Вы находитесь на странице: 1из 52

Relion® Protection and Control

670 series 2.1 IEC


SPA Communication protocol manual
Document ID: 1MRK 511 353-UEN
Issued: December 2015
Revision: -
Product version: 2.1

© Copyright 2014 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographic
software written/developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson
(tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure
would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that
all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series.
Table of contents

Table of contents

Section 1 Introduction.......................................................................3
This manual........................................................................................ 3
Intended audience.............................................................................. 3
Product documentation.......................................................................4
Product documentation set............................................................4
Document revision history............................................................. 5
Related documents........................................................................5
Document symbols and conventions..................................................7
Symbols.........................................................................................7
Document conventions.................................................................. 8

Section 2 SPA application.............................................................. 11


SPA communication protocol........................................................... 11
Application................................................................................... 11
Setting guidelines........................................................................ 12

Section 3 SPA operation principle..................................................13


Operation principle........................................................................... 13
Introduction of SPA protocol...................................................13
SPA protocol.......................................................................... 13
Communication ports...................................................................18
Design.............................................................................................. 18

Section 4 SPA settings...................................................................21


Settings.............................................................................................21

Section 5 SPA technical data......................................................... 23


Technical data.................................................................................. 23

Section 6 Establishing connection and verifying the SPA/IEC-


communication .............................................................. 25
Establishing connection and verifying the SPA/IEC-
communication ................................................................................ 25
Entering settings..........................................................................25
Entering SPA settings............................................................ 25
Verifying the communication....................................................... 26
Verifying SPA communication................................................ 26
Fibre optic loop............................................................................ 26
Optical budget calculation for serial communication with
SPA/IEC ..................................................................................... 26

670 series 2.1 IEC 1


Communication protocol manual
Table of contents

Section 7 SPA functions.................................................................27


Event function EVENT......................................................................27
Identification................................................................................ 27
Function block............................................................................. 27
Signals.........................................................................................28
Settings........................................................................................29
Operation principle...................................................................... 31
Setting guidelines............................................................................. 32
EventMask (Ch_1 - 16)...........................................................32
LONChannelMask or SPAChannelMask................................32
MinRepIntVal (1 - 16)............................................................. 32
Logical signal status report BINSTATREP....................................... 33
Identification................................................................................ 33
Functionality................................................................................ 33
Function block............................................................................. 33
Signals.........................................................................................33
Settings........................................................................................34
Operation principle...................................................................... 35

Section 8 Glossary......................................................................... 37
Glossary........................................................................................... 37

2 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 1
Introduction

Section 1 Introduction

1.1 This manual

The communication protocol manual describes the communication protocols


supported by the IED. The manual concentrates on the vendor-specific
implementations.

1.2 Intended audience

This manual addresses the communication system engineer or system integrator


responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.

The system engineer or system integrator must have a basic knowledge of


communication in protection and control systems and thorough knowledge of the
specific communication protocol.

670 series 2.1 IEC 3


Communication protocol manual
Section 1 1MRK 511 353-UEN -
Introduction

1.3 Product documentation

1.3.1 Product documentation set

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual

Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd

IEC07000220 V4 EN

Figure 1: The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs using the
various tools available within the PCM600 software. The manual provides
instructions on how to set up a PCM600 project and insert IEDs to the project
structure. The manual also recommends a sequence for the engineering of protection
and control functions, LHMI functions as well as communication engineering for IEC
60870-5-103, IEC 61850, DNP3, LON and SPA.

The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in the chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for the checking
of external circuitry and energizing the IED, parameter setting and configuration as

4 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 1
Introduction

well as verifying settings by secondary injection. The manual describes the process of
testing an IED in a substation which is not in service. The chapters are organized in the
chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and
setting of the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.

The application manual contains application descriptions and setting guidelines


sorted per function. The manual can be used to find out when and for what purpose a
typical protection function can be used. The manual can also provide assistance for
calculating settings.

The technical manual contains operation principle descriptions, and lists function
blocks, logic diagrams, input and output signals, setting parameters and technical
data, sorted per function. The manual can be used as a technical reference during the
engineering phase, installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols


supported by the IED. The manual concentrates on the vendor-specific
implementations.

The point list manual describes the outlook and properties of the data points specific
to the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.

The cyber security deployment guideline describes the process for handling cyber
security when communicating with the IED. Certification, Authorization with role
based access control, and product engineering for cyber security related events are
described and sorted by function. The guideline can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.

