L(mm) sconf(mm) d´(mm) dbflexmin(mm) dbcor(mm) Nbarras en hc


300x300 300 300 100 40 19.05 9.53 2.00
1500x200 200 1500 50 40 19.05 9.53 3.00
1500x200 200 1500 50 40 19.05 9.53 3.00

Luz libre (mm) hc(mm) fc(MPa) fyh(MPa) Ag(mm2) Ach(mm2) Ash1(mm2) Ash2(mm2)
4400.00 220 21 420 90000 67600 72.90 66.00
4400.00 1420 21 420 300000 233600 201.82 213.00
4400.00 1420 21 420 300000 233600 201.82 213.00

Ash(mm2)min Smaxconf(mm) lo(mm) Smax(mm) Ash(mm2)sum Ashsum>Ashmin


72.90 100.00 733.33 152.48 142.66 VERDADERO
213.00 100.00 1500.00 152.48 213.99 VERDADERO
213.00 100.00 1500.00 152.48 213.99 VERDADERO

10 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

11 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Muro t(m) L(m) H(m) d aprox. (m) f'c(kg/cm2)


M1 0.15 1.50 4.40 1.2 210
M2 0.15 1.50 4.40 1.2 210

Muro Mur(kg-m) Mua(kg-m) n w Vua(kg)


M1 7,600 6,270 1 1 18300
M2 7,600 6,376 1 1 18700

Muro Vu mín(kg)  Vc(kg) ph disp. pv disp. ph mín


M1 22,182 13825 0.0094 0.044 Cumple
M2 22 288
22,288 13825 0 0095
0.0095 0 018
0.018 C
Cumple
l

Muro pv mín Sh disp.(m) Sv disp.(m) Sh max.(m) Sv max(m)


M1 Cumple 0.152 0.125 Cumple Cumple
M2 Cumple 0.150 0.128 Cumple Cumple

Muro t d (cm2) Asv disp.(cm2) Barra No. Ramas fyv(kg/cm2)


M1 1800 79.80 3 3 4200
M2 1800 31.68 3 3 4200

12 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Muro Vs(kg) Vn Vu ≤  Vc


M1 70732 84556 Cumple
M2 71901 85726 Cumple

Vigas entre muros: La fuerza cortante en las vigas que unen a los muros, deberá limitarse a:

y no se considerara ningun aporte del concreto a la resistencia. (Vc=0)


La fuerza cortante Vu de diseño, debera basarse ne la capacidad maxima de flexion de la viga, considerando una
sobreresistencia del acero del 25%.
Cuando la relacion In/h sea menor a 2, el esfuerzo por fuerza cortante debera ser absorbido por barraas diagonales
debidamente ancladas en el muro.

Para el predimensionamiento de los muros se tiene en cuenta ademas de lo anterior, que las columnas tomarán un
25% de la fuerza sismica y que los muros en conjunto con los pórticos tomarán el total de la fuerza sísmica, pero
no menos del 75% del cortante en la base, según el Artículo 12. Sistemas estructurales, Reglamento Nacional
de Edificaciones.

4.2. Dimensionamiento de elementos

El dimensionamiento de los elementos de la estructura se realizó con base al capitulo


p 5 ((Diseño),
), del Reglamento
g
Nacional de Edificaciones.
Las vigas que cumplan con la relacion h<=L/16, no tendrán necesidad de ser revisadas para deflexiones
permisibles, según 10.4.1.4.

L= 6.00 m
h>= 0.38 m
Se escoje una altura de viga de 40cm.

El
Elementos
t a flexión
fl ió resistentes
i t t a sísmo
í

b h b/h d L d<=0.25L
0.25 0.40 Cumple 0.35 6.00 Cumple

bmin≥0.25m bcol-apoyo bmax Pu(kg) f'c Pu<0.10 f`c Ag


Cumple 0.30 Cumple 0 210 Cumple

No se debe traslapar acero longitudinal en zonas de confinamiento


En las zonas de traslapo deben disponerse flejes cerrados con una separacion no mayor a 16 diametros de la barra
longitudinal, ni 30cm.

Columnas sujetas a flexo-compresión

La cuantia minima del refuerzo vertical no puede ser menor de 0.01, ni mayor a 0.06. Cuando exceda 0.04 el plano
debe contener detalle de la conexión viga columna.

13 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Losas Nervadas

Espesor mínimo: 0 10 m
0.10 Según 9
9.9.2
92
hmáx: 3.50tlosa Según 9.9.2 0.35 m
Separacion máxima nervios: 0.75 m Según 9.9.3

Separacion adoptada: 0.736 m


Espesor mínimo losa: 1/12 Slibre la menor Según 9.9.6 0.06 m
5cm 0.05 m
Espesor adoptado: 0.10 m Cumple
h adopada nervio: 0 35 m
0.35 Cumple

Resistencia Requerida

Las siguientes combinaciones de carga deben ser usadas como mínimo para el diseño de elementos de concreto
reforzado.

