Академический Документы
Профессиональный Документы
Культура Документы
CONTENTS
Controller ............................................................................................................... 2
Function of the Relays ........................................................................................... 2
Gas Detectors ........................................................................................................ 2
Cabling .................................................................................................................. 4
Mechanical Installation of the gas detectors ........................................................... 6
SCAN20 Series Gas Detection Controllers ................................................................ 8
SCAN200E Controller.............................................................................................. 11
DGTec2 Gas Detector ............................................................................................. 13
DGTm3 Gas Detector .............................................................................................. 16
DGTi2 Gas Detector ................................................................................................ 18
DGTt2 Gas Detector ................................................................................................ 20
DGTk2 Gas Detector ............................................................................................... 24
MAINTENANCE AND CALIBRATION ..................................................................... 26
RECYCLING ........................................................................................................... 27
PUBLISHER
Detector Oy, Telekatu 8, 20360 Turku, Finland
Telephone +358 207 756 480, Email detector@detector.fi
© Detector Oy 2017
Copying contents of this booklet or handing over to third party is strictly forbidden without written
permission from Detector Oy.
All efforts have been made to ensure the content of this booklet to be correct, however Detector
Oy does not take responsibility for damage caused by errors or missing information in this booklet.
Technical specifications may change without prior notice.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 2/30
_____________________________________________________________________________
INSTALLATION IN GENERAL
Controller
The controller shall preferable be installed at a central place, where person-
nel is present at all times, i.e. in the control room. The controller shall be
protected from dirt and water coming along the wall or the mounting plate.
The controller shall not be installed in the area under monitoring, e.g. in a
refrigeration compressor room. In constraining situations, as minimum re-
quirement gas alarming sound and/or flashing equipment shall be installed
at the entrance of the room.
Do not install any third-party components or devices on the gas detection
controller. Use of uninterrupted power source is recommended to maintain
monitoring during power outage.
A map containing all gas detector and alarm device locations shall be avail-
able near the gas detection controller. It is also advisable to provide any
site-specific instructions for alarm events.
Gas detection controller and gas detectors require regular maintenance.
The controller and detectors shall be maintained at the same time to ensure
reliable operation of the system. It is recommended to test any external
alarm functionality during the maintenance.
Function of the Relays
Ensure the compatibility of the load and relays beforehand. The relays in
the AVACO SYSTEMS products are designed for resistive load. When con-
necting capacitive / inductive loads, e.g. flashes or contactors, the load
must be adapted appropriate to the relays. In most cases this can be done
by connecting a metal oxide varistor or an RC filter parallel to the relay tips.
Apply relay controls only after successful system test.
Gas Detectors
The gas detectors need regular maintenance. The accessibility has to be
taken into account when choosing the installation place, if necessary,
maintenance platforms has to be arranged. Do not expose gas detectors to
strong infrared radiation or steam clouds.
Gas detectors are to be installed as late as possible during construction
work to avoid any damage due to welding and painting. However, installa-
tion and stabilization must be carried out before using any gases or liquids
the detectors are to measure. Stabilization time is 2 to 4 days or more
depending on sensor type and temperature unless otherwise noted. By-
pass all relay controls during the stabilization.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 3/30
_____________________________________________________________________________
To protect the gas detector from dirt and moisture the casing has to be in-
stalled with the sensor protection cover directed downwards. Also, the ca-
bling shall be done from below for the same reasons. When the cabling in
constraining situations is done from above, the gland has to be sealed
properly.
During gas detector installation or when making electrical changes into the
gas detection system, the power must be disconnected to prevent damage.
The gas detector shall be assembled near to a presumptive leakage place
to achieve a fast response, however, the density of the gas shall be taken
into account when defining the assembly height.
• when monitoring gases, which are heavier than air the gas detectors
shall be assembled at a height of 30 – 50 cm from the floor level.
Thus, there is enough space between the gas detector and the floor
for the maintenance of the gas detector and for the cleaning of the
floor. If there are possibilities of mechanical damage, a protection
shield shall be assembled around the sensor.
• when monitoring gases, which are lighter than air the gas detectors
shall be assembled at or near to the ceiling.
• when the density for the measured gas is approximately the same as
for air the gas detectors shall be installed at the breathing height.
• Install splash protection in areas where detectors are exposed to wa-
ter. (see page 7, consult manufacturer for more information)
• A heated enclosure may be required when using the detector outside
of normal operating temperature and/or humidity.
The detectors are meant for alarm limit based detection of gases and sol-
vents. These devices require regular maintenance and testing to ensure
correct operation. Full calibration must be done at least once a year and
testing more often. On-site safety statement will define the correct test inter-
val.
Test gas pressure at detector gas inlet shall be within ±10% of nominal air
pressure.
Calibration and test gas concentration must not exceed the range of the de-
tector. In case of flammable gas the concentration must be 0 – 50 %LEL.
Excess gas concentration may damage the sensor element. Make sure the
gas flow at the calibration adapter is unobstructed. Contact your dealer for
most of calibration gases.
In unclear situations regarding the installation of the gas detectors, kindly
contact DETECTOR Oy, or the local authorities for occupational health and
safety or the fire brigade.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 4/30
_____________________________________________________________________________
Cabling
The gas detectors are cabled to the controllers as own circuits, by e.g.
JAMAK 2x(2+1)x0.5 mm2 or by an equivalent cable. At ATEX sites standard
EN 60079-14 will specify the cable type. The type of the gas detector de-
fines the number of wires in the cable. If the cable is exposed for vandalism
or mechanical stress, an armoured cable shall be used.
Signal cable shields are grounded only from the controller to prevent
ground current loops. If the gas detector casing is not earth connected, the
signal cable shield shall be connected to the casing.