1.3.2 Document revision history


Document revision/date History
December 2015 First release

1.3.3 Related documents


Documents related to REB670 Document numbers
Application manual 1MRK 505 337-UEN
Commissioning manual 1MRK 505 339-UEN
Product guide 1MRK 505 340-BEN
Technical manual 1MRK 505 338-UEN
Type test certificate 1MRK 505 340-TEN

670 series 2.1 IEC 5


Communication protocol manual
Section 1 1MRK 511 353-UEN -
Introduction

Documents related to REC670 Document numbers


Application manual 1MRK 511 358-UEN
Commissioning manual 1MRK 511 360-UEN
Product guide 1MRK 511 361-BEN
Technical manual 1MRK 511 359-UEN
Type test certificate 1MRK 511 361-TEN

Documents related to RED670 Document numbers


Application manual 1MRK 505 343-UEN
Commissioning manual 1MRK 505 345-UEN
Product guide 1MRK 505 346-BEN
Technical manual 1MRK 505 308-UEN
Type test certificate 1MRK 505 346-TEN

Documents related to REG670 Document numbers


Application manual 1MRK 502 065-UEN
Commissioning manual 1MRK 502 067-UEN
Product guide 1MRK 502 068-BEN
Technical manual 1MRK 502 066-UEN
Type test certificate 1MRK 502 068-TEN

Documents related to REL670 Document numbers


Application manual 1MRK 506 353-UEN
Commissioning manual 1MRK 506 355-UEN
Product guide 1MRK 506 356-BEN
Technical manual 1MRK 506 354-UEN
Type test certificate 1MRK 506 356-TEN

Documents related to RET670 Document numbers


Application manual 1MRK 504 152-UEN
Commissioning manual 1MRK 504 154-UEN
Product guide 1MRK 504 155-BEN
Technical manual 1MRK 504 153-UEN
Type test certificate 1MRK 504 155-TEN

6 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 1
Introduction

Documents related to RES670 Document numbers


Application manual 1MRK 511 364-UEN
Commissioning manual 1MRK 511 366-UEN
Product guide 1MRK 511 367-BEN
Technical manual 1MRK 511 365-UEN
Type test certificate 1MRK 511 367-TEN

670 series manuals Document numbers


Operation manual 1MRK 500 123-UEN
Engineering manual 1MRK 511 355-UEN
Installation manual 1MRK 514 024-UEN
Communication protocol manual, DNP3 1MRK 511 348-UUS
Communication protocol manual, IEC 1MRK 511 351-UEN
60870-5-103
Communication protocol manual, IEC 61850 1MRK 511 349-UEN
Edition 1
Communication protocol manual, IEC 61850 1MRK 511 350-UEN
Edition 2
Communication protocol manual, LON 1MRK 511 352-UEN
Communication protocol manual, SPA 1MRK 511 353-UEN
Point list manual, DNP3 1MRK 511 354-UUS
Accessories guide 1MRK 514 012-BEN
Cyber security deployment guideline 1MRK 511 356-UEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN

1.4 Document symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard which


could result in electrical shock.

The warning icon indicates the presence of a hazard which could


result in personal injury.

The caution hot surface icon indicates important information or


warning about the temperature of product surfaces.

670 series 2.1 IEC 7


Communication protocol manual
Section 1 1MRK 511 353-UEN -
Introduction

The caution icon indicates important information or warning related


to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.

The information icon alerts the reader of important facts and


conditions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand


that under certain operational conditions, operation of damaged equipment may result
in degraded process performance leading to personal injury or death. It is important
that the user fully complies with all warning and cautionary notices.

1.4.2 Document conventions


• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press
.
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the
signal name may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to
achieve a valid application configuration.
• Logic diagrams describe the signal logic inside the function block and are
bordered by dashed lines.

8 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 1
Introduction

• Signals in frames with a shaded area on their right hand side represent
setting parameter signals that are only settable via the PST or LHMI.
• If an internal signal path cannot be drawn with a continuous line, the suffix
-int is added to the signal name to indicate where the signal starts and
continues.
• Signal paths that extend beyond the logic diagram and continue in another
diagram have the suffix ”-cont.”

670 series 2.1 IEC 9


Communication protocol manual
10
1MRK 511 353-UEN - Section 2
SPA application

Section 2 SPA application

2.1 SPA communication protocol

2.1.1 Application
SPA communication protocol as an alternative to IEC 60870-5-103. The same
communication port as for IEC 60870-5-103 is used.

When communicating with a PC connected to the utility substation LAN, via WAN
and the utility office LAN, as shown in figure 2, and using the rear Ethernet port on the
optical Ethernet module (OEM), the only hardware required for a station monitoring
system is:

• Optical fibres from the IED to the utility substation LAN.


• PC connected to the utility office LAN.

Utility LAN

Remote monitoring

WAN

Substation LAN

IED IED IED

IEC05000715-3-en.vsd
IEC05000715 V3 EN

Figure 2: SPA communication structure for a remote monitoring system via a


substation LAN, WAN and utility LAN

The SPA communication is mainly used for the Station Monitoring System. It can
include different IEDs with remote communication possibilities. Connection to a
computer (PC) can be made directly (if the PC is located in the substation) or by
telephone modem through a telephone network with ITU (former CCITT)
characteristics or via a LAN/WAN connection.

glass <1000 m according to optical budget


plastic <20 m (inside cubicle) according to optical budget

670 series 2.1 IEC 11


Communication protocol manual
Section 2 1MRK 511 353-UEN -
SPA application

Functionality
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The
communication is based on a master-slave principle, where the IED is a slave and the
PC is the master. Only one master can be applied on each fibre optic loop. A program
is required in the master computer for interpretation of the SPA-bus codes and for
translation of the data that should be sent to the IED.