CM Carga muerta
CV Carga viva
CS Carga de sismo
Cvi Carga de viento

1 U= 1.50CM+1.80CV
2 U= 1.25(CM+CV+CS)
3 U= 1.25(CM+CV-CS)
4 U= 1.25(CM+CS)
5 U= 1.25(CM-CS)
1 25(CM CS)
6 U= 1.25(CM+CV+Cvi)
7 U= 1.25(CM+Cvi)
8 U= 0.90(CM+1.25CS)
9 U= 0.90(CM-1.25CS)

Requisitos para el diseño de zapatas

14 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

8.3 Combinaciones por cargas reales

COMBO TYPE FACTOR


1 PP 1.00
1 CM 1.00
2 PP 1.00
2 CM 1.00
2 CV 1.00
3 PP 1.00
3 CM 1.00
3 CV 1.00
3 V 1.00
4 PP 1.00
4 CM 1.00
4 CV 1 00
1.00
4 EQX 1.00
4 EQZ 1.00
5 PP 1.00
5 CM 1.00
5 CV 1.00
5 EQY 1.00
5 EQZ 1.00
6 PP 1.00
6 CM 1.00
6 EQX 1.00
6 EQZ 1.00
7 PP 1.00
7 CM 1.00
7 EQY 1.00
7 EQZ 1.00

15 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

9. Cálculo de zapatas

9.1 Geometría

9.2 Reacciones por cargas reales

TABLE:  Joint Reactions
Joint OutputCase CaseType F1 F2 F3 M1 M2
Text Text Text Ton Ton Ton Ton‐m Ton‐m
9 1 Combination ‐1.35 ‐0.03 22.10 0.23 4.35
9 2 Combination ‐2.05 ‐0.16 28.11 0.51 4.25
9 3 Combination ‐1.49 ‐0.73 25.83 1.61 5.83
9 4 Combination ‐20.36 ‐0.17 22.63 0.51 ‐88.44
9 5 Combination ‐3.19 ‐0.77 25.36 2.66 ‐1.23
9 6 Combination ‐19.65 ‐0.04 16.62 0.23 ‐88.35

16 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

9 7 Combination ‐2.48 ‐0.64 19.35 2.37 ‐1.13


18 1 Combination 0.99 ‐0.08 23.36 0.43 ‐0.45
18 2 Combination 1.56 ‐0.02 29.23 0.33 0.09
18 3 Combination 1.07 ‐0.85 27.50 1.85 ‐1.83
18 4 Combination ‐14.65 ‐0.04 26.16 0.37 ‐83.49
18 5 Combination 2.64 ‐0.65 25.84 2.54 5.83
18 6 Combination ‐15.23 ‐0.10 20.29 0.47 ‐84.02
18 7 Combination 2.07 ‐0.71 19.97 2.64 5.30
41 1 Combination ‐0.06 ‐0.15 15.77 1.46 ‐3.07
41 2 C bi ti
Combination 0 08
‐0.08 0 18
‐0.18 18 90
18.90 1 52
1.52 3 11
‐3.11
41 3 Combination ‐0.11 ‐0.57 18.05 2.25 ‐3.19
41 4 Combination ‐0.75 ‐0.22 14.48 1.65 ‐5.09
41 5 Combination ‐0.03 ‐1.07 12.61 3.99 ‐2.98
41 6 Combination ‐0.73 ‐0.20 11.35 1.59 ‐5.05
41 7 Combination ‐0.02 ‐1.04 9.48 3.93 ‐2.94
43 1 Combination 0.03 ‐0.16 15.23 1.42 2.98
43 2 Combination 0 02
0.02 ‐0.20
0 20 18 33
18.33 1 52
1.52 2 94
2.94
43 3 Combination 0.03 ‐0.90 17.60 2.75 2.95
43 4 Combination ‐0.68 ‐0.16 17.08 1.39 0.90
43 5 Combination 0.08 ‐0.95 12.39 3.61 3.11
43 6 Combination ‐0.66 ‐0.12 13.99 1.29 0.94
43 7 Combination 0.10 ‐0.92 9.29 3.51 3.15
47 1 Combination ‐0.13 0.00 27.03 ‐0.39 2.65
47 2 Combination ‐0.16
0.16 0.01 38.77 ‐0.39
0.39 2.59
47 3 Combination ‐0.15 ‐0.09 34.18 ‐0.08 2.61
47 4 Combination ‐0.85 ‐0.06 35.59 ‐0.26 0.54
47 5 Combination ‐0.15 ‐0.62 36.15 1.50 2.61
47 6 Combination ‐0.81 ‐0.07 23.85 ‐0.27 0.60
47 7 Combination ‐0.12 ‐0.63 24.41 1.49 2.68
51 1 Combination 0.15 0.00 20.66 ‐2.45 ‐5.14
51 2 Combination 0.24 ‐0.09 25.82 ‐2.25 ‐4.95
51 3 Combination 0.20 ‐0.41 24.80 ‐1.65 ‐5.02
51 4 Combination ‐0.49 ‐0.16 22.10 ‐2.09 ‐7.11
51 5 Combination 0.18 ‐0.90 24.62 0.05 ‐5.10
51 6 Combination ‐0.58 ‐0.06 16.94 ‐2.29 ‐7.30
51 7 Combination 0.09 ‐0.80 19.46 ‐0.15 ‐5.29
53 1 Combination 0.18 ‐0.09 16.15 ‐2.16 1.58
53 2 Combination 0.24 ‐0.22 20.52 ‐1.88 1.72
53 3 Combination 0.25 ‐0.73 19.40 ‐0.95 1.74
53 4 Combination ‐0.58 ‐0.19 21.03 ‐1.98 ‐0.64
53 5 Combination 0.21 ‐0.86 19.44 0.01 1.60
53 6 Combination ‐0.65 ‐0.06 16.66 ‐2.26 ‐0.78
53 7 Combination 0.14 ‐0.74 15.07 ‐0.27 1.46
152 1 Combination 0.01 0.98 27.22 0.85 ‐2.04
152 2 Combination 0.00 1.54 35.39 0.12 ‐2.05

