ELECTRICAL GENERAL NOTES

A. ALL ELECTRICAL INSTALLATION HEREIN AND OTHER RELATED WORKS TO


BE DONE ON THIS BUILDING SHALL COMFORM IN ACCORDANCE WITH THE
1.60 PROVISIONS AND CODE STANDARD OF THE FOLLOWING :
m 1. LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE ( PEC/NEC )
4.27 2. REPUBLIC ACT 7920 OTHERWISE KNOWN AS THE NEW ELECTRICAL
m ENGINEERING LAW
7.55 3. NATIONAL BUILDING CODE
7.55 m 4. FIRE CODE OF THE PHILIPPINES
m
5. EXISTING LOCAL UTILITY COMPANY
6. EXISTING CITY/ MUNICIPALITY ORDINANCES AND THE
7. REQUIREMENTS OF THE BUREAU OF LABOR STANDARDS

B. ELECTRICAL INSTALLATION HEREIN SHALL BE DONE UNDER THE DIRECT


1.92 3.13
1.40 1.92 m 3.13
m m m
SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. THE ELECTRICAL
ENGINEER SHALL BE RESPONSIBLE IN THE INTERPRETATION OF THE DESIGN
ALL MEASUREMENTS ARE TO BE VERIFIED ON SITE BY THE CONTRACTOR. ALL DISCREPANCIES ARE TO
BE IMMEDIATELY REPORTED TO THE ARCHITECT. CONTRACTORS ARE TO PREPARE AND SUBMIT SHOP
m DRAWINGS TO THE ARCHITECT PRIOR TO COMMENCEMENT OF WORKS. THIS DRAWING IS THE
INTENT, PLANS AND SPECIFICATIONS AND THE REQUIRED STANDARD OF THE PROPERTY OF ARCHITECT BRADLEY ROME BALTAZAR AND IS NOT TO BE REPRODUCED OR USED
ELECTRICAL CODE. WITHOUT WRITTEN CONSENT.
1.35 1.35 -REPUBLIC ACT NO. 545-
m m C. MATERIALS AND EQUIPMENT TO BE USED ( BALLAST, FLUORESCENT TUBE,
WIRING DEVICES, CIRCUIT BREAKERS, CONDUIT AND PIPES, ENCLOSURES, WIRES KEY PLAN
AND CABLES, PRODUCTS AND P.S. MARK FOR LOCAL IN NATURE OF THE

m
m
BUREAU OF PRODUCT STANDARDS ( BPS ).

2.27
2.27
m
D. PROVIDE GROUNDING AND NEUTRAL WIRE TO ALL OUTLETS AND LIGHTING

1.05
CIRCUITS. ALL NON-CURRENT CARRYING METAL PARTS SHALL BE GROUNDED
AND BONDED ETC... ) SHALL HAVE IMPORTED COMMODITY CLEARANCE ( ICC )
N LABEL FOR FOREIGN MADE

m
m
CKT1

3.92
3.92
K
O E. ALL PANELBOARDS, MAIN DISTRIBUTION PANELS, ETC SHALL HAVE
G
K GROUNDING BUS FOR BRANCH CIRCUITS AND SUB-FEEDER GROUNDING
SYSTEM, MAIN GROUNDING SYSTEM SHALL BE BONDED TO THE NEAREST UNIT 309
P
METAL WATER PIPE IN SERVICE.

m
m

G J

5.70
F. MOUNTING HEIGHTS FOR ALL WIRING DEVICES AND PANELBOARDS SHALL
5.70

M Q
CKT1 G
CKT4 BE AS
F 1. LIGHTING SWITCHES 1.4 M ABOVE FLOOR FINISH
J R 2. CONVENIENCE OUTLET 0.3 M ABOVE FLOOR FINISH
H 3. TELEPHONE OUTLET 0.3 M ABOVE FLOOR FINISH
4. PANELBOARDS AND CABINETS 1.8 M ON TOP ABOVE FLOOR FINISH
5. MOTOR CONTROL AND ECB 1.8 M ON TOP ABOVE FLOOR FINISH
H 6. MANUAL TRANSFER SWITCH 1.8 M ON TOP ABOVE FLOOR FINISH

m
m

7. EMERGENCY LIGHT FIXTURE 0.3 M BELOW CEILING LINE

8.60
8.60

F H
CKT4 S
G. WIRING METHOD SHALL BE AS FOLLOWS:
1. SERVICE ENTRANCE RISER-------------------INTERMEDIATE METALLIC
CONDUIT ( IMC )
B
2. LIGHTING AND POWER SYSTEM------------ELECTRICAL METALLIC TUBING

m
m

A (EMT)

0.98
0.98

I T
3. TELEPHONE SYSTEM ------------------------ ELECTRICAL METALLIC TUBING
E
B (EMT) PROJECT TITLE
4. ALL VIBRATING EQUIPMENT------------LIQUIDTIGHT FLEXIBLE CONDUIT
5. JUNCTION BOX TO LIGHTING FIXTURE ----- FLEXIBLE METAL CONDUIT
10mm dia.
CKT4
L
A D G M U
B E H L H.LIGHTING FIXTURE WITH FLOURESCENT TUBE SHALL HAVE PROTECTOR
E C F I
HIGH-POWER FACTOR BALLAST.( PRE-HEAT )
I SANDREALEE SALON