For the specification of the SPA protocol V2.5, refer to SPA-bus Communication
Protocol V2.5.

2.1.2 Setting guidelines


The setting parameters for the SPA communication are set via the local HMI.

SPA, IEC 60870-5-103 and DNP3 uses the same rear communication port. Set the
parameter Operation, under Main menu /Settings /General settings /
Communication /SLM configuration /Rear optical SPA-IEC-DNP port /
Protocol selection to the selected protocol.

When the communication protocols have been selected, the IED is automatically
restarted.

The most important settings in the IED for SPA communication are the slave number
and baud rate (communication speed). These settings are absolutely essential for all
communication contact to the IED.

These settings can only be done on the local HMI for rear channel communication and
for front channel communication.

The slave number can be set to any value from 1 to 899, as long as the slave number
is unique within the used SPA loop.

The baud rate, which is the communication speed, can be set to between 300 and
38400 baud. Refer to technical data to determine the rated communication speed for
the selected communication interfaces. The baud rate should be the same for the whole
station, although different baud rates in a loop are possible. If different baud rates in
the same fibre optical loop or RS485 network are used, consider this when making the
communication setup in the communication master, the PC.

For local fibre optic communication, 19200 or 38400 baud is the normal setting. If
telephone communication is used, the communication speed depends on the quality of
the connection and on the type of modem used. But remember that the IED does not
adapt its speed to the actual communication conditions, because the speed is set on the
local HMI.

12 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 3
SPA operation principle

Section 3 SPA operation principle

3.1 Operation principle

The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data
bits + even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more
information on recommended baud rate for each type of IED, refer to Technical
reference manual. Messages on the bus consist of ASCII characters.

3.1.1.1 Introduction of SPA protocol

The basic construction of the protocol assumes that the slave has no self-initiated need
to talk to the master but the master is aware of the data contained in the slaves and,
consequently, can request required data. In addition, the master can send data to the
slave. Requesting by the master can be performed either by sequenced polling (for
example, for event information) or only on demand.

The master requests slave information using request messages and sends information
to the slave in write messages. Furthermore, the master can send all slaves in common
a broadcast message containing time or other data. The inactive state of bus transmit
and receive lines is a logical "1".

3.1.1.2 SPA protocol

The tables below specify the SPA addresses for reading data from and writing data to
an IED with the SPA communication protocol implemented.

The SPA addresses for the pulse counter values PCFCNT:1 to PCFCNT:16 are found
in table 1.
Table 1: SPA addresses for the PCFCNT function
Function block SPA address CNT_VAL SPA address NEW_VAL
PCFCNT:1 6-O-2788 6-O-2787
PCFCNT:2 6-O-2794 6-O-2793
PCFCNT:3 6-O-2800 6-O-2799
PCFCNT:4 6-O-2806 6-O-2805
PCFCNT:5 6-O-2812 6-O-2811
PCFCNT:6 6-O-2818 6-O-2817
PCFCNT:7 6-O-2824 6-O-2823
PCFCNT:8 6-O-2830 6-O-2829
PCFCNT:9 6-O-2836 6-O-2835
Table continues on next page

670 series 2.1 IEC 13


Communication protocol manual
Section 3 1MRK 511 353-UEN -
SPA operation principle

Function block SPA address CNT_VAL SPA address NEW_VAL


PCFCNT:10 6-O-2842 6-O-2841
PCFCNT:11 6-O-2848 6-O-2847
PCFCNT:12 6-O-2854 6-O-2853
PCFCNT:13 6-O-2860 6-O-2859
PCFCNT:14 6-O-2866 6-O-2865
PCFCNT:15 6-O-2872 6-O-2871
PCFCNT:16 6-O-2878 6-O-2877

I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function
block are used, that is, the addresses for BI1 – BI16. For SPA addresses, refer to
section Related documents in Product Guide.

Single command, 16 signals


The IEDs can be provided with a function to receive signals either from a substation
automation system or from the local HMI. That receiving function block has 16
outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.

Single command, 16 signals function consists of three function blocks;


SINGLECMD:1 to SINGLECMD:3 for 16 binary output signals each.

The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 3 signals function
block, SINGLECMD:1 to SINGLECMD:3, the address is for the first output. The
other outputs follow consecutively after the first one. For example, output 7 on the
SINGLECMD:2 function block has the 5O533 address.

The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to


SINGLECMD:3 are found in table 2.
Table 2: SPA addresses for SINGLECMD function
Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd1 4-S-4639 5-O-511
SINGLECMD1-Cmd2 4-S-4640 5-O-512
SINGLECMD1-Cmd3 4-S-4641 5-O-513
SINGLECMD1-Cmd4 4-S-4642 5-O-514
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
Table continues on next page

14 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 3
SPA operation principle

Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558

670 series 2.1 IEC 15


Communication protocol manual
Section 3 1MRK 511 353-UEN -
SPA operation principle

Figure 3 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection IED
for control of a circuit breaker.