17 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

152 3 Combination ‐0.03 ‐0.76 33.55 11.70 ‐2.12


152 4 Combination ‐0.69 0.50 32.19 5.30 ‐4.42
152 5 Combination 0.00 ‐17.16 34.10 92.53 ‐2.04
152 6 Combination ‐0.68 ‐0.06 24.02 6.03 ‐4.42
152 7 Combination 0.01 ‐17.72 25.93 93.27 ‐2.03
161 1 Combination 0.17 ‐0.47 25.09 6.27 1.08
161 2 Combination 0.22 ‐0.68 33.18 8.96 1.18
161 3 Combination 0.23 ‐3.65 30.82 23.77 1.19
161 4 Combination ‐0.51 0.50 30.61 3.43 ‐1.27
161 5 C bi ti
Combination 0 25
0.25 16 56
‐16.56 31 36
31.36 87 26
87.26 1 25
1.25

9.2 Esfuerzos en el suelo de fundación y diseño de zapatas

Zapata nudo: 9
COMBO Fx Fy Fz Mx My
COMB1 -1.14 -0.95 118.16 9.43 -9.17
COMB2 -1.49
1 49 -1.05
1 05 144 99
144.99 9 58
9.58 -9.87
9 87
COMB3 -1.51 -4.09 139.04 15.05 -9.91
COMB4 -9.18 -1.55 61.62 11.08 -31.24
COMB5 -1.90 -8.08 66.00 29.01 -11.15
COMB6 -8.83 -1.45 34.79 10.92 -30.55
COMB7 -1.55 -7.97 39.17 28.86 -10.45

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.20 m
Ancho Zapata en Y 2.20 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 5.29 m^2
Ix Zapata 2.33 m^4
Iy Zapata 2.33 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 38.09 kN
Peso Suelo Sobre Zapata 66.654 kN

COMBO P / A A B C D  Prom

COMB1 39.9 48.0 29.7 38.7 38.8 39.9


COMB2 45.2 53.5 34.3 44.0 43.9 45.2
COMB3 44.2 55.1 30.5 40.2 42.8 44.2
COMB4 37.3 49.0 7.3 38.1 28.1 37.3
COMB5 32.6 48.8 9.2 20.2 29.0 32.6

18 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

COMB6 32.1 43.5 2.6 32.8 23.1 32.1


COMB7 27.3 43.3 4.5 14.8 23.9 27.3
Máximos 55 09
55.09 34 32
34.32 44 05
44.05 43 91
43.91
Mínimos 43.29 2.63 14.83 23.08

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 55.09 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 48.78 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 45.17 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa Y
fy 420 MPa B
Cuantía Mímina 0.00333333
My
Cuantía Repartición 0.0020
Altura efectiva d 0 23
0.23 m
Momento de diseño 52.26 kN-m/m Fx/ 8
= 1.5 * 39.31kN/m^2 * 3m^2
Cuantía requerida 0.00269955
1.33 * Cuantína 0.0035904 Mx
Cuantía Suministrada 0.0033 Fy
As por metro de ancho 7.67 cm^2/m
C
CHEQUEO POR CORTANTE
vc 649.2 kN/m^2
Vu / m 90.9 kN/m
vu 395.2 kN/m^2 Bien!!

