Академический Документы
Профессиональный Документы
Культура Документы
Ft Area
Illuminated Area: 6600 Sq.Ft
Desired Footcandles: 40
No of Lamps per Fixture: 2 Nos
Each Fixture Watts: 56 Watt
Ballast Factor: 0.88
Rated mean Lumens per Lamp: 2650
Coefficient of Utilization: 0.6
Fixtures Burning hours per Year: 3200
Energy Rate (Rs.Per Kwh): र 0.10
:Results:
Jignesh.Parmar
jiguparmar@yhaoo.com
www.electricalnotes.wordpress.com
Calculate No of Fixtures / Lux for Indoor Lighting
Required Lux: (E) 200
Room Index
Length:(L) 7 Meter
Width: (w) 4 Meter
Height: (h) 3 Meter
Working Level: 0 Meter Reflection Fac
Fixture hanging Level : 0 Meter Ceiling Reflection Factor
Actual Height: (Hm) 3 Meter Light & Very Light Color
Reflection Factors: Light Color
Ceiling Reflection Factor: 0.5 Medium Color
Wall Reflection Factor: 0.5 Wall & Floor Reflection Fac
Floor Reflection Factor: 0.2 Light & Very Light Color
Type of Luminaire / Fixtures: Medium Color
Type of Fixture: Dark Color
Type of Lamp:
No of Lamps per Fixture: (n) 1 Nos Maintenance Fac
Lamp Watt: 15 Watt Good & Clear Condition
Lamp Flux: 1500 Lumen Average Condition
Room Index: (K) 0.8484848485 Poor & Dirty Condition
Utilization Factor: (Uf) 0.48
Maintenance Factor: (Mf) 0.6
:Results:
Required No of Fixtures: 13 Nos
Required No of Fixtures along Length: 5 Nos
Required No of Fixtures across Length: 3 Nos
Actual No of Fixtures along Length: 3 Nos