A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:
1 are shown in table 2.
SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
#CD01-CMDOUT1 ^OUT2
#CD01-CMDOUT2 ^OUT3
#CD01-CMDOUT3 ^OUT4
#CD01-CMDOUT4 ^OUT5 AND PULSETIMER
^OUT6 INPUT1 OUT INPUT OUT To output board, OPEN
#CD01-CMDOUT5
#CD01-CMDOUT6 ^OUT7 INPUT2 NOUT
#CD01-CMDOUT7 ^OUT8 INPUT3
#CD01-CMDOUT8 ^OUT9 INPUT4
#CD01-CMDOUT9 ^OUT10
#CD01-CMDOUT10 ^OUT11
#CD01-CMDOUT11 ^OUT12
#CD01-CMDOUT12 ^OUT13
#CD01-CMDOUT13 ^OUT14
#CD01-CMDOUT14 ^OUT15
#CD01-CMDOUT15 ^OUT16
#CD01-CMDOUT16

IEC05000717-3-en.vsd
SYNCH OK

IEC05000717 V3 EN

Figure 3: Application example showing a simplified logic diagram for control of


a circuit breaker

The MODE input defines if the output signals from SINGLECMD:1 is off, steady or
setable pulse length signals. This is set in Parameter Setting Tool (PST) under: Main
Menu/Settings / IED Settings / Control / Commands / Single Command or via
Parameter Setting Tool (PST).

Event function
Event function is intended to send time-tagged events to the station level (for example,
operator workplace) over the station bus. The events are there presented in an event
list. The events can be created from both internal logical signals and binary input
channels. All the internal signals are time tagged in the main processing module, while
the binary input channels are time tagged directly on each I/O module. The events are
produced according to the set of event masks. The event masks are treated commonly
for both the LON and SPA channels. All events according to the event mask are stored
in a buffer, which contains up to 1000 events. If new events appear before the oldest
event in the buffer is read, the oldest event is overwritten and an overflow alarm
appears.

Two special signals for event registration purposes are available in the IED, Terminal
Restarted (0E50) and Event buffer overflow (0E51).

The input parameters can be set individually from the Parameter Setting Tool (PST)
under: Main Menu/Settings / IED Settings / Monitoring / Event Function or via
parameter Setting Tool (PST) as follows:

16 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 3
SPA operation principle

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)

The Status and event codes for the Event functions are found in table 3.
Table 3: Status and event codes

Single indication1) Double indication


Event block Status Set event Reset Intermedi Closed 10 Open 01 Undefined
event ate 00 11
EVENT:1
Input 1 22O1 22E33 22E32 22E0 22E1 22E2 22E3
Input 2 22O2 22E35 22E34 22E4 22E5 22E6 22E7
Input 3 22O3 22E37 22E36 22E8 22E9 22E10 22E11
Input 4 22O4 22E39 22E38 22E12 22E13 22E14 22E15
Input 5 22O5 22E41 22E40 22E16 22E17 22E18 22E19
Input 6 22O6 22E43 22E42 22E20 22E21 22E22 22E23
Input 7 22O7 22E45 22E44 22E24 22E25 22E26 22E27
Input 8 22O8 22E47 22E46 22E28 22E29 22E30 22E31
Input 9 22O9 22E49 22E48 - - - -
Input 10 22O10 22E51 22E50 - - - -
Input 11 22O11 22E53 22E52 - - - -
Input 12 22O12 22E55 22E54 - - - -
Input 13 22O13 22E57 22E56 - - - -
Input 14 22O14 22E59 22E58 - - - -
Input 15 22O15 22E61 22E60 - - - -
Input 16 22O16 22E63 22E62 - - - -

EVENT:2 230.. 23E.. 23E.. 23E.. 23E.. 23E.. 23E..


EVENT:3 240.. 24E.. 24E.. 24E.. 23E.. 24E.. 24E..
- - - - - - - -
- - - - - - - -
- - - - - - - -
EVENT:20 410.. 41E.. 41E.. 41E.. 41E.. 41E.. 41E..

These values are only applicable if the Event mask is masked ≠ OFF.

Connection of signals as events


Signals coming from different protection and control functions and must be sent as
events to the station level over the SPA-bus (or LON-bus) are connected to the Event
function block according to figure 4.

670 series 2.1 IEC 17


Communication protocol manual
Section 3 1MRK 511 353-UEN -
SPA operation principle

EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC07000065-2-en.vsd
IEC07000065 V2 EN

Figure 4: Connection of protection signals for event handling

3.1.1 Communication ports


The serial communication module (SLM) is a mezzanine module placed on the
numeric processing module (NUM) and is used for LON, SPA, IEC60870-5-103, or
DNP communication.

There are two types of IO connectors: 1) snap-in for plastic fibre cables and 2) ST/
bayonet for glass fibre cables. The SLM can be equipped with either type or a
combination of both, which is identified by a tag.

Connect the incoming optical fibre to the RX receiver input, and the outgoing optical
fibre to the TX transmitter output. Pay special attention to the instructions concerning
handling and connection of fibre cables.

For setting the transfer rate (baud rate) and slave number, please refer to the
Application Manual and Commissioning Manual respectively.