Zapata nudo: 18
COMBO Fx Fy Fz Mx My
COMB1 -0.03 -1.61 123.99 10.78 -0.07
COMB2 -0.04 -1.74 151.64 10.99 -0.09
COMB3 -0.04 -7.13 146.60 20.02 -0.10
COMB4 -8.98 -1.90 110.08 11.56 -23.93
COMB5 -0.71 -8.76 84.94 30.73 -1.89
COMB6 -8.97 -1.77 82.43 11.36 -23.91
COMB7 -0.70 -8.63 57.29 30.53 -1.87

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00
18 00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.20 m
Ancho Zapata en Y 2.20 m
Centro Zapata X 0.00 m

19 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Centro Zapata Y 0.00 m


Área Zapata 5.29 m^2
Ix Zapata 2 33
2.33 m^4
m 4
Iy Zapata 2.33 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 38.09 kN
Peso Suelo Sobre Zapata 66.654 kN

COMBO P / A A B C D  Prom

COMB1 37.6 45.3 34.6 34.7 39.9 37.6


COMB2 37.6 50.6 39.7 39.8 45.2 37.6
COMB3 36.8 54.1 34.3 34.4 44.2 36.8
COMB4 31.1 54.8 19.8 43.4 37.3 31.1
COMB5 27.1 48.6 16.5 18.3 32.6 27.1
COMB6 26.7 49.5 14.7 38.3 32.1 26.7
COMB7 22.8 43.3 11.4 13.2 27.3 22.8
Máximos 54.81 39.70 43.41 45.17
Mínimos 43 31
43.31 11 35
11.35 13 20
13.20 27 33
27.33

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 54.81 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 49.47 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 37.64 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 37.33 kN-m/m = 1.5 * 39.31kN/m^2 * 3m^2 / 8
Cuantía requerida 0.00190999
1.33 * Cuantína 0.00254029
Cuantía Suministrada 0 0025
0.0025
As por metro de ancho 5.84 cm^2/m

CHEQUEO POR CORTANTE


vc 649.20 kN/m^2
Vu / m 64.92 kN/m
vu 282.28 kN/m^2 Bien!!

Zapata nudo: 41
COMBO Fx Fy Fz Mx My
COMB1 -0.02 -1.61 118.69 7.33 -0.06
COMB2 -0.03 -1.88 144.08 7.80 -0.08
COMB3 -0.04 -7.36 140.08 17.00 -0.10
COMB4 -8.93 -1.69 106.09 7.44 -23.84
COMB5 -0.70 -10.25 46.64 30.51 -1.87
COMB6 -8.92 -1.42 80.70 6.96 -23.82

20 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

COMB7 -0.70 -9.98 21.25 30.03 -1.86

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo
g Zapata en X 2.20 m
Ancho Zapata en Y 2.20 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 4.84 m^2
Ix Zapata 1.95 m^4
Iy Zapata 1.95 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 34.85 kN
Peso Suelo Sobre Zapata 60 984
60.984 kN

COMBO P / A A B C D  Prom

COMB1 41.0 45.2 36.9 36.9 41.0 41.0


COMB2 46.3 50.7 41.8 41.9 46.3 46.3
COMB3 45.4 55.1 35.8 35.9 45.4 45.4
COMB4 38.4 56.0 20.8 47.7 38.4 38.4
COMB5 26.1 44.4 7.9 10.0 26.1 26.1
COMB6 33.2 50.5 15.8 42.7 33.2 33.2
COMB7 20.9 38.9 2.9 5.0 20.9 20.9
Máximos 56.04 41.83 47.66 46.27
Mínimos 38.86 2.92 5.01 20.89

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
E f
Esfuerzo Máximo
Má i D+L 56 04 kN/m^2
56.04 kN/ ^2 < 70
70.00
00 Bi
Bien !!
Esfuerzo Máximo D+L + Sismo 50.52 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 46.27 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 41.99 kN-m/m = 1.5 * 39.31kN/m^2 * 3m^2 / 8
Cuantía requerida 0.00215458
1.33 * Cuantína 0.00286559
Cuantía Suministrada 0.0029
As por metro de ancho 6.59 cm^2/m

CHEQUEO POR CORTANTE


vc 649.20 kN/m^2

21 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Vu / m 76.34 kN/m
vu

Zapata nudo: 43
COMBO Fx Fy Fz Mx My
COMB1 -1.73 1.31 205.54 24.93 -37.84
COMB2 -2.38 2.25 256.43 23.03 -39.12
COMB3 -2.55 1.43 253.16 25.26 -39.45
COMB4 -7.78 1.42 212.27 25.18 -56.26
COMB5 -2.43 -5.01 249.75 42.92 -39.38
COMB6 -7.13 0.48 161.39 27.09 -54.98
COMB7 -1.79 -5.95 198.87 44.82 -38.11

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.10 m
Ancho Zapata en Y 2.10 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 9.61 m^2
Ix Zapata 7.70 m^4
Iy Zapata 7 70
7.70 m^4
m 4
Área Pedestal 0 m^2
Peso Propio Zapata 69.19 kN
Peso Suelo Sobre Zapata 121.086 kN