When using other than recommended cable, correct operation of the sys-
tem is not guaranteed.
The type of the gas detector, the supply voltage and the cable cross-section
area defines the maximum cable length. It is recommended to use the fol-
lowing formula for calculating the maximum cable length, when the distance
is over 300 m. The formula is valid for AVACO SYSTEMS gas detectors,
when the cable cross section area, the maximum allowed loss of voltage,
the specific resistance of the used cable material and the power consump-
tion of the gas detector are known.
Voltage Loss: The minimum required voltage for the gas detector is sub-
tracted from the supply voltage; the result is the biggest allowed loss of volt-
age in the cable, which is used in the formula as voltage loss.
Detector Current: The current consumption in Ampere written on the equip-
ment plate or in the inspection sheet for the equipment.
Wire Area: The wire cross section area in square millimetres.
Wire Resistance Factor: The specific resistance for the wire material, for
copper 0.0172 Ω/m*mm2.
The result for cable length is expressed in meters.
For example, a wire with a maximum voltage loss of 10V, cross section
area of 0.8 mm2 and with gas detector current consumption of 205 mA, the
maximum cable length is calculated to be approximately 1 100 m.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 5/30
_____________________________________________________________________________
Figure 1, Recommended cabling for 2-wire connection when gas detector casing is
isolated from surface using non conducting plate.
Figure 3, Recommended cabling for 4-wire connection when gas detector casing is
isolated from surface using non conducting plate.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 6/30
_____________________________________________________________________________
Figure 6, Installation position for ceiling and wall mounted versions. Sensor cover is
pointing downwards.
Figure 7, Duct mounted version includes 132 mm long probe and mounting ring.
168 mm
149 mm
255 mm
142 mm
Figure 8, Stainless steel double skin weather enclosure with rain cover (H225 x W168 x
D149 mm), image without pipe mounting kit.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 8/30
_____________________________________________________________________________
Figure 9, SCAN20 gas detection controller general view and mounting dimensions. The
photo is missing the bottom cable entry.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 10/30
_____________________________________________________________________________
Figure 10, SCAN20 gas detection controller terminal blocks found on the circuit board
(version E or later).
NOTE: Connections described here are not connected in all SCAN20 models.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 11/30
_____________________________________________________________________________
SCAN200E Controller
Construction: Controller consisting of CPU unit and input
and relay modules. Possibility to connect sub-
controllers equipped with input and relay
modules to the controller. Maximum distance
between the controller unit and sub-control-
lers using RS485 is one kilometre.
Installation: In a 19” rack or in a metal or PC enclosure,
fixed to the wall by screws.
Inputs: 8…64 pcs, in 8 input units, standard current
signal 0(4)…20mA, voltage signals 0(2)…10V
and direct measuring.
Outputs: From 8 to 128 relays in modules of 8 relays.
Relay contacts for 230 VAC 1 A resistive
load.
RS-232 for modem/maintenance. The op-
tional GSM modem enables alarm SMS for up
to 3 different cell phone numbers.
RS-485 for Modbus/Profibus (optional).
Display: 240 x 128 pixel back lighted LCD display, in-
dicators for the alarm levels I, II, III and for
malfunction
Operating Voltage: 230 VAC / 24 VDC
Operating Temperature: 0…50°C
Operating Humidity: 10…90 % RH, non-condensing
Note: The controller is delivered with complete and
project specific installation documents.
Figure 13, DGTec2 gas detector general view. The model and the size of the sensor
protection depend on the type of the gas specific sensor. Duct mounted DGTec2d is
also available.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 14/30
_____________________________________________________________________________
Figure 14, DGTec2 connections and layout on the circuit board. The circuit board
version depends on the target gas.
Figure 15, DGTec2 oxygen/O2 connections and layout on the circuit board.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 15/30
_____________________________________________________________________________
24
22
20
Voltage [V]
18
16
14
12
10
0 100 200 300 400 500
Resistance [Ω]
24
22
20
Voltage [V]
18
16
14
12
10
0 100 200 300 400 500
Resistance [Ω]
Constant yellow:
Sensor failure.
Blinking red:
Gas alarm. Blinking will stop when the gas
concentration is lower than the alarm limit.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 19/30
_____________________________________________________________________________
Figure 21, DGTi2 connections and layout on the circuit board. Buzzer and relay on
DGTi2r.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 20/30
_____________________________________________________________________________
Constant red:
Sensor failure.
Blinking red:
Gas alarm. Blinking will stop when the gas
concentration is lower than the alarm limit.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 21/30
_____________________________________________________________________________
Figure 22, DGTt2 gas detector general view (-w, wall mounted). The DGTt2 gas detector
can also be mounted to the ceiling (model -c) or to a duct (model -d).
Constant red:
Sensor failure.
Blinking red:
Gas alarm. Blinking will stop when the gas
concentration is lower than the alarm limit.
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 25/30
_____________________________________________________________________________
We will help you to plan and conduct maintenance planning and calibration.
Maintenance contracts are custom made to suite individual needs.
DETECTOR OY
Telekatu 8
FI-20360 TURKU
FINLAND
detector@detector.fi
www.detector.fi
Installation manual detector and controller
Code no. 20711062
Rev. 5.9
Page 27/30
_____________________________________________________________________________
RECYCLING
Please follow the instructions for recycling the gas detectors:
DETECTOR OY
Telekatu 8
FI-20360 TURKU
FINLAND
detector@detector.fi
www.detector.fi
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 28/30
_____________________________________________________________________________
Figure 30, Declaration of conformity for SCAN series gas detection controllers.
Code no. 20711062 Installation manual detector and controller
Rev. 5.9
Page 30/30
_____________________________________________________________________________