3.2 Design

Using the rear SPA port for either local or remote communication with a PC requires
the following equipment:

• Optical fibres
• Opto/electrical converter for the PC
• PC

18 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 3
SPA operation principle

The software needed in the PC, either local or remote, is PCM600. (Note! SPA cannot
be used with PCM600 2.6 or later).

When communicating between the local HMI and a PC, the only hardware required is
a front-connection cable. Note! SPA cannot be used from LHMI front, except for
using "FSTACCS", that is, Field Service Tool Access.

670 series 2.1 IEC 19


Communication protocol manual
20
1MRK 511 353-UEN - Section 4
SPA settings

Section 4 SPA settings

4.1 Settings

Table 4: SPA Non group settings (basic)


Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd - - 9600 Bd Baudrate on serial line
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

Table 5: LONSPA Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
SlaveAddress 1 - 899 - 1 30 Slave address

670 series 2.1 IEC 21


Communication protocol manual
22
1MRK 511 353-UEN - Section 5
SPA technical data

Section 5 SPA technical data

5.1 Technical data

Table 6: SPA communication protocol


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400
Bd
Slave number 1 to 899

670 series 2.1 IEC 23


Communication protocol manual
24
1MRK 511 353-UEN - Section 6
Establishing connection and verifying the SPA/IEC- communication

Section 6 Establishing connection and verifying the


SPA/IEC- communication

6.1 Establishing connection and verifying the SPA/IEC-


communication

About this chapter


This chapter contains instructions on how to establish connection and verify that the
SPA/IEC-communication operates as intended, when the IED is connected to a
monitoring or control system via the rear SPA/IEC port.

6.1.1 Entering settings


If the IED is connected to a monitoring or control system via the rear SPA/IEC port,
the SPA/IEC port has to be set either for SPA or IEC use.

6.1.1.1 Entering SPA settings

The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can
be used:

• for plastic fibres with connector type HFBR


• for glass fibres with connectors type ST

When using the SPA protocol, the rear SPA/IEC port must be set for SPA use.

Procedure

1. Set the operation of the rear optical SPA/IEC port to “SPA”.


The operation of the rear SPA port can be found on the local HMI under Main
menu/Configuration/Communication/Station communication/Port
configuration/SLM optical serial port/PROTOCOL:1
When the setting is entered the IED restarts automatically. After the restart the
SPA/IEC port operates as a SPA port.
2. Set the slave number and baud rate for the rear SPA port
The slave number and baud rate can be found on the local HMI under Main
menu/Configuration/Communication/Station communication/SPA/SPA:1
Set the same slave number and baud rate as set in the SMS system for the IED.

670 series 2.1 IEC 25


Communication protocol manual
Section 6 1MRK 511 353-UEN -
Establishing connection and verifying the SPA/IEC- communication

6.1.2 Verifying the communication


To verify that the rear communication with the SMS/SCS system is working, there are
some different methods. Choose one of the following.

6.1.2.1 Verifying SPA communication

Procedure

1. Use a SPA-emulator and send “RF” to the IED. The answer from the IED should
be the type and version of it, for example, “REL670 2.1...”.
2. Generate one binary event by activating a function, which is configured to an
event block where the used input is set to generate events on SPA. The
configuration must be made with the PCM600 software. Verify that the event is
presented in the SMS/SCS system.

During the following tests of the different functions in the IED, verify that the events
and indications in the SMS/SCS system are as expected.

6.1.3 Fibre optic loop


The SPA communication is mainly used for SMS. It can include different numerical
IEDs with remote communication possibilities. The fibre optic loop can contain <
20-30 IEDs depending on requirements on response time. Connection to a personal
computer (PC) can be made directly (if the PC is located in the substation) or by
telephone modem through a telephone network with ITU (CCITT) characteristics.
Table 7: Max distances between IEDs/nodes

glass < 1000 m according to optical budget


plastic < 25 m (inside cubicle) according to optical budget

6.1.4 Optical budget calculation for serial communication with


SPA/IEC
Table 8: Example
Distance 1 km Distance 25 m
Glass Plastic
Maximum attenuation - 11 dB - 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um 4 dB -
0.16 dB/m plastic: 620 nm - 1mm - 4 dB
Margins for installation, aging, and so on 5 dB 1 dB
Losses in connection box, two contacts (0.5 dB/contact) 1 dB -
Losses in connection box, two contacts (1 dB/contact) - 2 dB
Margin for 2 repair splices (0.5 dB/splice) 1 dB -
Maximum total attenuation 11 dB 7 dB

26 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 7
SPA functions

Section 7 SPA functions

7.1 Event function EVENT

7.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Event function EVENT -
S00946 V1 EN

When using a Substation Automation system with LON or SPA communication,


time-tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The event function block is used for LON and SPA
communication.

Analog and double indication values are also transferred through EVENT function.