COMBO P / A A B C D  Prom

COMB1 31.6 50.5 25.2 40.5 37.9 31.6


COMB2 36.0 55.7 30.7 46.4 43.2 36.0
COMB3 35.7 55.9 29.8 45.7 42.8 35.7
COMB4 32.2 55.0 22.2 44.8 38.6 32.2
COMB5 35.4 59.1 25.9 41.8 42.5 35.4
COMB6 27.7 49.8 16.8 38.9 33.3 27.7
COMB7 31.0 53.9 20.5 35.8 37.2 31.0
Máximos 59.07 30.67 46.42 43.18
Mínimos 49.82 16.76 35.84 33.29

Sigma Admisible = 70.0


70 0 kN/m 2
kN/m^2
1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 67.05 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 70.88 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 51.82 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa

22 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Cuantía Mímina 0.00333333


Cuantía Repartición 0.0020
Altura efectiva d 0 23 m
0.23
Momento de diseño 93.37 kN-m/m = 1.5 * 70.88kN/m^2 * 3.1m^2 / 8
Cuantía requerida 0.00495982
1.33 * Cuantína 0.00659656
Cuantía Suministrada 0.0050
As por metro de ancho 11.41 cm^2/m

CHEQUEO POR CORTANTE


vc 649.20 kN/m^2
Vu / m 120.48 kN/m
vu 523.83 kN/m^2 Bien!!

Zapata nudo: 47
COMBO Fx Fy Fz Mx My
COMB1 0.32 1.97 207.97 0.81 0.61
COMB2 0.45 3.56 277.30 -2.35 0.87
COMB3 0.46 2.19 252.73 0.96 0.89
COMB4 -6.06
6 06 3 12
3.12 236 51
236.51 -1.23
1 23 -18.45
18 45
COMB5 0.29 -3.96 263.03 18.36 0.39
COMB6 -6.19 1.53 167.18 1.93 -18.71
COMB7 0.15 -5.54 193.70 21.52 0.13

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24 00
24.00 kN/m^3
kN/m 3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.70 m
Ancho Zapata en Y 2.70 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 7.29 m^2
Ix Zapata 4.43 m^4
Iy Zapata 4.43 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 52.49 kN
Peso Suelo Sobre Zapata 91.854 kN

COMBO P / A A B C D  Prom

COMB1 45.0 45.1 45.0 44.6 45.0 45.0


COMB2 54.5 53.6 55.5 55.0 54.5 65.4
COMB3 51.2 51.2 51.1 50.6 51.2 61.4
COMB4 48.9 54.2 43.7 54.9 48.9 58.7
COMB5 52.6 58.1 47.1 46.9 52.6 63.1
COMB6 39.4 45.7 33.1 44.5 39.4 47.3
COMB7 43.1 49.6 36.5 36.5 43.1 51.7

23 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Máximos 58.06 55.52 54.99 54.54


Mínimos 45.09 33.14 36.47 39.43

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 66.62 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 69.95 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 65.45 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 89.46 kN-m/m = 1.5 * 69.95kN/m^2 * 2.7m^2 / 8
Cuantía requerida 0.00473866
1.33 * Cuantína 0.00630242
Cuantía Suministrada 0.0047
As por metro de ancho 10 90
10.90 cm^2/m

CHEQUEO POR CORTANTE


vc 649.2 kN/m^2
Vu / m 132.5 kN/m
vu 576.2 kN/m^2 Bien!!

Zapata nudo: 51
COMBO Fx Fy Fz Mx My
COMB1 -0.02 2.09 234.55 28.76 -0.05
COMB2 -0.02 3.73 303.36 25.49 -0.07
COMB3 -0.03 2.30 279.78 28.91 -0.08
COMB4 -6.25 3.61 259.81 25.71 -18.82
COMB5 -0.17 -4.50 291.36 47.92 -0.50
COMB6 -6.24 1.98 191.00 28.98 -18.81
COMB7 -0.16 -6.14 222.55 51.19 -0.48

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.20
2 20 m
Ancho Zapata en Y 2.20 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 9.00 m^2
Ix Zapata 6.75 m^4
Iy Zapata 6.75 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 64.80 kN

24 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Peso Suelo Sobre Zapata 113.4 kN

COMBO P / A A B C D  Prom

COMB1 42.6 49.0 36.2 36.2 42.6 42.6


COMB2 50.2 55.9 44.5 44.6 50.2 50.2
COMB3 47.6 54.0 41.1 41.2 47.6 47.6
COMB4 45.4 55.3 35.5 43.8 45.4 45.4
COMB5 48.9 59.6 38.1 38.3 48.9 48.9
COMB6 37.7 48.3 27.1 35.5 37.7 37.7
COMB7 41.2 52.7 29.7 30.0 41.2 41.2
Máximos 59.63 44.53 44.56 50.21
Mínimos 48.34 27.10 29.96 37.72

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 67.06 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 71.56 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 60.25 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 101.67 kN-m/m = 1.5 * 71.56kN/m^2 * 3m^2 / 8
Cuantía requerida
q 0.00543264
1.33 * Cuantína 0.00722541
Cuantía Suministrada 0.0054
As por metro de ancho 12.50 cm^2/m

CHEQUEO POR CORTANTE


vc 649.2 kN/m^2
Vu / m 135.6 kN/m
vu 589.4 kN/m^2 Bien!!