m
m

A A I. MECHANICAL EQUIPMENT WITH HIGH VIBRATION MOVEMENTS SHALL HAVE


UNIT309 - 225 General Kalentong St., Brgy. DaangBakal,

2.90
2.90

FLEXIBLE CONDUIT CONNECTION FROM MOTOR TERMINAL BOX TO


OVERCURRENT DEVICE ENCLOSURE ( ECB ). Mandaluyong City
D
V
J. PRIOR TO ITS MOUNTING AND TERMINATION OF LIGHTING FIXTURES, WIRING
DEVICES, EQUIPMENT, ETC... CONTRACTOR SHALL ENGAGE WITH THE
D
CONSULTANT OR OWNER REPRESENTATIVE THE FOLLOWING FIELD
CKT2 CKT3 ACCEPTANCE TEST AND MATERIAL INSPECTION: CLIENT
CKT4 1. BRANCH CIRCUITS AND SUB-FEEDER INSULATION RESISTANCE TEST MEASUREMENT
D I 2. POLARITY TEST ON WIRING DEVICES
W 3. GROUND RESISTANCE TEST MEASUREMENT
4. MATERIALS QUALITY INSPECTION AS REQUIRED IN THE ABOVE SPECIFICATION
C 5. GROUND WELL RESISTANCE TEST MEASUREMENT FOR LIGHTNING SYSTEM
SIGNAGE

3.90 m 1.55 m 6.15 m 3.90 m 1.55 m 6.15 m K. ALL WORKS SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL
11.60 m PRESENT A NEAT AND ORDERLY ACCEPTANCE. ALL WIRINGS SHALL BE
11.60 m CONCEALED SANDREALEE SALON
CEILING MOUNTED LIGHTING LAYOUT WALL MOUNTED LIGHTING LAYOUT ELECTRICAL SYMBOLS
7.55
SCALE:1:50m
m SCALE:1:50m
1 2 2- 5 WATTS LED DOUBLE
RECESSED DOWNLIGHT
ARCHITECT

E 1 1.92 3.13
E 1
m m S SINGLE SWITCH

S
1.35 S TWO-GANG SWITCH
m ARCH. BRADLEY ROME V. BALTAZAR
LOAD COMPUTATION AND TABULATION S
S THREE-GANG SWITCH
m

REG. NO. T.I.N. NO. P.T.R NO. ISSUED AT ISSUED ON


S
2.27

CKT DESCRIPTION LO CO WATTS VOLTS AMPS CIRCUIT WIRE SIZE CONDUIT 044540 700-937-019-000 BAGUIO CITY 01-21-2019

1 NO. LIGHTING 8 800 230 3.48 BREAKER


15 AMPS 2-2.0 sq.mm 1/2 " PVC CONDUIT PROFESSIONAL ELECTRICAL ENGINEER
2 LIGHTING 9 900 230 3.92 15 AMPS THHN
2-2.0 sq.mm 1/2 " PVC CONDUIT 9WATTS T5 LED TUBE
230 THHN 1/2 " PVC CONDUIT
m

3 LIGHTING 10 1000 4.34 15 AMPS 2-2.0 sq.mm

unit 301
3.92

CKT 7 - AC 4 LIGHTING 9 900 230 3.92 15 AMPS THHN


2-2.0 sq.mm 1/2 " PVC CONDUIT
5 POWER 8 1,600 230 6.96 20 AMPS 2-3.5 sq.mm
THHN 1/2 " PVC CONDUIT 12WATTS PANEL LIGHT
6 POWER 6 1,200 230 5.22 20 AMPS THHN
2-3.5 sq.mm 1/2 " PVC CONDUIT
PB THHN
m

CKT5 7 SPARE 30 AMPS 3-5.5 sq.mm 1 " PVC CONDUIT


6 WATTS T5 LED TUBE WITH ENG'R. PAULINO DELMAS, PEE
5.70

8 SPARE 30 AMPS THHN


3-5.5 sq.mm 1 " PVC CONDUIT
6,400 27.84 THHN ACRYLIC COVER
UNIT 309 UNIT 309 6,400/ 230 x 80% DF = 22.26 amps
REG. NO. T.I.N. NO. P.T.R NO. ISSUED AT ISSUED ON

*** USE 30 AMPERES CIRCUIT BREAKER 2 GANG CONVENIENCE OUTLET REVISIONS


30 AMP 30 AMP 4 - 5.5mm sq TW copper wire,
1 - 5.5mm sq THW ground wire NO. DATE REMARKS
1 FCU - CS, 5TR IN 25mm dia. RSC PIPE
m

1 LIGHTING 15 AMP 15 AMP LIGHTING


2 PANEL BOX
8.60

LIGHTING 15 AMP 15 AMP LIGHTING


3 4
POWER 20 AMP 20 AMP POWER TELEPHONE
5 6
m

SPARE 30 AMP 30 AMP SPARE


7 8
0.98

CKT6 CIRCUIT CONDUCTORS

GROUND WIRE GROUND WIRE


DOCUMENT TYPE
CKT DESCRIPTION LO CO WATTS VOLTS AMPS CIRCUIT WIRE SIZE CONDUIT FOR BUILDING PERMIT
1 NO. 1 FCU- CS, 5TR 1 5,000 230 21.74 BREAKER
30 AMPS 3-5.5 sq.mm 1 " PVC CONDUIT
CKT6 THHN SHEET CONTENT
5,000/ 230 x 80% DF = 17.40 amps LIGHTING LAYOUT
*** USE 30 AMPERES CIRCUIT BREAKER
m

POWER LAYOUT
2.90

4 - 5.5mm sq TW copper wire,


1 - 5.5mm sq THW ground wire ELECTRICAL NOTES, LEGEND AND SYMBOL
IN 25mm dia. RSC PIPE
LOAD COMPUTATION AND TABULATION

SHEET NUMBER
DRAWN BY: BRB

CONVENIENCE OUTLET LAYOUT SCALE: AS SHOWN

3 SCALE:1:50m E-001
CHECKED BY: BRB

E 1 APPROVED BY: BRB


PROJECT NO.: 2019 -003

DATE: JANUARY 18,2019