7.1.2 Function block


EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000697-2-en.vsd
IEC05000697 V2 EN

Figure 5: EVENT function block

670 series 2.1 IEC 27


Communication protocol manual
Section 7 1MRK 511 353-UEN -
SPA functions

7.1.3 Signals
Table 9: EVENT Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 GROUP 0 Input 1
SIGNAL
INPUT2 GROUP 0 Input 2
SIGNAL
INPUT3 GROUP 0 Input 3
SIGNAL
INPUT4 GROUP 0 Input 4
SIGNAL
INPUT5 GROUP 0 Input 5
SIGNAL
INPUT6 GROUP 0 Input 6
SIGNAL
INPUT7 GROUP 0 Input 7
SIGNAL
INPUT8 GROUP 0 Input 8
SIGNAL
INPUT9 GROUP 0 Input 9
SIGNAL
INPUT10 GROUP 0 Input 10
SIGNAL
INPUT11 GROUP 0 Input 11
SIGNAL
INPUT12 GROUP 0 Input 12
SIGNAL
INPUT13 GROUP 0 Input 13
SIGNAL
INPUT14 GROUP 0 Input 14
SIGNAL
INPUT15 GROUP 0 Input 15
SIGNAL
INPUT16 GROUP 0 Input 16
SIGNAL

28 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 7
SPA functions

7.1.4 Settings
Table 10: EVENT Non group settings (basic)
Name Values (Range) Unit Step Default Description
SPAChannelMask Off - - Off SPA channel mask
Channel 1-8
Channel 9-16
Channel 1-16
LONChannelMask Off - - Off LON channel mask
Channel 1-8
Channel 9-16
Channel 1-16
EventMask1 NoEvents - - AutoDetect Reporting criteria for input 1
OnSet
OnReset
OnChange
AutoDetect
EventMask2 NoEvents - - AutoDetect Reporting criteria for input 2
OnSet
OnReset
OnChange
AutoDetect
EventMask3 NoEvents - - AutoDetect Reporting criteria for input 3
OnSet
OnReset
OnChange
AutoDetect
EventMask4 NoEvents - - AutoDetect Reporting criteria for input 4
OnSet
OnReset
OnChange
AutoDetect
EventMask5 NoEvents - - AutoDetect Reporting criteria for input 5
OnSet
OnReset
OnChange
AutoDetect
EventMask6 NoEvents - - AutoDetect Reporting criteria for input 6
OnSet
OnReset
OnChange
AutoDetect
EventMask7 NoEvents - - AutoDetect Reporting criteria for input 7
OnSet
OnReset
OnChange
AutoDetect
EventMask8 NoEvents - - AutoDetect Reporting criteria for input 8
OnSet
OnReset
OnChange
AutoDetect
EventMask9 NoEvents - - AutoDetect Reporting criteria for input 9
OnSet
OnReset
OnChange
AutoDetect
Table continues on next page

670 series 2.1 IEC 29


Communication protocol manual
Section 7 1MRK 511 353-UEN -
SPA functions

Name Values (Range) Unit Step Default Description


EventMask10 NoEvents - - AutoDetect Reporting criteria for input 10
OnSet
OnReset
OnChange
AutoDetect
EventMask11 NoEvents - - AutoDetect Reporting criteria for input 11
OnSet
OnReset
OnChange
AutoDetect
EventMask12 NoEvents - - AutoDetect Reporting criteria for input 12
OnSet
OnReset
OnChange
AutoDetect
EventMask13 NoEvents - - AutoDetect Reporting criteria for input 13
OnSet
OnReset
OnChange
AutoDetect
EventMask14 NoEvents - - AutoDetect Reporting criteria for input 14
OnSet
OnReset
OnChange
AutoDetect
EventMask15 NoEvents - - AutoDetect Reporting criteria for input 15
OnSet
OnReset
OnChange
AutoDetect
EventMask16 NoEvents - - AutoDetect Reporting criteria for input 16
OnSet
OnReset
OnChange
AutoDetect
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

30 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 7
SPA functions

7.1.5 Operation principle


The main purpose of the event function (EVENT) is to generate events when the state
or value of any of the connected input signals is in a state, or is undergoing a state
transition, for which event generation is enabled.

Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a
name from the Application Configuration tool. The inputs are normally used to create
single events, but are also intended for double indication events.

EVENT function also has an input BLOCK to block the generation of events.

The events that are sent from the IED can originate from both internal logical signals
and binary input channels. The internal signals are time-tagged in the main processing
module, while the binary input channels are time-tagged directly on the input module.
The time-tagging of the events that are originated from internal logical signals have a
resolution corresponding to the execution cycle-time of the source application. The
time-tagging of the events that are originated from binary input signals have a
resolution of 1 ms.

The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each input
is intended to be used by the station level.

All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.

The events are produced according to the set-event masks. The event masks are treated
commonly for both the LON and SPA communication. The EventMask can be set
individually for each input channel. These settings are available:

• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect

It is possible to define which part of EVENT function generates the events. This can
be performed individually for the SPAChannelMask and LONChannelMask
respectively. For each communication type these settings are available:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

For LON communication the events normally are sent to station level at change. It is
possibly also to set a time for cyclic sending of the events individually for each input
channel.

670 series 2.1 IEC 31


Communication protocol manual
Section 7 1MRK 511 353-UEN -
SPA functions

To protect the SA system from signals with a high change rate that can easily saturate
the event system or the communication subsystems behind it, a quota limiter is
implemented. If an input creates events at a rate that completely consume the granted
quota then further events from the channel will be blocked. This block will be
removed when the input calms down and the accumulated quota reach 66% of the
maximum burst quota. The maximum burst quota per input channel is 45 events per
second.