Zapata nudo: 53
COMBO Fx Fy Fz Mx My
COMB1 -1.21 0.82 117.99 -9.66 -9.30
COMB2 -1.63 0.88 145.31 -9.81 -10.13
COMB3 -1.61 -1.56 140.26 -5.27 -10.11
COMB4 -10.34 0.19 62.25 -7.95 -34.30
COMB5 -0.88 -5.59 128.37 8.51 -8.18
COMB6 9.92
-9 92 0.13
0 13 34.93
34 93 7.79
-7 79 33.47
-33 47
COMB7 -0.46 -5.65 101.05 8.67 -7.35

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m

25 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Altura Zapata 0.30 m


Altura Pedestal 0.00 m
Largo Zapata en X 2 20
2.20 m
Ancho Zapata en Y 2.20 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 4.84 m^2
Ix Zapata 1.95 m^4
Iy Zapata 1.95 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 34.85 kN
Peso Suelo Sobre Zapata 60.984 kN

COMBO P / A A B C D  Prom

COMB1 40.9 40.7 41.1 51.6 40.9 40.9


COMB2 46.5 46.7 46.3 57.8 46.5 46.5
COMB3 45.5 48.2 42.8 54.1 45.5 45.5
COMB4 29 4
29.4 44 2
44.2 14 5
14.5 53 2
53.2 29 4
29.4 29 4
29.4
COMB5 43.0 52.4 33.6 42.8 43.0 43.0
COMB6 23.7 38.2 9.2 47.0 23.7 23.7
COMB7 37.4 46.4 28.4 36.6 37.4 37.4
Máximos 52.43 46.34 57.76 46.52
Mínimos 38.19 9.24 36.63 23.72

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma
( g Admisible)) = 93.1 kN/m^2
Esfuerzo Máximo D+L 69.32 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 62.92 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 55.83 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0 0020
0.0020
Altura efectiva d 0.23 m
Momento de diseño 50.66 kN-m/m = 1.5 * 62.92kN/m^2 * 2.2m^2 / 8
Cuantía requerida 0.00261426
1.33 * Cuantína 0.00347697
Cuantía Suministrada 0.0033
As por metro de ancho 7.67 cm^2/m

Q
CHEQUEO POR CORTANTE
vc 649.2 kN/m^2
Vu / m 92.1 kN/m
vu 400.5 kN/m^2 Bien!!

Zapata nudo: 152


COMBO Fx Fy Fz Mx My
COMB1 -0.05 -0.92 129.36 -4.23 -0.11
COMB2 -0.08 -3.55 173.98 0.89 -0.17

26 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

COMB3 -0.07 -6.53 157.68 5.74 -0.15


COMB4 -10.26 -3.78 132.86 1.60 -27.22
COMB5 0 64
0.64 -8 38
-8.38 137 67
137.67 16 32
16.32 1 73
1.73
COMB6 -10.23 -1.15 88.24 -3.52 -27.15
COMB7 0.67 -5.75 93.04 11.20 1.79

DATOS DE LA CIMENTACIÓN
Gama Suelo 18.00 kN/m^3
Gama Concreto 24.00 kN/m^3
Sigma
g Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.30 m
Ancho Zapata en Y 2.30 m
Centro Zapata X 0.00 m
Centro Zapata Y 0.00 m
Área Zapata 5.29 m^2
Ix Zapata 2 33
2.33 m^4
Iy Zapata 2.33 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 38.09 kN
Peso Suelo Sobre Zapata 66.654 kN

COMBO P / A A B C D  Prom

COMB1 41.0 38.9 43.0 43.1 41.0 41.0


COMB2 49.4 49.9 48.9 49.0 49.4 49.4
COMB3 46.3 49.2 43.4 43.6 46.3 46.3
COMB4 41.6 55.8 27.4 54.2 41.6 41.6
COMB5 42.5 49.7 35.3 33.6 42.5 42.5
COMB6 33.2 44.8 21.5 48.3 33.2 33.2
COMB7 34.1 38.7 29.5 27.7 34.1 34.1
Máximos 55.83 48.87 54.25 49.39
Mí i
Mínimos 38 73
38.73 21 52
21.52 27 68
27.68 33 18
33.18

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 66.99 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 61.71 kN/m^2 < 93.10 Bien !!
Esfuerzo Promedio Diseño 59.27 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 58.79 kN-m/m = 1.5 * 61.71kN/m^2 * 2.3m^2 / 8
Cuantía requerida 0.00304955
1.33 * Cuantína 0.0040559
Cuantía Suministrada 0.0033

27 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

As por metro de ancho 7.67 cm^2/m

CHEQUEO POR CORTANTE


vc 649.2 kN/m^2
Vu / m 102.2 kN/m
vu 444.5 kN/m^2 Bien!!

