Вы находитесь на странице: 1из 4

SuperTAPP n+®

Voltage Control for Active Networks

SuperTAPP n+ is an innovative tap changer With more and more distributed generation
control system which incorporates market- becoming integrated into the network
leading and unrivalled functionality to these problems are bound to increase.
provide complete AVC (Automatic Voltage SuperTAPP n+ functionality and adaptability
Control) for modern power networks. ensures that it can accommodate the
SuperTAPP n+ solves problems associated connection of more and more distributed
with distributed generation, network generation from a wide range of sources.
interconnections, busbar configuration It can be configured as a standard AVC
changes, troublesome loads and other system and is easily upgraded to enable
voltage control issues. advanced AVC. It has been future proofed.

Key Features Key Benefits


• Solutions for embedded generation • Optimise network voltages
• Reverse power functions • Reduce operational costs
• Load correction for abnormal power • Reduce tap changer maintenance costs
factor loads
• Reduce risk of tap changer
• Double-secondary winding transformers failure/damage
• Standard voltage control functions • Reduce network reinforcement costs
• SCADA communications • Maximise headroom for generation
connections
• Remote application web monitoring
• Reduce generator curtailment
• Flexible and future-proof
• Fewer customer complaints
Flexible and Future-Proof
SuperTAPP n+ is available as a ‘basic’ • Solutions for Distributed Generation
relay with standard AVC functions and • Remote Measurements and Monitoring
can be easily and economically upgraded
• Load Exclusion/Correction for
to an ‘advanced’ version to activate extra
Abnormal Power Factor Loads
innovative functions with no software
or hardware changes required: • Double-Secondary Winding Transformers

Solutions for Distributed Generation


Countries are turning increasingly to distributed The result can be unacceptable and
generation in order to achieve carbon unpredictable voltage levels throughout
emissions obligations. Electrical power grids the network leading to increased customer
were designed to accommodate uni-directional complaints, generator curtailment and/or
power flow from the ‘top’ of the network where requirement for network reinforcement,
it is generated down to consumers at the increased tap changer operations and
‘bottom’. The emergence of distributed therefore maintenance, increased alarms
generation has therefore introduced a number on the system and related engineering/
of technical problems for network operation support costs, increased outages and
relating to bi-directional power flow such as possible tap changer failure, transformer
quality, thermal limits and voltage control. damage and H&S issues.
Increased protection and control are required
SuperTAPP n+ has been developed to
for the new grid.
incorporate functions to address these
Fundamentals is widely recognised as the issues which are enabled by use of built-in
leading expertise for voltage control and current measurements for feeders to
are well known for SuperTAPP system and which generation is connected:
later MicroTAPP system (co-developed with
• Generator compensation
Reyrolle Protection). More than two decades
of experience with network applications • Accurate load drop compensation
has identified the effect of distributed • Advanced transformer paralleling
generation on voltage control to include: principle
• Voltage rise at the point of generator • Reverse power OLTC blocking
connection(s)
• Facility to implement remote network
• Compromised LDC (load/line drop measurements
compensation)
• Compromised control of paralleled CAN BUS

transformers
n+ n+
• Reverse power flow on transformers
beyond OLTC rating

G
Remote Measurements and Monitoring
CAN BUS
ENVOY Increased accuracy can be realised by incorporation
of remote network measurements via
n+ n+
communications, e.g. at the point of connection
of downstream generation.
No system should be totally reliant on remote
GPRS
X
communications and SuperTAPP n+ offers distinct
advantages due to its ability to optimise the ‘view’
of the network each time it receives network
G
measurements. If communication links are lost,
accurate voltage control is maintained by use of
ENVOY DAM
local measurements and an estimation algorithm
based on the most up-to-date network data.
Remote monitoring and management of Super
TAPP n+ applications is possible through a dedicated
web interface. This enables configurable alerts and
notifications, data gathering and performance
analysis to provide the ultimate support tool.

Load Correction for Abnormal


Power Factor Loads
n+ There are network components other than
ITL generation connections which can cause problems
Icap
ITL
V
for voltage control because of their effect on the
measured transformer load power factor. Examples
I1 are heavy industrial loads, capacitor banks and
Icap I2
other compensation equipment. SuperTAPP n+
CAPACITOR can reduce or remove the effects of such
BANK I1 I2
components by manipulation of measured load
LOAD LOAD
power factors.

Double Secondary Winding Transformers


Voltage control for double-secondary winding
transformers is possible with SuperTAPP n+.
n+
Built-in voltage averaging and load current
summation, with auto-detection of single-secondary
winding operation result in a compact and efficient
solution for these critical transformers.

X
Specification
• Power Supply • Digital Status Inputs
• 80 – 260 V AC • 6 available
• 90 – 140 V DC • Operating range 20- 250 V AC/DC
• Voltage Measurement Inputs • Outputs
• 2 inputs available • 6 available
• Nominal 110 V • Rated 12 A continuous
• Rated up to 150 V • CAN bus peer-to-peer communications
• Current Measurement Inputs • SCADA interface for DNP3, IEC 61850 etc.
• 3 inputs available* • Fully type tested to ENATS 48-5
• External interposer CTs used (protection relays)
• Safe, flexible and low burden
• Rated up to 10 A • Compatible with TMU
(tap changer monitor unit)
*more current measurements can
be accommodated with use of the • Tap changer runaway prevention
Data Acquisition Module • Over-voltage and under-voltage blocking
• Comprehensive 19’’ rack system
Contact
Fundamentals Ltd can assist with all applications
concerning voltage control of electrical networks:
• Technical support • Commissioning
• Troubleshooting • Power system analysis
• Design and engineering • Generation connection assessment
• Installation • Consultancy
• Site surveys • Panel / cubicle build

Fundamentals Ltd Telephone 01793 847163 www.fundamentalsltd.co.uk


4 Hillmead Enterprise Park Fax 01793 847245 enquiries@fundamentalsltd.co.uk
Marshall Road, Swindon
Wiltshire, SN5 5FZ

Вам также может понравиться