7.2 Setting guidelines

The parameters for the Event (EVENT) function are set via the local HMI or PCM600.

7.2.1.1 EventMask (Ch_1 - 16)


The inputs can be set individually as:

• NoEvents
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect

7.2.1.2 LONChannelMask or SPAChannelMask


Definition of which part of the event function block that shall generate events:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

7.2.1.3 MinRepIntVal (1 - 16)


A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.

It is important to set the time interval for cyclic events in an optimized


way to minimize the load on the station bus.

32 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 7
SPA functions

7.3 Logical signal status report BINSTATREP

7.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Logical signal status report BINSTATREP - -

7.3.2 Functionality
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other functions.

7.3.3 Function block


BINSTATREP
BLOCK OUTPUT1
^INPUT1 OUTPUT2
^INPUT2 OUTPUT3
^INPUT3 OUTPUT4
^INPUT4 OUTPUT5
^INPUT5 OUTPUT6
^INPUT6 OUTPUT7
^INPUT7 OUTPUT8
^INPUT8 OUTPUT9
^INPUT9 OUTPUT10
^INPUT10 OUTPUT11
^INPUT11 OUTPUT12
^INPUT12 OUTPUT13
^INPUT13 OUTPUT14
^INPUT14 OUTPUT15
^INPUT15 OUTPUT16
^INPUT16

IEC09000730-1-en.vsd
IEC09000730 V1 EN

Figure 6: BINSTATREP function block

7.3.4 Signals
Table 11: BINSTATREP Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Single status report input 1
INPUT2 BOOLEAN 0 Single status report input 2
INPUT3 BOOLEAN 0 Single status report input 3
INPUT4 BOOLEAN 0 Single status report input 4
Table continues on next page

670 series 2.1 IEC 33


Communication protocol manual
Section 7 1MRK 511 353-UEN -
SPA functions

Name Type Default Description


INPUT5 BOOLEAN 0 Single status report input 5
INPUT6 BOOLEAN 0 Single status report input 6
INPUT7 BOOLEAN 0 Single status report input 7
INPUT8 BOOLEAN 0 Single status report input 8
INPUT9 BOOLEAN 0 Single status report input 9
INPUT10 BOOLEAN 0 Single status report input 10
INPUT11 BOOLEAN 0 Single status report input 11
INPUT12 BOOLEAN 0 Single status report input 12
INPUT13 BOOLEAN 0 Single status report input 13
INPUT14 BOOLEAN 0 Single status report input 14
INPUT15 BOOLEAN 0 Single status report input 15
INPUT16 BOOLEAN 0 Single status report input 16

Table 12: BINSTATREP Output signals


Name Type Description
OUTPUT1 BOOLEAN Logical status report output 1
OUTPUT2 BOOLEAN Logical status report output 2
OUTPUT3 BOOLEAN Logical status report output 3
OUTPUT4 BOOLEAN Logical status report output 4
OUTPUT5 BOOLEAN Logical status report output 5
OUTPUT6 BOOLEAN Logical status report output 6
OUTPUT7 BOOLEAN Logical status report output 7
OUTPUT8 BOOLEAN Logical status report output 8
OUTPUT9 BOOLEAN Logical status report output 9
OUTPUT10 BOOLEAN Logical status report output 10
OUTPUT11 BOOLEAN Logical status report output 11
OUTPUT12 BOOLEAN Logical status report output 12
OUTPUT13 BOOLEAN Logical status report output 13
OUTPUT14 BOOLEAN Logical status report output 14
OUTPUT15 BOOLEAN Logical status report output 15
OUTPUT16 BOOLEAN Logical status report output 16

7.3.5 Settings
Table 13: BINSTATREP Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.0 - 60.0 s 0.1 10.0 Time delay of function

34 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 7
SPA functions

7.3.6 Operation principle


The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or via
SPA communication.

When an input is set, the respective output is set for a user defined time. If the input
signal remains set for a longer period, the output will remain set until the input signal
resets.

INPUTn

OUTPUTn
t t

IEC09000732-1-en.vsd
IEC09000732 V1 EN

Figure 7: BINSTATREP logical diagram

670 series 2.1 IEC 35


Communication protocol manual
36
1MRK 511 353-UEN - Section 8
Glossary

Section 8 Glossary

8.1 Glossary

AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time
synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fibre optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication

670 series 2.1 IEC 37


Communication protocol manual
Section 8 1MRK 511 353-UEN -
Glossary

CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations-sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves
two twisted pairs making it possible to transmit information
in both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchange
format for Disturbance recorder according to IEEE/ANSI
C37.111, 1999 / IEC60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves
four twisted pairs, two of which are used for transmitting
data in both directions and two for transmitting clock
signals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current

38 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 8
Glossary

DFC Data flow control


DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility
EMF Electromotive force
EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fibre connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech,
data and protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of
up to seven duplex channels of digital data over optical
fibers
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines used
by local telephone companies. Can be transported over
balanced and unbalanced lines
GCM Communication interface module with carrier of GPS
receiver module