Zapata nudo: 161


COMBO Fx Fy Fz Mx My
COMB1 -0.02 -1.13 127.57 -3.82 -0.06
COMB2 -0.03 -3.97 170.83 1.72 -0.09
COMB3 -0.03 -6.88 155.05 6.43 -0.08
COMB4 -10.24 -3.97 131.02 1.71 -27.19
COMB5 0.67 -8.96 135.44 17.78 1.78
COMB6 -10.23 -1.13 87.76 -3.83 -27.16
COMB7 0.68 -6.12 92.18 12.24 1.81

DATOS DE LA CIMENTACIÓN
Gama Suelo
G S 18.00 kN/m^3
/ ^
Gama Concreto 24.00 kN/m^3
Sigma Admisible 70.00 kN/m^2
Profundidad Cimiento 1.00 m
Altura Zapata 0.30 m
Altura Pedestal 0.00 m
Largo Zapata en X 2.30 m
Ancho Zapata en Y 2.30 m
Centro Zapata X 0 00
0.00 m
Centro Zapata Y 0.00 m
Área Zapata 5.29 m^2
Ix Zapata 2.33 m^4
Iy Zapata 2.33 m^4
Área Pedestal 0 m^2
Peso Propio Zapata 38.09 kN
Peso Suelo Sobre Zapata 66.654 kN

COMBO P / A A B C D  Prom

COMB1 40.6 38.8 42.5 42.5 32.2 40.6


COMB2 48.8 49.7 47.9 48.0 41.2 48.8
COMB3 45.8 49.0 42.6 42.7 40.7 45.8
COMB4 41.3 55.5 27.0 53.8 46.1 41.3
COMB5 42.1 50.0 34.2 32.5 41.5 42.1
COMB6 33.1
33 1 44.6
44 6 21.6
21 6 48.4
48 4 37.0
37 0 33.1
33 1
COMB7 33.9 39.1 28.8 27.0 32.4 33.9
Máximos 55.52 47.90 53.83 46.08
Mínimos 38.76 21.58 27.00 32.17

Sigma Admisible = 70.0 kN/m^2


1.33*(Sigma Admisible) = 93.1 kN/m^2
Esfuerzo Máximo D+L 66.62 kN/m^2 < 70.00 Bien !!
Esfuerzo Máximo D+L + Sismo 62.10 kN/m^2 < 93.10 Bien !!

28 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

Esfuerzo Promedio Diseño 58.55 kN/m^2

DISEÑO A FLEXIÓN
f'c 21 MPa
fy 420 MPa
Cuantía Mímina 0.00333333
Cuantía Repartición 0.0020
Altura efectiva d 0.23 m
Momento de diseño 58.08 kN-m/m = 1.5 * 62.10kN/m^2 * 2.3m^2 / 8
Cuantía requerida 0.00301135
1.33 * Cuantína 0.0040051
Cuantía Suministrada 0.0033
As por metro de ancho 7.67 cm^2/m

CHEQUEO POR CORTANTE


vc 649.2 kN/m^2
Vu / m 101.0 kN/m
vu 439.1 kN/m^2 Bien!!

Puesto que los bordes de las zapatas aquí presentadas, quedan muy cercanos, se opta por realizar cimientos
corridos en algunas zonas de la fundación.

11.5 Diseño de la losa

CM= 0.27 ton/m2


CV= 0.30 ton/m2
Mu 1.40M(CM) 1.70M(CV)
Mu=1.40M(CM)+1.70M(CV)
Mu+= 0.062 ton-m/m
Mu-= 0.046 ton-m/m

Mu = 6.18 4.65 Ton-cm


e= 10.00 10.00 cm
b= 100.00 100.00 cm
d
d= 7 00
7.00 6 00
6.00 cm
f´c= 210 210 kg/cm2
fy= 4200 4200 kg/cm2
fi= 0.90 0.90 -
B1= 0.85 0.85 -
1,20xMcr= 57.39 57.39 Ton-cm
k= 0.001262 0.001291 Ton/cm2
c= 0.065 0.057 cm
a= 0.055 0.048 cm
a/d= 0.008 0.008 -
ro= 0.000335 0.000343 -
rox4/3= 0.000447 0.000457 -
romin= 0.003333 0.003333 -
romax= 0.016063 0.016063 -

29 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

As/ml= 0.23 0.21 cm2/ml


As= 0.23 0.21 cm2
A min=
As i 2 33
2.33 2 00
2.00 cm2/ml
2/ l
As x 4/3= 0.31 0.27 cm2/ml

Distribución del refuerzo por ml para:

Varilla Separación Separación


-
4.5mm 6.8 8.0 cm
5mm 8.4 9.8 cm
6mm 12.1 14.1 cm
8mm 21.5 25.1 cm
N3: 30.4 35.5 cm
N4: 54.4 63.5 cm
Se dispone malla de 8mm a cada 15cm
15cm.

