Академический Документы
Профессиональный Документы
Культура Документы
9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
*EPA Certified Prime ratings are not available in the US or its Territories
Image used for illustration purposes only
every step of the supply chain and delivery process, so you benefit
from single-source responsibility.
NFPA 37, 70, 99, 110
Plus, Generac Industrial Power’s distribution network provides
® all parts and service so you don’t have to deal with third-party
NEC 700, 701, 702, 708
suppliers. It all leads to a positive owner experience and higher
confidence level. Generac spark-ignited engines give you more
SPEC SHEET
ANSI/IEEE C62.41 1 OF 6
MG750 | 33.9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
CONTROL SYSTEM • Alarm and Event Logging with Real Time Stamping 7” Color Touch Screen Display
• Expandable Analog and Digital Inputs and Outputs
• Capacitive Color Touch Screen
• Remote Wireless Software Update Capable
• Sunlight Readable (1400 NITS)
• Wi-Fi, Bluetooth, BMS and Remote Telemetry Single
• Easily Identifiable Icons
Point Ground
• Multi-Lingual
• Built-In Programmable Logic Eliminates The Need
For External Controllers Under Most Conditions • On Screen Editable Parameters
• Ethernet Based Communications • Key Function Monitoring
Between Generators • Three Phase Voltage, Amperage, kW, kVa, and kVar
• Programmable I/O Channel Properties • Selectable Line to Line or Line to Neutral
• Built-In Diagnostics Measurements
• Frequency
Protections • Engine Speed
• Engine Coolant Temperature
• Low Oil Pressure
• Engine Oil Pressure
• Low Coolant Level
• Engine Oil Temperature
• High/Low Coolant Temperature
• Battery Voltage
• Sensor Failure
• Hourmeter
• Oil Temperature
• Warning and Alarm Indication
Power Zone® • Over/Under Speed
• Diagnostics
SPEC SHEET
• Over/Under Voltage
• NFPA 110 Level 1 Complaint • Maintenance Events/Information
• Over/Under Frequency
• Engine Protective Functions
• Over/Under Current
• Alternator Protective Functions Parallel Control Features
• Over Load
• Digital Engine Governor Control • Paralleling Control (Synchronizing)
• High/Low Battery Voltage
• Digital Voltage Regulator • Reverse Power
• Battery Charger Current
• Multiple Programmable Inputs and Outputs • Loss Of Synchronization Between Gensets
• Phase To Phase and Phase To Neutral Short Circuits
• Remote Display Capability (I2T Algorithm) • Load and VAR Sharing 2 OF 6
• Remote Communication Via Modbus® RTU, Modbus
TCP/IP, Ethernet 10/100
MG750 | 33.9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
GENERATOR SET
○○ Extended Factory Testing
○○ 24 Position Load Center
ENGINEERED OPTIONS
SPEC SHEET
3 OF 6
MG750 | 33.9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
Lubrication System
Oil Pump Type Gear
Oil Filter Type Cartridge
Crankcase Capacity with Filters - L (qts) 160 (151)
ALTERNATOR SPECIFICATIONS
4 OF 6
MG750 | 33.9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
FUEL CONSUMPTION RATES*- Natural Gas – scfh (m3/hr) [at standard conditions 68°C, 14.7 psi]
Percent Load Standby
25% 2,718 (77)
50% 4,110 (116)
75% 5,820 (165)
100% 7,770 (220)
* Fuel supply installation must accommodate fuel consumption rates at 100% load.
COOLING
Standby/Demand Response
Air Flow (Fan Air Flow Across Radiator) scfm (m /min)
3
32,515 (920.7)
Coolant Flow gpm (Lpm) 291 (1,101)
Coolant System Capacity gal (L) 55 (208)
Max. Operating Ambient Temperature °F (°C) 122 (50)
Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD
Maximum Radiator Backpressure in H2O (kPa) 0.50 (0.12)
ENGINE EXHAUST
SPEC SHEET
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please consult a Generac Power Systems Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528 and DIN6271 standards.
MG750 | 33.9L | 750kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Cer tified Stationary Emergency and Non Emergency
H
OPEN SET (Includes Exhaust Flex)
L x W x H - in (mm) 182.5 (4,637) x 84.3 (2,141) x 142.0 (3,606)
W L
W L
W L
Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please consult a Generac Power Systems Industrial Dealer for detailed installation drawings. 6 OF 6
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 Part No 10000024341
P: (262) 544-4811 ©2018 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Rev. 1 07/10/18