670 series 2.1 IEC 39


Communication protocol manual
Section 8 1MRK 511 353-UEN -
Glossary

GDE Graphical display editor within PCM600


GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLC
standard
HFBR connector type Plastic fiber connector
HMI Human-machine interface
HSAR High speed autoreclosing
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6:
Requirements for protective current transformers for
transient performance
IEC 60870-5-103 Communication standard for protection equipment. A serial
master/slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s
on twisted-pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules.
References the CMC (IEEE P1386, also known as Common
Mezzanine Card) standard for the mechanics and the PCI
specifications from the PCI SIG (Special Interest Group) for
the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices
(IEDs) Cyber Security Capabilities
IED Intelligent electronic device
I-GIS Intelligent gas-insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are
available in the IED, they are referred to as instances of that

40 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 8
Glossary

function. One instance of a function is identical to another of


the same kind but has a different number in the IED user
interfaces. The word "instance" is sometimes defined as an
item of information that is representative of a type. In the
same way an instance of a function in the IED is
representative of a type of function.
IP 1. Internet protocol. The network layer for the TCP/IP
protocol suite widely used on Ethernet networks. IP is a
connectionless, best-effort packet-switching protocol. It
provides packet routing, fragmentation and reassembly
through the data link layer.
2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level 20
IP 40 Ingression protection, according to IEC 60529, level 40
IP 54 Ingression protection, according to IEC 60529, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B,
standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDCM Line differential communication module
LDD Local detection device
LED Light-emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MIM Milli-ampere module
MPM Main processing module
MVAL Value of measurement
MVB Multifunction vehicle bus. Standardized serial bus
originally developed for use in trains.
NCC National Control Centre
NOF Number of grid faults
NUM Numerical module
OCO cycle Open-close-open cycle

670 series 2.1 IEC 41


Communication protocol manual
Section 8 1MRK 511 353-UEN -
Glossary

OCP Overcurrent protection


OEM Optical Ethernet module
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than
start/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a fault
condition. For example, a distance relay is overreaching
when the impedance presented to it is smaller than the
apparent impedance to the fault applied to the balance point,
that is, the set reach. The relay “sees” the fault but perhaps
it should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near
proximity to the measured and/or controlled components
PSM Power supply module
PST Parameter setting tool within PCM600
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital
data in point-to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close

42 670 series 2.1 IEC


Communication protocol manual
1MRK 511 353-UEN - Section 8
Glossary

SCL Short circuit location


SCS Station control system
SCADA Supervision, control and data acquisition
SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SLM Serial communication module.
SMA connector Subminiature version A, A threaded connector with
constant impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize
computer clocks on local area networks. This reduces the
requirement to have accurate hardware clocks in every
embedded system in a network. Each embedded node can
instead synchronize with a remote clock, providing the
required accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/
slave protocol for point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport
layer protocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The
de facto standard Ethernet protocols incorporated into
4.2BSD Unix. TCP/IP was developed by DARPA for
Internet working and encompasses both network layer and
transport layer protocols. While TCP and IP specify two
protocols at specific protocol layers, TCP/IP is often used to
refer to the entire US Department of Defense protocol suite
based upon these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)

670 series 2.1 IEC 43


Communication protocol manual
Section 8 1MRK 511 353-UEN -
Glossary

TNC connector Threaded Neill-Concelman, a threaded constant impedance


version of a BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and
voltages taken from the process into levels suitable for
further signal processing.
TYP Type identification
UMT User management tool
Underreach A term used to describe how the relay behaves during a fault
condition. For example, a distance relay is underreaching
when the impedance presented to it is greater than the
apparent impedance to the fault applied to the balance point,
that is, the set reach. The relay does not “see” the fault but
perhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale,
maintained by the Bureau International des Poids et
Mesures (BIPM), which forms the basis of a coordinated
dissemination of standard frequencies and time signals.
UTC is derived from International Atomic Time (TAI) by
the addition of a whole number of "leap seconds" to
synchronize it with Universal Time 1 (UT1), thus allowing
for the eccentricity of the Earth's orbit, the rotational axis tilt
(23.5 degrees), but still showing the Earth's irregular
rotation, on which UT1 is based. The Coordinated
Universal Time is expressed using a 24-hour clock, and uses
the Gregorian calendar. It is used for aeroplane and ship
navigation, where it is also sometimes known by the
military name, "Zulu time." "Zulu" in the phonetic alphabet
stands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
X.21 A digital signalling interface primarily used for telecom
equipment
3IO Three times zero-sequence current.Often referred to as the
residual or the earth-fault current
3UO Three times the zero sequence voltage. Often referred to as
the residual voltage or the neutral point voltage

44 670 series 2.1 IEC


Communication protocol manual
45
Contact us

1MRK 511 353-UEN - © Copyright 2014 ABB. All rights reserved.


ABB AB
Substation Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Fax +46 (0) 21 14 69 18

www.abb.com/substationautomation

Вам также может понравиться