12. Cálculo del refuerzo necesario para la losa de contrapiso:

Se calculará la losa de contrapiso con un espesor de 15cm con el cuantía mínima de =0.0022.

Cuantías y refuerzos de la losa de contrapiso

ro= 0.0022 -
h= 10.00 cm
d= 7.50 cm
b= 100.00 cm
As/ml= 1.65 cm2/ml

Distribución del refuerzo por ml para:

Malla Separación -
5mm 11.9 cm
6mm 17.1 cm
Se utilizará malla electrosoldada de 6mm a cada 150mm

13. Diseño de elementos estructurales

13.1 Vigueta principal

Ancho efectivo

L= 6.00 m
S= 0.74 m
1/8 (L)= 0.75 m

30 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

1/2(S)= 0.37 m
bef= 0.74 m

CM= 0.31 ton/m


CV= 0.26 ton/m

Las fuerzas internas provienen del modelo de análisis.

Mu = 223.30 363.50 Ton-cm


e= 35.00 35.00 cm
b= 73.50 15.00 cm
d= 32.00 32.00 cm
f´c= 210 210 kg/cm2
fy= 4200 4200 kg/cm2
fi= 0.90 0.90 -
B1= 0.85 0.85 -
1,20xMcr= 516.69 105.45 Ton-cm
k
k= 0 002671
0.002671 0 024219
0.024219 Ton/cm2
c= 0.631 6.185 cm
a= 0.536 5.257 cm
a/d= 0.017 0.164 -
ro= 0.000712 0.006982 -
rox4/3= 0.000950 0.009310 -
romin= 0.003333 0.003333 -
romax= 0.016063 0.016063 -
As/ml= 2.28 22.34 cm2/ml
As= 1.68 3.35 cm2
As min= 10.67 10.67 cm2/ml
As x 4/3= 2.23 4.47 cm2/ml

vu ≤ F Vn
Vu= 4020.00 kg
bw= 15.0 cm
d= 32.00 cm
vu= Vu / bw d = 4.19 kg/cm2
f´c= 210 kg/cm2
2
vc= √f`c/6 = g
7.64 kg/cm
2
vc= 0.85 vc= 6.49 kg/cm
Las secciones no necesitan refuerzo a cortante pues vu ≤ F vc.

13.1 Vigueta de borde

Ancho efectivo

31 de 32
INGENIERÍA DETALLE DISEÑO Y ESTUDIOS AMBIENTALES DE LA DOCUMENTO No
RED TRONCAL DEL GASODUCTO Y LA RED SECUNDARIA DE LAS ZONAS DLY-MC-C-TS-501-CO_GE
URBANAS RESIDENCIALES, COMERCIALES E INDUSTRIALES EN EL
DEPARTAMENTO DE ICA – PERÚ
REV. 0

MEMORIA DE CÁLCULO CUARTO DE CONTROL 
HUMAY, PISCO, MARCONA Y CHINCHA 28-JUN-10

L= 6.00 m
1/8 (L)= 0.75 m
1/2(S)
1/2(S)= 0 30
0.30 m
bef= 0.30 m

CM= 0.08 ton/m


CV= 0.26 ton/m

Las fuerzas internas provienen del modelo de análisis.

Mu = 169.00 275.60 Ton-cm


e= 35.00 35.00 cm
b= 30.00 15.00 cm
d= 32.00 32.00 cm
f´c= 210 210 kg/cm2
fy= 4200 4200 kg/cm2
fi= 0.90 0.90 -
B1=
1 0 85
0.85 0 85
0.85 -
1,20xMcr= 210.89 105.45 Ton-cm
k= 0.004818 0.018424 Ton/cm2
c= 1.147 4.599 cm
a= 0.975 3.910 cm
a/d= 0.030 0.122 -
ro= 0.001294 0.005192 -
rox4/3= 0 001726
0.001726 0 006923 -
0.006923
romin= 0.003333 0.003333 -
romax= 0.016063 0.016063 -
As/ml= 4.14 16.62 cm2/ml
As= 1.24 2.49 cm2
As min= 10.67 10.67 cm2/ml
As x 4/3= 1.66 3.32 cm2/ml

vu ≤ F Vn
Vu= 2680.00 kg
bw= 15.0 cm
d= 32.00 cm
vu= Vu / bw d = 2.79 kg/cm2
f´c= 210 kg/cm2
vc= √f`c/6 = 7.64 kg/cm2
2
vc= 0.85 vc= 6.49 kg/cm
Las secciones no necesitan refuerzo a cortante pues vu ≤ F vc.

32 de 32